Sie sind auf Seite 1von 34

CENTRIFUGAL LIQUID CHILLER

WITH ECONOMIZER COMPRESSOR

OPERATION AND MAINTENANCE Supersedes: 160.77-O1 (611) Form 160.77-O1 (1111)

MODEL YKEP
2700 - 3200 TON

LD15101

R-134a

Issue Date:
November 15, 2011
FORM 160.77-O1
ISSUE DATE: 11/15/2011

IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During installation, operation maintenance or service, death to themselves and people at the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized
materials under pressure, rotating components, and operating/service personnel. It is expected that these
both high and low voltage. Each of these items has the individuals possess independent training that will en-
potential, if misused or handled improperly, to cause able them to perform their assigned tasks properly and
bodily injury or death. It is the obligation and respon- safely. It is essential that, prior to performing any task
sibility of operating/service personnel to identify and on this equipment, this individual shall have read and
recognize these inherent hazards, protect themselves, understood this document and any referenced mate-
and proceed safely in completing their tasks. Failure rials. This individual shall also be familiar with and
to comply with any of these requirements could result comply with all applicable governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.

SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:

Indicates a possible hazardous situation Identifies a hazard which could lead to


which will result in death or serious injury damage to the machine, damage to other
if proper care is not taken. equipment and/or environmental pollu-
tion if proper care is not taken or instruc-
tions and are not followed.

Indicates a potentially hazardous situa- Highlights additional information useful


tion which will result in possible injuries to the technician in completing the work
or damage to equipment if proper care is being performed properly.
not taken.

External wiring, unless specified as an optional connection in the manufacturer’s product line, is
not to be connected inside the control panel cabinet. Devices such as relays, switches, transducers
and controls and any external wiring must not be installed inside the control panel. All wiring must
be in accordance with Johnson Controls’ published specifications and must be performed only by
a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting
from improper connections to the controls or application of improper control signals. Failure to
follow this warning will void the manufacturer’s warranty and cause serious damage to property or
personal injury.

2 JOHNSON CONTROLS
FORM 160.77-O1
ISSUE DATE: 11/15/2011

CHANGEABILITY OF THIS DOCUMENT

In complying with Johnson Controls’ policy for con- Operating/service personnel maintain responsibility for
tinuous product improvement, the information con- the applicability of these documents to the equipment.
tained in this document is subject to change without If there is any question regarding the applicability of
notice. Johnson Controls makes no commitment to these documents, the technician should verify whether
update or provide current information automatically to the equipment has been modified and if current litera-
the manual owner. Updated manuals, if applicable, can ture is available from the owner of the equipment prior
be obtained by contacting the nearest Johnson Controls to performing any work on the chiller.
Service office.

ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER

YKEP Installation & Re-assembly 160.77-N1


YKEP Unit Operation & Maintenance 160.77-O1

YKEP Control Center Operation 160.77-O2

YKEP Unit & Control Panel Renewal Parts 160.77-RP1

YKEP Installation Checklist 160.77-CL1

YKEP Startup Checklist 160.77-CL2

YKEP Wiring Diagram - Field Connections 160.77-PW1

YKEP Wiring Diagram - Unit Wiring and Field Control Modification 160.77-PW2

Liquid Cooled Solid State Starter - Operation 160.00-O2

Medium Voltage Variable Speed Drive (2300v - 6600v) - Operation 160.00-O6

Medium Voltage Variable Speed Drive (10,000v - 13,800v) - Operation 160.00-O8

Unit Mounted Medium Voltage Solid State Starter (2300v - 4160v) - Operation 160.00-O7

Long-Term Storage Requirements - General 50.20-NM1

Long-Term Storage Requirements - Field Preparation 50.20-NM5


Long-Term Storage - Periodic Checklist and Logs 50.20-CL5

NOMENCLATURE

LD15116

JOHNSON CONTROLS 3
FORM 160.77-O1
ISSUE DATE: 11/15/2011

THIS PAGE INTENTIONALLY LEFT BLANK

4 JOHNSON CONTROLS
FORM 160.77-O1
ISSUE DATE: 11/15/2011

TABLE OF CONTENTS

SECTION 1 - SYSTEM FUNDAMENTALS................................................................................................................7


General.............................................................................................................................................................. 7
Components...................................................................................................................................................... 7
YKEP System Flow Explanation..................................................................................................................... 12

SECTION 2 - SYSTEM OPERATING PROCEDURES............................................................................................15


Oil Heaters...................................................................................................................................................... 15
Pre-Starting..................................................................................................................................................... 15
Start-Up........................................................................................................................................................... 15
Chiller Operation............................................................................................................................................. 15
Condenser Water Temperature Control........................................................................................................... 16
Operating Logs................................................................................................................................................ 16
Operating Inspections..................................................................................................................................... 16
Need For Maintenance Or Service.................................................................................................................. 18
Stopping The System...................................................................................................................................... 18
Prolonged Shutdown....................................................................................................................................... 18

SECTION 3 - MAINTENANCE.................................................................................................................................19
Renewal Parts................................................................................................................................................. 19
Oil Return System........................................................................................................................................... 19
Checking System For Leaks........................................................................................................................... 21
Conducting An R-22 Pressure Test................................................................................................................. 22
Vacuum Testing............................................................................................................................................... 23
Vacuum Dehydration....................................................................................................................................... 24
Operation......................................................................................................................................................... 24
Refrigerant Charging....................................................................................................................................... 25
Handling Refrigerant For Dismantling And Repairs......................................................................................... 26
Megging The Motor......................................................................................................................................... 26
Condensers And Evaporators......................................................................................................................... 26
Compressors................................................................................................................................................... 28
Electrical Controls........................................................................................................................................... 29
Compressor Motors......................................................................................................................................... 29
Leak Testing.................................................................................................................................................... 29
Evaporator And Condenser............................................................................................................................. 29
Oil Return System........................................................................................................................................... 29
Electrical Controls........................................................................................................................................... 29

SECTION 4 - TROUBLESHOOTING.......................................................................................................................31
SI Metric Conversion....................................................................................................................................... 33
Temperature.................................................................................................................................................... 33

JOHNSON CONTROLS 5
FORM 160.77-O1
ISSUE DATE: 11/15/2011

LIST OF FIGURES

FIGURE 1 - YKEP Chiller Major Components (Front View)��������������������������������������������������������������������������������������7


FIGURE 2 - YKEP Chiller (Rear View)����������������������������������������������������������������������������������������������������������������������8
FIGURE 3 - Medium Voltage VSD����������������������������������������������������������������������������������������������������������������������������8
FIGURE 4 - Medium Voltage SSS�����������������������������������������������������������������������������������������������������������������������������8
FIGURE 5 - YKEP System Flow Diagram���������������������������������������������������������������������������������������������������������������13
FIGURE 6 - Oil Livel Indicator���������������������������������������������������������������������������������������������������������������������������������15
FIGURE 7 - Liquid Chiller Log Sheets���������������������������������������������������������������������������������������������������������������������17
FIGURE 8 - Oil Return System�������������������������������������������������������������������������������������������������������������������������������19
FIGURE 9 - Charging Oil Reservoir With Oil�����������������������������������������������������������������������������������������������������������20
FIGURE 10 - Evacuation of Chiller��������������������������������������������������������������������������������������������������������������������������21
FIGURE 11 - Saturation Curve��������������������������������������������������������������������������������������������������������������������������������23
FIGURE 12 - Megging Motor Windings�������������������������������������������������������������������������������������������������������������������25
FIGURE 13 - Motor Starter Temperature and Insulation Resistances���������������������������������������������������������������������26

LIST OF TABLES

TABLE 1 - System Pressures���������������������������������������������������������������������������������������������������������������������������������22


TABLE 2 - Refrigerant Charge��������������������������������������������������������������������������������������������������������������������������������24
TABLE 3 - Operation Analysis Chart�����������������������������������������������������������������������������������������������������������������������31
TABLE 4 - Analog Input Ranges (Low Pressure Chillers)���������������������������������������������������������������������������������������33

6 JOHNSON CONTROLS
FORM 160.77-O1
ISSUE DATE: 11/15/2011

SECTION 1 - SYSTEM FUNDAMENTALS 1

GENERAL COMPONENTS
The YORK® YKEP Chiller extends the YORK single- YKEP chillers are equipped with:
stage centrifugal chiller product range by providing
additional capacity and greater efficiency through an • Single-Stage Flash Economizer
economized cycle. This is the only product available • Primary Compressor: K7 (Model YDHA119)
that uses a second single-stage compressor to perform
half lift in parallel. The advantage of this cycle is great- • Economizer Compressor: Q3 (Model HF416)
er control flexibility to move the intermediate pressure • YORK Unit-Mounted Low-Voltage Solid State
to maximize efficiency or extend cooling capacity. Starter (LV-SSS) for the economizer compressor
motor.
The primary compressor starter, both compressor mo-
tors, the evaporator, and the condenser are job-specific.
Figure 1 on Page 7 identifies the major YKEP
components, which are described in detail on the fol-
lowing pages.

PRIMARY PRIMARY (K7)


OPEN-DRIVE COMPRESSOR
MOTOR
ECONOMIZER (Q3)
COMPRESSOR

SECONDARY
OPEN-DRIVE
MOTOR
EVAPORATOR

SOLID STATE
STARTER

OIL PUMP
PANEL
CONTROL
PANEL

ECONOMIZER

CONDENSER ISOLATION
VALVE
LD15103

Figure 1 - YKEP CHILLER MAJOR COMPONENTS (FRONT VIEW)

JOHNSON CONTROLS 7
FORM 160.77-O1
Section 1 - System Fundamentals
ISSUE DATE: 11/15/2011

PRIMARY (K7)
COMPRESSOR PRIMARY
OPEN-DRIVE
SECONDARY MOTOR
OPEN-DRIVE
MOTOR

HOT GAS
BYPASS

COMPACT
WATER
BOXES

SIGHT GLASS EVAPORATOR

LD15102
Figure 2 - YKEP CHILLER (REAR VIEW)

Starters
The Economizer compressor motor is always equipped Available YORK starters include a Floor-Mounted
with a YORK Unit-Mounted LV-SSS. Medium-Voltage Variable Speed Drive (MV-VSD)
(Figure 3 on Page 8) and a Unit-Mounted MV-SSS
The Primary compressor motor can be equipped with (Figure 4 on Page 8).
one of two YORK starters, or optionally, supplied by
the customer. Customer-supplied starters must be floor-mounted.

LD15104 LD15105

Figure 3 - MEDIUM VOLTAGE VSD Figure 4 - MEDIUM VOLTAGE SSS

8 JOHNSON CONTROLS
FORM 160.77-O1
Section 1 - System Fundamentals
ISSUE DATE: 11/15/2011

Compressors for the VSD can be found in MV VSD (2300v - 6600v)


- Operation (Form 160.00-O6), and MV VSD (10,000v 1
Two centrifugal compressors are provided, operating
partially in parallel and discharging to a common con- - 13,800v) - Operation (Form 160.00-O8).
denser on the chiller. Check valves are supplied on the
Medium Voltage Solid-State Starter
discharge of the economizer compressor to control re-
frigerant flow during single compressor operation. A Solid-State Starter is a unit mounted reduced volt-
age in-line bypass starter that controls and maintains
Each of the YKEP’s two compressors is a single-stage a constant current flow to the motor during startup.
centrifugal type powered by an open-drive electric mo- Power and control wiring between the starter and
tor. The casing is fully accessible with vertical circular the chiller are factory-installed. Available for 4160V
joints and fabricated of close-grain cast iron. The com- 3-phase 60Hz, 2300V 3-phase 60 Hz or 3300V
plete operating assembly is removable from the com- 3-phase 50 Hz applications, the starter enclosure is
pressor and scroll housing. NEMA-1, with a hinged access door with lock and
key. Electrical lugs for incoming power wiring are not
The rotor assembly consists of a heat-treated alloy steel
provided. Operational information for the solid state
drive shaft and impeller shaft with a high strength, cast
starter can be found in Unit Mounted Medium Volt-
aluminum alloy, fully shrouded impeller. The impeller
age Solid State Starter (2300v - 4160v) - Operation
is designed for balanced thrust and is dynamically bal-
(Form 160.00-O7).
anced and overspeed tested for smooth, vibration free
operation.
Flash Economizer (Intercooler)
The insert-type journal and thrust bearings are fabri- The Flash Economizer is a single-stage type, con-
cated of aluminum alloy and are precision bored and sisting of a horizontal pressure vessel with internally
axially grooved. The specially engineered, single heli- mounted baffles and liquid spray pipe, an externally
cal gears with crowned teeth are designed so that more mounted level transmitter located with a liquid level
than one tooth is in contact at all times to provide even pipe assembly, and an external control valve mounted
distribution of compressor load and quiet operation. in the liquid outlet to the evaporator. Refrigerant from
Gears are integrally assembled in the compressor rotor the condenser, after expanding through the condenser
support and are film lubricated. Each gear is individu- subcooler level control valve, enters through the inter-
ally mounted in its own journal and thrust bearings to nal spray pipe, where flash gas is removed and chan-
isolate it from impeller and motor forces neled through baffles, out the top and on to the econo-
mizer compressor suction. The remaining liquid feeds
Motors out of the economizer through a liquid level control
YORK YKEP centrifugal chillers utilize air-cooled valve to the evaporator.
motors. This means that refrigerant never comes in
contact with the motor. Heat Exchangers
Shells
Starters
Evaporator and condenser shells are fabricated from
Medium Voltage VSD rolled carbon steel plates with fusion welded seams or
A variable speed drive is factory-packaged and con- carbon steel pipe. Carbon steel tube sheets, drilled and
figured for easy remote mounting. It is designed to reamed to accommodate the tubes, are welded to the
vary the compressor motor speed by controlling the end of each shell. Intermediate tube supports are fab-
frequency and voltage of the electrical power to the ricated from carbon steel plates, drilled and reamed to
motor. The adaptive capacity control logic automati- eliminate sharp edges, and spaced no more than four
cally adjusts motor speed and compressor pre-rotation feet apart. The refrigerant side of each shell is designed,
vane position independently for maximum part load ef- tested, and stamped in accordance with ASME Boiler
ficiency by analyzing information fed to it by sensors and Pressure Vessel Code, Section VIII – Division I, or
located throughout the chiller. Operational information other pressure vessel codes, as appropriate.

JOHNSON CONTROLS 9
FORM 160.77-O1
Section 1 - System Fundamentals
ISSUE DATE: 11/15/2011

Tubes C-606 grooves are welded to the water boxes. These


Heat exchanger tubes are state-of-the-art, high-effi- nozzle connections are suitable for ANSI/AWWA
ciency, externally and internally enhanced type to pro- C-606 couplings, welding or flanges, and are capped
vide optimum performance. Tubes in both the evapora- for shipment. Plugged 3/4” (19 mm) drain and vent
tor and condenser are 3/4” (19 mm) O.D. standard or connections are provided in each water box.
1” (25.4 mm) copper alloy and utilize the “skip-fin”
Water Flow Switches
design, providing a smooth internal and external sur-
face at each intermediate tube support. This provides Thermal type water flow switches are factory mounted
extra wall thickness (nearly twice as thick) and non in the chilled and condenser water nozzles, and are fac-
work-hardened copper at the support location, extend- tory wired to the control panel. These solid state flow
ing the life of the heat exchangers. Each tube is roller sensors have a small internal heating-element. They use
expanded into the tube sheets providing a leak-proof the cooling effect of the flowing fluid to sense when
seal, while still individually replaceable. an adequate flow rate has been established. The sealed
sensor probe is 316 stainless steel, which is suited for
Evaporator very high working pressures.
The evaporator is a shell and tube, flooded type heat
Refrigerant Flow Control
exchanger. A distributor trough provides uniform dis-
tribution of refrigerant over the entire shell length to Refrigerant flow to the evaporator is controlled by the
yield optimum heat transfer. A suction baffle or alu- YORK variable orifice control system. Liquid refrig-
minum mesh eliminators are located above the tube erant level is continuously monitored to provide op-
bundle to prevent liquid refrigerant carryover into the timum subcooler, condenser, and evaporator perfor-
compressor. A 1 1/2” (38 mm) liquid level sight glass mance. The variable orifice electronically adjusts to
is conveniently located on the side of the shell. The all real-world operating conditions, providing the most
evaporator shell contains a dual refrigerant relief valve efficient and reliable operation of refrigerant flow con-
arrangement set at 180 psig (12.4 barg); or single-relief trol.
valve arrangement, if the chiller is supplied with the
optional refrigerant isolation valves. A 1” (25.4 mm) Optional Service Isolation Valves
refrigerant charging valve is provided. If your chiller is equipped with optional service iso-
lation valves on the discharge and liquid line, these
Condenser valves must remain open during operation. These
The condenser is a shell and tube type, with a discharge valves are used for isolating the refrigerant charge in
gas baffle to prevent direct high velocity impingement either the evaporator or condenser to allow service ac-
on the tubes. The baffle is also used to distribute the cess to the system. A refrigerant pump-out unit will be
refrigerant gas flow properly for most efficient heat required to isolate the refrigerant.
transfer. An optional cast steel condenser inlet diffuser
may be offered in lieu of the baffle, to provide dynamic Isolation of the refrigerant in this system
pressure recovery and enhanced chiller efficiency. An must be performed by a qualified service
integral subcooler is located at the bottom of the con- technician.
denser shell providing highly effective liquid refriger-
ant subcooling to provide the highest cycle efficiency.
The condenser contains dual refrigerant relief valves
set at 235 psig (16.2 barg). Optional Hot Gas Bypass
Water Boxes The optional hot gas bypass is used to provide greater
turndown than otherwise available for load and head
The removable water boxes are fabricated of steel. The
conditions. The Control Center will automatically
design working pressure is 150 psig (10.3 barg) and
modulate the hot gas valve open and closed as re-
the boxes are tested at 225 psig (15.5 barg). Integral
quired. Adjustment of the hot gas control valve must
steel water baffles are located and welded within the
only be performed by a qualified service technician.
water box to provide the required pass arrangements.
Stub out water nozzle connections with ANSI/AWWA

10 JOHNSON CONTROLS
FORM 160.77-O1
Section 1 - System Fundamentals
ISSUE DATE: 11/15/2011

Control Center The position of the vanes is automatically controlled


through a lever arm attached to an electric motor lo- 1
The chiller is controlled by a stand-alone PLC based
control center. The chiller control center provides all cated outside the compressor housing.
the necessary controls and control logic to provide au- Compressor speed is controlled to overcome aerody-
tomatic start-up, operation, capacity control and safety namic surge and further modulated above the surge
protection of the chiller. limit as part of the capacity control routine.
Control Panel Compressor Lubrication System
For operator interface the control panel includes a The chiller lubrication system consists of the oil pump,
10.4” (264.16 mm) color active matrix display with oil filter, oil cooler and all interconnecting oil piping
integral keypad. The control panel resides in a factory and passages.
wired, unit mounted, NEMA 12, gasketed enclosure.
The enclosure is fabricated 10 gauge steel and includes The submerged oil pump (oil sump) takes suction from
full height front access doors. The panel enclosure is the surrounding oil and discharges it to the oil cooler
painted to match the chiller color on the outside, and where heat is rejected. The oil flows from the oil cooler
gloss white on interior surfaces. All controls are ar- to the oil filter. The oil leaves the filter and flows to the
ranged for easy access and internally wired to clear- emergency oil reservoir where it is distributed to the
ly marked terminal strips or pre-wired PLC interface compressor bearings. The oil lubricates the compressor
modules for external wiring connections. Wiring is rotating components and is returned to the oil sump.
color-coded black (control), white (neutral), and green
There is an emergency oil reservoir located at the high-
(ground), with each wire numerically identified at
est point in the lubrication system internally in the com-
both ends with heat shrinkable wire markers. Wiring
pressor. It provides an oil supply to the various bearings
enclosed in shielded cables and pre-wired cables are
and gears in the event of a system shutdown due to pow-
color coded per the wiring diagram.
er failure. The reservoir allows the oil to be distributed
The screen details all operations and parameters, using through the passages by gravity flow, thus providing
a graphical representation of the chiller and its com- necessary lubrication during compressor coastdown.
ponents. The operator interface is programmed to pro-
vide display of all major operating parameters in both Oil Pump
graphical and list type screen displays. PID control For normal operation, the oil pump should operate at
loop setpoints and Manual/Auto functions are also ac- all times during chiller operation.
complished by the operator interface. Alarm indicators
on the graphic display screen provide annunciation, On shutdown of the system for any reason, the oil
and an alarm history screen is provided which shows pump continues operate for 150 seconds. During this
the most recent alarms, with the time and date of occur- time the system cannot restart.
rence. Trip status screens are provided which show the
Oil Heater
values of all analog inputs at the time of the last five
chiller safety shutdowns. The time and date of the shut- During long idle periods, the oil in the compressor oil
down are also shown. A separate push button is provid- reservoir tends to absorb refrigerant as it can hold, de-
ed on the face of the control panel for Emergency Stop. pending upon the temperature of the oil and the pres-
sure in the reservoir. As the oil temperature is lowered,
Capacity Control System the amount of refrigerant absorbed will be increased. If
The major components of a chiller are selected for full the quantity of refrigerant in the oil becomes excessive,
load capacities at the highest design head, therefore ca- violent oil foaming will result as the pressure within the
pacity must be controlled to maintain a constant chilled system is lowered on starting. This foaming is caused
liquid temperature leaving the evaporator. The YKEP by refrigerant boiling out of the oil as the pressure is
chiller uses a combination of prerotation vanes (PRV) lowered. If this foam reaches the oil pump suction, the
located at the entrance to the compressor impeller, op- bearing oil pressure will fluctuate with possible tempo-
tional hot gas bypass, and variable compressor speed to rary loss of lubrication, causing the oil pressure safety
control capacity. cutout to actuate and stop the system. The oil heater
maintains oil temperature above refrigerant tempera-
ture while shutdown to avoid foaming.

JOHNSON CONTROLS 11
FORM 160.77-O1
Section 1 - System Fundamentals
ISSUE DATE: 11/15/2011

YKEP SYSTEM FLOW EXPLANATION Step 4. Expansion and Economizer


The YORK YKEP chiller operates much the same as The refrigerant liquid from the condenser is partially
the YORK YK Single Stage chiller. The only exception expanded to a pressure intermediate to the evaporator
is a small economizer loop to compress partially ex- and condenser. The partially expanded two phase re-
panded gas to extend capacity and improve efficiency. frigerant is separated to liquid and vapor streams in the
Refer to the illustration in Figure 5 on Page 13 as economizer. The liquid stream is expanded a second
each step in the flow is described. time to repeat the cycle in the evaporator. The vapor
stream is drawn out of the economizer by the econo-
Step 1. Evaporator mizer compressor. Note that the quality of refrigerant
Liquid refrigerant (R134a) flows into the evaporator delivered to the evaporator as a result of economizing
and is distributed for contact to a bundle of tubes that extends the refrigerating effect of the flow through the
carry the chilled liquid for the system. The low pres- evaporator and primary compressor.
sure liquid refrigerant absorbs heat from the chilled
Step 5. Economizer Compressor
liquid causing the refrigerant to boil. The boiled refrig-
erant rises to the top of the tube bundle as vapor and The economizer compressor draws the refrigerant va-
passes through a mesh pad that prevents liquid refrig- por from the economizer. The efficiency benefit of the
erant droplets from being drawn into the compressor. cycle is a result of not having to compressor this gas
over the full head of the chiller system. As in the pri-
Step 2. Primary Compressor mary compressor, centrifugal compression is used to
The refrigerant vapor that has passed through the mesh pressurize the refrigerant and develop flow. The high
pad is drawn up to the compressor. Centrifugal com- pressure vapor refrigerant is then discharged from the
pression is used to pressurize the refrigerant and gen- economizer compressor to the condenser.
erate flow. The high pressure refrigerant vapor is then
discharged from the compressor to the condenser.

Step 3. Condenser
The high pressure refrigerant vapor is distributed
across a bundle of tubes carrying cooling liquid in the
condenser. The high temperature and high pressure re-
frigerant vapor rejects heat to the cooling liquid that
is passing through the tubes. The cooling liquid will
reject its heat to the environment in a cooling tower.
When the refrigerant vapor gives up its heat to the
cooling liquid, it condenses on the outside of the tubes
and drips down to the subcooler. The liquid refrigerant
passes through the subcooler where it rejects more heat
to the cooling liquid as the refrigerant temperature is
reduced.

12 JOHNSON CONTROLS
FORM 160.77-O1
Section 1 - System Fundamentals
ISSUE DATE: 11/15/2011

LD15103

Figure 5 - YKEP SYSTEM FLOW DIAGRAM

JOHNSON CONTROLS 13
FORM 160.77-O1
ISSUE DATE: 11/15/2011

This page intentionally left blank

14 JOHNSON CONTROLS
FORM 160.77-O1
ISSUE DATE: 11/15/2011

SECTION 2 - SYSTEM OPERATING PROCEDURES


OIL HEATERS PRE-STARTING
This section along with the YKEP Startup Checklist Prior to starting the chiller, observe the Control Center
2
(Form 160.77-CL2) details the process and procedures Refer to the YKEP Control Panel Operations Manual
used to startup and operate the YKEP chiller. If the oil (Form 160.77-O2). Make sure the display reads "SYS-
heater is de-energized during a shutdown period, it TEM READY TO START".
must be energized for 12 hours prior to starting com-
pressor, or remove all oil and recharge compressor with Vent any air from the chiller water boxes
new oil. (See Oil Charging Procedure on page 21.) prior to starting the water pumps. Failure
to do so will result in pass baffle damage.
Oil Heater Operation
The oil heater operation is controlled by the YKEP
Control Center. The heater is turned on and off to main-
tain the oil temperature differential to a value 50°F START-UP
(27.8°C) above the condenser saturation temperature.
This target value is maintained by the control panel. 1. If the chilled water pump is manually operated,
start the pump. The Control Center will not al-
If the target value is greater than 160°F (71°C), the tar- low the chiller to start unless chilled liquid flow
get defaults to 160°F (71°C). If the target value is less is established through the unit. If the chilled liq-
than 110°F (43.3°C), it defaults to 110°F (43.3°C). uid pump is wired to the Microcomputer Control
Center, the pump will automatically start; there-
To prevent overheating of the oil in the event of a con-
fore this step is not necessary.
trol center component failure, the oil heater thermostat
(1HTR) is set to open at 180°F (82°C). 2. To start the chiller, press the COMPRESSOR
START button on the control panel. When the
Checking the Oil Level in the Oil Reservoir start switch is energized, the Control Center is
During operation, the proper oil level should fall into placed in an operating mode and any malfunction
the “Operating Range” identified on the vertical oil will be noted by messages on the graphic display.
level indicator label located on the oil reservoir cover For display messages and information pertaining
plate. to the operation of the YKEP Control Center, re-
• If the oil level during operation is in the “Over fer to the YKEP Control Panel Operations Manu-
Full” region of the oil level indicator, oil should al (Form 160.77-O2).
be removed from the oil reservoir.
Any malfunctions which occur during
• If the oil level during operation is in the “Low SHUTDOWN are also displayed and
Oil” region of the oil level indicator, oil should recorded.
be added to the oil reservoir. (See Oil Charging
Procedure, page 20.)

Always comply with EPA and Local regu-


lations when removing or disposing of CHILLER OPERATION
Refrigeration System Oil. The chiller will vary capacity to maintain the leav-
ing CHILLED LIQUID TEMPERATURE setpoint
through a specific sequencing of optional hot gas by-
pass, pre-rotation vanes, and compressor speed.
Throughout capacity control, the compressor speed is
maintained above the minimum required for the pre-
vailing head condition, to avoid surge. Otherwise, the
LD08647
device maintaining capacity is controlled by a pro-
Figure 6 - OIL LIVEL INDICATOR portional-integral-derivative (PID) control based on

JOHNSON CONTROLS 15
FORM 160.77-O1
Section 2 - System Operating Procedures
ISSUE DATE: 11/15/2011

leaving chilled liquid temperature. Pressure and motor denser water temperature) may be an indication of
current overrides also apply as necessary to maintain dirty condenser tubes.
operating limits.
OPERATING INSPECTIONS
CONDENSER WATER TEMPERATURE CONTROL
By following a regular inspection using the display
The YKEP chiller is designed to use less power by tak- readings of the YKEP Control Center, and maintenance
ing advantage of lower than design water temperatures procedure, the operator will ensure smooth operation
that are naturally produced by cooling towers through- of the unit. The following list of inspections and proce-
out the operating year. Exact control of condenser wa- dures should be used as a guide.
ter, such as a cooling tower bypass, is not necessary for
most installations. The minimum entering condenser Daily
water temperature for full and part load conditions is 1. Check the YKEP Control Center displays for sta-
specified in the chiller engineering guide. tus and error messages.
Where: 2. If either compressor is in operation, check the
Min. ECWT = LCWT – C RANGE + 5ºF + 12 ( % Load
)
bearing oil pressure on the SYSTEM screen and
100
then check the oil level in the oil reservoir. The
% Load oil level should be within the operating range as
Min. ECWT = LCWT – C RANGE + 2.8ºC + 6.6 ( 100 )
marked on the oil indicator. Drain or add oil if
necessary.
ECWT = Entering Condensing Water Temperature
LCWT = Leaving Chilled Water Temperature 3. Check the entering and leaving condenser water
C Range = Condensing water temperature range at the pressure and temperatures. Condenser water tem-
given load condition. peratures can be checked on the SYSTEM Screen.
At start-up, the entering condenser water temperature 4. Check the entering and leaving chilled liquid tem-
may be as much as 25°F (14°C) colder than the stand- peratures and evaporator pressure on the SYS-
by return chilled water temperature. Cooling tower fan TEM Screen.
cycling will normally provide adequate control of the 5. Check the condenser saturation temperature
entering condenser water temperature on most instal- (based upon condenser pressure sensed by the
lations. condenser transducer) on the SYSTEM Screen.
OPERATING LOGS 6. Check the compressor discharge temperature on
A permanent daily record of system operating condi- the SYSTEM Screen. During normal operation
tions (temperatures and pressures) recorded at regular discharge temperature should not exceed 220°F
intervals throughout each 24-hour operating period (104°C).
should be kept. Automatic data logging is possible by 7. Check the compressor motor current on the ap-
connecting the optional printer and programming the plicable MOTOR Screen.
DATA LOGGER function. An optional status printer
is available for this purpose. Figure 7 on Page 17 8. Check for signs of dirty or fouled condenser
shows an example log sheet used for recording data tubes. The temperature difference between water
on chiller systems. Log sheets are available in pads leaving the condenser and the saturated condens-
of 50 sheets and may be obtained through the nearest ing temperature should not exceed the difference
YORK/Johnson Controls office; request the Liquid recorded for a new unit by more than 4°F (2.2°C).
Chiller Log Sheets (Form 16.44-F7). Weekly
An accurate record of readings serves as a valuable ref- 1. Check the refrigerant charge. Refer to Checking
erence for operating the system. Readings taken when the Refrigerant Charge During Unit Shutdown in
a system is newly installed will establish normal condi- SECTION 3 - MAINTENANCE.
tions with which to compare later readings.
Monthly
For example, an increase in condenser approach tem-
1. Leak check the entire chiller.
perature (condenser temperature minus leaving con-

16 JOHNSON CONTROLS
FORM 160.77-O1
Section 2 - System Operating Procedures
ISSUE DATE: 11/15/2011

Quarterly 2. Check the Evaporator and Condenser.


1. Perform chemical analysis of oil. a. Inspect and clean water strainers.
Semi-Annually (Or More Often As Required) b. Inspect and clean tubes as required. 2
1. Change and inspect each compressor's oil filter c. Inspect end sheets.
element.
3. Inspect the Compressor Drive Motors (see motor
2. Inspect the Oil return system manufacturers maintenance and service instruc-
a. Change dehydrator tion supplied with the unit).

b. Check nozzle of eductor for foreign particles. a. Meg motor windings – Refer to Figure 12 on
Page 26 for details.
3. Check controls and safety cutouts.
4. Inspect and service electrical components as nec-
Annually (More Often If Necessary) essary.
1. Drain and replace the oil in the compressor oil 5. Perform refrigerant analysis.
sump - refer to Oil Changing Procedure on page
20.

Chiller Location
LIQUID CHILLER LOG SHEET
System No.

Date
Time
Hour Meter Reading
O.A. Temperature Dry Bulb / Wet Bulb / / / / / / / / / /
Oil Level
Oil Pressure
Compressor

Oil Temperature
Suction Temperature
Discharge Temperature
PRV % Open
Volts
Motor
Amps
Refrigerant Suction Pressure
Inlet Temperature
Inlet Pressure
Cooler

Liquid Outlet Temperature


Outlet Pressure
Flowrate - GPM
Discharge Pressure
Refrigerant

Corresponding Temperature
High Pressure Liquid Temperature
System Air - Degrees
Condenser

...an Energ
y-S
Inlet Temperature
approach to aving
Inlet Pressure your
Service ne
eds...
Water

Outlet Temperature
Outlet Pressure
Price $4.50
Flow Rate - GPM
Form 160.4
Issue Date: Supersede 4-F6 (311)
Remarks: March 18, 2011 s 160.44-F6
(579)

Form 160.44-F6 (311)


Supersdes 160.44-F6 (579)
Issue Date: Marh 18, 2011

* NOTE: These items can be printed by an electronic printer connected to the Microboard and
pressing the PRINT key on the Keypad, or automatically using the Data Logger feature.

Figure 7 - LIQUID CHILLER LOG SHEETS

JOHNSON CONTROLS 17
FORM 160.77-O1
Section 2 - System Operating Procedures
ISSUE DATE: 11/15/2011

NEED FOR MAINTENANCE OR SERVICE PROLONGED SHUTDOWN


If the system is malfunctioning in any manner or the If the chiller is to be shut down for an extended period
unit is stopped by a safety shutdown, refer to the Opera- of time (for example, over the winter season), the fol-
tion Analysis Chart shown in SECTION 4 - TROUBLE- lowing procedure should be followed.
SHOOTING Table 3 on Page 31. After consulting
this chart, if you are unable to make the proper repairs 1. Test all system joints for refrigerant leaks with a
or adjustments to start the compressor or the particular leak detector. If any leaks are found, they should
trouble continues to hinder the performance of the unit, be repaired before allowing the system to stand
please call the nearest Johnson Controls District Of- for a long period of time.
fice. Failure to report constant troubles could damage During long idle periods, the tightness of
the unit and increase the cost of repairs. the system should be checked periodically.

STOPPING THE SYSTEM


The YKEP Control Center can be programmed to start
and stop automatically (maximum - once each day).
For more information on this refer to the YKEP Con- 2. If freezing temperatures are expected while the
trol Center Operation Manual (Form 160.77-O2). system is idle, carefully drain the cooling water
from the cooling tower, condenser, condenser
To stop the chiller, proceed as follows: pump, and the chilled water system pump and
1. Push the soft shutdown key on the homescreen of coils.
the Control panel. The compressor will stop auto- Open the drains on the evaporator and condenser
matically. Normal stop raises the driveline to stop liquid heads to assure complete drainage.
and should always be used instead of the E-Stop
during regular operation. 3. Drain the VSD cooling system and/or the Solid
State Starter cooling loop. If freezing tempera-
2. Stop the chilled water pump (if not wired into the tures are expected for periods longer than a few
Control Center, in which case it will shut off auto- days, the refrigerant should be evacuated to con-
matically simultaneously with the oil pump). tainers to prevent leakage from O-ring joints.
BRINE APPLICATIONS When the chill- 4. Open the main disconnect switches to the com-
er is not running, brine should not be run pressor motor, condenser water pump, and the
through the evaporator. However, if there chilled water pump. Open the 115 volt circuit to
is brine running through the evaporator, the Control Center.
there must be flow through the condenser
to prevent tubes from freezing.

3. Open the switch to the cooling tower fan motors,


if used.
In the event of an unusual circumstance
requiring immediate stoppage, an emer-
gency stop switch is located on the side of
the control panel.

18 JOHNSON CONTROLS
FORM 160.77-O1
ISSUE DATE: 11/15/2011

SECTION 3 - MAINTENANCE

RENEWAL PARTS Changing The Dehydrator


For any required Renewal Parts, refer to the YKEP Unit To change the dehydrator, use the following procedure:
Renewal Parts Manual (Form 160.77-RP1).
1. Isolate the dehydrator at the stop valves.
3
OIL RETURN SYSTEM 2. Remove the dehydrator (refer to Figure 8 on Page
The oil return system continuously maintains the prop- 19).
er oil level in the compressor oil sump (See Figure 8 3. Assemble the new filter-drier.
on Page 19).
4. Open evaporator stop valve and check dehydrator
High pressure condenser gas flows continuously connections for refrigerant leaks.
through the eductor inducing the low pressure, oil rich
liquid to flow from the evaporator, through the dehy- 5. Open all the dehydrator stop valves.
drator to the compressor sump.

COMPRESSOR

SOLENOID VALVE

CHECK VALVE OIL EDUCTOR BLOCK

SOLENOID VALVE

STOP VALVE DEHYDRATOR

STOP VALVE

LD08578
Figure 8 - OIL RETURN SYSTEM

JOHNSON CONTROLS 19
FORM 160.77-O1
Section 3 - Maintenance
ISSUE DATE: 11/15/2011

Oil Charge the pump discharge connection to the oil charg-


The YKEP oil system uses YORK “K” type oil. The ing valve located on the remote oil reservoir cover
nominal oil charge for the YKEP compressors is 40 plate (see Figure 8 on Page 19). Do not tighten
gallons. the connection at the charging valve until after the
air is forced out by pumping a few strokes of the
Always use new YORK refrigeration oil in the centrif- oil pump. This fills the lines with oil and prevents
ugal compressor. Oil absorbs moisture when exposed air from being pumped into the system.
to the atmosphere, therefore, it should be kept tightly
3. Open the oil charging valve and pump oil into the
capped until used.
system until oil level in the compressor oil reser-
Oil Charging Procedure voir is in the “Over Full” region of the oil level
indicator label. Close the charging valve and dis-
During operation the compressor oil level must be connect the hand oil pump.
maintained in the “Operating Range” identified on the
vertical oil level indicator (refer to Figure 6 on Page 4. As soon as oil charging is complete, close the
15). If the oil level falls into the lower oil range, it power supply to the starter to energize the oil
is necessary to add oil to the compressor oil reservoir. heater. This will keep the concentration of refrig-
The oil should be charged into the oil reservoir using erant in the oil to a minimum.
the YORK Oil Charging Pump (YORK Part No. 070- When the oil reservoir is initially charged with oil, the
10654). oil pump should be started manually to fill the lines,
Using the following procedures: passages, oil cooler and oil filter. This will lower the oil
level in the reservoir. It may then be necessary to add
1. The unit must be shut down. oil to bring the level back into the “Operating Range”
2. Immerse the suction connection of the oil charging of the oil level indicator label.
pump in a clean container of new oil and connect

OIL RESERVOIR

GAGE LIQUID
LEVEL SIGHT

LD08579

OIL CHARGING VALVE


LD08648

Figure 9 - CHARGING OIL RESERVOIR WITH OIL

20 JOHNSON CONTROLS
FORM 160.77-O1
Section 3 - Maintenance
ISSUE DATE: 11/15/2011

CHECKING SYSTEM FOR LEAKS Do not use carbon tetrachloride for this
purpose since its fumes give the same
Leak Testing During Operation flame discoloration that the refrigerant
The refrigerant side of the system is carefully pressure does.
tested and evacuated at the factory. However, after the
system has been charged, the system should be care-
fully leak tested with a R-134a compatible leak detec- 3. With nitrogen or dry air, blow out the tubes to 3
tor to be sure all joints are tight. clear them of traces of refrigerant laden moisture
If any leaks are found, they must be repaired immedi- from the circulation water.
ately. Usually, leaks can be stopped by tightening flare 4. As soon as the tubes are clear, a cork should be
nuts or flange bolts; however, for any major repair, the driven into each end of the tube.
refrigerant charge must be removed. Refer to Handling
Refrigerant For Dismantling And Repairs in this section. 5. Pressurize the dry system with 50 to 100 PSIG
(345 to 690 kPa) of nitrogen. Repeat this with all
Never perform welding on the chiller un- of the other tubes in the suspected section or, if
less the refrigerant has been completely necessary, with all the tubes in the evaporator or
evacuated and all other safety measures condenser.
have been taken.
6. Allow the evaporator or condenser to remain
corked up to 12 to 24 hours before proceeding.
Depending upon the amount of leakage, the corks
Testing for Evaporator and Condenser Tube may blow from the end of a tube, indicating the
Leaks location of the leakage. If not, if will be neces-
Evaporator and condenser tube leaks in R-134a sys- sary to make a very thorough test with the leak
tems may result in refrigerant leaking into the water detector.
circuit, or water leaking into the shell depending on the
pressure levels. If refrigerant is leaking into the water, 7. After the tubes have been corked for 12 to 24
it can be detected at the liquid head vents after a period hours, it is recommended that two people, work-
of shutdown. If water is leaking into the refrigerant, ing at both ends of the evaporator, carefully test
system capacity and efficiency will drop off sharply. If each tube, – one person removing corks at one
a tube is leaking and water has entered the system, the end and the other at the opposite end to remove
evaporator and condenser should be valved off from corks and handle the leak detector. Start with the
the rest of the water circuit and drained immediately top row of tubes in the section being investigated.
to prevent severe rusting and corrosion. The refriger- Remove the corks at the ends of one tube simul-
ant system should then be drained and purged with dry taneously and insert the exploring tube for 5 sec-
nitrogen to prevent rusting and corrosion. If a tube leak onds – this should be long enough to draw into
is indicated, the exact location of the leak may be de- the detector any refrigerant gas that might have
termined as follows: leaked through the tube walls. A fan placed at the
end of the evaporator opposite the detector will
1. Remove the heads and listen at each section of assure that any leakage will travel through the
tubes for a hissing sound that would indicate gas tube to the detector.
leakage. If the probable location of the leaky tubes
8. Mark any leaking tubes for later identification.
has been determined, treat that section in the fol-
lowing manner (if the location is not definite, all 9. If any of the tube sheet joints are leaking, the leak
the tubes will need to be checked). should be indicated by the detector. If a tube sheet
leak is suspected, its exact location may be found
2. Wash off both tube heads and the ends of all tubes
by using a soap solution. A continuous buildup of
with water.
bubbles around a tube indicates a tube sheet leak.

JOHNSON CONTROLS 21
FORM 160.77-O1
Section 3 - Maintenance
ISSUE DATE: 11/15/2011

LD00949

Figure 10 - EVACUATION OF CHILLER

CONDUCTING AN R-22 PRESSURE TEST


With the R-134a charge removed and all known leaks 3. Test around each joint and factory weld. It is im-
repaired, the system should be charged with a small portant that this test be thoroughly and carefully
amount of R-22 mixed with dry nitrogen so that a ha- done, spending as much time as necessary and us-
lide torch or electronic leak detector can be used to de- ing a good leak detector.
tect any leaks too small to be found by the soap test.
4. To check for refrigerant leaks in the evaporator
To test with R-22, proceed as follows: and condenser, open the vents in the evaporator
and condenser heads and test for the presence of
1. With no pressure in the system, charge R-22 gas refrigerant. If no refrigerant is present, the tubes
into the system through the charging valve to a and tube sheets may be considered tight. If refrig-
pressure of 2 PSIG (14 kPa). erant is detected at the vents, the heads must be
2. Build up the system pressure with dry nitrogen to removed, the leak located (by means of soap test
approximately 75 to 100 PSIG (517 to 690 kPa). or leak detector) and repaired.
To be sure that the concentration of refrigerant has
reached all parts of the system test for the pres-
ence of refrigerant with a leak detector at an ap-
propriate service valve.

22 JOHNSON CONTROLS
FORM 160.77-O1
Section 3 - Maintenance
ISSUE DATE: 11/15/2011

Table 1 - SYSTEM PRESSURES

*GAUGE ABSOLUTE

BOILING
INCHES OF TEMPERATURES
MERCURY (HG) MILLIMETERS OF
BELOW ONE PSIA OF MERCURY MICRONS WATER 3
STANDARD (HG) °F
ATMOSPHERE

0" 14.6960 760.00 760,000 212


10.240" 9.6290 500.00 500,000 192
22.050" 3.8650 200.00 200,000 151
25.980" 1.9350 100.00 100,000 124
27.950" 0.9680 50.00 50,000 101
28.940" 0.4810 25.00 25,000 78
29.530" 0.1920 10.00 10,000 52
29.670" 0.1220 6.30 6,300 40
Water
29.720" 0.0990 5.00 5,000 35
Freezes
29.842" 0.0390 2.00 2,000 15
29.882" 0.0190 1.00 1,000 1
29.901" 0.0100 0.50 500 –11
29.917" 0.0020 0.10 100 –38
29.919" 0.0010 0.05 50 –50
29.9206" 0.0002 0.01 10 –70
29.921" 0 0 0

*One standard atmosphere = 14.696 PSIA NOTES: PSIA = Lbs. per sq. in. gauge pressure
= 760 mm Hg. absolute pressure at 32°F = Pressure above atmosphere
PSIA = Lbs. per sq. in. absolute pressure
= 29.921 inches Hg. absolute at 32°F
= Sum of gauge plus atmospheric
pressure

VACUUM TESTING bulb temperature of +32°F (0°C) or a pressure of


5 mm Hg is reached. Refer to Table 1 on Page
After the pressure test has been completed, the vacuum
23 for corresponding pressure values.
test should be conducted as follows:
4. To improve evacuation circulate hot water, not
1. Connect a high capacity vacuum pump, with in- to exceed 125°F (51.7ºC) through the evapora-
dicator, to the system charging valve as shown in tor and condenser tubes to thoroughly dehydrate
Figure 10 on Page 22 and start the pump. Refer the shells. If a source of hot water is not readily
to Vacuum Dehydration in this section. available, a portable water heater should be em-
2. Be sure all valves to the atmosphere are closed ployed. DO NOT USE STEAM. Another sug-
and then open wide all system valves. gested method is to connect a hose between the
source of hot water under pressure and the evapo-
3. Operate the vacuum pump in accordance with rator head drain connection, out the evaporator
Vacuum Dehydration in this section until a wet vent connection, into the condenser head drain

JOHNSON CONTROLS 23
FORM 160.77-O1
Section 3 - Maintenance
ISSUE DATE: 11/15/2011

and out the condenser vent. To avoid the possi- pressure in the system to a point where its saturation
bility of causing leaks, the temperature should be temperature is considerably below that of room tem-
brought up slowly so that the tubes and shell are perature, heat will flow from the room through the
heated evenly. walls of the system and vaporize the water, allowing
a large percentage of it to be removed by the vacuum
5. Close the system charging valve and the stop
pump. The length of time necessary for the dehydra-
valve between the vacuum indicator and the vac-
tion of a system is dependent on the size or volume of
uum pump. Then disconnect the vacuum pump
the system, the capacity and efficiency of the vacuum
leaving the vacuum indicator in place.
pump, the room temperature and the quantity of water
6. Hold the vacuum pressure obtained in Step 3 in present in the system. By using a vacuum indicator,
the system for 8 hours; the slightest rise in pres- the test tube will be evacuated to the same pressure as
sure indicates a leak or the presence of moisture, the system, and the distilled water will be maintained
or both. If after 24 hours the wet bulb temperature at the same saturation temperature as any free water in
in the vacuum indicator has not risen above 40°F the system. This temperature can be observed on the
(4.4°C) or a pressure of 6.3 mm Hg, the system thermometer.
may be considered tight.
If the system has been pressure tested and found to be
Be sure the vacuum indicator is valved off tight prior to evacuation, then the saturation tempera-
while holding the system vacuum and be ture recordings should follow a curve similar to the
sure to open the valve between the vacuum typical saturation curve shown in Figure 11 on Page
indicator and the system when checking 24.
the vacuum after the 8 hour period.
The temperature of the water in the test tube will drop
as the pressure decreases, until the boiling point is
7. If the vacuum does not hold for 8 hours within the reached, at which point the temperature will level off
limits specified in Step 6, the leak must be found and remain at this level until all of the water in the
and repaired. shell is vaporized. When this final vaporization has
taken place, the pressure and temperature will continue
VACUUM DEHYDRATION to drop until eventually a temperature of 35°F (1.6°C)
To obtain a sufficiently dry system, the following in- or a pressure of 5 mm Hg. is reached.
structions have been assembled to provide an effective
method for evacuating and dehydrating a system in the
field. Although there are several methods of dehydrat-
ing a system, we are recommending the following, as
it produces one of the best results, and affords a means
of obtaining accurate readings as to the extent of de-
hydration.
The equipment required to follow this method of dehy-
dration consists of
• a wet bulb indicator or vacuum gauge.
• a chart showing the relation between dew point
temperature and pressure in inches of mercury LD00474

(vacuum), (refer to Table 1 on Page 23). Figure 11 - SATURATION CURVE


• a vacuum pump capable of pumping a suitable
vacuum on the system. When this point is reached, practically all of the air
OPERATION has been evacuated from the system, but there is still
a small amount of moisture left. In order to provide
Dehydration of a refrigerant system can be obtained a medium for carrying this residual moisture to the
by this method because the water present in the sys- vacuum pump, nitrogen should be introduced into the
tem reacts similar to refrigerant. By pulling down the system to bring it to atmospheric pressure and the indi-

24 JOHNSON CONTROLS
FORM 160.77-O1
Section 3 - Maintenance
ISSUE DATE: 11/15/2011

cator temperature will return to approximately ambient water, the pressure corresponding to the freezing point
temperature. Close off the system again, and start the is 29 PSIG (200 kPa) for R-134a (at sea level).
second evacuation.
While charging, every precaution must be taken to pre-
The relatively small amount of moisture left will be vent moisture laden air from entering the system. Fab-
carried out through the vacuum pump and the tem- ricate a suitable charging connection from new copper
perature or pressure shown by the indicator should tubing to fit between the system charging valve and the 3
drop uniformly until it reaches a temperature of 35°F fitting on the charging drum. This connection should
(1.6°C) or a pressure of 5 mm Hg. be as short as possible, but long enough to permit suffi-
cient flexibility for changing drums. The charging con-
When the vacuum indicator registers this tempera- nection should be purged each time a full container of
ture or pressure, it is a positive sign that the system is refrigerant is connected. Changing containers should
evacuated and dehydrated to the recommended limit. If be done as quickly as possible to minimize the loss of
this level cannot be reached, it is evident that there is a refrigerant.
leak somewhere in the system. Any leaks must be cor-
rected before the indicator can be pulled down to 35°F The weight of the refrigerant charged should be record-
(1.6°C) or 5 mm Hg. in the primary evacuation. ed after initial charging. Refrigerant may be furnished
in cylinders containing either 30, 50, 125, 1,025 or
During the primary pulldown, carefully watch the wet 1750 lbs. (13.6, 22.6, 56.6, 464 or 794 kg) of refriger-
bulb indicator temperature, and do not let it fall below ant.
35°F (1.6°C). If the temperature is allowed to fall to
32°F (0°C), the water in the test tube will freeze, and The refrigerant charge is specified for each chiller
the result will be a faulty temperature reading. model in Table 2 on Page 25. Charge the correct
amount of refrigerant and note the level in the evapora-
REFRIGERANT CHARGING tor sight glass.
To avoid the possibility of freezing the liquid within Proper refrigerant charge trimming is accomplished
the evaporator tubes when charging an evacuated sys- while running at design full load. Ensure condenser
tem, only refrigerant vapor from the top of the drum and economizer level settings cover the condenser
or cylinder must be admitted to the system pressure. subcooler and maintain economizer liquid seal. Then
Continue charging vapor only into the system until the trim charge for design evaporator approach (leaving
system pressure is raised above the point correspond- chilled liquid temperature minus refrigerant tempera-
ing to the freezing point of the evaporator liquid. For ture) and compressor discharge superheat.

Table 2 - REFRIGERANT CHARGE

ESTIMATE REFRIGERANT
COMPRESSOR CONDENSER EVAPORATOR
CHARGE LBS (KGS) 1

BB 8300 (3765)

BC 7800 (3538)

K7 (YDHA119) and BD 7320 (3320)


BB, BC, BD, B5, B6, B7, B8
Q3 (HF416) B6 8080 (3665)

B7 7800 (3538)

B8 7520 (3411)

1 Refrigerant charge quantity and weights will vary based on tube count.
* Refer to product drawings for detailed weight information.

JOHNSON CONTROLS 25
FORM 160.77-O1
Section 3 - Maintenance
ISSUE DATE: 11/15/2011

HANDLING REFRIGERANT FOR CONDENSERS AND EVAPORATORS


DISMANTLING AND REPAIRS
Maintenance of condenser and evaporator shells is im-
If it becomes necessary to open any part of the refriger- portant to provide trouble free operation of the chiller.
ant system for repairs, it will be necessary to remove The water side of the tubes in the shell must be kept
the charge before opening any part of the unit. If the clean and free from scale. Proper maintenance such as
chiller is equipped with optional valves, the refrigerant tube cleaning, and testing for leaks, is covered on the
can be isolated in either the condenser or the evapora- following pages.
tor / compressor while making any necessary repairs.
Chemical Water Treatment
MEGGING THE MOTOR The mineral content of the water circulated through
While the compressor motor leads are lifted at the lugs evaporators and condensers varies with almost every
in the drive, meg the motor as follows: source of supply. Water containing excess amounts of
minerals may corrode the tubes or deposit heat resistant
1. Using a megohm meter (megger), meg between scale in them. Reliable water treatment companies are
phases and each phase to ground (refer to Figure available in most larger cities to supply a water treat-
12 on Page 26). These readings can be inter- ing process which will greatly reduce the corrosive and
preted using the graph shown in Figure 13 on scale forming properties of almost any type of water.
Page 27.
As a preventive measure against scale and corrosion,
2. If readings fall below the shaded area, remove ex- and to prolong the life of evaporator and condenser
ternal leads from motor and repeat the test. tubes, a chemical analysis of the water should be made
preferably before the system is installed. A reliable wa-
The motor is to be megged with the starter ter treatment company can be consulted to determine
at ambient temperature after 24 hours of whether water treatment is necessary, and if so, to fur-
idle standby with no water flow through nish the proper treatment for the particular water con-
the unit. dition.
The unit must be at positive pressure (no
vacuum) during the megging procedure.

LD00475

Figure 12 - MEGGING MOTOR WINDINGS

26 JOHNSON CONTROLS
FORM 160.77-O1
Section 3 - Maintenance
ISSUE DATE: 11/15/2011

LD00476

Figure 13 - MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES

JOHNSON CONTROLS 27
FORM 160.77-O1
Section 3 - Maintenance
ISSUE DATE: 11/15/2011

Cleaning Evaporator and Condenser Tubes Improved results can be obtained by admitting water
into the tube during the cleaning process. This can be
Evaporator
done by mounting the brush on a suitable length of 1/8"
It is difficult to determine by any particular test wheth- pipe with a few small holes at the brush end and con-
er possible lack of performance of the water evaporator necting the other end by means of a hose to the water
is due to fouled tubes alone or due to a combination of supply.
other issues. Trouble which may be due to fouled tubes
is indicated when, over a period of time, the cooling Acid Cleaning of Tubes
capacity decreases and the approach (temperature dif- Tubes that are fouled with a hard scale deposit, may re-
ference between water leaving the evaporator and the quire acid cleaning. The tubes should always be brush
refrigerant temperature in the evaporator) increases. A cleaned before acid cleaning. If the relatively loose
gradual drop-off in cooling capacity can also be caused foreign material is removed before the acid cleaning,
by a gradual leak of refrigerant from the system or by the acid solution will have less material to dissolve and
a combination of fouled tubes and shortage of refriger- flush from the tubes resulting in a better cleaning job.
ant charge.
Acid cleaning should only be performed
Condenser by an expert. Please consult your local
water treatment representative for as-
In a condenser, trouble due to fouled tubes is usually
sistance in removing scale buildup and
indicated by a steady rise in head pressure, over a pe-
preventative maintenance programs to
riod of time, accompanied by a steady rise in condens-
eliminate future problems.
ing temperature, and noisy operation. These symptoms
rarely may also be due to improper evacuation before Commercial Acid Cleaning
charging refrigerant during system breach.
In many major cities, commercial organizations now
Tube Fouling offer a specialized service of acid cleaning evaporators
and condensers. If acid cleaning is required, Johnson
Fouling of the tubes can be due to deposits of two types Controls recommends the use of this type of organiza-
as follows: tion. The Dow Industries Service Division of the Dow
1. Rust or sludge – which finds its way into the tubes Chemical Company, Tulsa, Oklahoma, with branches
and accumulates there. This material usually does in principal cities is one of the most reliable of these
not build up on the inner tube surfaces as scale, companies.
but does interfere with the heat transfer. Rust or
COMPRESSORS
sludge can generally be removed from the tubes
by a thorough brushing process. Maintenance for the compressor assembly consists of
the following checks:
2. Scale – due to mineral deposits. These deposits,
even though very thin and scarcely detectable • checking the operation of the oil return system
upon physical inspection, are highly resistant to and changing the dehydrator
heat transfer. They can be removed most effec-
• checking and changing the oil
tively by circulating an acid solution through the
tubes. • checking and changing the oil filters
Tube Cleaning Procedures • checking the operation of the oil heater

Brush Cleaning of Tubes • checking the operation of the oil pump


If the tube fouling consists of dirt and sludge, it can • observing the operation of the compressor.
usually be removed by means of the brushing pro-
Internal wearing of compressor parts could be caused
cess. Drain the water sides of the circuit to be cleaned
by improper lubrication, brought about by restricted oil
(cooling water or chilled water) remove the heads and
lines, passages, or dirty oil filters. If the unit is shut-
thoroughly clean each tube with a soft bristle bronze
ting down on High Oil Temperature (HOT) or Low Oil
or nylon brush. DO NOT USE A STEEL BRISTLE
Pressure (LOP), change the oil filter element. Exam-
BRUSH. A steel brush may damage the tubes.
ine the oil filter element for the presence of aluminum

28 JOHNSON CONTROLS
FORM 160.77-O1
Section 3 - Maintenance
ISSUE DATE: 11/15/2011

particles. Aluminum gas seal rings can contact the im- The use of untreated water in cooling towers, closed
peller and account for some aluminum particles accu- water systems, etc. frequently results in one or more of
mulating in the oil filter, especially during the initial the following:
start up and first several months of operation. How-
ever, if aluminum particles continue to accumulate and • Scale Formation.
the same conditions continue to stop the unit operation • Corrosion or Rusting.
after a new filter is installed, notify the nearest Johnson 3
Controls office to request a Johnson Controls Service • Slime and Algae Formation.
Technician. Therefore, proper water treatment is essential to
provide for longer and more economical life of the
ELECTRICAL CONTROLS equipment. The following recommendations should be
For information covering the YKEP Control Center op- followed in determining the condition of the water side
eration, refer to the YKEP Control Center Operations of the condenser and evaporator tubes.
Manual (Form 160.77-O2).Preventative Maintenance
1. The condenser tubes should be cleaned annually
It is the responsibility of the owner to provide the nec- or earlier if conditions warrant. If the temperature
essary daily, monthly and yearly maintenance require- difference between the water off the condenser
ments of the system. and the condenser liquid refrigerant temperature
is more than 4°F (2°C) greater than the difference
If a unit failure occurs due to improper recorded on a new unit, it is a good indication
maintenance during the warranty period; that the condenser tubes require cleaning. Refer
Johnson Controls will not be liable for to Cleaning Evaporator and Condenser Tubes
costs incurred to return the system to on Page 28 in this section for condenser tube
satisfactory operation. cleaning instructions.
2. The evaporator tubes under normal circumstances
In any operating system it is most important to provide will not require cleaning. If the temperature dif-
a planned maintenance and inspection of functioning ference between the refrigerant and the chilled
parts to keep the unit operating at its peak efficiency. water increases slowly over the operating season,
Therefore, the following maintenance should be per- it is an indication that the evaporator tubes may be
formed as prescribed in Table 3 on Page 31. fouling or that there may be a water bypass in the
water box requiring gasket replacement or refrig-
COMPRESSOR MOTORS erant may have leaked from the chiller.
1. Check mounting screws and piping joint nuts fre-
OIL RETURN SYSTEM
quently to insure tightness.
1. Change the dehydrator in the oil return system
2. Meg motor windings annually to check for dete-
semi-annually or earlier if the oil return system
rioration of windings.
fails to operate.
LEAK TESTING 2. When the dehydrator is changed, use care that any
The unit should be leak tested monthly. Any leaks foreign particles that may obstruct the eductor ori-
found must be repaired immediately. fices are removed.

EVAPORATOR AND CONDENSER ELECTRICAL CONTROLS

The major portion of maintenance on the condenser 1. All electrical controls should be inspected for ob-
and evaporator will deal with maintaining the water vious malfunctions.
side of the condenser and evaporator in a clean condi- 2. It is important that the factory control settings (op-
tion. eration and safety) not be changed. If the settings
are changed without Johnson Controls approval,
the warranty may be voided.

JOHNSON CONTROLS 29
30
MAINTENANCE REQUIREMENTS FOR YORK YKEP CHILLERS

PROCEDURE DAILY WEEKLY MONTHLY YEARLY OTHER

Record operating conditions (on applicable Log Form) X


Check oil levels X
Check refrigerant levels X
Check oil return system operation X
Check operation of motor starter X
Check sump heater and thermostat operation X
Check three-phase voltage and current balance X
1
Verify proper setting of safety controls X
Verify condenser and evaporator water flows X
Leak check and repair leaks as needed1 X
Check and tighten all electrical connections X
Megohm motor windings X
Replace oil filter and oil return filter/driers X
Clean or backflush heat exchanger (VSD, SSS Applications) X
Replace starter coolant (VSD, SSS Applications) X
Replace or clean starter air filters if applicable X2
Perform oil analysis on compressor lube oil1 X
1
Perform refrigeration analysis X
Perform vibration analysis X
Clean tubes X2
Perform Eddy current testing and inspect tubes 2 - 5 Years
Lubricate motor Refer to motor manufacturer’s recommendations

For operating and maintenance requirements listed above, refer to appropriate service literature, or contact your local Johnson Controls Service Office. A record of all procedures being success-
fully carried out (as well as operating logs) must be maintained on file by the equipment owner should proof of adequate maintenance be required at a later date for warrenty validation purposes.
1 This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of YORK equipment.
2 More frequent service may be required depending on local operating conditions.

Form 160.77-MR1 (1111)

JOHNSON CONTROLS
New Release
Issue Date: November 15, 2011
FORM 160.77-O1
ISSUE DATE: 11/15/2011

SECTION 4 - TROUBLESHOOTING
If the system is malfunctioning in any manner, refer to son Controls District Office. Failure to report constant
the Operation Analywsis Chart shown in Table 4. After troubles could damage the unit and increase the cost of
consulting these references, if you are unable to make repairs. If the system shuts down on a safety fault, refer
the proper repairs or adjustments to start the compres- to the control panel operating manual Form 160.77-O2
sor or the particular trouble continues to hinder the or contact JCI Service.
performance of the unit, please call the nearest John-
4
Table 3 - OPERATION ANALYSIS CHART
SYMPTOM RESULTS POSSIBLE CAUSE REMEDY
Temperature difference between Air in condenser.
condensing temperature and water off Condenser tubes dirty or Clean condenser tubes.
condenser higher than normal. scaled Check water conditioning.
Reduce condenser water
Abnormally High High condenser water tem- inlet temperature. (Check
High discharge pressure.
Discharge perature. cooling tower and water
Pressure circulation.)
Temperature difference between con-
Increase the quantity of water
denser water on and water off higher Insufficient condensing water
through the condenser to
than normal, with normal evaporator flow.
proper value.
pressure.
Temperature difference between leaving Insufficient charge of refriger- Check for leaks and charge
chilled water and refrigerant in evapo- ant. refrigerant into system.
rator greater than normal with high
Variable orifice problem. Remove obstruction.
discharge temperature.
Temperature difference between leav-
Abnormally Low
ing chilled water and refrigerant in the Evaporator tubes dirty or
Suction Pressure Clean evaporator tubes.
evaporator greater than normal with restricted.
normal discharge temperature.
Check prerotation vane mo-
Temperature of chilled water too low Insufficient load for system
tor operation and setting of
with low motor amperes. capacity.
controls.
Prerotation vanes fail to Check the prerotation vane
open. motor positioning circuit.
High Evaporator Be sure the vanes are wide
High chilled water temperature.
Pressure open (without overloading
System overload.
the motor) until the load
decreases.
No Oil Pressure Oil pump running in wrong Check rotation of oil pump
When System Low oil pressure displayed on control direction. (Electrical Connections).
Start Button center; compressor will not start. Troubleshoot electrical prob-
Oil pump not running.
Pushed lem with oil pump VSD.
Unusually High Oil
Unusually high oil pressure is displayed
Pressure Develops High oil pressure. Transducer Replace low or high oil pres-
when the oil pressure display key is
When Oil Pump defective. sure transducer.
pressed when the oil pump is running.
Runs

JOHNSON CONTROLS 31
FORM 160.77-O1
Section 4 - Troubleshooting
ISSUE DATE: 11/15/2011

TABLE 3 - OPERATION ANALYSIS CHART (CONT'D)

Oil pump vibrates or is extremely noisy Oil not reaching pump


with some oil pressure when pressing suction inlet in sufficient Check oil level.
OIL PRESSURE display key. quantity.
When oil pump is run
Oil Pump Vibrates without an oil supply
Or Is Noisy it will vibrate and be-
come extremely noisy. Worn or failed oil pump. Repair/Replace oil pump.

Excessive end clearance


Inspect and replace worn
pump. Other worn pump
Reduced Oil parts.
Oil pump pumping capacity. parts.
Pump Capacity
Partially blocked oil supply
Check oil inlet for blockage.
inlet.
Symptom:
Oil Pressure
When oil pump VSD frequency in-
Gradually
creases to 55 + hz to maintain target oil Oil filter is dirty. Change oil filter.
Decreases (Noted
pressure.
by Observation of
Daily Log Sheets)
Symptom: Filter-drier in oil return Replace old filter-drier with
Oil Return System system dirty. new.
Ceases To Return Oil refrigerant return not functioning. Remove jet, inspect for dirt.
Jet or orifice of oil return jet
An Oil/Refrigerant Remove dirt using solvent
clogged.
Sample and replace.
Symptom:
No oil pressure registers when pressing
Oil Pump Fails Faulty oil pressure transducer. Replace oil pressure trans-
OIL PRESSURE display key when oil
To Deliver Oil Faulty wiring/connectors. ducer.
pump runs.
Pressure

32 JOHNSON CONTROLS
FORM 160.77-O1
ISSUE DATE: 11/15/2011

SI METRIC CONVERSION

The following factors can be used to convert from


English to the most common SI Metric values.

Table 4 - ANALOG INPUT RANGES (LOW PRESSURE CHILLERS)

MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT

Capacity Tons Refrigerant Effect (ton) 3.516 Kilowatts (kW)

Power Horsepower 0.7457 Kilowatts (kW)

Flow Rate Gallons / Minute (gpm) 0.0631 Liters / Second (l/s)

Feet (ft) 304.8 Meters (m)


Length
Inches (in) 25.4 Millimeters (mm)

Weight Pounds (lbs) 0.4538 Kilograms (kg)

Velocity Feet / Second (fps) 0.3048 Meters / Second (m/s)

Feet of Water (ft) 2.989 Kilopascals (kPa)


Pressure Drop
Pounds / Square Inch (psi) 6.895 Kilopascals (kPa)

TEMPERATURE
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 27.2°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range

JOHNSON CONTROLS 33
P.O. Box 1592, York, Pennsylvania USA 17405-1592 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2011 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 160.77-O1 (1111)
Issue Date: November 15, 2011
Supersedes: 160.77-O1 (611)

Das könnte Ihnen auch gefallen