HVAC Clinic

Load
Contents
Introduction .....................................................................................................................................3
Fundamentals of Heat Transfer .....................................................................................................3
Energy Measurement .....................................................................................................................4
Load Estimation ..............................................................................................................................5
Example 1 ........................................................................................................................................7
Example 2 ......................................................................................................................................14
Weather Design Conditions .........................................................................................................18
Design Conditions For Reno, NV (ASHRAE 2005 Fundamentals .......................................................... 18
Rates Of Heat Gain from Occupants (ASHRAE 1997 Fundamentals, Chapter 28, Table 3) ................. 19
Heat Gain for Appliances (ASHRAE 1997 Fundamentals, Chapter 28, Table 5 & 6) ............................. 19
Thermal Properties Of Layers (ASHRAE 1997 Fundamentals, Chapter 28, Table 11) .......................... 20
Roofs ..............................................................................................................................................21
Roof Group Numbers & CLTD (ASHRAE 1997 Fundamentals, Chapter 28, Table 30 & 31) ................. 21
Walls ..............................................................................................................................................22
Wall Types Mass Located Inside Wall (ASHRAE 1997 Fundamentals, Chapter 28, Table 33A) ........... 22
Wall Types Mass Evenly Distributed (ASHRAE 1997 Fundamentals, Chapter 28, Table 33B) ............. 23
Wall Types Mass Evenly Distributed (ASHRAE 1997 Fundamentals, Chapter 28, Table 33B) ............. 24
Wall CLTD (ASHRAE 1997 Fundamentals, Chapter 28, Table 33B) ..................................................... 25
Wall Types Mass Located Inside Wall (ASHRAE 1997 Fundamentals, Chapter 28, Table 33A) ........... 28
Glass/Fenestration .......................................................................................................................29
U-Factors for Various Fenestration (ASHRAE 2005 Fundamentals, Chapter 29, Table 4) .................... 29
Shading Coefficient (ASHRAE 1997 Fundamentals, Chapter 29, Table 11) ......................................... 30
CLTD for Conduction through Glass (ASHRAE 1997 Fundamentals, Chapter 28, Table 34) ................ 31
Zone Types for Use with SCL (ASHRAE 1997 Fundamentals, Chapter 28, Table 35) ......................... 31
Zone Types for Use with SCL (ASHRAE 1997 Fundamentals, Chapter 28, Table 35) ......................... 32
Infiltration ......................................................................................................................................33
Infiltration Models (US Department Of Energy, Table 3, Table 4, Table 5) ............................................ 33
HVAC Clinics Draft - Not For Distribution
Introduction

Cooling load estimation is the foundation for which everything is based in HVAC. Without an accurate load, we couldn’t
perform the psychrometrics required to determine the cooling airflow or the refrigeration load. An accurate load
provides us with the information required to size our plant, determine the fraction of outside air, and most importantly,
how to maintain occupant comfort.

This particular clinic introduces the reader to cooling load estimation. It is intended to introduce the concepts of
estimating building cooling and is limited to introducing the components that make up the load on a building. This
includes the variables that affect each of these components, and simple methods used to estimate these load
components. It is not intended to teach all the details or latest computerized techniques of how to calculate these loads.
In addition, this clinic does not cover the process of determining the heating load. If the principles are understood for
cooling load estimation, heating load estimation can easily be inferred.

Fundamentals of Heat Transfer


The three primary rules of heat transfer are:
1. Heat energy cannot be destroyed
2. Heat always flows from a higher temperature source to a lower temperature source
3. Heat can be transferred from one substance to another substance

Heat energy cannot be destroyed. Energy can be transferred from one substance to another substance, but the energy
is maintained. This is the first law of thermodynamics and is known as the conservation of energy.
Heat always flows from a higher temperature source to a lower temperature source. Heat is a measure of the motion of
(i.e. the kinetic energy of) molecules. When an object in motion impacts with an object that is stationary, it imparts some
of its energy to the stationary object (via movement and plastic deformation). The same is true of heat. Thus heat
always flow from a high temperature source to a low temperature source much the same way a moving object transfer’s
energy to a stationary object.

Heat energy can be transferred from one substance to another substance by one of three processes; convection,
conduction and radiation. Convection is the transfer of energy between two fluids. Convection cannot flow between
solids. Conversely, conduction is the transfer of energy between adjacent molecules of a solid. Finally, radiation is the
emission of electromagnetic waves from all matter that has a temperature greater than absolute zero. It represents a
conversion of thermal energy into electromagnetic energy. Radiation does not require the presence of matter to
propagate.

An example of a device that exhibits all three methods of heat transfer is a baseboard convector. Heat is transferred
from the warm inner tube to the cooler outer fins by conduction. The fins of baseboard then warm the air contained
within the casing. The buoyant (less dense) air within the casing then rises and mixes with the cooler room air by the
process of convection. Finally, the warm casing surface transfers heat to objects in room air by electromagnetic energy
or radiation (figure 1). Radiation does not head the adjacent air; it only heats the objects that the electromagnetic waves
impact.

Figure 1. Baseboard Convector

Nevada Mechanical Systems Duct Design Page 3 of 33


HVAC Clinics Draft - Not For Distribution
Energy Measurement
The IP method of measuring heat is the Btu, or British Thermal Unit. A Btu is defined as the amount of heat energy
required to raise one on pound of water 1oF (figure 2). In thermodynamics, we often want to measure the rate of heat
transfer, or the amount of heat energy per unit time. This rate of heat transfer is generally measured as a Btu/hr or the
amount of heat transfer required to increase one pound of water 1 oF in one hour.

Figure 2. Btu

Sensible Vs Latent Heat

In environmental building conditioning, we typically deal with two types of energy transfer; sensible and latent heat
transfer. Sensible heat transfer is the process of increasing the dry bulb temperature of a substance. As discussed in
the psychrometric clinic, latent heat transfer is the process of increasing or decreasing the moisture content of a
substance. However, latent energy can also refer to the amount of heat that is released or absorbed during the phase
change of a substance. This is analogous to the energy absorbed when boiling water and creating steam (figure 3).

Figure 3. Sensible versus Latent Energy

ASHRAE standard 55, Environmental Conditions for Human Occupancy, defines the psychrometric conditions for
human comfort in a conditioned space. These conditions allow for 80% occupant acceptability in terms of comfort
(figure 4). Note that as the humidity ratio increases, the acceptable dry bulb temperature decreases. The maximum
humidity ratio for comfort is constant and is defined as .012 lb-water/lb-air.

Nevada Mechanical Systems Duct Design Page 4 of 33


HVAC Clinics Draft - Not For Distribution

Figure 4. ASHRAE Standard 55

Load Estimation
The method for determining space loads used in this clinic will be based on the Load Temperature Difference/Solar
Cooling Load/ Cooling Load (CLTD/SCL/CLF) load estimation method developed by ASHRAE.
A building typically has two type of cooling load components; space load and system load. Space load components
comprise of:

 Wall Conduction
 Glass Conduction
 Roof Conduction
 Glass Solar
 Partition Conduction
 Infiltration
 People
 Lights
 Equipment
 Floor

System load components comprise of:

 Plenum heat pickup


 Fans
 Ventilation

As discussed in the psychrometric clinic, space load components are totaled in order to determine the airflow to the
zone. Space load plus system load components are totaled in order to determine the total load to the coil.

Nevada Mechanical Systems Duct Design Page 5 of 33


HVAC Clinics Draft - Not For Distribution

Figure 5. Load Components

Conduction

Conduction through a shaded surface is defined as:

Where:

Q = heat gain by conduction, Btu/hr


U = overall heat-transfer coefficient of the surface, Btu/hr • ft2 • °F
A = area of the surface, ft2
ΔT = dry-bulb temperature difference across the surface, ºF

The overall heat transfer coefficient is also called the U-factor. The U-factor is the rate at which heat will be transferred
through the structure. A wall is typically composite in nature, consisting of multiple layers of materials.
A wall generally consists of multiple layers of materials, each of which has an associated thermal resistance (figure 6).

Figure 6. U-factor
Nevada Mechanical Systems Duct Design Page 6 of 33
HVAC Clinics Draft - Not For Distribution
The overall U factor is the inverse of the sum of the thermal resistance of each of these layers.

Where:

R = Resistance, hr • ft2 • °F/ Btu

For the wall in figure 5. The overall U factor would be

All surfaces also have an indoor and outdoor surface resistance. AHRAE gives the R values of common materials along
with indoor and outdoor surface resistance.

Example 1
Find the overall heat transfer coefficient for the wall in figure 7.

Figure 7. Example 1

Solution:

First, we must sum all of the R values along with the R values of the inside and outside surface resistance. Inside and
outdoor surface resistance values as given by the 1997 ASHRAE Handbook—Fundamentals and ASHRAE’s Cooling
and Heating Load Calculation Principles manual are .68 and .25 hr • ft2 • °F/ Btu respectively.

Nevada Mechanical Systems Duct Design Page 7 of 33


HVAC Clinics Draft - Not For Distribution

Most surfaces are not shaded. They are exposed to direct sunlight during some portion of the day. The sun imparts
radiant energy on opaque or non-transparent surfaces. The amount of energy depends on the color of the surface,
smoothness of the surface and the angle at which the sun’s rays impact the surface. The radiant energy from the sun is
at a maximum when the rays strike at an angle that is 90o from the surface. The angle at which the sun’s rays strike the
surface depend on the time of day, the latitude and the month of the year.

In addition, a wall has the capacity to store heat. The amount of heat storage is a function of the density and width of the
wall. The greater the storage capacity of the wall, the longer the time delay or time lag (figure 8) before the heat that
impacts the structure enters the space.

Figure 8. Time Lag

The cooling load temperature difference (CLTD) is used to account for the added heat from radiant heat transfer due to
the sun shining on exterior walls, roofs, and windows, and the capacity of the wall and roof to store heat. The CLTD is
substituted for ΔT in the equation to estimate heat transfer by conduction.

Tables for various wall and roof types, as well as correction factors can be found in the 1997 ASHRAE
Handbook—Fundamentals and ASHRAE’s Cooling and Heating Load Calculation Principles manual.

Solar Radiation Through Glass

Earlier in this clinic, we estimated the heat transferred through glass windows by the process of conduction. However, a
large part of the solar heat energy that shines on a window or skylight is radiated through the glass and transmitted
Nevada Mechanical Systems Duct Design Page 8 of 33
HVAC Clinics Draft - Not For Distribution
directly into the space. The amount of solar heat radiated through the glass depends primarily on the reflective
characteristics of the glass and the angle at which the sun’s rays strike the surface of the glass.
The equation used to predict the amount of solar heat gain through glass is:

Where:

Q = heat gain by solar radiation through glass, Btu/hr


A = total surface area of the glass, ft2
SC = shading coefficient of the window, dimensionless
SCL = solar cooling load factor, Btu/hr • ft2
.
Factors which affect the solar cooling load factor are:
 Time of day
 Month
 Direction that the window faces
 Latitude
 Construction of interior partition walls
 Type of floor covering
 Internal shading devices (if any)

The solar cooling load factor (SCL) is used to estimate the rate at which solar energy radiates into the space, heats up
the internal components (furniture, partitions, etc), and is then released into the space. Much like the CLTD, the SCL
factor accounts for the capacity of the space to absorb and store heat.

The shading coefficient (SC) is used to define how much of the radiant solar energy which strikes the outer surface of
the window is transmitted through the window and into the space. The shading coefficient for a particular window is
determined by comparing its reflective properties to a standard reference window. A higher shading coefficient
represents the ability of a window to reflect more radiant energy.

Internal shading devices can reduce the amount of solar energy passing through a window. The effectiveness of such
shading devices depends on their ability to reflect incoming solar radiation back through the window. Lighter colored
blinds or drapes are more effective than dark colored shading devices. External shading devices act in much the same
manner as internal shading devices. External shading devices reflect the incident solar energy and prevent it from
entering the space.

Internal Heat Gains

The next component of a load analysis is to account for the internal load gains. Internal load gains consist of the heat
introduced by people, lighting, and equipment. People introduce both sensible and latent heat gains. Those gains are
a function of activity level and vary with age, physical size, gender and type of clothing. ASHRAE
Handbook—Fundamentals gives both sensible and latent heat gains for people based on activity type based on an
average person.

The equations for calculating the sensible and latent heat gain produced by people are:

Where:

QS = sensible heat gain from people, Btu/hr


QL = latent heat gain from people, Btu/hr
CLF = cooling load factor, dimensionless
Nevada Mechanical Systems Duct Design Page 9 of 33
HVAC Clinics Draft - Not For Distribution

Much like the SCL for solar heat gain, the cooling load factor (CLF) is used to account for ability of the space to absorb
and store heat. The CLF depends on the construction of the interior partition walls, the type of floor covering, the total
number of hours that the space is occupied and the number of hours since the people entered the space. ASHRAE
Handbook—Fundamentals give CLF for various space types.

Lighting

Often, the single greatest internal load producing component is lighting. The equation to estimate the heat gain from
lighting is:

Where:

Q = sensible heat gain from lighting, Btu/hr


3.41 = conversion factor from W to Btu/hr
Watts = total energy input to lights
CLF = cooling load factor (dimensionless)
Ballast factor = 1.2 for fluorescent lights, 1.0 for incandescent lights

Equipment

Equipment can be a very large contributor to internal heat loads. With the proliferation of the use and increased
processing powers of personal computers, computer loads can be as high as 1.5 watts/sq-ft. Additional equipment such
as printers, coffee makers, etc can additionally contribute load. ASHRAE Handbook—Fundamentals gives both
sensible and latent heat gains for various types of equipment loads. All equipment loads must be summed and
accounted for when calculating the load.

Infiltration

In buildings, air can leak into and out of the building through cracks around windows, door and small cracks in the
building exterior. The direction of air leakage (into or out) will depend on space pressurization and wind direction. Air
leaking into a space is called infiltration. Air that leaks into the space can introduce both sensible and latent loads.

Three Methods Infiltration Load Calculation


 Air change method
 Crack method
 Effective leakage-area method

For the purposes of this discussion, we will focus on the air change method. The air change method is the easiest but
least accurate method. The air change methods uses ASHRAE tables to estimate the expected number of air changes
per hour based on building construction. The infiltration airflow is then calculated as:

The sensible and latent load introduced by infiltration then be calculated as:

Where:

Infiltration airflow = quantity of air infiltrating into the space, cfm


Volume of space = length × width × height of space, ft3
Nevada Mechanical Systems Duct Design Page 10 of 33
HVAC Clinics Draft - Not For Distribution
Air change rate = air changes per hour
60 = conversion from hours to minutes
ΔT = design outdoor dry-bulb temperature minus the desired indoor dry bulb temperature, oF
ΔW = design outdoor humidity ratio minus the desired indoor humidity ratio, grains of water/lb of dry air

The crack method is based upon the average quantity of air known to enter through cracks around windows and doors
when the wind velocity is constant. The effective leakage area method takes wind speed, shielding, and “stack effect”
into account. The effective leak method should be used when calculating infiltration for high rise buildings.

System Loads

System loads are loads that impact the refrigeration coil but do not directly impact the space. System loads include
ventilation loads, plenum/return duct heat pickup and fan heat gain.

Outdoor air is used to remove contaminants from the indoor air. Outdoor air introduced through the buildings HVAC
system is called ventilation. ASHRAE 62.1 provides equations to determine the quantity of ventilation air based on
space type and occupant density. This air must typically be cooled and dehumidified before it can be provided to the
space. The cooling and dehumidification of the ventilation air provides an additional system load to the analysis. The
equations for determining the system ventilation load are:

.
Where:

Ventialtion airflow = quantity of air infiltrating into the space, cfm


ΔT = design outdoor dry-bulb temperature minus the desired indoor drybulb temperature, oF
ΔW = design outdoor humidity ratio minus the desired indoor humidity ratio, grains of water/lb of dry air

Fans cans be another significant contributor to system heat. The amount of system heat is a function of the fan
efficiency, motor efficiency airflow and external static pressure. Supply fans can introduce system load either before the
refrigeration coil or after the refrigeration coil depending on the type of system. In blow through systems, fan heat is
added before the coil. In draw through systems, fan head is added after the coil. The position of the fan relative to the
coil (blow through or draw through) will affect the psychrometrics and thus system airflow determination. Exhaust fans
will additionally add heat to the system, whereas return fans reject all of their heat outside the system and thus do not
add additional system heat. The equation for determining the amount of heat a fan introduces to a system is:

Where:

745.7 = conversion from watts to bhp


3.41 = conversion from btu’s to watts
Fan motor bhp = actual fan motor brake horse power required to drive the fan, bhp

Lastly, duct heat gain must be accounted for. Typically, supply duct heat gain is minimal. Supply ductwork is often
insulated, minimizing potential heat gain. Return systems may be either ducted or use the return plenum. Open plenum
return systems typically experience some degree of heat pickup from lighting and/or roof loads. Supply duct and return
system heat pickup should be accounted for during a load analysis.
Nevada Mechanical Systems Duct Design Page 11 of 33
HVAC Clinics Draft - Not For Distribution

Load Analysis

Finally, a load analysis can be performed. First, we must summarize all of our load components. Those load
components are summed as they impact the space load and system loads (figure x).

Load Component Space Load System Load


Conduction through walls, roof & X X
windows
Solar radiation through windows X X
Conduction through ceiling, X X
interior partitions walls and floor
People X X
Lights X X
Equipment & Appliances X X
Infiltration X X
Fans X
Ventilation X
Supply and Return Duct/Plenum X

However, the load components will fluctuate with the time of day. For example, roof conduction for a flat roof will
typically peak at the same time the ambient temperature peaks (generally somewhere between 3pm and 6pm). Solar
radiation will peak when the incident angle from the sun is at a maximum angle relative to the exposed window or wall.
An eastern facing window for example will experience its maximum solar radiation exposure in the morning. Conversely,
a western facing window will experience its maximum solar radiation exposure in the afternoon. So, the question
becomes when does the particular zone experience its maximum load? Is it at 9 am, 12 pm, 3 pm or some other time
(figure 9)?

Figure 9. Time Of Peak Cooling Load

The answer to the question is determined by summarizing all of the load components at one hour intervals during the
occupied hours of the building. This is the method employed by computer load analysis tools. However, due to the time
required to perform an hourly analysis, this is impractical for a hand calculated load analysis. If we are going to manually
calculate a building load, we will sum the loads at 9am, 12pm, 3pm and 6 pm.

After the space and system load peaks have been determined along with its associated peak time of day, a
psychrometric analysis can be performed (please see Clinic One for a review of psychrometrics). As discussed in the
psychrometric clinic, the intersection of the cooling coil curve with the sensible heat ratio (SHR) line determines the
cooling supply air temperature. The SHR is determined from the cooling load analysis. Recall that:

Nevada Mechanical Systems Duct Design Page 12 of 33


HVAC Clinics Draft - Not For Distribution

The sensible and latent heat gains used in the SHR equation are determined from the load analysis. Having determined
the peak load and SHR, the cooling airflow and cooling coil discharge air temperature can be calculated.

Block Load Versus Sum Of The Peaks

Often times, a single air handler will serve multiple spaces. The example in figure 10 shows a building with two rooms.
Room 101 has a wall with a window with a western exposure and room 102 with a wall and a window with an eastern
exposure.

Figure 10

Room 101 with the western exposure will likely peak in the afternoon. Room 102 with the eastern exposure will likely
peak in the morning. Assuming the loads shown in table 2:

Room 101 102 Total


9 am 5 tons 8 tons 13 Tons
6 pm 10 Tons 5 Tons 15 Tons

The peak load occurs at 6 pm and totals 15 tons. This is known as the block load. The block load is the single instance
of time in which the loads are the greatest. If the air handler was a variable air volume (VAV) unit, it would be sized for
the block load. It would only need to deliver the worst case block load, or 15 tons.

However, if the air handler was a constant volume unit, it would need to be able to deliver the equivalent of 8 tons of
airflow to room 102 during all hours of operation and 10 tons of airflow to room 101 during all hour of operation. This is
because the supply fan cannot unload or deliver a reduced quantity of airflow. Thus the fan would need to be sized to
deliver 18 tons (10 tons for 101 and 8 tons for 102). The air handler fan would be sized to deliver the sum of the peaks
airflow. The sum of the peaks is defined as the peak load delivered to each space regardless of the time in which it
occurs. The refrigeration or coil load would still be sized for the block load.

Similarly, regardless of system type, ductwork must always be sized for the sum of the peaks. This is why VAV air
handler size can typically be reduced when compared to constant volume air handlers. Additionally, the discussion of
block load versus sum of the peak loads underlines the importance of placing spaces with similar load profiles together
on constant volume systems. Placing spaces with vastly differing load profiles on the same constant volume air handler
can waste unnecessary energy and create control and comfort related issues.

Nevada Mechanical Systems Duct Design Page 13 of 33


HVAC Clinics Draft - Not For Distribution

Example 2
Single Space Cooling Example

 Open-plan office space located in a single-story office building in Reno, Nevada


 Floor area = 45’ x 60’
 Floor-to-ceiling height = 15’ (3’ Plenum)
 Ducted Return
 Desired indoor conditions = 75oF dry bulb, 50% relative humidity during cooling season
 West-facing wall, 15’ height x 45’ long, constructed of 4” heavy weight concrete block with 1” stucco siding, 3”
insulation and ¾” gypsum board on the inside
 Eight double glazed 1/8” clear, fixed (e=0.2 on surface 3, ¼” airspace) windows mounted in aluminum frames
with thermal break. Each window is 4’ wide x 5’ high.
 Flat, 45’ x 60’ roof constructed of steel deck with 3.64” insulation and an acoustic tile drop ceiling (3’ plenum).
 Space is occupied from 8:00 a.m. until 5:00 p.m. by 14 people doing moderate active work.
 Fluorescent lighting in space = 2 W/ft2
 Computer and office equipment in space = 0.5 W/ft2 plus one coffee maker.

Room 101 is surrounded by spaces that are conditioned to the same temperature as this space. Find the space load at
5 PM.

Solution:

First, we should find the climatic data for Reno. From ASHRAE table 1B (1997 Fundamentals).

0.4% 1% Range of DB
DB MWB DB MWB
95 61 92 60 35.5

All values for conduction must be corrected for actual design conditions. For example, at the bottom of Table 32
(ASHRAE 1997 Fundamentals) Notes 2 reads:

Note that two sets of data are listed. One set of data reads 0.4%. The second reads 1%. These numbers denote the
percentage of hours out of the year that the design conditions exceed the listed temperatures. For example, the 0.4%
column list a dry bulb of 95oF and a wet bulb of 61oF. Thus, 0.4% of the time (out of a year consisting of 8760 hours per
year) the temperature exceeds 95oF dry bulb and 61oF wet bulb.

For this example, we will calculate the load at 0.4%.

Calculating the design conduction correction factor:

Substituting tm:

Nevada Mechanical Systems Duct Design Page 14 of 33


HVAC Clinics Draft - Not For Distribution
Next, we should calculate the conduction through the west facing wall. Recalling that conduction is:

We need to find the heat transfer coefficient for the wall. The resistance of each of the materials is shown in the table
below (ASHRAE 1997 Fundamentals Table 11).

Material Resistance
Outside Surface Resistance .33
1” Stucco .21
4” Heavy Weight Concrete (C3) .71
3” Insulation 1.19
¾” Gypsum .15
Inside Surface Resistance .69

Calculating the resistance of the wall:

Calculating the heat transfer coefficient:

Before we can determine the CLTD of the wall, we must determine the wall type. ASHRAE table 33A (1997
Fundamentals) lists a stucco wall with a principle wall material of 4” heavy weight concrete (C3) at a wall type 2. Having
found the wall type, we enter table 32 (ASHRAE 1997 Fundamentals) for wall number 2. A west facing wall a 5 PM has
a CLTD of 59.

Solving for the corrected CLTD for the west wall:

Solving for the conduction through the west wall:

Note that we are assuming that 100% of the wall load is being transferred to the space. This is a conservative
assumption based on the knowledge that some of the wall conduction load will be transferred to the plenum (we have a
3’ plenum). If the system was an open return system, we would assume that 3’ of the conduction would be transferred
to the plenum load and not the space load.

Next, we will move to conduction for glass. ASHRAE Table 5 (2005 Fundamentals) lists the U factor ¼” airspace double
coated, e=.2, fixed operation, aluminum with thermal break windows as having a heat transfer coefficient of 0.54. Table
34 (AHSHRAE 1997 Fundamentals) lists the CLTD’s for Conduction through glass. At 5 PM, the CLTD is 13. However,
we must correct the CLTD according to the conduction correction factor found in the previous example.

Nevada Mechanical Systems Duct Design Page 15 of 33


HVAC Clinics Draft - Not For Distribution
Solving for glass conduction:

Having solved glass conduction, we next find the glass solar load. In order to find glass solar, we must first find the
shading coefficient (SC) and solar cooling load (SCL) for the west facing glass. The SC can be found from ASHRAE
table 11 (1997 Fundamentals). For double glazed clear 1/8” e=.2 on surface 3,, the SC is 0.81. Like CLTD, SCL
accounts for the space’s capacity to absorb heat. In order to determine the zone type based on heat capacity, we
examine ASHRAE table 35B. For a space with three interior walls constructed primarily of gypsum, no inside window
shades and carpeted floors, the glass solar zone type is A. Entering ASHRAE table 36 (1997 Fundamentals) for zone
type A, a west wall at 5 PM has a SCL of 192. Solving for glass solar:

Moving on to roof conduction, we first must find the roof R value. Using a procedure similar to that of the wall, we find the
total resistance of each material (ASHRAE 1997 Fundamentals Table 11).

Material Resistance
Outside Surface Resistance .33
Steel Deck 0
3.64” Insulation 12.0
Air Space 1.0
Acoustic Tile 1.79
Inside Surface Resistance .69

Solving for the resistance of the roof:

Calculating the heat transfer coefficient for the roof:

The cooling load temperature differences for flat roofs is ASHRAE table 30 (1997 Fundamentals). However, like walls,
we must account for the roofs ability to absorb heat. Table 31 (ASHRAE 1997 Fundamentals) allows us to account for
the heat absorbing capability of the wall. For a roof constructed primarily of steel deck, R=15.81, with the mass evenly
placed and a suspended ceiling is a roof type 2. Entering table 30, we get a roof CLTD of 80 at 5 PM. Correcting the
CLTD:

Solving for the roof load:

Note that this assumes that the system is a ducted return with no ceiling plenum return air. In this example 100% of the
roof load is assumed to be conducted to the space. In most instances, some percentage of the roof load (especially if it

Nevada Mechanical Systems Duct Design Page 16 of 33


HVAC Clinics Draft - Not For Distribution
is an open plenum return system) is picked up by the return air. In those situations, we generally estimate the
percentage of load that is conveyed to the space and the load that is picked up by the return air.
Having solved the wall, roof, glass conduction and glass solar loads, all that remains is to find the internal loads. The
first internal load we calculate is the internal load. Recall that the lighting load is:

The ballast factor for fluorescent lights is 1.2. Based on a space that is 2700 sq-ft @ 2 watts/sq-ft, the lighting load is:

Note, we assumed a cooling load factor (CLF) for lighting of 1.0. Generally, the a CLF of 1.0 is a safe assumption for
lighting and people based on the fact that the heat absorbed by the space will eventually have to be picked up by the
cooling equipment.

Next, we should find the load for people. Again, we will assume a CLF of 1.0. ASHRAE table 3 (1997 fundamentals)
gives the rates of heat gain from occupants. For moderately active office work, a typical adult male emits 250 btus/hr
sensible and 200 btu’s/hr latent. For a space with 14 people, the people load is:

Finally, we must account for miscellaneous office equipment. We have computers and office equipment which
consume .5 watts/sq-ft. The miscellaneous computers and office equipment load is:

We have one last load contributing device. That is the coffee maker. ASHRAE table 8 (1997 Fundamentals) gives the
recommended heat gain from restaurant equipment. A coffee maker gives off approximately 1500 btu/hr sensible and
790 btu/hr latent.

Finally, summarizing and totaling all the space load components gives us:

Load Component Sensible Load (btu/hr) Latent Load (btu/hr)


Wall Conduction 8,382
Window Conduction 713
Window Radiation 24,883
Roof Conduction 12,800
Lights 22,097
People 3,500 2,800
Misc Computers & Equip 4,604
Coffee Maker 1,500 790
Total 78,479 3,590

Note that we did not solve for infiltration. The ACCA gives tables for calculating the air changers per hour based on
building construction and wind speeds. For a building with low exhaust CFM and tight construction, there is little to no
infiltration and thus no infiltration load. However, if the building is of looser construction, infiltration should be accounted
for.

Nevada Mechanical Systems Duct Design Page 17 of 33


HVAC Clinics Draft - Not For Distribution
Weather Design Conditions
Design Conditions For Reno, NV (ASHRAE 2005 Fundamentals

Nevada Mechanical Systems Duct Design Page 18 of 33


HVAC Clinics Draft - Not For Distribution
People, Materials, and Appliance Heat Gains/Properties
Rates Of Heat Gain from Occupants (ASHRAE 1997 Fundamentals, Chapter 28, Table 3)

Heat Gain for Appliances (ASHRAE 1997 Fundamentals, Chapter 28, Table 5 & 6)

Nevada Mechanical Systems Duct Design Page 19 of 33


HVAC Clinics Draft - Not For Distribution

Thermal Properties Of Layers (ASHRAE 1997 Fundamentals, Chapter 28, Table 11)

Nevada Mechanical Systems Duct Design Page 20 of 33


HVAC Clinics Draft - Not For Distribution
Roofs
Roof Group Numbers & CLTD (ASHRAE 1997 Fundamentals, Chapter 28, Table 30 & 31)

Nevada Mechanical Systems Duct Design Page 21 of 33


HVAC Clinics Draft - Not For Distribution
Walls
Wall Types Mass Located Inside Wall (ASHRAE 1997 Fundamentals, Chapter 28, Table 33A)

Nevada Mechanical Systems Duct Design Page 22 of 33


HVAC Clinics Draft - Not For Distribution
Wall Types Mass Evenly Distributed (ASHRAE 1997 Fundamentals, Chapter 28, Table 33B)

Nevada Mechanical Systems Duct Design Page 23 of 33


HVAC Clinics Draft - Not For Distribution
Wall Types Mass Evenly Distributed (ASHRAE 1997 Fundamentals, Chapter 28, Table 33B)

Nevada Mechanical Systems Duct Design Page 24 of 33


HVAC Clinics Draft - Not For Distribution
Wall CLTD (ASHRAE 1997 Fundamentals, Chapter 28, Table 33B)

Nevada Mechanical Systems Duct Design Page 25 of 33


HVAC Clinics Draft - Not For Distribution

Nevada Mechanical Systems Duct Design Page 26 of 33


HVAC Clinics Draft - Not For Distribution

Nevada Mechanical Systems Duct Design Page 27 of 33


HVAC Clinics Draft - Not For Distribution

Wall Types Mass Located Inside Wall (ASHRAE 1997 Fundamentals, Chapter 28, Table 33A)

Nevada Mechanical Systems Duct Design Page 28 of 33


HVAC Clinics Draft - Not For Distribution

Glass/Fenestration
U-Factors for Various Fenestration (ASHRAE 2005 Fundamentals, Chapter 29, Table 4)

Nevada Mechanical Systems Duct Design Page 29 of 33


HVAC Clinics Draft - Not For Distribution
Shading Coefficient (ASHRAE 1997 Fundamentals, Chapter 29, Table 11)

Nevada Mechanical Systems Duct Design Page 30 of 33


HVAC Clinics Draft - Not For Distribution
CLTD for Conduction through Glass (ASHRAE 1997 Fundamentals, Chapter 28, Table 34)

Zone Types for Use with SCL (ASHRAE 1997 Fundamentals, Chapter 28, Table 35)

Nevada Mechanical Systems Duct Design Page 31 of 33


HVAC Clinics Draft - Not For Distribution

Zone Types for Use with SCL (ASHRAE 1997 Fundamentals, Chapter 28, Table 35)

Nevada Mechanical Systems Duct Design Page 32 of 33


HVAC Clinics Draft - Not For Distribution
Infiltration
Infiltration Models (US Department Of Energy, Table 3, Table 4, Table 5)

Nevada Mechanical Systems Duct Design Page 33 of 33