TEST REPORT

Standard as per : BS 6004 & BDS 900 & IEC 60227 Date : 29.11.2017
Size of Cable : 1x400 rm (Sq. mm) Colour : Black
Type of Cable : BAYA / AAC Locast Length : 1010 Meter
Voltage Grade : 450/750 V Party : BAY Agro Industries Ltd, Thakur
Sl. Description of test Unit Required
No. Value

Nominal Cross-sectional Area of Conductor mm2 400


Number of core no. 1
Conductor
Material - Aluminium

Stranded
Shape of conductor -
Circular
01 Physical Test
Minimum Number of wire no. 53
Insulation

Material - PVC
Nominal thickness mm 2.6
Minimum thickness mm 2.24

Approximate overall diameter mm 31.20


Max. D.C. Resistance of conductor at 20oC Ω/km 0.0778
Min. Insulation resistance constant ki at 20⁰ C MΩ-km 35.0
02 Electrical Test
A.C. Voltage Test kV 3.0
Spark Test (A.C.) kV 25.0
Before ageing
03 Mechanical Test Min. Tensile Strength of Insulation N/mm2 12.5
Min. Elongation of Insulation % 150

Flame propagation of a single cable

04 Flame Test a. The test if the distance between the lower


edge of the top support and the onset of mm 50
charging is greater than 50mm
Remerks: The above test results are found Passed.

Tested by- Checked by-

Md. Lutfor Rahman Md. Sarowar Hossain


Supervisor (QC) Asst. Engineer (QC)
AY Agro Industries Ltd, Thakurgoan
Observed
Value

400
1

Aluminium

Stranded Circular

61

PVC
2.68
2.57

31.30
0.0675
127.00
Withstood
Withstood

15.34
238

376.00
Md. Iqbal Hasan
Engineer (QC)