Min/Max actuators 2.

2 –
TOC

X XMin/Max actuatorstestregistrierung

Actuators
for CAV controllers
Type: Min/Max actuators
2

For constant volume flows with min/max switching in


air conditioning systems
Actuators for mechanical self-powered CAV controllers Type EN, RN, or VFC,
and for flow adjustment dampers Type VFR
Switching between two volume flow setpoint values, e.g. for daytime
and night-time operation
Supply voltage 24 V AC/DC or 230 V AC
Control input signal: 1-wire control or 2-wire control (3-point)
Potentiometer or mechanical stops
Positive lock connection with CAV controller
Retrofit possible

04/2013 – DE/en K5 – 2.2 – 1


Actuators for CAV controllers
TOC

General information Min/Max actuators

Type Page
Min/Max actuators General information 2.2 – 2
Special information – B5* 2.2 – 4
Special information – B6* 2.2 – 5
Special information – B2* 2.2 – 6
Special information – E01 2.2 – 7
Special information – M01 2.2 – 8
Special information – E02 2.2 – 9
2 Special information – M02 2.2 – 10

Basic information and nomenclature 2.3 – 1

Description Application Parts and characteristics


– Actuators for min/max switching – Potentiometer or mechanical stops for setting
– Switching between volume flow setpoint values the volume flow rate setpoints
of mechanical self-powered CAV controllers – Supply voltage 24 V AC/DC or 230 V AC
Type RN, EN or VFC – Overload protection
– Change of the damper blade positions of flow – 1-wire control or 2-wire control (3-point)
adjustment dampers Type VFR – Optional auxiliary switch for capturing the end
positions

Any attachments are Actuators for volume flow controllers Type RN or EN


defined with the order
code of the CAV Actuator Auxiliary switch
Order code detail
controller. Part number Model Supply voltage Part number Model
B50 M466DT4 LM24A-F 24 V – –
B52 M466DT4 LM24A-F 24 V M536AI3 S2A
B60 M466DT5 LM230A-F 230 V – –
B62 M466DT5 LM230A-F 230 V M536AI3 S2A

Actuators for volume flow controllers Type VFC and for flow adjustment dampers Type VFR
Order code detail Part number Model Setpoint setting Supply voltage
E01 M466EP6 224-024-02 Potentiometer 24 V
M01 M466EP4 CM24-F Mechanical stops 24 V
E02 M466EP8 224-230-02 Potentiometer 230 V
M02 M466EP5 CM230-F Mechanical stops 230 V

K5 – 2.2 – 2 04/2013 – DE/en


Actuators for CAV controllers
TOC

General information Min/Max actuators

Function Functional description


The actuator moves a damper blade or a damper
blade mechanism to the minimum or maximum
position.
Minimum and maximum positions can be set on
potentiometers or using mechanical stops.
1-wire control or 2-wire control (3-point) can be
used.
1-wire control is actually an open/close control or
min/max control.
2
1-wire control 2-wire control (3-point)

S1 S2 S1

1 2 3 1 2 3
N L L N L L
͛ ~ ~ ͛ ~ ~
̋ + + ̋ + +

Switch functions Switch functions


S1 closed: Direction of rotation 1 S1 and S2 open: Actuator has stopped (any position)
S1 open: Direction of rotation 2 S1 closed: Direction of rotation 1
S1 open, S2 closed: Direction of rotation 2

Control input signal for module groups B** and E** Control input signal for attachment group M**
Direction of rotation 1: max Direction of rotation 1: min
Direction of rotation 2: min Direction of rotation 2: max

04/2013 – DE/en K5 – 2.2 – 3


Actuators for CAV controllers
TOC

Special information – B5* Min/Max actuators

Description Application Parts and characteristics


– Actuator LM24A-F for the min/max switching of – Supply voltage 24 V AC/DC
volume flow setpoint values of mechanical self- – 1-wire control or 2-wire control (3-point)
/ B50 powered volume flow controllers Type RN or – Mechanical stops for setting the volume flow
/ B52 EN (only up to a height of 300 mm) rate setpoints
– Direction of action can be reversed
Order code detail Variants – Positive lock connection with damper blade
– B52: with auxiliary switch for capturing the end shaft
positions – Release button to allow for manual operation

2 Commissioning
– Set the mechanical stops according to the
minimum and maximum volume flow rates

Technical data Actuators LM24A and LM24A-F


Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz
Supply voltage (DC) 24 V DC ± 20 %
Power rating (AC) max. 2 VA
Power rating (DC) max. 1 W
Torque 5 Nm
Running time for 90° 150 s
Control input signal 1-wire control or 2-wire control (3-point)
Connecting cable 3 × 0.75 mm², 1 m long
IEC protection class III (protective extra-low voltage)
Protection level IP 54
EC conformity EMC according to 2004/108/EG
Operating temperature –30 to 50 °C
Weight 0.5 kg

Actuator LM24A-F

Electrical connection Connecting cable core identification

BK RD WT

1 2 3
͛ ~ ~
̋ + +

LM24A

1 ⊥, –: Ground, neutral
2 ~, +: Control voltage for direction of rotation 1
3 ~, +: Control voltage for direction of rotation 2

LM24A and LM24A-F

Direction of rotation 1: max


Direction of rotation 2: min

K5 – 2.2 – 4 04/2013 – DE/en


Actuators for CAV controllers
TOC

Special information – B6* Min/Max actuators

Description Application Parts and characteristics


– Actuator LM230A-F for the min/max switching – Supply voltage 230 V AC
of volume flow setpoint values of mechanical – 1-wire control or 2-wire control (3-point)
/ B60 self-powered volume flow controllers Type RN – Mechanical stops for setting the volume flow
/ B62 or EN (only up to a height of 300 mm) rate setpoints
– Direction of action can be reversed
Order code detail Variants – Positive lock connection with damper blade
– B62: with auxiliary switch for capturing the end shaft
positions – Release button to allow for manual operation

Commissioning
– Set the mechanical stops according to the 2
minimum and maximum volume flow rates

Technical data Actuator LM230A


Supply voltage 85 – 265 V AC, 50/60 Hz
Power rating max. 4 VA
Torque 5 Nm
Running time for 90° 150 s
Control input signal 1-wire control or 2-wire control (3-point)
Connecting cable 3 × 0.75 mm², 1 m long
IEC protection class II (protective insulation)
Protection level IP 54
EC conformity EMC to 2004/108/EG, low voltage to 2006/95/EG
Operating temperature –30 to 50 °C
Weight 0.5 kg

Actuator LM230A-F

Electrical connection Connecting cable core identification

BL BR WT

1 2 3
N L L

LM230A

1 N:
N N
Neutrall
2 L: Control voltage for direction of rotation 1
3 L: Control voltage for direction of rotation 2

Direction of rotation 1: max


Direction of rotation 2: min

04/2013 – DE/en K5 – 2.2 – 5


Actuators for CAV controllers
TOC

Special information – B2* Min/Max actuators

Description Application
– Auxiliary switch S2A for capturing damper
/ B52 blade end positions (end positions reached
through actuator operation)
/ B62 – Volt-free contacts for signalling or activating
Order code detail
switch functions
– Two integral switches, e.g. damper blade
OPEN and damper blade CLOSED
– Potentiometer for setting any switch point

2
Auxiliary switch S2A
Type of contact 2 changeover contacts1)
Max. switching voltage (AC) 250 V AC
Max. switching current (AC) 3 A (resistive load); 0.5 A (inductive load)
Max. switching voltage (DC) 110 V DC
Max. switching current (DC) 0.5 A (resistive load); 0.2 A (inductive load)
Connecting cable 6 × 0.75 mm², 1 m long
IEC protection class II (protective insulation)
Protection level IP 54
EC conformity EMC to 2004/108/EG, low voltage to 2006/95/EG
Auxiliary switch S2A
Operating temperature –30 to 50 °C
Weight 0.25 kg
1)
If both auxiliary switches are used the switching voltages must be the same

Connecting cable core identification

Electrical connection
VI RD WT OR PK GR

S1 S2 S3 S4 S5 S6

S2A

S1: Common contact


S2: Mechanical stop 1 < x
S3: Mechanical stop 1 > x
S4: Common contact
S5: Mechanical stop 2 < x
S6: Mechanical stop 2 > x
x: 0 – 100 %

K5 – 2.2 – 6 04/2013 – DE/en


Actuators for CAV controllers
TOC

Special information – E01 Min/Max actuators

Description Application Commissioning


– Actuator 224-024-02-001 for min/max – Use the potentiometer to set the minimum or
switching maximum volume flow rate or the damper
/ E01 – Min/Max switching between volume flow blade position
setpoint values of mechanical self-powered
Order code detail CAV controllers Type VFC
– Min/Max change of the damper blade positions
of flow adjustment dampers Type VFR

Parts and characteristics


– Supply voltage 24 V AC/DC
– 1-wire control or 2-wire control (3-point) 2
– Potentiometer for setting the volume flow rate
setpoints
– Positive lock connection with damper blade
shaft
– Functional test button: Motor drives first to
minimum position, then to maximum position,
then returns to the set position
– Indicator light: Actuator has reached setpoint,
actuator in motion, actuator blocked

Technical data Actuator 224-24-02-001


Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz
Supply voltage (DC) 24 V DC ± 20 %
Power rating (AC) max. 3 VA
Power rating (DC) max. 2 W
Torque 1 Nm
Running time for 90° 20 – 60 s
Control input signal 1-wire control or 2-wire control (3-point)
Connecting cable 3 × 0.75 mm², 1 m long
IEC protection class III (protective extra-low voltage)
Protection level IP 42
Actuator 224-024-02-001
EC conformity EMC according to 2004/108/EG
Operating temperature –30 to 50 °C
Weight 0.30 kg

Electrical connection Connecting cable core identification

BL BR BK

1 2 3
͛ ~ ~
̋ + +

224-24-02-001

1 ⊥, –: Ground, neutral
2 ~, +: Control voltage for direction of rotation 1
3 ~, +: Control voltage for direction of rotation 2

Direction of rotation 1: max


Direction of rotation 2: min

04/2013 – DE/en K5 – 2.2 – 7


Actuators for CAV controllers
TOC

Special information – M01 Min/Max actuators

Description Application Commissioning


– Actuator CM24-F for min/max switching – Set the mechanical stops according to the
– Min/Max switching between volume flow minimum and maximum volume flow rates or
/ M01 setpoint values of mechanical self-powered the damper blade position
CAV controllers Type VFC
Order code detail – Min/Max change of the damper blade positions
of flow adjustment dampers Type VFR

Parts and characteristics


– Supply voltage 24 V AC/DC
2 – 1-wire control or 2-wire control (3-point)
– Mechanical stops for setting the volume flow
rates
– Positive lock connection with damper blade
shaft
– Release button to allow for manual operation

Technical data Actuator CM24-F


Supply voltage (AC) 24 V AC ± 20 %, 50/60 Hz
Supply voltage (DC) 24 V DC ± 20 %
Power rating (AC) max. 1 VA
Power rating (DC) max. 0.5 W
Torque 2 Nm
Running time for 90° 75 s
Control input signal 1-wire control or 2-wire control (3-point)
Connecting cable 3 × 0.75 mm², 1 m long
IEC protection class III (protective extra-low voltage)
Protection level IP 54
EC conformity EMC according to 2004/108/EG
Operating temperature –30 to 50 °C
Weight 0.185 kg

Actuator CM24-F

Electrical connection Connecting cable core identification

BK RD WT

1 2 3
͛ ~ ~
̋ + +

CM24-F

1 ⊥, –: Ground,
G d neutrall
2 ~, +: Control voltage for direction of rotation 1
3 ~, +: Control voltage for direction of rotation 2

Direction of rotation 1: min


Direction of rotation 2: max

K5 – 2.2 – 8 04/2013 – DE/en


Actuators for CAV controllers
TOC

Special information – E02 Min/Max actuators

Description Application Commissioning


– Actuator 224-230-02-002 for min/max – Use the potentiometer to set the minimum or
switching maximum volume flow rate or the damper
/ E02 – Min/Max switching between volume flow blade position
setpoint values of mechanical self-powered
Order code detail CAV controllers Type VFC
– Min/Max change of the damper blade positions
of flow adjustment dampers Type VFR

Parts and characteristics


– Supply voltage 230 V AC
– 1-wire control or 2-wire control (3-point) 2
– Potentiometer for setting the volume flow rate
setpoints
– Positive lock connection with damper blade
shaft
– Functional test button: Motor drives first to
minimum position, then to maximum position,
then returns to the set position
– Indicator light: Actuator has reached setpoint,
actuator in motion, actuator blocked

Technical data Actuator 224-230-02-002


Supply voltage 230 V AC, 50/60 Hz
Power rating 3 VA
Torque 1 Nm
Running time for 90° 20 – 60 s
Control input signal 1-wire control or 2-wire control (3-point)
Connecting cable 3 × 0.75 mm², 1 m long
IEC protection class II (protective insulation)
Protection level IP 42
EC conformity EMC to 2004/108/EG, low voltage to 2006/95/EG
Operating temperature –30 to 50 °C
Actuator 224-230-02-002
Weight 0.30 kg

Electrical connection Connecting cable core identification

BL BR SW

1 2 3
N L L

224-230-02-002

1 N: Neutral
2 L: Control voltage for direction of rotation 1
3 L: Control voltage for direction of rotation 2

Direction of rotation 1: max


Direction of rotation 2: min

04/2013 – DE/en K5 – 2.2 – 9


Actuators for CAV controllers
TOC

Special information – M02 Min/Max actuators

Description Application Commissioning


– Actuator CM230-F for min/max switching – Set the mechanical stops according to the
– Min/Max switching between volume flow minimum and maximum volume flow rates or
/ M02 setpoint values of mechanical self-powered the damper blade position
CAV controllers Type VFC
Order code detail – Min/Max change of the damper blade positions
of flow adjustment dampers Type VFR

Parts and characteristics


– Supply voltage 230 V AC
2 – 1-wire control or 2-wire control (3-point)
– Mechanical stops for setting the volume flow
rate setpoints
– Positive lock connection with damper blade
shaft
– Release button to allow for manual operation

Technical data Actuator CM230-F


Supply voltage 100 to 240 V AC –15 % +10 %, 50/60 Hz
Power rating 3 VA
Torque 2 Nm
Running time for 90° 75 s
Control input signal 1-wire control or 2-wire control (3-point)
Connecting cable 3 × 0.75 mm², 1 m long
IEC protection class II (protective insulation)
Protection level IP 54
EC conformity EMC to 2004/108/EG, low voltage to 2006/95/EG
Operating temperature –30 to 50 °C
Weight 0.185 kg

Actuator CM230-F

Electrical connection Connecting cable core identification

BL BR WT

1 2 3
N L L

CM230-F

1 N: Neutral
2 L: Control voltage for direction of rotation 1
3 L: Control voltage for direction of rotation 2

Direction of rotation 1: min


Direction of rotation 2: max

K5 – 2.2 – 10 04/2013 – DE/en


2.3 –
TOC

X XBasic information and nomenclature testregistrierung

Basic information and


nomenclature
2

Constant volume flow control – CONSTANTFLOW


Product selection
Principal dimensions
Nomenclature
Correction values for system attenuation
Measurements
Sizing and sizing example

04/2013 – DE/en K5 – 2.3 – 1


Constant volume flow control – CONSTANTFLOW
TOC

Basic information and nomenclature

Product selection
Type

RN EN VFL VFC RN-Ex EN-Ex

Type of system
Supply air Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Extract air Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Duct connection,
fan end
2 Circular Ѐ Ѐ Ѐ Ѐ

Rectangular Ѐ Ѐ

Volume flow rate range


Up to [m³/h] 5040 12100 900 1330 5040 12100
Up to [l/s] 1400 3360 250 370 1400 3360
Air quality
Filtered Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Office extract air Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Polluted Ͽ Ͽ Ͽ Ͽ Ͽ Ͽ
Contaminated Ͽ Ͽ Ͽ Ͽ Ͽ Ͽ
Control function
Constant Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Variable Ͽ Ͽ Ͽ
Min/Max Ͽ Ͽ Ͽ
Acoustic requirements
High < 40 dB (A) Ͽ Ͽ Ͽ Ͽ Ͽ
Low < 50 dB (A) Ѐ Ѐ Ѐ Ѐ Ѐ Ѐ

Special areas
Potentially explosive
Ѐ Ѐ
atmospheres
Ѐ Possible
Ͽ Possible under certain conditions: Robust unit variant and/or specific actuator
or useful additional product
Not possible

K5 – 2.3 – 2 04/2013 – DE/en


Constant volume flow control – CONSTANTFLOW
TOC

Basic information and nomenclature

Principal dimensions ØD [mm] B₃ [mm]


Outside diameter of the connecting spigot Unit width

ØD₁ [mm] H [mm]


Pitch circle diameter of flanges Duct height

ØD₂ [mm] H₁ [mm]


Outside diameter of flanges Screw hole pitch of air duct profile (vertical)

ØD₄ [mm] H₂ [mm]

2
Inside diameter of the flange screw holes Outside dimension of air duct profile (height)

L [mm] H₃ [mm]
Length of unit including spigot Unit height

L₁ [mm] n[]
Length of casing or acoustic cladding Number of flange screw holes

W [mm] T [mm]
Width of the duct Flange thickness

B₁ [mm] m [kg]
Screw hole pitch of air duct profile (horizontal) Unit weight including the minimum required
attachments (e.g. Compact controller)
B₂ [mm]
Outside dimension of air duct profile (width)

Nomenclature fm [Hz] nom [m³/h] and [l/s]


Octave band centre frequency Nominal volume flow rate (100 %)

LPA [dB(A)]  [m³/h] and [l/s]


A-weighted sound pressure level of Volume flow rate
air-regenerated noise of the CAV controller,
system attenuation taken into account Δ [± %]
Volume flow rate accuracy
LPA1 [dB(A)]
A-weighted sound pressure level of Δpst [Pa]
air-regenerated noise of the CAV controller with Static differential pressure
secondary silencer, system attenuation taken into
Δpst min [Pa]
account
Minimum static differential pressure
LPA2 [dB(A)]
A-weighted sound pressure level of case- All sound pressure levels are based on 20 μPa.
regenerated noise of the CAV controller, system
attenuation taken into account

LPA3 [dB(A)]
A-weighted sound pressure level of
case-regenerated noise of the CAV controller with
acoustic cladding, system attenuation taken into
account

Definition of noise Static differential pressure

‫ݑ‬

‫ݣ‬ ‫ݢ‬

͍Æst
LPA

① Air-regenerated noise
② Case-radiated noise

04/2013 – DE/en K5 – 2.3 – 3


Constant volume flow control – CONSTANTFLOW
TOC

Basic information and nomenclature

The quick sizing tables Reducing the sound pressure level of the air-regenerated noise
show the sound pressure
levels that can be
expected in a room both
for the air-regenerated
noise and for the case-
radiated noise. The sound
pressure level in a room
results from the sound
power level of the
products – for a given

2 volume flow rate and


differential pressure – and
the attenuation and
insulation on site. This is
why generally accepted
attenuation and insulation
values have been taken
into account for the tables. ‫ݢ‬

The distribution of air ‫ݣ‬


across the ductwork, ‫ݤ‬
‫ݦ‬ ‫ݥ‬
changes of direction, end
reflection, and room
attenuation all affect the
sound pressure level of
the air-regenerated noise.
① VAV terminal unit ④ End reflection
Ceiling insulation and
② Distribution in the ducting ⑤ Ceiling insulation
room attenuation
influence the sound ③ Change of direction
pressure level of the case-
radiated noise.

Correction values for Octave correction for the distribution in the ducting,
acoustic quick sizing used to calculate the air-regenerated noise
The correction values for  [m³/h] 500 1000 1500 2000 2500 3000 4000 5000 6000
the distribution in the [l/s] 140 280 420 550 700 840 1100 1400 1700
ducting are based on the
number of diffusers [dB] 0 3 5 6 7 8 9 10 11
assigned to any one air
terminal unit. If there is
just one diffuser
(assumption: 140 l/s or
500 m³/h), no correction
is necessary.

One change of direction, System attenuation per octave to VDI 2081 for the calculation of the air-regenerated noise
e.g. at the horizontal
connection of the diffuser Centre 63 125 250 500 1000 2000 4000 8000
plenum box, has been frequency ΔL ΔL
taken into consideration [Hz] dB dB dB dB dB dB dB dB
for the system attenuation
values. Vertical Change of
0 0 1 2 3 3 3 3
connection of the plenum direction
box does not result in a End reflection 10 5 2 0 0 0 0 0
system attenuation.
Room
Additional changes of 5 5 5 5 5 5 5 5
attenuation
direction result in lower
sound pressure levels.
Octave correction for the calculation of case-radiated noise

Centre 63 125 250 500 1000 2000 4000 8000


frequency ΔL
[Hz] dB dB dB dB dB dB dB dB
Ceiling
4 4 4 4 4 4 4 4
insulation
Room
5 5 5 5 5 5 5 5
attenuation

K5 – 2.3 – 4 04/2013 – DE/en


Constant volume flow control – CONSTANTFLOW
TOC

Basic information and nomenclature

Measurements Measuring the air-regenerated noise

The acoustic data for the


air-regenerated noise and
case-radiated noise are
determined according to
EN ISO 5135. All
measurements are
carried out in a ‫ݢ‬
reverberation chamber to
EN ISO 3741.

2
‫ݥ‬ ‫ݦ‬ ‫ݣ‬ ‫ݦ‬

‫ݑ‬ ǎÆst
‫ ݤ‬LPA

① Reverberation chamber ④ Fan


② VAV terminal unit ⑤ Sound attenuator
③ Microphone

Measuring the case-radiated noise

‫ݢ‬

‫ݥ‬ ‫ݦ‬

‫ݣ‬

‫ݑ‬ ǎÆst
‫ ݤ‬LPA2

① Reverberation chamber ④ Fan


② VAV terminal unit ⑤ Sound attenuator
③ Microphone

04/2013 – DE/en K5 – 2.3 – 5


Constant volume flow control – CONSTANTFLOW
TOC

Basic information and nomenclature

Sizing with the help of This catalogue provides convenient quick sizing
this catalogue tables for CAV controllers.
The sound pressure levels for air-regenerated
noise and for case-radiated noise are provided for
all nominal sizes. In addition, generally accepted
attenuation and insulation values have been taken
into account.
Sizing data for other volume flow rates and
differential pressures can be determined quickly
and precisely using the Easy Product Finder
2 design programme.

Sizing example Given data


max = 280 l/s (1010 m3/h)
Δpst = 150 Pa
Required sound pressure level in the room 30
dB(A)

Quick sizing
RN/200
Air-regenerated noise LPA = 47 dB(A)
Case-radiated noise LPA = 39 dB(A)

Sound pressure level in the room = 27 dB(A)


(logarithmic addition since the terminal unit is
installed in the suspended ceiling of the room)

Easy Product Finder

The Easy Product Finder


allows you to size
products using your
specific data.

You will find the Easy


Product Finder on our
website.

K5 – 2.3 – 6 04/2013 – DE/en