Sie sind auf Seite 1von 3

<Project> Centralized Control1 <System> CDU-1

<Outdoor Unit Title> Model Quantity HP Cooling Capacity(Rated)


<Outdoor Unit Model> PUHY-P500YSHM-A 1 20 191100

Cooling Total
Capacity(Rated)
<Indoor Unit Title> Model Quantity
<Indoor Unit> PEFY-P100VMA-E 3 38200
<Indoor Unit> PEFY-P63VMAL-E 2 24200
<Indoor Unit> PEFY-P50VMS1-E 1 19100
<Branch Title> Model Quantity
<Branch> CMY-Y102SS-G2 1
<Branch> CMY-Y102LS-G2 2
<Branch> CMY-Y202S-G2 2
<Branch> CMY-Y100VBK 1
<Pipe Title> Liquid Gas Length
<Outdoor Unit to first joint> 15.88 28.58 25
<Outdoor Unit to first joint> 9.52 22.2 0
<Outdoor Unit to first joint> 9.52 22.2 0
<Pipe Title> Liquid Gas Length
<First joint to Indoor unit> 9.52 15.88 14.5
<First joint to Indoor unit> 9.52 19.05 3
<First joint to Indoor unit> 9.52 22.2 3
<First joint to Indoor unit> 12.7 28.58 0.5
<First joint to Indoor unit> 15.88 28.58 3
<First joint to Indoor unit> 6.35 12.7 7.5
<Pipe Summary Totals Title > Size Length
<Pipe Summary Totals> 15.88 42.5
<Pipe Summary Totals> 9.52 20.5
<Pipe Summary Totals> 19.05 3
<Pipe Summary Totals> 22.2 3
<Pipe Summary Totals> 28.58 28.5
<Pipe Summary Totals> 12.7 8
<Pipe Summary Totals> 6.35 7.5
<Additional Refrigerant charge Titl Type Amount
<Additional Refrigerant charge> R410A 11.6
<design condition>
<Temperature Title> Indoor DB Indoor WB Outdoor D Outdoor WB
<Temperature Cooling> 27 19 35
<Temperature Heating> 20 7 6
<Unit Title> length diameter capacity temperature
<Unit> m mm BTU/h Celsius

<Prepared on> 20150514 <Cont No>


<Customer's name> MR. YI
<Comment>
<Frequency> 50

<version> 4.30.0
The power input value
of indoor unit is the
maximum value at
selected power supply
Note) frequency.
Please refer to the
specification sheet for
actual value.
city(Rated)

Cooling
Sensible
Capacity(
Rated)
30100 114600
18600 48400
12600 19100

Bend
3
0
0
Bend
7
0
0
0
1
0

28.58 28.5
22.2 3
19.05 3
15.88 42.5
12.7 8
9.52 20.5
6.35 7.5

Amount water flow water pressure drop


kg cfm kPa