TOROIDAL CURRENT TRANSFORMERS

TART
These transformers are used when it is necessary to survey the homopolar With passing primary cable
currents(imbalance of current existing on a three phase cable) or in those Running temperature: - 25°C ÷ +40°C.
cases where substantial performance is necessary) If immersed in oil, the maximum running temperature rises to 60°C
The dimensions are not pre-determined but calculated each time on the Finished with cotton taping protected with insulating epoxy varnish
basis of the technical characteristics required

When ordering, indicate: - primary current value (min. 50A)


- secondary current value (min. 1A)
- precision class
- burden (VA)
- internal diameter
The external diameter and the thickness are variable according to the above
mentioned data
The insulation betwee the primary and the secondary cables must be
carried out by the client during assembly

SUMMATION CURRENT TRANSFORMERS


TARS
For vectorial summation of the current of several phases in a single voltage system.
Maximum reference voltage for insulation: 0,72 kV / 3kV
Fixing system: to wall by accessories supplied together with the current transformer

If the primary currents have different ratios,


specify the ratios when ordering Dimensions in mm
Diagram TARS4

IV°.../5A III°.../5A II° .../5A


P1 P2 P1 P2 P1 P2

76 21

18,5

I° P1 P2
..../5A
S1
5A
S2
76

Diagram TARS3

121 III° P1 P2
..../5A
P1 P2
..../5A II°

100

I° P1 P2
..../5A
S1
5A
S2

85

Diagram TARS2
3,7

P1 P2
..../5A II°
91,2

kg class 0,5
secondary current secondary current
weigth

5A 1A I° P1 P2
..../5A
S1
5A
S2

range code VA range code VA


5+5 TARS2 10 1+1 TARS21 10 57
1 5+5+5 TARS3 10 1+1+1 TARS31 10
5+5+5+5 TARS4 10 1+1+1+1 TARS41 10 Base Mounting dimensions

299
TARSD
For vectorial summation of the current of several phases in a single voltage system.
Maximum reference voltage for insulation: 0,72 kV / 3kV
Fixing system: to DIN rail

If the primary currents have different ratios,


specify the ratios when ordering
Diagram TARSD2

P1-15
5A

P2-16
L3

S1-13
L2 I°
L1

L3
L2 II°
P2-4 L1
S2-1 P1-3

Diagram TARSD3

P1-15

P2-16
P1-18 L3
5A L2 I°
S1-13

P2-19
L1

L3
L2 III°
L1

P2-4
S2-1 P1-3
kg class 0,5
L3
secondary current secondary current L2 II°
weigth

5A 1A L1
range code VA range code VA
5+5 TARSD2 6 1+1 TARSD21 6
5+5+5 TARSD3 6 1+1+1 TARSD31 6
5+5+5+5 TARSD4 6 1+1+1+1 TARSD41 6 Diagram TARSD4
P1-15

P2-16

L3
Dimensions in mm L2 I°
58 L1

P2-19
5A
S1-13

P1-18
L3
L2
III°
85 L1
45

L3
L2 IV°
105
S2-1 P2-7 L1
P1-6
The dimension of 105 mm correspond to a 6 DIN
P2-4
modules (17,5 mm each)
P1-3

L3
These diagrams refer to a connection of one phase. In case of a 2 systems
connection (ARON) 2 summation CTs and 2 current transformers (one for phase L1
L2 II°
and one for phase L3) must be used. In case of 3 systems connection 3 summation L1
CTs and 3 current transformers (one for phase L1, one for phase L2 and one for
phase L3) must be used.