by LESLIE STOCH
As everyone knows, Rule 10-700(2) speci©es that a rod grounding electrode (with a few
exceptions) must consist of at least two ground rods driven a minimum of 3 m apart. And
for high voltage substations, Rule 36-302(1) also requires that every station must be
grounded with at least four ground rods, not less than 3 m long, spaced a minimum
distance of one rod length apart. Why does spacing between ground rods matter? What
would be the problem if ground rods were to be more closely spaced?
Our story begins with the grounding resistance of every grounding electrode, which has
three components:
1. the resistance of the metal ground rods, grounding conductors and connections;
2. contact resistance between the grounding electrode and the earth; and
3. the resistance of the earth.
As it turns out, the ©rst two are relatively small and can usually be considered insigni©cant
when considering total grounding resistance. Grounding resistance can be considered as
http://iaeimagazine.org/magazine/2011/01/16/groundingresistanceandspacingofgroundrods/ 1/4
3/11/2017 Grounding Resistance and Spacing of Ground Rods ‹ IAEI Magazine
This tells us that ground rods would need to be spaced 7.6 m apart to achieve the best Read the article
grounding e^ect. Obviously, the 3 m rule provided by the Canadian Electrical Code is a Connections, 20
compromise, good but not perfect.
Other available data also supports these ©ndings. Question – if we know the grounding
resistance of a single ground rod (say 25 ohms), and we want to reduce the resistance by
adding a second rod spaced in accordance with the CEC, will this reduce grounding
resistance to 50%? Actually, no. It will only reduce the total grounding resistance to 25/2 x
1.16 = 14.5 ohms. The result of adding two rods will be 25/3 x 1.29 = 10.75 ohms.
Multiplying factors for multiple rod arrangements are available.
As with previous articles, you should always consult the electrical inspection authority in
each province or territory for a more precise interpretation of any of the above.
Views Today 9
http://iaeimagazine.org/magazine/2011/01/16/groundingresistanceandspacingofgroundrods/ 2/4
3/11/2017 Grounding Resistance and Spacing of Ground Rods ‹ IAEI Magazine
LESLIE STOCH
SLEEKER,
UNDERST
2017 NEC
PREVIOUS POST NEXT POST
The 10 Pi
Stay Warm Conductor Sizing and Overcurrent Bid — Pa
Device Ratings
Adventur
Scale PV
YOU MIGHT ALSO LIKE
6 lockout
electricia
Journey to the Future of
respect
260-year-old Lighting Rod:
Where lighting protection
Service E
technology is going
NEC 2017
DECEMBER 6, 2016
Grounding and Bonding What Is Earthing & Why Medium Voltage Earth
JUNE 7, 2016
and How Do We Connect Systems – Arrangemen
to it? and Comparison
NOVEMBER 10, 2015
http://iaeimagazine.org/magazine/2011/01/16/groundingresistanceandspacingofgroundrods/ 3/4
3/11/2017 Grounding Resistance and Spacing of Ground Rods ‹ IAEI Magazine
http://iaeimagazine.org/magazine/2011/01/16/groundingresistanceandspacingofgroundrods/ 4/4