Sie sind auf Seite 1von 1

TEST REPORT

Standard as per : BDS 899-3, BS-6500 & IEC 60228 Date : 17.04.2018
Size of Cable : 3X1.2 rm (mm2) Color : White
Type of Cable : Flexible Client : Robi Axiata Ltd.
Voltage Grade : 300/500 Volts
SL. Description of test Unit Required Value Observed Value
No.
Visual Check - Smooth OK
Nominal cross-sectional area of conductor mm² 1.2 1.2
Number of core’s no. 03 03
Color of core’s - Red, Yellow & Blue Red, Yellow & Blue
Conductor: (Class-5)
Material - Copper Copper
Physical Test
01 Shape of conductor - Stranded Stranded
circular circular
Number of wire no. 40 40
Diameter of Wire 0.193 0.193
Insulation:-
Material - PVC PVC
Nominal thickness of insulation mm 0.80 0.81
Minimum Thickness of Insulation mm 0.62 0.78
Sheath:-
Material - PVC PVC

Nominal thickness of Sheath mm 0.9 0.92


Minimum Thickness of Sheath mm 0.67 0.89
Approximate overall diameter of cable mm 8.0 8.05-8.10
Max.m D.C resistance of conductor at 20⁰ C Ω/Km 16.44 15.85
m
Electrical Test Min. Insulation resistance constant ki at 20⁰ C MΩ.km 35 128
02
A.C High Voltage Test for 05 minutes 1.5 kv No Break Down Withstood
Before ageing:
03 Mechanical Min. Tensile strength of PVC nsulation N/ mm² 12.5 15.65
Test Min. Elongation of PVC Insulation % 150 232
Min. Tensile strength of PVC Sheath N/ mm² 12.5 15.95
Min. Elongation of PVC Sheath % 150 235
04 Flame Test Unaffected portion from lower edge of the clamp mm 50 387
should be minimum 50 mm

Remarks: The above test results are found Passed.

Tested By─ Checked by ─

Md. Lutfor Rahman Jamil Sharif


Md Iqbal Hasan
Supervisor (QC) Asst. Engr. (QC)
Asst. Manager (QC)