Sie sind auf Seite 1von 14

See

discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/272997536

Performance evaluation of ceiling mounted


personalized ventilation system

Article in ASHRAE Transactions · January 2009

CITATIONS READS

23 142

3 authors, including:

Bin Yang Chandra Sekhar


Umeå University National University of Singapore
79 PUBLICATIONS 233 CITATIONS 85 PUBLICATIONS 614 CITATIONS

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Building Energy Efficiency Hub View project

Personalized Ventilation View project

All content following this page was uploaded by Bin Yang on 02 March 2015.

The user has requested enhancement of the downloaded file.


© 2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers,
Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, vol. 115, part 2. For
personal use only. Additional reproduction, distribution, or transmission in either print
or digital form is not permitted without ASHRAE’s prior written permission.

LO-09-036

Performance Evaluation of Ceiling Mounted


Personalized Ventilation System

Bin Yang Arsen Melikov, PhD Chandra Sekhar, PhD


Student Member ASHRAE Fellow ASHRAE Fellow ASHRAE

ABSTRACT -0.5°C (-0.9°F) to -4°C (-7.2°F) under 26°C (78.8°F)/26°C


(78.8°F) case, which are the two extreme cases among the four
The interaction of the personalized airflow supplied from cases studied. The personalized airflow was least efficient to
ceiling mounted nozzle (diameter of 0.095 m (0.312ft)) with the cool the body when the manikin was moved forward.
thermal plume generated by a seated thermal manikin with the
body size of an average Scandinavian woman and its impact INTRODUCTION
on the body cooling was studied. Experiments were performed
in a test room with mixing ventilation at numerous conditions Personalized ventilation aims to provide clean and cool
comprising four combinations of room air temperature and air in the vicinity of the breathing zone of human body and thus
personalized air temperature (23.5°C (74.3°F) / 21°C to improve inhaled air quality. Occupants’ thermal comfort is
(69.8°F), 23.5°C (74.3°F) / 23.5°C (74.3°F), 26°C (78.8°F) / also improved, especially at relatively high room temperatures
23.5°C (74.3°F), 26°C (78.8°F) / 26°C (78.8°F)), four airflow (Gong et al. 2005, Kaczmarczyk et al. 2006). Most often,
rates of the personalized air (4 (8.48), 8 (16.95), 12 (25.43), personalized ventilation systems (PV) with desk mounted air
16 (33.91) L/s (cfm)) and positioning of the manikin directly terminal devices (ATD) have been studied (Faulkner et al.,
below the nozzle (1.3m (4.265ft) distance between the top of 1999, Tszuzuki et al. 1999, Melikov et al. 2002, Kaczmarc-
manikin’s head and the nozzle). The asymmetric exposure of zyk et al. 2004, etc.). The idea of ceiling mounted PV ATD
the body to the personalized flow was studied by moving the provides more flexibility in arranging the furniture in the
manikin 0.2m (0.656ft) forward, backward and sideward. The occupied zone. It also improves the indoor aesthetics because
blockage effect of the unheated manikin on the personalized extended air ducts for transporting of clean and cool air to
airflow distribution, studied at the case 23.5°C (74.3°F)/ different workstations are not needed. Occupants may be
23.5°C (74.3°F), was clearly observed 0.2m (0.656ft) above provided with individual control of the PV airflow rate in order
the top of manikin’s head where the centerline velocity was to obtain preferred micro-environment in term of thermal
reduced to about 85% under all personalized airflow rates. The comfort and indoor air quality.
neutral level, Xnl, defined as the distance from the nozzle where The cooling effect of ceiling mounted nozzle depends on
the impact of the thermal plume on the velocity distribution in the PV airflow rate and the temperature of the PV supply air
the personalized airflow was observed, increased from 0.8m (Yang et. al. 2008). The size of the nozzle (its diameter if it is
(2.625ft) to 1.1m (3.609ft) with the increase of the airflow rate. circular nozzle) and the initial airflow conditions at the exit
Above 16L/s (33.91cfm) the personalized airflow was able to define the size of the target area in contact with the body. The
completely destroy the thermal plume. In comparison with the system can be regarded as one kind of individual spot cooling
reference case without personalized airflow, the manikin based system by vertical air jet, which can provide occupants with
equivalent temperature for the head decreased with the acceptable thermal comfort conditions (Azer et al. 1971, 1972;
increase of the airflow rate from -1°C (-1.8°F) to -6°C (- Azer and Nevins 1974; Olesen and Nielsen 1980, 1983; Ma
10.8°F) under 23.5°C (74.3°F)/21°C (69.8°F) case and from and Qin 1991; Melikov et al. 1994, 1994a). At constant airflow

Bin Yang is a doctoral student in the NUS-DTU Joint PhD program and Chandra Sekhar is an associate professor in the Department of Build-
ing, National University of Singapore (NUS), Singapore. Arsen Melikov is an associate professor in the Department of Civil Engineering,
Technical University of Denmark (DTU), Denmark.

©2009 ASHRAE 395


rate, the increasing of the nozzle outlet diameter will reduce air different conditions. The impact of occupant’s movement on
velocity of the personalized airflow but will increase the size the airflow interaction and thus on the body cooling was
of the target area of the jet (target area is defined as the cross explored. The results are presented and discussed in this paper.
section of the jet where it first meets the occupant) while It may be noted that CFD tools could be employed in stud-
decreasing nozzle diameter will increase airflow velocity at ies involving room air distribution. A validated CFD model is
the target area but will decrease its size, i.e. the airflow will not useful for parametric variation studies in which refine grids
cover occupant’s body (Melikov et al. 1994a). Human body become essential, especially for simulating thermal plume
will affect the personalized airflow as an obstacle and with the around human body. However, this is beyond the scope of the
generated thermal plume. The characteristics of the thermal present paper.
plume generated by human body depend on the body posture
(standing and seated), clothing design and thermal insulation, METHODS
type of the chair, surrounding air and radiant temperature, etc.
(Hyldgaard 1998, Zukowska et al. 2007, 2007a). The interac- Experimental Set-Up
tion of the personalized airflow with the thermal plume gener-
Experiments were conducted in a field laboratory (4.7m
ated by the human body is of major importance for the body
(15.42ft)×5.4m (17.71ft)×2.6m (8.53ft)) specially designed
cooling. It may also affect the air distribution pattern in the
for studying PV systems. An air distribution system was modi-
entire space. In reality, people at workplaces will move and
fied to provide personalized air to a nozzle mounted at the ceil-
may not be located directly below the nozzle. The asymmetric
ing in the middle of the room (Figure 1). The nozzle with a
exposure of the body, i.e. the changes in positioning of the
parabolic contracting profile was designed to generate vertical
thermal plume will affect its interaction with the personalized
downward circular free jet with initial diameter of 0.095m
airflow, which will result in a non-uniform cooling of the body.
(0.312ft) and uniform velocity profile. The nozzle was
Thus the whole body cooling effect of the personalized airflow connected to a circular duct with its larger diameter of 0.16m
will decrease while the local cooling of some body parts may (0.525ft). The exit of the installed nozzle was located at the
increase leading to draught discomfort. These effects need to height of 2.5m (8.202ft) above the floor.
be studied for proper design of ceiling mounted personalized
The ambient cooling in the PV lab was managed by a
ventilation.
mixing ventilation system supplying airflow from four swirl
The interaction of the personalized airflow from ceiling diffusers symmetrically mounted on the ceiling. One return air
mounted PV nozzle with the thermal plume from human body grill was located at the upper part of one side wall and a
and its whole body and local cooling effect was studied under completely ducted return route was used.

Figure 1 Personalized ventilation (PV) laboratory.

396 ASHRAE Transactions


Measuring Instruments Experiments were performed at four different personalized
airflow rates (4, 8, 12 and 16 L/s) [8.48. 16.95, 25.43 and
A thermal manikin consisting of 23 individually
33.91cfm]. The supply temperature of personalized airflow was
controlled body segments with the size of an average Scandi-
controlled at 21°C (69.8°F) and 23.5°C (74.3°F). The room air
navian woman was used to resemble human body with the
temperature was controlled at 23.5°C (74.3°F) and 26°C
generated thermal plume. A comfort control mode was used,
(78.8°F). As a result, four temperature combinations were
i.e. the surface temperature of the manikin was controlled to be
achieved: 23.5°C (74.3°F) / 21°C (69.8°F), 23.5°C (74.3°F) /
the same as the skin temperature of an average person in state
23.5°C (74.3°F), 26°C (78.8°F) / 23.5°C (74.3°F), 26°C
of thermal comfort under the exposed environmental condi-
(78.8°F) / 26°C (78.8°F)). The isothermal case 23.5°C (74.3°F)
tions (Tanabe et al., 1994). The control system allows for read-
/ 23.5°C (74.3°F) was selected to explore velocity distribution
ing of the surface temperature of each body segment and the
under the nozzle without manikin, with unheated manikin and
supplied heat power. The manikin was dressed with long
with heated manikin. Average velocity and Reynolds number at
sleeve shirt, trousers, underwear, socks and shoes at about
nozzle exit, centerline velocity at target area without manikin
0.7clo (0.1085m2K/W) thermal insulation and was seated in
under this isothermal case are listed in Table 1.
an office chair with thermal insulation of approximately 0.15-
0.2 clo (0.02325-0.031 m2K/W).
Multi-channel low velocity thermal anemometer with
five omni-directional velocity probes (SENSOR-ELEC-
TRONIC HT-400) was used to perform measurements of
velocity field in the personalized airflow. The velocity
measurement range of the system was 0.05m/s (±0.164fps) to
5m/s (±16.4fps), with the accuracy of ±0.03m/s (±0.098fps).
In order to obtain accurate velocity results, all probes were
calibrated before the measurements in a low velocity wind
tunnel. A rake of five velocity probes placed beside each other
horizontally (Figure 1) was used to measure velocity distribu-
tion at eight cross sections of the airflow above the manikin as
schematically shown in Figure 2. For the two cross sections
close to the nozzle outlet, 5 points were selected. For other
cross sections, velocity measurements at 9 points were
performed. Another single channel low velocity thermal
anemometer with omni-directional probe (SWEMA 300) was
used for measuring velocity at nozzle outlet. The accuracy of
the instrument was ±0.03 m/s (±0.098fps) and it was cali-
brated by the manufacturer. Each of the velocity measure-
ments lasted 3 minutes.

Experimental Conditions
The distance between nozzle outlet and the head of the
seated manikin was 1.3m (4.265ft). The nozzle was selected
according to the jet theory (Awbi, 2003) to provide airflow
with diameter of 0.35-0.5m (1.148-1.64ft) at the target area,
i.e. a airflow covering the head/shoulders of the seated mani-
kin. Depending on the supply airflow rate the potential core
region of the generated personalized airflow was 0.25-0.45m Figure 2 Distribution of omni-directional thermal
(0.82-1.476ft) long. anemometer probes.

Table 1. Personalized Air Velocity at Nozzle Exit and Target Area under Different Personalized Airflow Rates

Personalized Airflow Rate (L/s, cfm) Exit Velocity (m/s, fps) Re Number Target Velocity (m/s, fps)
4 (8.48) 0.55 (1.804) 3393 0.24 (0.787)
8 (16.95) 1.22 (4.003) 7526 0.39 (1.28)
12 (25.43) 1.52 (4.987) 9377 0.61 (2.001)
16 (33.91) 1.96 (6.43) 12091 0.8 (2.625)

ASHRAE Transactions 397


The Reynolds number is defined as follows: performed in the case of free vertical jet without manikin, with
unheated manikin and with heated manikin. Mean velocity
Re = ud ⁄ υ (1)
profiles measured at selected cross sections without manikin,
υ = μ⁄ρ (2) with unheated manikin and with heated manikin were
compared for exploring the blockage effect and the neutral
Where level. The mean velocity profiles measured at selected cross
u = exit velocity (m/s, fps) sections with a heated manikin at 4 L/s (8.48 cfm) is shown in
d = characteristic length (diameter of nozzle outlet) Figure 3. Velocity profiles similar to those shown in Figure 3
(m, ft) were obtained for the remaining airflow rates of 8, 12 and 16
υ = kinematic viscosity (m²/s, ft2/s) L/s (16.95, 25.43 and 33.91 cfm) and similar results have been
observed. At the two cross sections close to nozzle outlet,
µ = dynamic viscosity of the fluid (N·s/m², lbm/ft·h)
centerline velocities are only slightly lower than the velocity
ρ = density of the fluid (kg/m³) at nozzle outlet because they were within the core region. The
comparison of the results show that at 4 L/s (8.48 cfm) the
Furthermore, experiments with manikin moved 0.2m
blocking effect of the unheated manikin on velocity distribu-
(0.656ft) forward, backward and sideward were performed to
tion in the personalized airflow was observed after approxi-
simulate occupant’s movement in reality at workplace and to
mately. 11.58 initial nozzle diameters, i.e. approximately. at
study its impact on the airflow interaction. All temperature
combinations under different personalized airflow rates were distance of 1.1m (3.609ft) from the exit of the nozzle and 0.2m
explored. Some results, which include 16 L/s (33.91cfm) (0.656ft) from manikin’s head. The centerline velocity in the
personalized airflow rate under different temperature combi- personalized airflow at a distance x/D=11.58 is substantially
nations and isothermal case 23.5°C (74.3°F)/23.5°C (74.3°F) lower with manikin present than without manikin. The veloc-
under different personalized airflow rates were utilized to ity measurements at 8, 12 and 16 L/s (16.95. 25.43 and 33.91
demonstrate the change of local cooling effect. cfm) were analyzed in similar way and show a similar trend.
Figure 4 compares the dimensionless centerline velocity V/Vo
Data Analyses without manikin, with unheated manikin and with heated
manikin at 4 L/s (8.48 cfm). Similar plots were also obtained
The measurements allowed for determination of the
for 8, 12 and 16 L/s (16.95, 25.43 and 33.91 cfm) personalised
blockage effect and the neutral level in the airflow. The block-
airflow. The results identify that the blockage effect of the
age effect was caused by unheated manikin, which can be only
unheated manikin is observed almost at the same cross section,
regarded as an obstacle for the personalized airflow. The
which was 0.2m (0.656ft) above manikin’s head. Centerline
neutral level, Xnl, was defined as the vertical distance from the
velocity began to reduce at that level under different person-
nozzle to the point where the impact of the thermal plume on
alized airflow rates. Although the absolute values of the reduc-
the velocity distribution in the personalized airflow begins to
tions were different, the reduction ratios defined as the
be observed, i.e. the vertical distance from the nozzle to the
centerline velocity with unheated manikin divided by the
point where the difference in velocity distribution across the
airflow with and without the presence of heated manikin was
observed.
In order to quantify the cooling effect of the thermal envi-
ronment which the manikin was exposed to, sensible heat loss
measured from each body segment as well as from the whole-
body of the manikin was transformed into a parameter named
manikin-based equivalent temperature. The manikin-based
equivalent temperature was defined as the temperature of a
uniform enclosure in which a thermal manikin with realistic
skin surface temperature would lose heat at the same rate as it
would in the actual environment (Nilson et al. 1999). The
difference of manikin based equivalent temperature with and
without personalized air supply (ΔTeq) calculated for each
body segment and for the whole body was used as an evaluat-
ing index. The manikin was calibrated before the experiments.

RESULTS

Airflow Interaction
Comprehensive measurements of the velocity field across Figure 3 Air velocity profile under 4 L/s personalized
the personalized airflow at eight different cross sections were airflow rate with heated manikin.

398 ASHRAE Transactions


centerline velocity without manikin were almost same, 85% (0.984fps)). The neutral level at 4 L/s (8.48cfm) personalized
(Table 2). Air velocity along the jet radius at this cross section airflow rate was 0.8 m (2.625ft). Similarly the interaction of
increased slightly because of the bypass airflow. the two airflows and the neutral levels were identified under all
The thermal plume generated by the heated manikin personalized airflow rates. At 16 L/s (33.91cfm) the person-
created further resistance for the personalized airflow. For alized airflow was strong enough to almost completely destroy
example the comparison of the centerline velocity measured the thermal plume. This can be seen from the centerline
with heated manikin at x/D= 10.53 and 11.58 is lower than the dimensionless velocity shown in Figure 4. The neutral levels
centerline velocity measured with unheated manikin and with- increased from 0.8 m (2.625ft) to 1.1m (3.609ft) when person-
out manikin. Clear deformation of the velocity profiles and alized airflow rates increased from 4 L/s (8.48cfm) to 16 L/s
reduction of the centerline velocity due to the impact of the (33.91cfm), as shown in Table 3; the stronger the personalized
interaction of the personalized airflow and thermal plume airflow was, the easier it could offset the opposing thermal
from the manikin was observed at a distance of x/D= 8.42 [0.8 plume generated by the heated manikin.
m (2.625 ft)] that is much closer to the nozzle exit, i.e. further Based on plots similar to the one shown in Figure 4, it was
from the manikin’s head [0.5 m (1.64ft)], than in the case of observed that the blockage effect of the unheated manikin and
unheated manikin. As expected, stronger deformation of the neutral level appeared at the same cross section at 16 L/s
velocity field of the personalized airflow was seen at low (33.91cfm) personalized airflow rate, which confirms that the
airflow rates, because the personalized airflow was not strong personalized airflow at 16 L/s (33.91cfm) was strong enough
enough to offset the thermal plume close to the manikin, i.e. to destroy the thermal plume.
the strength of the thermal plume (centerline velocity of about
0.25 m/s (0.82fps)) was comparable to the strength of the Heat Loss from Manikin’s Body
personalized airflow (centerline velocity of 0.3 m/s The interaction of the personalized airflow with the ther-
mal plume generated by the manikin had direct effect on the
equivalent temperature determined by the manikin. Figure 5
shows the difference in segmented equivalent temperature
determined from the reference measurement, i.e. without
personalized airflow, and the measurements with personalized
jet at different airflow rates under 23.5°C (74.3°F)/21°C
(69.8°F) temperature combination. As expected, the results
identify that the head region of the manikin (scull, left/right
face, back of the neck) were the body segments most cooled by
the personalized airflow. For left/right face, ΔTeq changed
from -1°C (-1.8°F) to -6°C (-10.8°F) under 23.5°C (74.3°F)/
21°C (69.8°F) case and from -0.5°C (-0.9°F) to -4°C (-7.2°F)
under 26°C (78.8°F)/26°C (78.8°F) case when the PV airflow
rate increased. These are the two extreme cases among the four
cases. For scull, ΔTeq changed from -0.5°C (-0.9°F) to -4°C (-
Figure 4 Comparison of centreline velocity distribution: 7.2°F) under 23.5°C (74.3°F)/21°C (69.8°F) case and from -
V (m/s)—centreline mean velocity; V0 (m/s)— 0.25°C (-0.45°F) to -2°C (-3.6°F) under 26°C (78.8°F)/26°C
mean velocity at nozzle outlet; X (m)—distance (78.8°F) case. For back of the neck, ΔTeq changed from -0.7 °C
between measuring point and nozzle outlet; (-1.26°F) to -4.5°C (-8.1°F) under 23.5°C (74.3°F)/21°C
D (m)—nozzle diameter. (69.8°F) case and from -0.5°C (-0.9°F) to -2.5°C (-4.5°F)

Table 2. Centreline Velocity and Reduction Ratio of Centreline Velocity at 0.2m (0.656ft) above Manikin’s Head

4L/s, cfm 8L/s, cfm 12L/s, cfm 16L/s, cfm


Centerline velocity without manikin (m/s, fps) 0.29 (0.951) 0.49 (1.608) 0.7 (2.297) 0.92 (3.018)
Centerline velocity with unheated manikin (m/s, fps) 0.24 (0.787) 0.42 (1.378) 0.6 (1.969) 0.81 (2.657)
Reduction ratio (%) 82.8 85.7 85.7 88.0

Table 3. Dimensionless Neutral Level as a Function of Personalized Airflow Rates

PV air flow rate (L/s, cfm) 4 (8.48) 8 (16.95) 12 (25.43) 16 (33.91)


Dimensionless neutral level (Xn/D) 8.42 9.47 10.53 11.58
Note:Xnl (m) – neutral level; D (m) – nozzle diameter

ASHRAE Transactions 399


Figure 5 Cooling effect analysis under 23.5°C/21°C temperature combination.

under 26°C (78.8°F)/26°C (78.8°F) case. This means that the personalized air and by 4°C (7.2°F) at 23.5°C (74.3°F) person-
cooling due to the personalized airflow was as much as the alized air when room air temperature was 23.5°C (74.3°F).
cooling which would be obtained when corresponding room The segmented equivalent temperature at the face decreased
air temperature drop was achieved. For left and right chest, by 3.4°C (6.12°F) at 23.5°C (74.3°F) personalized air and by
ΔTeq changed from -0.5°C (-0.9°F) to -3.5°C (-6.3°F) under 3.3°C (5.94°F) at 26°C (78.8°F) personalized air when room
23.5°C (74.3°F)/21°C (69.8°F) case and from -0.25°C (- air temperature was 26°C (78.8°F). This indicates that the
0.45°F) to -2°C (-3.6°F) under 26°C (78.8°F)/26°C (78.8°F) influence of personalized air temperature on equivalent
case, when the airflow rate increased. The cooling effect of temperature at the face becomes striking when room air
whole body was smaller, from -0.25°C (-0.45°F) to -2°C (- temperature becomes low. Due to an increase in the airflow
3.6°F) under 23.5°C (74.3°F)/21°C (69.8°F) case and from - rate, the segmented equivalent temperature at the face
0.1°C (-0.18°F) to -1.5°C (-2.7°F) under 26°C (78.8°F)/26°C decreased by 4°C (7.2°F) at 23.5°C (74.3°F) room air temper-
(78.8°F) case, when the PV airflow rate increased. Figure 6 ature and by 3.4°C (6.12°F) at 26°C (78.8°F) room air temper-
shows the difference in segmented equivalent temperature ature when personalized air temperature was 23.5°C (74.3°F).
determined from the reference measurement, i.e. without This indicates that the equivalent temperature at the face was
personalized airflow, and the measurements with personalized also affected by room air temperature. The lowest whole-body
jet at different PV/ambient temperature combinations under equivalent temperature is 21.5°C (70.7°F) at 23.5°C (74.3°F)/
16 L/s (33.91cfm) PV airflow rates. Under the lowest person- 21°C (69.8°F) temperature combination and 24.3°C (75.74°F)
alized airflow rates 4 L/s (8.48cfm), ΔTeq changed from -0.6°C at 26°C (78.8°F)/23.5°C (74.3°F) temperature combination.
(-1.08°F) to -1.1°C (-1.98°F), from -0.2°C (-0.36°F) to -0.6°C
(-1.08°F), from -0.3°C (-0.54°F) to -0.7°C (-1.26°F) and from Because of obvious cooling effects of the face and the
-0.3°C (-0.54°F) to -0.7°C (-1.26°F) for left/right face, for chest, six body segments were selected for further analysis,
scull, for back of the neck, for left and right chest, respectively. including the scull, the left face, the right face, the back of
Under the highest personalized airflow rates 16 L/s neck, the left chest and the right chest. The results from the
(33.91cfm), ΔTeq changed from -4°C (-7.2°F) to -6.2°C (- analyses of the results for these body segments are shown in
11.16°F), from -2°C-3.6°F) to -4.5°C (-8.1°F), from -2.5°C (- Figures 7 and 8. The decrease of the equivalent temperature in
4.5°F) to -4.7°C (-8.46°F) and from -2.5°C (-4.5°F) to -4°C (- comparison with the reference case without personalized
7.2°F) for left/right face, for scull, for back of the neck, for left airflow is shown in the figures. The results in the figures reveal
and right chest, respectively. that the influence of the PV airflow rate is not striking when
The impact of PV/Ambient temperature combination on it is lower than 8 L/s. This influence becomes obvious when
the equivalent temperature was demonstrated. Due to an PV airflow rate is greater than 12 L/s (25.43cfm) especially at
increase in the airflow rate, the segmented equivalent temper- personalized air temperature of 21°C (69.8°F). The ranges of
ature at the face decreased by 5°C (9°F) at 21°C (69.8°F) the equivalent temperature determined for the selected six

400 ASHRAE Transactions


Figure 6 Cooling effect analysis under 16 L/s PV airflow rate.

Figure 7 Cooling effect analysis under different personalized airflow rates.

body segments at the four temperature combinations studied decreased by 4°C (7.2°F) when the airflow rate increased and
when the personalized airflow changed from 4 L/s (8.48cfm) by 5°C (9°F) to 6°C (10.8°F) at 23.5°C (74.3°F) room air
to 16 L/s (33.91cfm) are shown in Figure 9. Figure 10 shows temperature (Figure 9). The cooling effect of the increased
the ranges of equivalent temperature obtained for the 4, 8, 12 airflow rate on the remaining four body segments was about
and 16 L/s (8.48, 16.95, 25.43 and 33.91 cfm) at the temper- 2°C (3.6°F) at 26°C (78.8°F) room air temperature and 3°C
ature combinations studied. The left face and the right face are (5.4°F) to 4°C (7.2°F) at 23.5°C (74.3°F) room air tempera-
the two body segments cooled mostly when the airflow ture. The influence of the PV airflow rate on the equivalent
increased from 4 L/s (8.48cfm) to 16 L/s (33.91cfm). At 26°C temperature becomes obvious when PV airflow rate is greater
(78.8°F). the equivalent temperature for the left and right face than 12 L/s (25.43cfm) (Figure 10). The decrease in the

ASHRAE Transactions 401


Figure 8 Cooling effect analysis under different ambient/PV temperature combinations.

Figure 9 Ranges of segmented equivalent temperature determined at four PV/ambient temperature combinations when PV
airflow rate was changed from 4 L/s to 16 L/s. Each line end indicates the highest and lowest of ET.

equivalent temperature is largest when the PV airflow rate i.e. ΔTeq, at personalized airflow rate at 16 L/s (33.91 cfm) and
changes from 12 L/s (25.43cfm) to 16 L/s (33.91cfm), i.e. the different temperature combinations is shown in Figure 11. The
penetration effect of the personalized air over thermal plume cooling effect decreased with the decrease of the airflow rate
felt at 8 L/s (16.95 cfm) increases with the increase of the however the impact of the positioning of the manikin on the
airflow rate and causes more cooling of the body. cooling of the body segments was the same. When the manikin
The impact of the body positioning with regard to the was moved forward or backward, the cooling effect was
personalized airflow on its cooling was studied under all reduced for the body segments remaining outside the person-
experimental conditions. The asymmetrical cooling effect of alized airflow. As expected, positioning the manikin sideward,
the body was strongest at high airflow rate. The cooling effect, caused asymmetry in the cooling of the face, the hands, the

402 ASHRAE Transactions


Figure 10 Ranges of segmented equivalent temperature determined at four PV airflow rates under four different PV/ambient
temperature combinations. Each line end indicates the highest and lowest of ET.

Figure 11 Occupant movement analysis under 16 L/s personalized airflow rate and different temperature combinations.

forearm, the upper arm and the chest. Moving the manikin DISCUSSION
forward decreased mostly the cooling effect of the personal- The airflow rate and the temperature of the personalized
ized airflow for the whole body because the lower body part air and the ambient air temperature influenced the cooling
was moved away from the jet. The cooling effect determined effect of the jet from the ceiling mounted nozzle. For the
at 23.5°C (74.3°F)/21°C (69.8°F) temperature combination ranges of these three parameters studied, the personalized
and different personalized airflow rates is shown in Figure 12. airflow rate is the most important factor which influences the
The asymmetry in the local cooling of the body increased with equivalent temperature, i.e. the heat loss from the manikins’
the increase of the airflow rate, especially above 8 L/s body. The cooling of the body segments was strongly asym-
(16.95 cfm). metrical, i.e. the head (scull, left/right face, back of neck) and

ASHRAE Transactions 403


Figure 12 Occupant movement analysis under 23.5°C/21°C temperature combination and different personalized airflow rates.

left/right chest were the most cooled body segments. For alent temperature obtained for the face with desk mounted PV
example, the equivalent temperature at the face decreased at 23.5°C (74.3°F)/21°C (69.8°F) with personalized flow rate
from 3°C (5.4°F) to 5°C (9°F) in comparison with the refer- of 16 (33.91) L/s (cfm) as reported by Gong et al. (2006) was
ence condition without personalized airflow when personal- 4°C (7.2°F) lower than the equivalent temperature obtained in
ized airflow rate changes from 4 L/s (8.48cfm) to 16 L/s this study with ceiling mounted nozzle.
(33.91cfm). For the face segment, the equivalent temperature The pressure exercised by the personalized airflow
decreased by 0.5°C (0.9°F) when the personalized airflow locally on the body (mainly the top of the head), will be
increased by 1L/s (2.119cfm) under the temperature condi- another factor which will influence the human response to the
tions 23.5°C (74.3°F)/21°C (69.8°F) (ambient temperature/ vertically applied personalized airflow and thus the perfor-
PV temperature). The equivalent temperature decreased by mance of personalized ventilation with ceiling mounted
0.3°C (0.54°F) when PV temperature decreased by 1°C nozzles in practice. The results suggest that individual control
(1.8°F) at 16 L/s (33.91 cfm) personalized airflow rates and of the personalized airflow rate is essential in practice for
23.5°C (74.3°F) room air temperature. Similarly, decrease in compensating the large differences which exist between
the equivalent temperature was obtained when at 16 L/s people with regard to preferred thermal sensation and air
(33.91cfm) and 23.5°C (74.3°F) PV temperature the room movement. Individual control of personalized airflow rate
temperature decreased by 1°C (1.8°F). The whole body cool- should also be considered as an important factor in the design
ing was much less affected by the change of the airflow rate of ceiling mounted personalized ventilation nozzles.
than the cooling of the segments directly exposed to the
People, while performing work at their desks, will typi-
personalized flow. The feet, lower legs, back thighs and the
cally move their body and this will affect the interaction of the
back side of the manikin’s body were almost not cooled (ΔTeq
thermal plume above the body with the personalized airflow
< 0.2°C (0.36°F)) and the hands, forearms, upper arms and
from the ceiling. The asymmetrical cooling effect of the body
back were cooled only slightly (ΔTeq <0.5°C (0.9°F)) by the
increased when personalized airflow rate increased. For the
personalized airflow. The identified large asymmetry in the
cases introducing the movement of manikin forward or back-
body cooling suggest that in practice the maximum cooling of
ward, cooling effect of corresponding body segments moving
individually controlled personalized air flow from ceiling
outside the personalized airflow was reduced. As expected, for
mounted nozzles will be limited due to the risk of local thermal
the cases of moving the manikin sideward, obvious asymme-
discomfort for the occupants.
try for cooling effect was observed in the following body
Due to the positioning of the air supply nozzles far from segments: face, hand, forearm, upper arm and chest. For
the occupant, the cooling effect of ceiling mounted personal- whole-body cooling effect, the case of moving the manikin
ized ventilation system is lower than the cooling effect of desk forward was the worst case because lower body part was
mounted PV system. For example, the manikin based equiv- moved far away from the jet target area.

404 ASHRAE Transactions


For energy conservation purpose, supplying warmer which influences the equivalent temperature, i.e. the heat loss
personalized air is better than supplying cooler personalized from manikins’ body.
air so as to obtaining the same cooling effect. The largest Obvious asymmetry for cooling effect was observed
equivalent temperature differences obtained for different body when manikin was moved forward, backward and sideward.
segments change from -1°C (-1.8°F) to -6°C (-10.8°F) under The whole-body cooling effect of the personalized airflow was
23.5°C (74.3°F)/21°C (69.8°F) temperature combination minimal when the manikin was moved forward and its lower
when personalized airflow rates increase from 4 L/s (8.48 cfm) body part remain out of the jet.
to 16 L/s (33.91 cfm). 23.5°C (74.3°F)/21°C (69.8°F) temper- The findings presented in this paper pertain to a ceiling
ature combination is the case which can achieve highest cool- mounted PV nozzle working in conjunction with a ceiling
ing asymmetry among the 4 temperature combinations. 16 L/ supply mixing ventilation system If a different type of room
s (33.91 cfm) personalized airflow rate, which can destroy ventilation diffuser or ventilation strategy is employed the
thermal plume completely, is suggested as maximum airflow results would likely be somewhat different. However, a ceiling
rate acceptable to people. mounted nozzle with high supply momentum would minimize
the influence from other diffusers, either adjacent ones or
CONCLUSION those that are used as displacement ventilation or under-floor
The interaction of personalized airflow supplied from the air distribution diffusers. It is to be noted that the farther the
ceiling mounted circular nozzle with a seated full size thermal distance between ceiling mounted nozzles and normal diffus-
manikin was studied with respect to the airflow distribution ers, less will be the influence.
and its body cooling effect.
REFERENCES
The blocking effect of unheated manikin on the person-
alized airflow supplied from above was observed up to 0.2m Awbi H.B. 2003. Ventilation of Buildings. London and New
(0.656ft) above manikin’s head and was not affected by the York: Spon Press.
personalized airflow rate. The centerline velocity was reduced Azer N.Z., McNall P.E. and Leung H.C. 1971. Physiological
by 85%. effects of localized ventilation. Journal of Applied Phys-
The neutral level obtained with heated manikin increased iology, 31 (5), 669-674.
from 0.8m (2.625ft) to 1.1m (3.609ft) with the increase of the Azer N.Z., Nevins R.G., Olesen S. and Leung H.C. 1972.
airflow rate. Improvements in sensory votes and their associated
Under the set-up used in the present study, personalized physiological responses by localized ventilation in hot
airflow at 16 L/s (33.91cfm) was strong enough to destroy the environments. Symposium on thermal comfort and
thermal plume from the manikin and to efficiently provide moderate heat stress, CIB Commission W45, September
cooling to manikin’s body. 13-15, 149-163.
The scull, the left/right face and the back of neck were the Azer N.Z. and Nevins R.G. 1974. Physiological effects of
body segments most cooled by the personalized airflow. The locally cooling the head in 95F and 75% RH environ-
cooling effect increased with the increase of the personalized ment. ASHRAE Transactions, 80 (1), 1-8.
airflow rate and the decrease of the room and personalized air Faulkner D, Fisk W.J., Sullivan D.P., Wyon D.P. 1999. Venti-
temperature. The maximum cooling of the left/right face lation efficiency of desk-mounted task/ambient condi-
obtained at room temperature of 23.5°C (74.3°F) and person- tioning systems. Indoor Air, 9, 273-281.
alized airflow with temperature of 21°C (69.8°F) and airflow Gong N., Tham K.W., Melikov A., Wyon D.P., Sekhar S.C.
rate of 16 L/s (33.91 cfm) was comparable with the cooling and Cheong K.W. 2006. The acceptable air velocity
effect caused by 6°C (10.8°F) decrease of the room air temper- range for local air movement in the tropics. HVAC&R
ature without personalized airflow. The cooling effect of the Research, 12 (4), 1065-1076.
personalized airflow on the whole body was smaller. Kaczmarczyk J., Melikov A., Fanger P.O. 2004. Human
The influence of personalized air temperature on equiv- response to personalized and mixing ventilation. Indoor
alent temperature at the face becomes striking when room air Air, 14 (suppl.8), 1-13.
temperature becomes low. The equivalent temperature at the Hyldgaard, C.E., Thermal Plumes above a person, Proc.
face was also affected by room air temperature. The lowest of Roomvent’98, Stockholm, Sweden, June 1998, 1,
whole-body equivalent temperature is 21.5°C (70.7°F) at 407-413.
23.5°C (74.3°F)/21°C (69.8°F) temperature combination and Kaczmarczyk, J., Melikov, A., Bolashikov, Z., Nikolaev, L.
24.3°C (75.74°F) at 26°C (78.8°F)/23.5°C (74.3°F) temper- and Fanger, P.O. 2006. Human response to five designs
ature combination. Personalized airflow rate is the most of personalized ventilation. International Journal of
important factor which influences the equivalent temperature Heating, Ventilation and Refrigeration Research, 12 (2),
the most. 367-384.
For the ranges of change of these three parameters stud- Ma, R.M. and Qin H. 1991. Experimental study of the per-
ied, the personalized airflow rate is the most important factor formance and thermal comfort of a spot cooling system.

ASHRAE Transactions 405


IAQ 91, Healthy Buildings, 186-191. Atlanta: mounted and floor-mounted task/ambient condition-
ASHRAE. ing (TAC) systems. In: Proceedings of Indoor Air,
Melikov, A., Helkjaer, L., Arakelian, R. and Fanger, P.O. Edinburgh, 2, 368-373.
1994. Spot Cooling - Part 1: Human response to cooling Yang B., Melikov A. and Sekhar S.C. 2008. Cooling effect
with air jet. ASHRAE Transactions, 100 (2), 476-499. of ceiling mounted personalized ventilation system. In:
Melikov, A., Halkjaer, L., Arakelian, R. and Fanger, P.O. Proceedings of Indoor Air, Copenhagen, Paper ID: 852.
1994. Spot Cooling - Part 2: Recommendations for Zukowska D., Popiolek Z., Melikov A.K. 2007. Impact of
design of spot cooling systems. ASHRAE Transactions, personal factors and furniture arrangement on the
100 (2), 500-510. thermal plume above a human body. In: Proceedings
Melikov A., Cermak R., Mayer M. 2002. Personalized venti- of the 10th International Conference on Air Distribu-
lation: Evaluation of different air terminal devices. tion in Rooms - Roomvent 2007, Helsinki, Session
Energy and Buildings, 34, 829-836. C02, paper 1017.
Nilson H., Holmer I., Bohm M. and Noren O. 1999. Defini-
Zukowska, D., Melikov, A.K., Popiolek, Z., 2007, Ther-
tion and theoretical background of the equivalent tem-
mal plume above a simulated sitting person with dif-
perature. In: Proceedings of the 6th international
ferent complexity of body geometry, In: Proceedings
conference FLORENCE ATA, Firenze, Italy, EQUIV
of the 10th International Conference on Air Distribu-
Seminar 2.
tion in Rooms - Roomvent 2007, Helsinki, session
Olesen B.W. and Nielsen R. 1980. Spot cooling of work C02, paper 1016.
places in hot industries. Final report of research program
“Ergonomics-Rehabilitation III,” No. 7245-35-9-004. DISCUSSION
Lyngby: Laboratory of Heating and Air Conditioning,
Technical University of Denmark. John Zhai, Assistant Professor, University of Colorado at
Olesen B.W. and Nielsen R. 1983. Convective spot cooling Boulder, Boulder, CO: For a ceiling-mounted PV system,
of hot working environments. In: Proceedings of the what about the thermal comfort performance related to draft
16th international conference of Refrigeration, Commis- issue and the IAQ performance due to the offset of downward
sion E1, Paris, 201-207. cool jet flow and upward human thermal plume?
Sekhar S.C., Gong N., Tham K.W., Cheong K.W., Melikov Bin Yang: Corresponding human subjective assessments
A., Wyon D.P. and Fanger P.O. 2005. Findings of per- under this new system were done by introducing 32 tropically
sonalized ventilation studies in a hot and humid climate. acclimatized persons. The local and whole body thermal
HVAC&R Research, 11 (4), 603-620. sensation decreased when PV airflow rates increased. No draft
Tanabe S., Arens E. A., Bauman F. S., Zhang H. and Madsen sensation was observed, even under high PV airflow rates and
T. L. 1994. Evaluating thermal environments by using a a low PV supply air temperature. Inhaled air quality improved
thermal manikin with controlled skin surface tempera- when PV airflow rates increased. Compared with conven-
ture. ASHRAE Transactions, 100 (1), 39 – 48. tional mixing ventilation systems, the improvement of inhaled
Tsuzuki K., Arens E.A., Bauman F.S., Wyon D.P. 1999. air quality was validated by both objective tracer gas measure-
Individual thermal comfort control with desk- ments and human subjective assessments.

406 ASHRAE Transactions


Copyright of ASHRAE Transactions is the property of ASHRAE and its content may not be copied or emailed
to multiple sites or posted to a listserv without the copyright holder's express written permission. However,
users may print, download, or email articles for individual use.

View publication stats

Das könnte Ihnen auch gefallen