Beruflich Dokumente
Kultur Dokumente
Table of Contents
Admonishments Used In This Document............................................................................................................... iv
Introduction ......................................................................................................................................................... 1
Preface ................................................................................................................................................................... 1
Overview ................................................................................................................................................................ 1
Function Descriptions ............................................................................................................................................. 1
Rectifier Control .............................................................................................................................................. 1
System Components Monitoring and System Alarms Generation ..................................................................... 1
Operating Data Acquisition and Data Logs ....................................................................................................... 1
Battery Management ....................................................................................................................................... 1
Battery Charge Temperature Compensation ............................................................................................. 2
Battery Equalize Charge and Battery Charge Current Limit ......................................................................... 2
High and Low Battery Temperature Alarms ............................................................................................... 3
Battery Discharge Test and Battery Test Logs ............................................................................................ 3
Battery LVD (Low Voltage Disconnect) ...................................................................................................... 4
Intelligent Power Matching (Energy Optimization Mode) .................................................................................. 4
Operation ............................................................................................................................................................. 5
Local Indicators....................................................................................................................................................... 5
Passwords and Access Rights .................................................................................................................................. 6
Local Keypad and Display Access ............................................................................................................................. 7
Local Menu Navigation Keys and LCD Display ................................................................................................... 7
Local Display Menus......................................................................................................................................... 7
Navigating the Menus............................................................................................................................... 7
WEB Interface Access .............................................................................................................................................. 8
Overview ......................................................................................................................................................... 8
Setting IP Communications Parameters .................................................................................................... 8
WEB Interface Menus................................................................................................................................ 8
Connecting to the Controller (over a network connection) ........................................................................ 8
Connecting the Controller Directly to your Computer ............................................................................... 8
Disabling Proxy Server Settings to Enable a Connection to the Controller over an Intranet
Network (if required) ................................................................................................................................ 8
Logging into the Controller ..................................................................................................................... 10
Common Tasks Performed via the Local Keypad and/or Web Interface ................................................................... 11
Procedures .................................................................................................................................................... 11
Changing the Local LCD Display Contrast ................................................................................................ 11
Changing the Time Zone ........................................................................................................................ 11
Changing the Date ................................................................................................................................. 11
Changing the Time ................................................................................................................................. 11
Setting IP Communications Parameters .................................................................................................. 11
Viewing/Changing the Float Voltage Setting ........................................................................................... 11
Viewing/Changing the Equalize Voltage Setting ...................................................................................... 11
DANGER! Warns of a hazard the reader will be exposed to that will likely result in death or serious injury
if not avoided. (ANSI, OSHA)
WARNING! Warns of a potential hazard the reader may be exposed to that could result in death or
serious injury if not avoided. This admonition is not used for situations that pose a risk only to
equipment, software, data, or service. (ANSI)
CAUTION! Warns of a potential hazard the reader may be exposed to that could result in minor or
moderate injury if not avoided. (ANSI, OSHA) This admonition is not used for situations that pose a risk
only to equipment, data, or service, even if such use appears to be permitted in some of the applicable
standards. (OSHA)
ALERT! Alerts the reader to an action that must be avoided in order to protect equipment, software,
data, or service. (ISO)
ALERT! Alerts the reader to an action that must be performed in order to prevent equipment damage,
software corruption, data loss, or service interruption. (ISO)
FIRE SAFETY! Informs the reader of fire safety information, reminders, precautions, or policies, or of the
locations of fire-fighting and fire-safety equipment. (ISO)
SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related
to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA)
Operating Data Acquisition and Data Logs No Alarm OFF OFF OFF
Battery Management The alarm indicator turns OFF if the fault(s) that triggered
the alarm clears.
Intelligent Power Matching (Energy Optimization Mode)
The audible alarm can be silenced by pressing any key on
The SCU+ controls the system automatically via configured
the SCU+ Controller local interface pad. The audible
parameters.
alarm is also silenced if the fault(s) that triggered the
A User interfaces with the SCU+ Controller locally using the local alarm clears.
keypad and LCD display or locally/remotely using the WEB
An audible alarm cutoff feature can be programmed that
Interface.
silences the audible alarm after a pre-set programmable
The SCU+ Controller can also be accessed via SNMP (v1 and v2). time period. The audible alarm can also be disabled.
Function Descriptions The available system alarms can also be mapped to alarm relays
(located on SCU+ interface boards) that can be wired to external
Rectifier Control
alarm circuits.
Rectifiers are automatically controlled by the SCU+ Controller, or a
Operating Data Acquisition and Data Logs
User can place the SCU+ Controller in manual mode to manually
control the rectifiers. The SCU+ Controller can also be The SCU+ Controller acquires and analyses real time data from the
programmed to provide an Energy Optimization Mode function. system’s components such as the rectifiers and batteries.
Energy Optimization permits an installation to only operate
The SCU+ Controller uses this data to process alarms and also
rectifiers as needed to maintain the load and keep batteries in a
records some data in logs. The logs are viewed using the Web
fully charged condition. As load increases, Energy Optimization
Interface and consist of...
turns on additional rectifiers as needed to maintain the load. As
load decreases, Energy Optimization places rectifiers in standby to Alarm History Log: Records 200 most recent alarms.
conserve energy usage. Rectifiers which are always operating to
Battery Test Log: Up to 10 battery discharge tests can be
maintain any load requirements are cycled through the group of
performed and recorded per year.
rectifiers controlled by this feature to provide uniform operating
times for each rectifier. Note: Once maximum number of log entries is reached, new entries
overwrite oldest entries.
System Components Monitoring and
System Alarms Generation Battery Management
The SCU+ Controller monitors the components comprising the The SCU+ Controller provides the following battery management
system (such as rectifiers) and generates alarms if a fault condition functions.
occurs. The SCU+ Controller also maintains an alarm history log.
Battery Charge Temperature Compensation DC over or under voltage alarm activates, a low voltage
disconnection occurs, manual mode is entered, or the system
Battery Equalize Charge and Battery Charge Current
enters the equalize or test modes.
Limit
Battery Equalize Charge and Battery Charge Current Limit
High and Low Battery Temperature Alarms
Battery Discharge Tests and Battery Test Logs The SCU+ Controller can increase system output voltage for
equalizing the charge on all battery cells of a conventional flooded
Battery LVD (Low Voltage Disconnect)
cell battery, or for recharging the battery following a commercial
Battery Charge Temperature Compensation power failure.
Compensation
Coefficient setting
(mV/°C)
V equalize
Equalize
Vnom
Mains fault
High and Low Battery Temperature Alarms Constant-Current Time Test: In this variation of the Full-
Load Time Test, a constant portion of the system load is
The SCU+ Controller can monitor battery temperature via a placed on the batteries for a preset period of time. Again,
temperature sensor mounted on a battery cell. Values for high if battery voltage and capacity remain above preset limits
battery temperature and low battery temperature alarms can then until the test time elapses, the battery passes. In addition
be programmed into the SCU+ Controller. to time, voltage and capacity settings, the User can select
the amount of load applied to the batteries.
Battery Discharge Test and Battery Test Logs
Short Time Test: This short-duration test monitors and
The SCU+ Controller can perform battery discharge tests to check compares the discharge currents of two parallel battery
the condition of the battery. Three test types are available. strings. If the difference in the two discharge currents
remains below a preset level until the test time elapses,
Full-Load Time Test: (See Figure 3.) In this test, the entire
the batteries pass. The User can choose the length of the
system load is placed on the batteries for a preset period
test, the alarm current and the interval between tests.
of time. If battery voltage and capacity remain above
(Note: This test requires two battery shunts.)
preset limits until the test time elapses, the batteries
pass. The User can program the test-ending settings of In all three tests, if test requirements are met the Controller
time, voltage and capacity. returns the system to the float charge mode. If requirements are
not met, the test is interrupted, a “test fail” alarm is activated and The batteries are reconnected automatically after a pre-
the Controller returns the system to the float charge mode. Test determined DC voltage level is reached. The User can select
results are automatically saved in a battery test log. whether or not restoration of AC input power is also required for
reconnection to occur.
A User can manually start a battery discharge test or program the
Controller to automatically start the tests at scheduled intervals. Voltage Controlled Disconnection: When the set voltage
level is reached, the batteries are disconnected.
Figure 3. Battery Full-Load and Constant-Current Time Test Diagram
Time Controlled Disconnection: When the set time has
elapsed, the batteries are disconnected.
V nom Test OK
Intelligent Power Matching (Energy Optimization Mode)
V end With Energy Optimization Mode (ECO):
Test not OK
The Controller monitors load current versus system
Test time Time (hours) capacity.
Operation
Local Indicators
Location and Identification: Refer to Figure 4.
Description: There are three (3) indicators located on the SCU+ Controller’s front panel. Refer to Table 2 for the function of the indicators.
10M Ethernet
Factory Use Only Port (RJ-45)
Major or Minor
Alarm Indicator
(Red)
Observation Alarm
Indicator (Yellow)
Status
Indicator
ESC
ENT
(Green)
Status
On Off No input power to the SCU+ Controller.
(Green)
The SCU+ accommodates up to three Users. Each has a User Name, Password, and Access Rights.
Description: There are four (4) menu navigation keys and an LCD display located on the SCU+ Controller’s front panel. Refer to Table 3 for
the function of the menu navigation keys.
Note: When the LCD is lit, if no button is pushed for 8 minutes, the backlight of the LCD display extinguishes and the SCU+ Controller returns to
the Main Screen. Press any key to re-activate the LCD display.
Up
Press
or to scroll through the
menus or to change the value of a
Down parameter.
Note: A valid password is required to access menus that allow changing any power system parameter. Refer to “Passwords and Access Rights”
on page 6.
To Select a Sub-Menu:
Press the up or down arrow keys to move the cursor up and down the list of sub-menus in the menu screen (selects the sub-menu), then
press ENT to enter the selected sub-menu.
To Enter a Password:
If a password screen opens, a password must be entered to allow the User to make adjustments. To enter a password, press ENT. Press
the up or down arrow key to choose character, then press ENT to accept and move to the next character. Repeat until password is
entered, then press ENT to accept password.
To Change a Parameter:
Press the up or down arrow keys to move the cursor up and down the list of parameters in the menu screen (selects the parameter to
change), then press ENT to change the selected parameter. The parameter field highlights. Press the up or down arrow keys to change
the parameter value. Press ENT to confirm the change.
Connecting the Controller Directly to your Computer Note: This procedure needs to be performed only when the
Controller is connected to an Intranet and the User’s computer
Before connecting your computer directly to the Controller’s is set to access the Intranet through a proxy server. Note that if
Ethernet Port, record your current network settings as outlined the Controller is connected to the Internet and the User’s
below, then change these settings to match the communications computer is connected to an Intranet, the User may not be
settings programmed in the Controller. able to disable the proxy server and access the Controller.
PROCEDURE
1. Internet Explorer, version 5.5 or newer, is required. It is best to view the WEB Interface at 1280 x 1024 resolution. In newer
versions of Internet Explorer, you may need to turn Compatibility View On (Tools Menu / Compatibility View).
2. In Internet Explorer, enter the IP address programmed into the Controller and press ENTER. The following Login window opens.
Enter a valid User Name and Password then click OK. For security, the password is not displayed on the computer’s screen while
you log on. You have three attempts to enter a valid User name and password. If both are not entered correctly in three
attempts, the browser is redirected to a blank page. You will then need to reenter the IP address and press ENTER to reopen the
login window.
Note: User names and passwords are case-sensitive. By default, there are two User Name and Password combinations. One is
“admin” and “3”; the other is “operator” and “1”.
3. After entering a valid User Name and Password and clicking LOGIN, the "HOMEPAGE" window opens. Refer to “Web Interface
Menus” on page 32.
Note: To prevent unauthorized personnel from accessing the power system with your Access Rights, it is recommended that you always
close your browser when finished with a session.
Local Menu Navigation: Note: When an arrow key is held depressed, scrolling speed will
To change the contrast of the LCD display, from the Main Screen, increase. To scroll quickly through seconds and minutes to
press and hold the Up Arrow (for increasing) or Down Arrow (for reach the correct hour, press and hold the required arrow key.
decreasing) then press and hold ENT until contrast is as desired. When close to the correct hour, release the key. Press and
Release both buttons. release arrow keys as required to display the correct hour.
Repeat process to reach the correct minute and then the
WEB Menu Navigation: none. correct second.
After selecting Time Zone (by pressing ENT when the cursor is in See also Setting IP Communications Parameters on page 8.
the Time Zone field), use and to select the time zone (time
difference from GMT time), then press ENT. Local Menu Navigation:
Main Menu / Settings / Communication / enter parameters.
WEB Menu Navigation: none.
WEB Menu Navigation:
Communication / enter parameters.
Changing the Date
WEB Menu Navigation: After selecting “Block Alarm” (by pressing ENT when the cursor is
Battery / Battery Charge. in the Block Alarm field), use and to select:
Viewing Alarms Y: Forces the alarm relays into the "off" state and blocks
alarms from changing the relay state.
Local Menu Navigation:
Press ENT.
Main Menu / Status / Active Alarm.
Web Menu Navigation: none.
The alarm number, name, severity, and start time are displayed.
For multiple alarms, use or to scroll up or down through the
alarms.
Clearing a Rectifier Lost Alarm
Web Menu Navigation:
Log / Active Alarms. Local Menu Navigation:
Main Menu / Settings / Alarm / Alarm Control / Clear.
After selecting “Clear” (by pressing ENT when the cursor is in the
Programming the Audible Alarm Feature
Clear field), use or as required to select "Rect Lost" from the
menu options. Press ENT to highlight the selection. Press ENT
Local Menu Navigation:
again. The alarm is cleared.
Main Menu / Settings / Alarm / Alarm Control / Alm Voice.
Web Menu Navigation: none.
Set "Alarm Voice" to:
After selecting “Clear” (by pressing ENT when the cursor is in the Local Menu Navigation:
Clear field), use or as required to select "History" from the Main Menu / Settings / Alarm / Alarm Control / Clear.
menu options. Press ENT to highlight the selection. Press ENT
After selecting “Clear” (by pressing ENT when the cursor is in the
again. The alarm history log is cleared.
Clear field), use or as required to select "TestFail” or “Short
Web Menu Navigation: none. Test” from the menu options. Press ENT to highlight the selection.
Press ENT again. The alarm is cleared.
Available Alarms
Table 4 lists the alarms that you can scroll through in the SETTINGS / ALARM / ALARM LEVEL menu. These are also the possible alarms that
display in the Active Alarm sub-menu. Table 4 also provides guidelines for alarm correction.
Note: These instructions describe the complete functionality of the SCU+. Some functionality is dependent on hardware connected to the SCU+.
Some alarms listed may not display in your system or may be named differently. Refer to the SCU+ Configuration Drawing (C-drawing)
furnished with your system.
Refer also to the SCU+ Configuration Drawing (C-drawing) furnished with your system for factory default “Alarm Severity” and “Alarm
Relay” settings.
Table 4
Table 4
Table 4
Table 4
Overview
This section provides descriptions of the Local Display Menus. Refer also to “Local Keypad and Display Access” on page 7. For Web
interface, refer to “Web Interface Menus” on page 32.
Menus
Figure 5 provides flow diagrams of the menus accessed via the SCU+ Controller local display and keypad.
Note: These instructions describe the complete functionality of the SCU+. Some functionality is dependent on hardware connected to the SCU+.
Some menu items shown may not be present in the SCU+ used in your system.
ESC
ENT Press or
Press or to browse through To enter password, press ENT,
ID: xxxxxxxxxx to move to MAIN MENU screen. then use or to choose
SW REV: x.xx next screen. character. Press ENT to accept
Cfg Rev: xxxxxx
Press ENT and move to the next character.
“config name”
to enter item. Press ENT to accept password.
RunTime: xxh
ECO Stat: N ENT
M A IN M E N U ENT L o g in: *
Sys Used: % ENT
ES C S tatu s P as swo rd : I B
Batt1: A
I Settings
Remain: % ESC ESC
ECO Mode
Manual
Quick Settings
E S C Temp: C ENT
AC A/AB: V
Batt Volt: V
M A IN M E N U ENT L o g in: ENT *
S tatu s P as swo rd : I C
Settings
I ECO Mode ESC ESC
Batt V1: V ENT Manual
ESC
Batt V2: V Quick Settings
Batt V3: V
Batt V4: V
Batt V5: V
Batt V6: V
Batt V7: V M A IN M E N U ENT Lo g in: ENT *
Batt V8: V S tatu s P as sw ord : I D
Settings
ECO Mode E SC ESC
To Change LCD Contrast: I Manual
While in the Main Screen, press ENT and , or ENT and at the same time. Quick Settings
Figure 5. Local Menu Flow Diagrams (cont’d from previous page, cont’d on next page)
Press or to cycle through list of alarms.
Press ESC to return to STATUS menu.
ESC
Figure 5. Local Menu Flow Diagrams (cont’d from previous page, cont’d on next page)
ENT
ALARM
ENT
Alarm Level
B1
Alarm Control
DI Settings
ENT ENT
RECTIFIER B2
Position: Dsbl (Enbl / Dsbl)
R-Posi: 1-1 (1-30) ENT
HVSD: 59.0V (57-59)* LVD
Default V: 53.5V (48-58) LVD1: Enbl (Enbl / Dsbl)
Walk-in On: Y (Y / N) LVD2: Dsbl (Enbl / Dsbl)
Walk-in T: 8s (8-128) LVDMode: Volt (Volt / Time)
Interval T: 0s (0-10) LVD1 Volt: 42.0V (40-60)**
Press or Ac OverV On: N (Y / N) LVD2 Volt: 42.0V (36-60)**
to browse through ACCurrLim: 30A (1-50) LVD1Time: 300min (3-999)
SETTINGS menu. LVD2Time: 600min (3-999)
SMDU1LVD1: 42.0V (40-60)
Press ENT to ENT SMDU1LVD2: 42.0V (40-60)
BATTERY
enter item. I Basic SMDU2LVD1: 42.0V (40-60)
SMDU2LVD2: 42.0V (40-60)
Charge
Test LVD1 Back: Y (Y / N)
ENT SETTINGS ESC LVD2 Back: Y (Y / N)
I Alarm Temp Comp
B Cyc Test Time Reconn: 49.0V (20-60)
Rectifier Ab. Reconn: 49.0V (20-60)
ES C Battery (Y / N)
MainsFailReq: N
LVD
AC ENT ENT
DC DC
Controller AC OverVolt2: 58.0V (40-60)***
Communication Over Volt: 280V (0-500) OverVolt1: 57.0V (40-60)
Under Volt: 90V (0-500) Under V1: 48.0V (40-60)
PH Fail: 80V (0-500) Under V2: 44.0V (40-60)†
ACFD Time: 0min (0-60) Amb High2: 60C (10-100)‡
Aux AC Input: N (Y / N) Amb High1: 40C (10-100)
AC PH: 1-PH (1-PH / 3-PH) Amb Low: -5C (-40-10)
Load Shunt: N (Y / N)
Shunt Coeff:
ENT - Current: 150A (50-5000)
COMMUNICATION - Volt: 25mV (1-150)
Address: 1 (1-254)
Notes: SOCID-L: 1 (1-255) ENT
* Lower limit of “HVSD” range SOCID-H: 0 (0-79) CONTROLLER
is restricted to “Equalize” setting Comm Mode: RS232 (RS232 / MODEM / ETH) Lang: English
in “Settings / Battery / Charge” Protocol: YDN23 (YDN23 / EEM / RSOC / SOCTPE) TZone: GMT+08:00
submenu. BaudRate: 9600 (1200 / 2400 / 4800 / 9600) Date: 2011-03-23
** Upper limits of “LVD1 Volt” Comm Para: N,8,1 (E,7,1 / N,8,1) Time: 22:17:18
and “LVD2 Volt” ranges are IP/Subnet/Gate: Vertical: N (Y / N)
restricted to “Under V2” setting 192.168.1.2 DownloadMode: N (Y / N)
in “Settings / DC” submenu. 255.255.255.0 Reset PWD: N (Y / N)
*** Lower limit of “Over Volt2” range 192.168.1.1 Reset Para: N (Y / N)
is restricted to “Over Volt1” setting. CallbackTime: 3 (1-10) Oper1PWD: ******
† Upper limit of ”Under V2” range Phone Number: Oper2PWD: ******
is restricted to “Under V1” setting. 8601067749 (or NoNumber) AdminPWD: ******
‡ Lower limit of “Amb High2” 8601080821 (or NoNumber) Sys Alm T: 720h (1-9999)
range is restricted to “Amb High1” 8601084801 (or NoNumber) Fail-Safe: Y (Y / N)
setting. IBAddress: IB2-0 (IB1-0 / IB1-1 / IB1-2 / IB1-3 /
IB2-0 / IB2-1 / IB2-2 / IB2-3)
Press or
to browse through
To change a parameter:
each item’s menu.
Press or to place cursor on parameter.
Press ENT to choose parameter.
Press ENT to
Press or to browse through list of values.
change parameter
Press ENT to choose value.
value.
Figure 5. Local Menu Flow Diagrams (cont’d from previous page, cont’d on next page)
ENT ALARM LEVEL ALARM LEVEL ALARM LEVEL
ALARM ENT
B1 I Alarm Level Alarms Blocked SPD Fault LFuse Alarm
E SC Alarm Control Severity: Severity: Severity:
DI Settings Observe Alarm Minor Alarm Major Alarm
E SC Out Relay: 0 Out Relay: 0 Out Relay: 6
Press or
to browse through E SC E SC E SC
ALARM menu.
Press ESC
to return to
Press ENT
ALARM menu.
to enter item.
To browse through ALARM LEVEL list, place cursor before ALARM LEVEL name,
and press ENT to highlight it. Press or to view other ALARM LEVEL screens and parameters.
E SC E SC
Press ESC
to return to To change a parameter value:
ALARM menu. Press or to place cursor on parameter.
Press ENT to choose parameter.
Press or to browse through list of values.
Press ENT to choose value.
To change a parameter name:
Press ENT to highlight character.
Press or to browse through character
options.
Press ENT to accept and move to
next character.
After entering the last character in the string,
press ENT to save the parameter name.
Figure 5. Local Menu Flow Diagrams (cont’d from previous page, cont’d on next page)
E NT
E NT BATTERY BASIC
I Basic Sys Mode: Auto (Auto / Manual)
B2
Charge Batt Fuse: 2 (0-6)
E S C Test Batt Type: 0 (0-10)
E SC CHARGE
Temp Comp Capacity: 300Ah (20-5000)
Batt Shunt1: Y Float: 54.0V (42-58)
Cyc Test Time (Y / N)
Batt Shunt2: N Equalize: 56.5V (42-58)***
(Y / N)
Shunt Coeff: Limit: 0.100C (0.100-0.250)
- Current: 150A Over: 0.300C (0.300-1.000)
(1-5000)
- Volt: 25mV Auto Equalize:
(1-500)
Press or High-T V: 51.0V - Dsbl (Enbl / Dsbl)
(42.0-58.0)
to browse through High T1: N - Curr: 0.060C (0.040-0.080)
(N / Volt / LVD)
BATTERY menu. High T2: N - Capacity: 0.80C (0-0.99)
(N / Volt / LVD)
Const EQ:
Press ENT BATTERY ENT - Curr: 0.010C (0.002-0.02)
to enter item. Basic - Time: 180min (0-1440)
I Charge Cyc Equalize:
Test E SC - Dsbl (Enbl / Dsbl)
Temp Comp - Period: 2400h (2-8760)
Cyc Test Time - Time: 720min (30-2880)
Press or to browse through
EQ Limit Time:
parameter list. Press ENT to change parameter.
- 1080min (60-2880)
E NT TEST
BATTERY End Test
Basic - Volt: 45.2V (43-58)
E SC - Time: 300min (5-1440)
Charge
I Test - Cap: 0.700C (0.000-1.000)
Temp Comp Cyc Test: Dsbl (Enbl / Dsbl)
Cyc Test Time ShortTest:
TEMP COMP - Dsbl (Enbl / Dsbl)
Temp 1: N (N / BattTemp / Amb Temp) - Alarm 10A (1-100)
Temp 2: N (N / BattTemp / Amb Temp) - Period: 720hr (24-8760)
T1-Ex: N (N / BattTemp / Amb Temp) - Time: 5min (1-60)
E NT T2-Ex: N (N/BattTemp/Amb Temp) ConCurr Test:
BATTERY Temp Comp: Dsbl (Enbl / Dsbl) -Dsbl (Enbl / Dsbl)
Basic Center Temp: 25C (10--40)
Charge -Current: 9999A (1-9999)
Coeff: 72mV / C (0-500)
Test E SC Batt T H2: 100C (10-100)*
I Temp Comp Batt T H1: 75C (10-100)
Cyc Test Time Batt T L1: 10C (-40-100)**
Temp Sel: T1-Ex (T1-EX / T2-EX / Temp1 / Temp2)
Notes:
* Lower limit of “Batt T H2” range
is restricted to “Batt T H1” setting. To change a parameter value:
** Upper limit of “Batt T L1” range Press or to place cursor on parameter.
is restricted to “Batt T H1” setting. Press ENT to choose parameter.
*** Lower limit of “Equalize” range is Press or to browse through list of values.
restricted to “Float” setting. Press ENT to choose value.
ENT
MANUAL
D Sys Mode: I Auto (Auto/Manual)
E SC in Manual
MANUAL
Start: I Float (Float/Boost/Test)
Note: LVD1: Reconn (Reconn/Disconn)
To enter MANUAL mode, press LVD2: Reconn (Reconn/Disconn)
ENT to highlight AUTO. Use arrow SM1LVD1: Reconn (Reconn/Disconn)
keys to change AUTO to MANUAL. SM1LVD2: Reconn (Reconn/Disconn)
Press ENT. Then press arrow to RectTrim: 54.0V (42.0 - 58.0)
display and move to MANUAL RectLimit: 121% (10-121)
mode screen. R-Reset: 1-N (Y/N)
R-DCStat: 1-On (On/Off)
R-ACStat: 1-On (On/Off)
Description of Local Display (and Web Interface) automatically silences after the selected time
Menus Line Items period.
The following are descriptions of the editable parameters Block Alarms: Blocks or allows operation of all external
presented in the local display menus. Parameter descriptions can alarm relays.
also be used for the WEB Interface menus. Note that the names in a. N: Alarms are processed normally
the WEB Interface menus may be longer since the WEB Interface
allows more characters to be displayed then the local (LCD) b. Y: Forces the alarm relays into the “off” state and
display. blocks alarms from changing the relay state.
Use the menus to assign an Alarm Severity Level (none, f. TestFail: Clears the alarm generated when batteries
observation, minor, major) to each possible alarm. You fail a “Full-Load Time Discharge test or Constant-
can also set the output relay number for the Current Time Discharge test.
corresponding alarm. g. Rect Lost: Clears a “Rectifier Lost” alarm.
Note: The severity levels of the “temperature sensor DI (DIGITAL INPUT) SETTINGS MENU
disconnected” and “temperature sensor failure” alarms
and the corresponding relay output cannot be set Menu Navigation: Main Menu / Settings / Alarm / DI Settings
through the LCD. The severity levels of these two alarms “DI Settings” Parameter Settings:
and the corresponding relay are the same as those of the
high temperature alarm setting. Use the menus to configure alarm activation for each
digital input.
Note: If an analog alarm has two levels of alarm thresholds and
if these two thresholds are set to the same value, then the a. High: Alarm is activated when the digital input
second level will be cancelled and the first level of the signal as applied.
alarm will be displayed in the LCD. For example, with the b. Low: Alarm is activated when the digital input signal
“high temperature 1” and “high temperature 2” alarm as removed.
thresholds both set to 40°C, if the temperature exceeds
40°C only a “high temperature 1” alarm will be issued. Note: DI No.1 through DI No.2 refers to the digital inputs on the
SCU+. DI No.1-EX through DI No.8-EX refers to the digital
ALARM CONTROL MENU inputs on the separate IB2 customer interface board.
Menu Navigation: Main Menu / Settings / Alarm / Alarm Control Rectifier
“Alarm Control” Parameter Settings:
RECTIFIER MENU
Alm Voice: Programs the audible alarm feature.
Menu Navigation: Main Menu / Settings / Rectifier
a. Off: Disables the audible alarm
“Rectifier” Parameter Settings:
b. On: When a new alarm occurs, the audible alarm
sounds. Press any key to silence the audible alarm. Position: Enables or Disables the rectifier positioning
setting.
c. 3min / 10min / 1h / 4h: When a new alarm occurs,
the audible alarm sounds. The audible alarm R-Posi: Indicates a rectifier position in a shelf or system.
Upon initial power system startup, the rectifiers are
HVSD: Sets the High Voltage Shutdown point for all Capacity: Should be set to the capacity of the battery
rectifiers. connected to the system.
Default V: Sets rectifier default output voltage. This is Batt Shunt1: Should be set to “Y” if system has a battery
the setting to which the rectifiers will revert should the shunt and “N” if system has no battery shunt.
Controller fail or be removed from the system, or if
Batt Shunt2: Should be set to “Y” if system has a second
communication between the controller and rectifiers is
battery shunt and “N” if system does not have a second
lost.
battery shunt.
Walk-in On: Selects whether the walk-in feature of all
Shunt Coeff: The following battery shunt parameters can
rectifiers is enabled (Y) or not (N).
be set.
Walk-in T: Sets the time, in seconds, required for rectifier
a. Current: Should be set to the current rating
output current to go from zero to full load at start-up.
(capacity) of the battery shunt(s).
This feature (also called soft-start, ramp-up or rate of rise)
is used to smooth the start-up current of the rectifiers in b. Volt: Should be set to the (full-load) voltage output
order to reduce inrush current on the AC supply. of the battery shunt(s).
Interval T: Sets the sequencing delay, in seconds, for the High-T V: Sets system output voltage level in the event
rectifiers in the system to start supplying current after AC of high battery temperature. (“High T1” or “High T2”
input power is applied to the system. This delay is applied must be set to “Volt”.)
to each rectifier in the system according to their
High T1: Selects from the following actions if battery
numbering sequence. For example, if 5 seconds is
temperature increases to the “Batt T H1” setpoint:
selected, the first rectifier will start after 5 seconds, the
second rectifier will start after 10 seconds, the third a. LVD: LVD contactor opens
rectifier will start after 15 seconds, and so on. This feature
b. Volt: Output voltage is reduced
(also called start-up delay) is used to stagger the start-up
of the rectifiers in order to reduce inrush current on the c. N: No action
AC supply.
High T2: Selects from the following actions if battery
AC OverV On: Selects whether the AC Over Voltage temperature increases to the “Batt T H2” setpoint:
feature is enabled (Y) or not (N). This feature allows the
a. LVD: LVD contactor opens
rectifiers to operate above their internal AC input
overvoltage threshold. (See Rectifier User Manual for b. Volt: Output voltage is reduced
threshold value.)
c. N: No action
ACCurrLim: Sets rectifier input current limit value during
startup process.
Over: Sets the Battery Over Charge alarm value. The EQ Limit Time: Sets the equalize charging time limit. This
displayed value is relative to the nominal capacity of the is the maximum duration, in minutes, that an Auto
battery. For example, a value of 0.300C10 means that if Equalize cycle will last regardless of any other settings.
the charging current reaches 30% of the battery’s
TEST MENU
nominal capacity, the alarm will be extended.
Menu Navigation: Main Menu / Settings / Battery / Test
Auto Equalize: The following parameters for starting an
Automatic Equalize charge cycle can be set. “Battery Discharge Test” Parameter Settings:
a. Enbl or Dsbl: Enables or disables the Automatic End Test: During Full-Load Current and Constant-Current
Equalize Charge feature. battery discharge tests, the output voltage of the
rectifiers is reduced so that the batteries supply all or
Note: If the power system has been automatically placed in
partial power, respectively, to the system load. The test
Equalize mode, disabling Auto Equalize will not
is interrupted when one of the following conditions is
return the system to the Float mode until the current
reached.
Equalize cycle is completed. To return immediately
to Float mode, navigate as follows: Main Menu / a. Volt: Sets the “end of test” voltage level for each
Manual / Start, and select Float. test (battery fails test).
b. Curr: The system is transferred to Equalize Charge b. Time: Sets the maximum duration, in minutes, for
mode if battery charging current increases to this each test (battery passes test).
setting (Auto Equalize must be enabled). For
c. Cap: Sets the value of the remaining battery
example, a value of 0.060C10 means that an
capacity at which a test will be interrupted (battery
Automatic Equalize is started if the battery charge
fails test). The displayed value is relative to the
current is greater than 6% of the battery’s nominal
nominal capacity of the battery. For example, a
capacity.
value of 0.700C10 means that when the discharging
c. Capacity: The system is transferred to Equalize current reaches 70% of the battery’s nominal
Charge mode if remaining battery capacity capacity, the battery test is interrupted.
decreases to this setting (Auto Equalize must be
Cyc Test: Enables or disables cyclic (scheduled) Full-Load
enabled).
Current or Constant-Current tests. To view or modify
Const EQ: The following parameters for ending an scheduled test dates and times, see Battery Cyclic Test
Automatic Equalize charge cycle can be set. Time Parameters in the following section.
a. Curr: When in Equalize Charge mode and the ShortTest: A short test is a short duration battery
battery charge current decreases below this setting discharge test used to verify that parallel strings of
for the time period selected in “Time” (below), the batteries are discharging equally. If the discharge current
system is transferred to Float Charge mode. For difference between the two battery strings exceeds a
example, a value of 0.010C10 means that when the preset adjustable level (default is 10A) within a preset
charging current is less than 1% of the battery’s time limit, a “Short Test Fail” alarm is generated. (Note:
This test requires two battery shunts.) The following interface board is used for battery or ambient
parameters can be set: temperature measurements, or not used.
a. Enbl/Dsbl: Selects whether the Short Battery T2-Ex: Selects whether a temperature probe connected
Discharge Test function is enabled or disabled. If to probe position 2 on the separate IB2 customer
enabled, the test will automatically repeat at preset interface board is used for battery or ambient
intervals. temperature measurements, or not used.
b. Alarm: Sets the discharge current difference Temp Comp: Selects whether temperature
between two battery strings at which the “Short Test compensation is enabled or disabled.
Fail” alarm will be extended.
Center Temp: Sets the temperature, in °C, at which the
c. Period: Sets the interval, in hours, between short system operates at normal voltage levels (float setting).
battery discharge tests.
Coeff: Sets the temperature compensation slope, or rate
d. Time: Sets the duration, in minutes, of each short of change per °C above or below the normal operation
battery discharge test. level selected in the second line. This value is expressed in
millivolt per °C per string (mV/°C/str). For example, for a
ConCurr Test: The Constant Current test is a variation of
rate of change of 72 mV/°C/str in a 24-cell, 48 V nominal,
the Full-Load Current test. In the Constant-Current test,
battery string, the rate of change is 3 mV per cell.
the Controller automatically adjusts the rectifiers to
maintain the battery discharge current at a constant Batt T H2: Sets the temperature at which the “Temp[#]
preset value. In addition to the settings listed under “End High2” or “Temp[#]-EX High2” alarm activates.
Test”, the following parameters can be set:
Batt T H1: Sets the temperature at which the “Temp[#]
a. Enbl/Dsbl: Selects whether the Constant-Current High1” or “Temp[#]-EX High1” alarm activates.
battery test function is enabled or disabled. If the
Note: When temperature compensation is enabled, if the
Constant-Current test is disabled, the Full-Load
“Temp High 1” alarm activates, the temperature
Current test is enabled by default.
compensation function will remain enabled, but output
b. Current: Sets the value of the constant load applied voltage will not decrease below the voltage present at the
to the battery. alarm setpoint regardless of temperature.
TEMP COMP (TEMPERATURE COMPENSATION) MENU Batt T L1: Sets the temperature at which the “Temp[#]
Low1” or “Temp[#]-EX Low1” alarm activates.
Menu Navigation: Main Menu / Settings / Battery / Temp Comp
Note: When temperature compensation is enabled, if the
“Battery Temperature Compensation” Parameter Settings:
“Temp Low 1” alarm activates, the temperature
Note: Setting any probe to “battery” or “ambient” without a compensation function will remain enabled, but output
probe connected will cause a “T# No Probe” alarm. voltage will not increase above the voltage present at the
alarm setpoint regardless of temperature.
Note: “Temp 1” and “Temp 2” refer to the probe inputs on the
SCU+. “Temp 1-EX” and “Temp 2-EX” refer to the probe Temp Sel: Selects which temperature probe is used for
inputs on the separate IB2 customer interface board. temperature compensation.
Temp 1: Selects whether a temperature probe CYC (CYCLIC) TEST TIME MENU
connected to probe position 1 on the SCU+ is used for
Menu Navigation: Main Menu / Settings / Battery / Cyc Test Time
battery or ambient temperature measurements, or not
used. “Battery Cyclic Test Time” Parameter Settings:
Temp 2: Selects whether a temperature probe 00-00 00:00: Setting for when a scheduled Battery
connected to probe position 2 on the SCU+ is used for Discharge Test occurs. Events are displayed in the MM-
battery or ambient temperature measurements, or not DD HH:MM format (the field for the minutes is not
used. adjustable). Note that there can be up to 12 scheduled
battery discharge tests per year. The date and time of
T1-Ex: Selects whether a temperature probe connected
any scheduled test can be modified as follows:
to probe position 1 on the separate IB2 customer
a. After selecting “Cyc Test Time” (by pressing ENT LVD2 Back: Selects whether or not contradictory
when the cursor is in the Cyc Test Time field), use feedback from the LVD2 contactor will issue an alarm.
or to move to the desired entry in the list. Alarm indicates a stuck contactor.
b. Press ENT to highlight the entry. Use or to Reconn: Sets the voltage at which LVD contactor(s) will
scroll through the hours, the days and the months. reconnect following a disconnect and subsequent DC
When the desired month, day and hour are voltage recovery. System AC input must be present.
displayed, press ENT.
Ab. Reconn: Sets the voltage at which LVD contactor(s)
Note: When an arrow key is held depressed, scrolling speed will will reconnect following a disconnect and subsequent DC
increase. To scroll quickly through hours and days to voltage recovery. System AC input need not be present.
reach the correct month, press and hold the required
MainsFailReq: This parameter affects the operation of
arrow key. When close to the correct month, release the
the LVD feature. when set to a value of “Yes”, the LVD
key. Press and release arrow keys as required to display
feature is restricted to operate only when there is an “AC
the correct month. Repeat process to reach the correct
Mains Failure” alarm.
day and then the correct hour.
AC
LVD (Low Voltage Disconnect)
AC MENU
LVD MENU
Menu Navigation: Main Menu / Settings / AC
Menu Navigation: Main Menu / Settings / LVD
“AC” Parameter Settings:
“Low Voltage Disconnect” Parameter Settings:
Over Volt: Sets the voltage at which the AC Over Voltage
LVD1: Enables or disables LVD1.
alarm activates.
LVD2: Enables or disables LVD2
Under Volt: Sets the voltage at which the AC Under
LVDMode: Sets the LVD by time or by voltage. Voltage alarm activates.
LVD1 Volt: Sets the voltage at which the LVD1 contactor PH Fail: Sets the voltage at which the AC Phase Fail alarm
disconnects if LVD Mode is set to “Volt”. activates.
LVD2 Volt: Sets the voltage at which the LVD2 contactor ACFD Time: Sets the length of time after an “AC Mains
disconnects if LVD Mode is set to “Volt”. Fail” alarm occurs before the ACFD alarm occurs. Valid
value are from 0-60 minutes. Setting the value to zero
LVD1Time: Sets the time period after which the LVD1
disables the ACFD alarm.
contactor disconnects if LVD Mode is set to “Time”.
Note: Ensure that no AC Mains Fail alarm is present before
LVD2Time: Sets the time after which the LVD2 contactor
enabling the ACFD alarm.
disconnects if LVD Mode is set to “Time”.
Aux AC Input: When set to “Yes”, AC input is measured
SMDU1LVD1: Sets the voltage at which the SMDU1 LVD1
by the Controller (AC sampler board). When set to “No”,
contactor disconnects.
the AC value is sent from rectifiers to Controller.
SMDU1LVD2: Sets the voltage at which the SMDU1 LVD2
Note: The AC Input option is not presently used. Feature should
contactor disconnects.
always be set to “No”.
SMDU2LVD1: Sets the voltage at which the SMDU2 LVD1
AC PH: Should be set to the type of AC source that
contactor disconnects.
supplies the system (1-phase or 3-phase).
SMDU2LVD2: Sets the voltage at which the SMDU2 LVD2
DC
contactor disconnects.
LVD1 Back: Selects whether or not contradictory DC MENU
feedback from the LVD1contactor will issue an alarm.
Menu Navigation: Main Menu / Settings / DC
Alarm indicates a stuck contactor.
OverVolt2: Sets the voltage at which the Over Volt2 Oper2PWD: Sets the password of operator 2.
alarm activates.
AdminPWD: Sets the password of administrator.
OverVolt1: Sets the voltage at which the Over Volt1
Sys Alm T: Sets the maximum time any system alarm will
alarm activates.
be active.
Under V1: Sets the voltage at which the Under V1 alarm
Fail-Safe: Sets whether or not the alarm relay assigned to
activates.
the “major summary” alarm operates in the fail-safe
Under V2: Sets the voltage at which the Under V2 alarm mode. (Fail-safe means the relay is energized during
activates. normal operation and de-energized for an alarm
condition.)
Amb High2: Sets the temperature at which the Amb
High2 alarm activates. Communication
Amb High1: Sets the temperature at which the Amb
COMMUNICATION MENU
High1 alarm activates.
Menu Navigation: Main Menu / Settings / Communication
Amb Low: Sets the temperature at which the Amb Low
alarm activates. “Communication” Parameter Settings:
Load Shunt: Selects whether or not the Controller Address: Equipment address for serial port
recognizes the load shunt. communications. Default setting is 1. (Function not used
at this time.)
Shunt Coeff: The following load shunt parameters can be
set. SOCID-L: System Operator Code identification low bit.
(Function not used at this time.)
a. Current: Should be set to the current rating
(capacity) of the load shunt. SOCID-H: System Operator Code identification high bit.
(Function not used at this time.)
b. Volt: Should be set to the (full-load) voltage output
of the load shunt. Comm Mode: Selects “RS232”, “MODEM” or “Ethernet”
as the serial port communication mode. Default setting
Controller
is RS232. (Function not used at this time.)
Lang: Sets the display language of the LCD. BaudRate: Selects the serial port baud rate for modem
communication. Default setting is 9600. (Function not
Tzone: Sets the time zone.
used at this time.)
Date: Sets the current date.
Comm Para: Serial port communication parameter.
Time: Sets the current time. Default setting is N,8,1. Setting should not be changed.
(Function not used at this time.)
Vertical: Sets the orientation of the local display for
vertical (Y) or horizontal (N) Controller installation. IP/Subnet/Gate: Setting for network communications.
DownloadMode: Enters the download mode via serial a. IP Address: Sets the Controller’s IP address. Enter
port. the address in the format nnn.nnn.nnn.nnn, where 0
≤ nnn ≤ 255. The address must be a valid address
Reset PWD: Resets the password to default.
and must not be 255.255.255.255.
Reset Para: Resets parameters to the default values
b. Subnet: Sets the Controller's network netmask.
provided by the configuration file loaded into the
Enter the address in the format nnn.nnn.nnn.nnn,
Controller.
where 0 ≤ nnn ≤ 255.
c. Gate: Sets the Controller's gateway address. Enter Start: Immediately starts the float, equalize or battery
the address in the format nnn.nnn.nnn.nnn, where 0 test mode.
≤ nnn ≤ 255. This is the address of the gateway of
Note: If an Equalize or Test cycle is started in manual mode,
the network on which the Controller resides. The
returning the system to “Auto” mode will not end the
address must be a valid address and must not be
Equalize or Test cycle. To immediately return the system
255.255.255.255.
to float mode, in the Manual menu select “Float” under
Callback Time: Sets the number of times the Modem will the Start parameter.
call back to host when an alarm is issued. (Function not
LVD1: Opens or closes the LVD1 contactor.
used at this time.)
LVD2: Opens or closes LVD2 contactor.
Phone Number: Phone number(s) Modem will call when
an alarm is issued. Up to three phone number can be SM1LVD1: Opens or closes SMDU1LVD1 contactor.
entered. (Function not used at this time.)
SM1LVD2: Opens or closes SMDU1LVD2 contactor.
IBAddress: Factory configured for the associated
RectTrim: Temporarily sets the output voltage for all
Customer Interface (IB) Board. Default setting is IB2-0.
rectifiers. Voltage can be increased or decreased from
Setting should not be changed. (Function not used at this
the existing Float Charge or Equalize Charge setting,
time.)
depending on which mode the Controller is set for (see
“Start”). Setting reverts to original when Controller is
returned to the Auto mode.
ECO Mode (Energy Optimization) Menu
RectLimit: Adjusts the output current limit point for all
Menu Navigation: Main Menu / ECO Mode
rectifiers.
“ECO Mode” Parameter Settings:
R-Reset: Resets a rectifier that has shut down and locked
Dsbl / Enbl: Disables or enables Energy Optimization out due to a High Voltage Shutdown.
Mode function.
R-DCStat: Turns the DC output of all rectifiers on or off.
Cyc Period: This is the time period that rectifiers are
R-ACStat: Turns the AC input of all rectifiers on or off.
turned on and off to maintain an equal operating time for
all rectifiers in the system.
BestOperPt: Percent of full load capacity below which Quick Settings Menu
the rectifiers will operate in the Energy Optimization
Menu Navigation: Main Menu / Quick Settings
mode.
“Quick Settings” Parameter Settings: The following settings are
MinOperRect: Minimum number of rectifiers that will
also available in other submenus.
operate in the Energy Optimization mode.
Capacity: Should be set to the nominal capacity of the
FluctRange: If load fluctuation is less than this value,
battery connected to the system.
rectifiers are not turned on or off for Energy Optimization
Batt Shunt1: Selects whether or not the Controller
StopPoint: Load at which ECO mode stops.
recognizes battery shunt 1.
Rect ON T: At the end of the every “Cyc Period”, the
Batt Shunt2: Selects whether or not the Controller
“Drytime” is the time ALL rectifiers will turn on and run
recognizes battery shunt 2.
before cycling again.
Shunt Coeff: The following battery shunt parameters can
be set.
Manual Mode Menu
a. Current: Should be set to the current rating
Menu Navigation: Main Menu / Manual (capacity) of the battery shunt(s).
Sys Mode: Selects Manual or Auto system operation. b. Volt: Should be set to the (full-load) voltage output
of the battery shunt(s).
“Manual” Parameter Settings: Allows you to manually change
system parameters when Sys Mode set to manual.
Load Shunt: Selects whether or not the Controller b. Volt: Should be set to the (full-load) voltage output
recognizes the load shunt. of the load shunt.
Note: To prevent unauthorized personnel from accessing the power system with your Access Rights, it is recommended that you always close
your browser when finished with a session.
Menu
Navigation
Area
The System Status Webpage is divided into two functional areas: the System Information and Menu Navigation Area.
AC Input Webpage
When AC Input is clicked in the menu tree, menu options AC Information and AC Settings are launched in the main frame, as shown in
the following figure.
Note: If “---“is shown as value, it means that the AC phase is set at “1-Phase”.
AC Settings Menu: Includes the following parameters:
Over Voltage Alarm: User can select the voltage at which the AC Over Voltage alarm activates.
Under Voltage Alarm: User can select the voltage at which the AC Under Voltage alarm activates.
Phase Fail Alarm: User can select the voltage at which the AC Phase Fail alarm activates.
AC Auxiliary Input: When set to “Yes”, AC input is measured by the Controller (AC sampler board). When set to “No”, the AC
value is sent from rectifiers to Controller.
AC Phase: User should set to the type of AC input that powers the system (1-phase” or “3-phase).
Note: When a value that is not within the allowed range is entered, a warning dialog box appears and prompts User to use correct value.
DC Output Webpage
When DC Output is clicked in the menu tree, menu options DC Information and DC Settings are launched in the main frame, as shown in
the following figure.
DC Information Menu: Provides Load Shunt and Load Shunt Coefficient values.
Over Voltage1 Alarm: User can set the voltage level at which the Over Voltage 1 alarm activates.
Over Voltage2 Alarm: User can set the voltage level at which the Over Voltage 2 alarm activates. This value cannot be set lower
than the Over Voltage1 value.
Under Voltage1 Alarm: User can set the voltage level at which the Under Voltage 1 alarm activates.
Under Voltage2 Alarm: User can set the voltage level at which the Under Voltage 2 alarm activates. This value cannot be set
higher than the Under Voltage 1 value.
Rectifiers Webpage
When Rectifiers is clicked from the menu tree, menu options Rectifier Settings and Rectifier Information are launched in the main frame,
as shown in the following figure.
High Voltage Shut Down: User can set the output voltage value at which rectifier(s) will shut down. This value cannot be set
lower than the Equalize charge value.
Default Voltage: User can set the output voltage a rectifier will revert to if communication with the controller is lost.
Walk-in On: User can “Enable” or “Disable” gradual increase of rectifier output when rectifier is first turned on.
Walk-in Time: User can set the amount of time required for rectifier output current to increase from zero to full load at startup.
Sequence Start Interval: User can set the interval between the start of one rectifier and the start of the next. When value is set
to “0”, all rectifiers start simultaneously.
AC Over Voltage On: User can “Enable” or “Disable” the function. When enabled, the function allows each rectifier to operate
with input voltages above its internal AC input overvoltage threshold.
AC Current Limit: User can limit rectifier input current during startup process.
Rectifier Over Current Alarm: User can set the output current value at which the “Rect Overload” alarm activates.
Rectifier Information Menu: Shows the Broadcast Current Limit Point, and various rectifier parameters. Details in red font indicate that
the rectifier is not communicating. Disconnected or nonexistent rectifiers are indicated with “---“.
Battery Groups Information Menu: Provides Battery1 Current, Battery2 Current, Battery1 Capacity, Battery2 Capacity, LVD Contactor
Mode, and Shunt Coefficient values.
Float Voltage: User can set the voltage value in Float mode.
Equalize Voltage: User can set the voltage value in Equalize mode.
Current Limit Point: User can set the battery charge current limit point.
Over Current Alarm Point: User can set the “Battery Over Charge" alarm point.
LVD1: User can select the LVD1 (Low Voltage Disconnect 1) value. This value cannot be set higher than the Under Voltage2
alarm value (see DC Webpage).
LVD2: User can select the LVD2 (Low Voltage Disconnect 2) value. This value cannot be set higher than the Under Voltage2
alarm value (see DC Webpage).
Battery Capacity: User should set this value to match the capacity of the battery being connected to the system.
Equalize Charge: User can “Enable” or “Disable” the battery equalize charge mode.
Cycle Test: User can enable or disable cyclical (scheduled) battery discharge tests.
End Test Voltage: User can select the bus voltage at which the test will terminate.
End Test Time: User can select the time limit of the test. The test will terminate if period indicated has lapsed.
End Test Capacity: User can select the battery capacity value. The test will terminate if battery capacity decreases below the
selected value.
Short Test: User can enable or disable the short test function. A short test is a short duration battery discharge test used to
verify that parallel battery strings are discharging equally. If the discharge current difference between the two battery strings
exceeds a preset level (default is 10A), a Short Test Fail alarm is generated.
Test Period: User can set the period between start of one short test and the next.
Constant Current Test: User can “Enable” and “Disable” Constant Current Test.
Constant Current: User can set current value. During the Constant Current Test, the battery will discharge at this value.
Temperature Information Menu: Provides Temperature1, Temperature2, Temp1-EX, and Temp2-EX values.
Temperature1 Setting: User can select whether a temperature probe connected to probe position 1 on the SCU+ is used for
battery or ambient temperature measurements, or not used.
Temperature2 Setting: User can select whether a temperature probe connected to probe position 2 on the SCU+ is used for
battery or ambient temperature measurements, or not used.
Temp1-EX Setting: User can select whether a temperature probe connected to probe position 1 on the separate IB2 customer
interface board is used for battery or ambient temperature measurements, or not used.
Temp2-EX Setting: User can select whether a temperature probe connected to probe position 2 on the separate IB2 customer
interface board is used for battery or ambient temperature measurements, or not used.
Note: Unused probe positions must be set to “None”; otherwise an alarm will be generated.
Temperature Compensation: User can “Enable” or “Disable” the temperature compensation function.
Battery Temperature High1 Alarm: User can select the temperature at which the “Battery Temperature High1” alarm activates.
Battery Temperature High2 Alarm: User can select the temperature at which the “Battery Temperature High2” alarm activates.
This value is greater than or equal to Battery Temperature High1 value.
Battery Temperature Low Alarm: User can select the temperature at which the “Battery Temperature Low” alarm activates.
Ambient Temperature High1 Alarm: User can select the temperature at which the “Ambient Temperature High1” alarm
activates.
Ambient Temperature High2 Alarm: User can select the temperature at which the “Ambient Temperature High2” alarm
activates. This value cannot be set lower than the Ambient Temperature High1 value.
Ambient Temperature Low Alarm: User can select the temperature at which the “Ambient Temperature Low” alarm activates.
ECO Mode: User can “Enable” or “Disable” the Energy Optimization Mode feature.
Cycle Period: User can select cycle period for each rectifier to enter another ECO process.
Rectifier Best Operating Point: User can select the percentage of full load capacity below which the rectifiers will operate in the
Energy Optimization mode.
Load Fluctuation-Range: If load fluctuation is less than this value, rectifiers are not turned on or off for Energy Optimization.
Activity Duration: User can select time in which lower efficiency rectifiers are activated.
Minimum Operating Rectifier: User can select minimum number of rectifiers that will operate when system is in the ECO mode.
Communication Webpage
When Communication is clicked from the menu tree, menu options Communication Information, IP Settings and Communication
Settings are launched in the main frame, as shown in the following figure.
Remote IP1: User can enter the remote computer IP, which communicates with the controller via EEM/SOCTPE/RSOC protocol.
(Function not used at this time.)
Remote IP2: User can enter another remote computer IP, which also communicates with the controller via EEM/SOCTPE/RSOC
protocol. (Function not used at this time.)
Alarm Report Port1: User can enter the port1 used for alarm repoting. (Function not used at this time.)
Alarm Report Port2: User can enter the port2 used for alarm repoting. (Function not used at this time.)
Trap Destination1: User can enter the remote computer IP, which is used when sending report to the controller via SNMP
protocol, during an alarm signal.
Trap Destination2: User can enter the remote computer IP, which is also used when sending report to the controller via SNMP
protocol, during an alarm signal.
Address/CCID: User can enter controller address for EEM communication. (Function not used at this time.)
SOCID: User can enter the System Operator Code Identification. (Function not used at this time.)
Protocol: User can set protocol to “YDN23”, “EEM”, “SOCTPE” or “RSOC”. (Function not used at this time.)
Communication Mode: User can set communication mode to “RS232”, “MODEM” or “Ethernet”.
(Function not used at this time.)
Alarm Report: U ser can “enable” or “disable” alarm reporting function. (Function not used at this time.)
Callback: User can “enable” or “disable” Callback function. (Function not used at this time.)
Alarm Report Attempts (modem): User can set alarm report attempts. (Function not used at this time.)
Baud Rate: User can set serial communication baud rate. (Function not used at this time.)
Phone Number1: User can set the phone number 1, which the controller contacts when reporting the alarm.
(Function not used at this time.)
Phone Number2: User can set the phone number 2, which the controller contacts when reporting the alarm.
(Function not used at this time.)
Phone Number3: User can set the phone number 3, which the controller contacts when reporting the alarm.
(Function not used at this time.)
EEM Port: User can enter the EEM port. (Function not used at this time.)
The details on each alarm are classified as Index, Alarm Name, Start Time and Severity Level.
The details on each alarm are classified as Index, Alarm Name, Start Time and End Time.
The details of each log entry are classified as Start Time, Start Mode, Start Voltage, End Time, End Mode, End Voltage,
Batt1DischargeCapacity and Batt2DischargeCapacity.
Alarm: Test ends due to any system alarm not related to the battery test.
Capacity: Test ends when capacity decreases below test setting before test time elapses.
Communication: Test ended due to lost communication between rectifier(s) and controller.
Little Curr: Test ended if there is no battery discharge current for three minutes.
Protection: Test ended when protection circuitry prevents the rectifier(s) from supplying sufficient load current.
Short Test: Short Test ended due to difference in battery string currents being greater than alarm setting before test time
elapses.
Voltage: Test ended due to voltage decreasing below test setting before test time elapses.
System Webpage
When System is clicked from the menu tree, menu options System Information and System Information Settings are launched in the
main frame, as shown in the following figure.
2.06
System Information Menu: Provides Software Version, Hardware Version, Barcode, and User Config Edition values.
Change the Operator Password: User can set new User password.
Change the Administrator Password: User can set new administrator password.
When changing Administrator password, the User must have the highest level of authority. Otherwise, a warning dialog box appears, as
shown in the following figure.
To reflect new passwords, the User must log out, and log in the system if necessary.
Up/Download Webpage
When Up/Download is clicked from the menu tree, menu option Upload/Download File is launched in the main frame, as shown in the
following figure.
Menu option Upload File allows User to upload a configuration file to the local server from the controller. Choose the configuration file
and click Upload.
Menu option Select Configuration File allows User to download a configuration file from the local server to the controller. Once the file
has been located, click the Download button. Choose the Save button in the dialog box as shown below.
The system will show the window below when the download process is completed.
The User must have the highest level of authority to download a configuration file. Otherwise, a warning dialog box appears, as shown in
the following figure.
When Go to Firmware Download Mode button is clicked, the Web BootLoader mode is launched.
The User must have the highest level of authority to use the Firmware Download Mode function. Otherwise, a warning dialog box
appears, as shown in the following figure.
Ver2.06
To download firmware, select Firmware, type in the filename in the text box and click the Download button.
Take note of the used filenames. Otherwise, when an incorrect filename is entered, a warning dialog box appears, as shown in the
following figure.
1. Set up a serial connection between the computer and the SCU+. Connect the DB9 terminal to the computer, and the RJ45
terminal to the assigned with “IOIO” in the SCU+.
3. Set the parameter values. In the figure above, COM3 is selected as connection option. Note that the User should choose the
connection setting to whichever COM port he is using.
4. After clicking the OK button, set the COM3 parameters as shown in the following.
After setting the values, the main Download/Upload menu appears, as shown in the following figure.
2.06)
To Update Application Program, Menu File and Configuration File Functions, use the Following Steps:
1. Using the main application menu, choose the desired function. User will be prompted to delete the existing file.
3. From the Top Menu, select Transfer, then Send File to locate the file to download.
2.06)
4. Select SCUPLUS_APPV***.bin file (*** represents the version number. For example: SCUPLUS_APPV206.bin for version 2.06)
and Ymodem as protocol. Click Send button.
APPV206.bin
APPV206.bin
APPV206.bin
To Update Menu File to PC and Data Configuration File to PC Functions, use the Following Steps:
2. From the Top Menu, select Transfer, then Receive File to choose the location to where the file is saved.
1. Using the main application menu, press “6” to launch the function.
2. From the Top Menu, select Transfer, then Send File to select the “.bin” file to be downloaded.
BOOTV206.bin
BOOTV206.bin
BOOTV206.bin
6. To execute the selected application program, press “7”. The status window appears, as shown below.
Accessing the Controller via a Information Base). This MIB contains parameters that are of
interest from a management perspective. All LAN connected
Network Management System (NMS) equipment that support SNMP also support a default MIB called
MIB-II.
General
The SNMP Agent responds to requests received via the SNMP
The Controller has an SNMP agent function.
protocol and also actively sends TRAPS to a specified manager
Users can use a Network Management System (NMS) to do when certain MIB values change state. This is used to actively
following operations: inform a manager when an alarm situation is recognized.
Query the operation status and input/output signals of MIB Installation
the devices connected to the Controller.
Installation
Browse the active alarms.
The Controller’s MIB is named "Netsure_ESNA.mib". Contact your
When the Controller generates alarms, the SNMP agent can notify Emerson representative for the location on the Web to download
the preset NMS through TRAPS automatically. the MIB file.
NMS Supported by SNMP Agent Use the MIB loading function of NMS to load the MIB database,
refer to the corresponding NMS User Manual for the detailed
The SNMP agent of the Controller supports SNMPv2c.
loading method.
All the NMS that supports SNMPv2c can be used to access the
Contents of the Controller’s MIB
Controller. The NMS includes HP OpenView, IBM NetView, Novell
ManageWise, SunNet Manager and so on. SNMP is a technology The contents of the MIB supported by the Controller’s SNMP agent
used for network management. The technology is based on and the OID are listed in Table 5. For the details, refer to the file
implementing an information base called MIB (Managed named "Netsure_ESNA.mib".
Table 5
identName The name of the power plant. This object should be set by the administrator. R/W
Table 5
Table 5
Date and time when event occurred (local time), including timezone if
alarmTime R
supported by Controller.
Table 5
The SNMP agent can send the active alarms to the specified NMS and the User
-- --
can define the lowest severity of the NMS accepted alarms.
In Table 5, R means OID is read-only (GET), and R/W means OID can be read and modified (GET/SET).
In order to use NMS to manage the devices connected to the Controller, the administrative authority needs to be applied for the NMS,
that is, add the NMS information to the access list of SNMP agent.
Refer to “Web Interface Menus” on page 32 for the method of adding NMS.
Replacement Procedures
SCU+ Controller Replacement
3. Connect an approved grounding strap to your wrist.
DANGER! Follow all “Important Safety Instructions”
Attach the other end to a suitable ground.
found in the documentation provided with the system
the SCU+ Controller is installed in. 4. Loosen the captive fastener securing the right side of the
latch mechanism to the front of the SCU+ Controller. Pull
WARNING! SCU+ CONTROLLER HANDLING. the right side of the latch mechanism away from the
Installation or removal of the SCU+ Controller requires SCU+ Controller (this will retract the latch mechanism
careful handling. To avoid possibility of SCU+ Controller located on the left side of the SCU+ Controller). This
damage from static discharge, a static wrist strap unlocks the SCU+ Controller from the shelf. Refer to
grounded through a one megohm resistor should always Figure 7.
be worn when handling the SCU+ Controller. ESD-
protective packaging material must also be used when 5. Slide the SCU+ Controller part way from the shelf. If
carrying/shipping the SCU+ Controller. wiring is attached to the connector on the right side (see
Figure 6), remove the wiring. You can remove the entire
Note: Depending on your network security settings, when you connector by grasping and pulling with a rocking motion
remove a device that is connected to your network and assign to separate the connector from its mating half. Slide the
the same IP address to the replacement device, you may not be SCU+ out of the shelf.
allowed to communicate with the replacement device over the
6. Loosen the captive fastener securing the right side of the
network. Contact your network administrator for assistance.
latch mechanism to the front of the replacement SCU+
The SCU+ Controller is hot swappable. It can be removed and Controller. Pull the right side of the latch mechanism
installed with the system operating and without affecting the away from the SCU+ Controller (this will retract the latch
output bus. mechanism located on the left side of the SCU+
Controller).
PROCEDURE
7. If wiring was present, slide the SCU+ part way into its
1. Before performing this procedure, ensure the
mounting position, and connect wiring. Slide the SCU+
replacement SCU+ Controller contains the same
completely into its mounting position.
configuration file as the existing SCU+ Controller. Refer
to the Configuration Label on the side of the replacement 8. Push the right side of the latch mechanism into the front
SCU+ Controller for the Configuration Part Number. If the panel of the SCU+ Controller, and secure by tightening
existing Controller is operational, navigate the menus to the captive fastener. This locks the SCU+ Controller
view its configuration file (MAIN SCREEN/ESC). securely to the shelf.
Figure 6. Configuration Label and Input/Output Connector Locations 9. Wait for the controller to finish booting and verify that
the complete system operates normally.
Specifications
Input Voltage Range: 19 to 60 VDC.
Remote Alarms:
The SCU+ provides two (2) sets of Form-C alarm relay dry contact outputs for connection of remote alarms. Screw-pressure
type connections are provided. Wire size range is 28-16 AWG. Refer to your Power System documentation for connector
location and pin-out. Relay contacts are rated for 2A @ 30VDC; 0.5A @ 125VAC (60W Max. Power Consumption).
When a separate Customer Interface (IB2) board is connected to the SCU+, the board provides eight (8) groups of Form-C alarm
relay dry contact outputs for connection of remote alarms. Refer to your Power System documentation for IB2 Interface Board
specifications.
Each relay is user configurable for alarm conditions. Alarm relay contacts can be connected to other monitoring equipment.
Binary Inputs:
The SCU+ provides two (2) digital inputs for alarms/events. Screw-pressure type connections are provided. Wire size range is
28-16 AWG. Refer to your Power System documentation for connector location and pin-out.
When a separate Customer Interface (IB2) board is connected to the SCU+, the board provides eight (8) digital inputs for
alarms/events. Note that some digital inputs may be factory wired to the system. Refer to your Power System documentation
for IB2 Interface Board specifications.
Local Access Passwords: The User must input the correct password before he/she has the authority to conduct “control output” and
“parameter setting” on the Controller.
Dimensions: 42mm (H) x 86.6mm (W) x 211.5mm (D) [1.65” (H) x 3.41” (W) x 8.33” (D)].
Indicators:
a. Power (Green)
Factory Default Setpoints: Refer to the Configuration Drawing (C-drawing) furnished with your system for a list of factory default values.