Spesifikasi Teknis Minimum

Proteksi incoming dan


Protection ANSI code Outgoing Feeder/ Outgoing
Substation
Phase Overcurrent 50/51 √
Earth fault (or neutral) 50N/51N √
Unbalance / negative sequence 46 √
79 ○
Recloser (4 cycles)

Metering
Phase current I1, I2, I3 rms ●
Residual current Io ●
Average current I1, I2, I3 ●
Peak demand phase current IM1, IM2, IM3 ●

Network diagnosis
Tripping current I1, I2, I3, and lo ●
Unbalance ratio / negative sequence current I(2) ●
Disturbance recording ●

Switchgear diagnosis
Cumulative breaking current ●
Trip circuit supervision ○
Number of operation ○
Operating time ○
Charging time ○

Self diagnosis
Watch dog ●
Output Relay test ○

Control and monitoring


Circuit Breaker/ contractor control ○
Logic Discrimination ○
4 Addresable logit output ●

Fitur Tambahan

-Display LCD dengan tampilan grafis memberikan kemudahan √


pembacaan dan penggunaan input dan output
-logic untuk kontrol CB close/ open, inhibit closing √
-Tegangan standard 24 - 250 Vdc/ 120- 240 Vac √
-Sertifikasi ISO 9001 √

√ = OK
● = standard
○ = according to parameter setting and optional module
DM EPMSD

ERWIN GUNAWAN