Sie sind auf Seite 1von 10

542 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO.

2, APRIL 2014

A Novel Fault Current Control Scheme to Reduce


Synchronous DG’s Impact on Protection Coordination
Hesam Yazdanpanahi, Student Member, IEEE, Wilsun Xu, Fellow, IEEE, and Yun Wei Li, Senior Member, IEEE

Abstract—Synchronous-machine DGs are well known to cause Generator’s current at phase .


miscoordination of distribution system protections because of the
generator’s ability to contribute large fault currents to the fault. AC component of current at phase .
This paper proposes a field discharge circuit to limit the gener- AC RMS ac component of current at phase .
ator’s fault current, thus leading to a synchronous-machine DG
with little impact on distribution system protection. In this paper, DC component of current at phase .
the operation of a solid-state switch-based field discharge circuit
is studied, and its effects on the generator’s output current during -axis winding’s total inductance.
the fault are investigated. It is shown that the proposed scheme -axis winding’s mutual inductance.
removes the steady-state component of the fault current and ac-
celerates the decay of the transient ac component of the current. Laplace transform of the -axis winding’s
The results demonstrate that the proposed field discharge circuit reactance.
is sufficient to prevent miscoordination of the feeder protections
when short time-delay and/or inverse-time overcurrent relays are Laplace transform of the -axis winding’s
involved in the protection scheme. reactance.
Index Terms—Compatibility, distributed generation (DG), fault, -axis synchronous reactance.
field discharge, overcurrent protection, synchronous generator.
-axis synchronous reactance.
-axis winding’s mutual reactance.
NOMENCLATURE
-axis winding’s mutual reactance.
Total flux linkage of the -axis. -axis damper winding’s leakage reactance.
Total flux linkage of the -axis. -axis damper winding’s leakage reactance.
Laplace operator. Armature leakage reactance.
Angular velocity. -axis transient short-circuit time constant.
Field winding resistance. -axis subtransient short-circuit time constant.
Stator resistance. -axis transient open-circuit time constant.
-axis damper winding resistance. -axis subtransient open-circuit time constant.
-axis damper winding resistance.
-axis subtransient short-circuit time constant.
Field excitation voltage.
-axis subtransient open-circuit time constant.
Instantaneous -axis machine’s terminal
voltage. Armature time constant.
Instantaneous -axis machine’s terminal
voltage. I. INTRODUCTION
-axis machine’s terminal voltage magnitude.
-axis machine’s terminal voltage magnitude.
-axis winding’s current.
D ESPITE their undoubted advantages, distributed-gener-
ation (DG) units can negatively impact the distribution
protection system and result in serious protection malfunctions,
-axis winding’s current. such as false tripping, relay desensitization, and miscoordina-
tion between the main and backup protections [1]–[5]. Most
Field winding’s current.
of these problems are due to the DG’s contribution to the fault
current.
Manuscript received December 07, 2012; revised April 01, 2013 and May To mitigate the DG’s impact on the distribution protection
31, 2013; accepted July 10, 2013. Date of publication August 23, 2013; date of system, several methods have been proposed, which can be clas-
current version March 20, 2014. Paper no. TPWRD-01331-2012.
sified into the following categories:
The authors are with the University of Alberta, Electrical and Computer En-
gineering, Edmonton, AB T6G 2V4 Canada. 1) tripping the DG immediately after fault detection;
Digital Object Identifier 10.1109/TPWRD.2013.2276948 2) limiting the DG capacity [6]–[8];

0885-8977 © 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
YAZDANPANAHI et al.: NOVEL FAULT CURRENT CONTROL SCHEME 543

3) modifying the protection system by using extra breakers or


reclosers, reconfiguration of the network, or using distance
or directional relays [9]–[12];
4) using adaptive protection [13]–[15];
5) utilizing fault current limiters (FCLs) [16]–[18].
Although these methods are effective for mitigating the DG
impact on the protection system, they have some obvious dis-
advantages. Tripping the DG immediately after fault detection
increases nuisance DG trips which are not desirable especially Fig. 1. Synchronous generator with its field discharge circuit.
at high DG penetration levels and when considering most faults
are temporary. Limiting the DG capacity is not desirable since
doing so also limits the DG penetration level. Modifying the
protection system is costly. Moreover, doing so requires utility
involvement and makes the protection procedure more compli-
cated. Similarly, adaptive protection requires new communica-
tion infrastructures as well as fast processing units. Finally, uti-
lizing FCLs is also undesirable because of the additional cost Fig. 2. Sample distribution network with synchronous-machine DG.
that using them imposes on the utility or DG owners.
This paper proposes a novel strategy to increase synchronous-
machine DG compatibility with distribution networks by miti- TABLE I
OPERATIONAL CONSTANTS OF THE SIMULATED
gating its negative impact on the protection system. The idea SYNCHRONOUS MACHINE [19]
is to establish a method to restrict the DG’s contribution to the
fault current, and consequently, prevent its impact on the over-
current (OC) protection. This idea is implemented by equipping
the generator with a solid-state-switch-based field discharge cir-
cuit. In comparison to other published or practiced methods, the
proposed solution is simpler and, more important, does not re-
quire utility involvement.
In this paper, the idea of utilizing a field discharge circuit is
described in Section II. Next, a detailed analysis is presented
in Section III, which includes a study of the synchronous ma- a discharge resistance is put in series with it to dissipate the
chine’s time constants and its fault current, and an analysis of the energy stored in the magnetic field.
effect of the field discharge application on the synchronous-ma- In order to investigate the effectiveness of this idea, a distribu-
chine DG’s contribution to the fault current. Subsequently, a tion network was simulated in Matlab/SIMULINK (see Fig. 2).
field discharge trigger mechanism is proposed in Section IV. In this system, embedding the DG at any of points S, A or B
Next, a case study is provided in Section V. Finally, Section VI may cause miscoordination between B1 and B2. In this simula-
presents the conclusion. tion, a synchronous-machine DG is arbitrarily embedded at S.
The synchronous machine’s parameters were taken from [19]
II. IDEA OF UTILIZING THE FIELD DISCHARGE CIRCUIT and tabulated in Table I.
Basically, the main source of a generator’s output current is Fig. 3 shows the rms of the generator’s output current during
the machine’s flux linkage which is established by the field’s the fault at point F, and Fig. 4 shows the rms of its ac component.
excitation. As a result, the controlling machine’s excitation can Note that most of protection devices, such as OC relays, filter
lead to the control of the machine’s output current. In case of the dc component of fault current and operate based on the rms
fault, discharging the flux linkage could decrease the generator’s of the ac component. The factor shows the ratio of total field
output current, eliminate its contribution to the fault, and con- circuit’s resistance, when the field discharge is applied, to its
sequently, prevent OC protection miscoordination. In addition, original one ( , where is the field
putting an external resistance in series with the field circuit when discharge resistance).
the excitation voltage is being removed can accelerate the ma- As Fig. 4 reveals, except for the synchronous-machine DG
chine’s discharge process. This procedure is called “field dis- with traditional excitation, the ac components of the machines’
charge.” Briefly, the idea is to utilize the field discharge circuit to output currents are decreasing. Fig. 4 also shows that applying a
minimize the generator’s output current during grid faults and, field discharge can remarkably decrease the ac component of the
consequently, prevent it from impacting the existing protection synchronous machine’s output during the fault. In the studied
system. case, the value of this current 0.2 sec. after the beginning of
Fig. 1 shows a synchronous generator with its solid-state the fault is 1.53, 1.25, and 0.64 p.u. for 3.7, 6.25, and 15,
switch-based field discharge circuit in which S1 and S2 are respectively.
controllable switches. In the proposed application, when a fault In addition, from these figures, it can be concluded that larger
is detected, the control unit closes S2 and then, opens S1. As resistances lead to faster decay in the ac component. However,
a result, the exciter is disconnected from field winding, and the field discharge resistance causes an overvoltage on field
544 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 2, APRIL 2014

tion does not significantly affect the resulting short-circuit cur-


rent or the conclusion about the effect of field discharge circuit
on it.
The -axis flux linkage of the machine can be written in terms
of the -axis current and the machine’s excitation voltage as
follows [21]:

(1)
Fig. 3. RMS of a machine’s output current during a three-phase fault at point
F. where

(2)

(3)

and

(4)

(5)
Fig. 4. RMS ac component of a machine’s output current during a fault at point
F.
(6)

(7)

(8)

(9)

(10)

Fig. 5. Voltage which appears at the field winding during the fault. In order to obtain the principal time constants of the machine,
should be rewritten as

winding (see Fig. 5). This overvoltage must not be higher than (11)
the winding’s maximum permissible voltage. According to the
recommendation in [20], it can be shown that 3.7 is the
largest resistance that can be used for DG with a 220 V field- , , , and are the principal time constants. Then
rated voltage and that 6.25 is the largest for a DG with a
110 V field-rated voltage. Therefore, 15 is not practical (12)
and is used only to clearly demonstrate the impact of the field (13)
discharge resistance.
By solving (12) and (13), the principal time constants of the
-axis will be determined. However, because normally,
III. DETAILED ANALYSIS , the following approximations have been accepted in [21]:

A. Synchronous Machine’s Constants (14)


(15)
In this subsection, the time constants and operational reac-
tances of a synchronous machine are reviewed. These param- (16)
eters will be used in the next subsection to determine the syn- (17)
chronous machine’s fault current. In practice, considering the
generator’s input-power constant during the fault is more real- Similarly, is defined as follows:
istic. However, in the calculations and simulations in this sec-
tion, the synchronous generator’s speed is assumed constant, so (18)
that the equations can be solved mathematically. This assump-
YAZDANPANAHI et al.: NOVEL FAULT CURRENT CONTROL SCHEME 545

where 1) the decaying ac at twice fundamental frequency which is


negligible due to the fact that ;
2) the decaying dc
(19)

(20)
(26)
During the subtransient condition, the operational imped-
ances are 3) the ac at the fundamental frequency, which itself consists
of three parts: subtransient, transient, and steady state
(21)

(22)

During the transient condition, when the damper windings


have no effect, the operational impedance is (27)

(23)
In the following text, the effect of the field discharge cir-
cuit operation on the machine’s current during the fault is
Finally, during the steady-state operation of the synchronous investigated.
machine, the operational impedances are and
, which are and , respectively. C. Effect of Field Discharge on the Synchronous Machine’s
Contribution to Fault
B. Synchronous Machine’s Fault Current
In field discharge application, when a fault is detected, the
For a three-phase solid fault at the generator’s terminals, the control unit closes S2 and then opens S1. Because the operation
- and -axes currents and, subsequently, the phase currents, are time of the control unit and switches is much less than the ma-
achieved by solving the following set of equations [21]: chine’s time constants, the field discharge activation is consid-
ered instantaneous in this paper. In addition, the field discharge
(24) operation can be considered as combining two actions together:
1) removing the excitation and 2) increasing the field circuit’s
By solving (24) and converting the parameters into ones, resistance. In the following text, the effects of each action on the
the current at phase is obtained as (25), where is the angle generator’s short-circuit current are studied separately, and then
between the field and phase coils’ axes at the fault instant. To the effect of the field discharge circuit operation is obtained as
achieve and , should be replaced by and the superposition of these effects.
, respectively Excitation removal eliminates the steady-state part of the ac
component from the generator’s current. Fig. 6 shows the short-
circuit current of a synchronous generator (for its parameters see
Table I) when the field winding is short-circuited. As Fig. 6(a)
shows, the steady-state value of the current is zero. Fig. 6(b)
shows the first 18 cycles of Fig. 6(a).
To take the effect of the field discharge resistance into ac-
count, should be replaced with in calculating
and . As a result, when the discharge resistance is added
in series to the field winding at the fault instance, the following
changes in the machine’s time constants are anticipated:

(28)

(29)

(25)
Moreover, substituting (28) and (29) into (21) and (23) is
not expected to change the operational reactances. As a result,
As (25) reveals, the fault current consists of three the generator’s output current is expected to be obtained by re-
components: placing and with and in (25), respectively.
546 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 2, APRIL 2014

Fig. 8. Accurate estimation of the synchronous generator’s fault current with


a discharge resistance in series with its field.

Then, and can be obtained by accurately solving


the following quadratic equations:

Fig. 6. Synchronous generator’s fault current with short-circuited field


winding: (a) complete waveform and (b) first 18 cycles. (32)

(33)

and, consequently, the operational reactances are achieved as


follows:

(34)

(35)

Fig. 8 shows how this procedure improves the estimation of the


generator’s fault current. Now, the effect of field discharge cir-
cuit operation is the superposition of the effects of these two
aforementioned actions, that is, the generator’s current has no
steady-state part, and , , , and are replaced by
, , , and , which are obtained from
(30)–(35). Briefly, the generator’s output current for a three-
Fig. 7. Synchronous generator’s fault current with discharge resistance in se- phase solid fault at its terminals when the field discharge cir-
ries with field winding: (a) complete waveform and (b) first six cycles. cuit operates at the fault instance can be obtained as

Fig. 7 shows the generator’s output current when a discharge re-


sistance is added to the field circuit at the fault instant. The com-
parison between Fig. 7(a) and Fig. 6(a) reveals that the transi-
tion to steady state in Fig. 7 is much faster. Moreover, Fig. 7(b)
shows that (28) and (29) are not accurate enough; that is., the
anticipated time constants are smaller than the real values and,
as a result, the expected current is not close enough to the gen-
erator’s output current because (14) to (17) are true on the con-
dition that . However, when a large discharge resis-
tance is added, this assumption is no longer true.
Under such circumstances, the machine’s operational param-
eters should be recalculated as follows:

(30)

(31) (36)
YAZDANPANAHI et al.: NOVEL FAULT CURRENT CONTROL SCHEME 547

Fig. 10. Sample distribution feeder with synchronous-machine DG.

Fig. 11. RMS ac component of the generator’s fault current with field discharge
operation in the system shown in Fig. 10.
Fig. 9. Synchronous generator’s fault current with field discharge operation:
(a) complete waveform and (b) first nine cycles.
And

Fig. 9 shows the effect of the field discharge circuit opera-


tion on the generator’s output current during the three-phase (40)
solid fault at the generator’s terminals. The comparison between
this figure and Fig. 6 shows that the field discharge circuit has The operation of OC devices normally coincides with the
almost no impact on the subtransient part of the ac compo- generator’s transient response. Consequently, (38) can be sim-
nent of the generator’s current (the first few cycles) because the plified by neglecting the subtransient terms in (39) and (40).
damper windings, but not the field winding, play the dominant Such an estimation is accurate from the 4th cycle after the fault
role during the subtransient period. In contrast, the field dis- instance 0.05 s)
charge operation accelerates the decrease in the transient com-
ponent. Also, the comparison between Figs. 9 and 7 shows that
the field discharge circuit removes the steady-state part of the (41)
fault current.
For OC relay coordination, the dc part of the generator’s cur- For distant faults, assume that the equivalent impedance from
rent can be neglected because these relays operate based on the the generator’s terminals to the fault is
rms of the ac component of current. Also, the second-order har-
monic is negligible. Therefore (42)

In this situation, the generator’s contribution can be estimated


by making modifications as follows.
• In calculating all of the time constants and operational re-
actances, should be replaced by .
• In calculating all of the time constants and operational re-
actances, should be replaced by .
(37) As an example, Fig. 11 shows the RMS ac component of the
generator’s current when the fault happens to be 1.6 km away
from the generator’s terminals in the sample network shown in
Note that is a random variable and depends on the fault Fig. 10, and the field discharge is applied 3). The estimated
instance. Since the OC relays operate based on the rms of the ac curve is obtained from (41) with the modifications mentioned
component of the current, it is advantageous to obtain the rms before.
of (37), which is as follows: Now, the effect of the field discharge in reducing the gener-
ator’s rms ac current can be evaluated by deducting the rms of
(38) the ac component of (25) from (41). As a result, the reduction
in the rms ac component of current due to field discharge can be
where expressed as follows:

(39) (43)
548 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 2, APRIL 2014

Fig. 12. Reduction in the synchronous generator’s rms ac component of fault


current due to the application of field discharge.

Fig. 14. Fault current components of the synchronous generator: (a) when tra-
ditional excitation is applied and (b) when field discharge is applied.

Fig. 13. Reduction in the generator’s rms ac component of fault current for
different values of field discharge resistance.
According to (26), the dc component is decaying with arma-
ture’s time constant, and is not a function of field circuit param-
Fig. 12 shows the reduction in the rms ac component of the eters. So, field discharge has no impact on the dc component
generator caused by the field discharge 3). The solid curve . However, field discharge can minimize by reducing
was obtained from the simulation, and the dashed curve was the ac component of DG’s current . Fig. 14 shows the
obtained from (41). As Fig. 12 reveals, after 0.05 s} (three impact of field discharge application on the DG’s fault current
cycles after the fault instance), the estimated result matches the components. As Fig. 14(a) reveals, when the traditional excita-
simulated one. tion system is applied, during the transient period, the dc com-
Now, by utilizing (43), the effect of the different values of ponent decreases, while the ac component increases due to the
field discharge resistances in reducing the generator’s fault cur- excitation’s response to voltage drop. This results in almost con-
rent can be compared. Fig. 13 shows the reduction in the rms ac stant total rms current around 3 p.u. In contrast, as Fig. 14(b) re-
component of the generator’s fault current for different values veals, when the field discharge is applied, both ac and dc compo-
of . To explain the effect of the field discharge operation on nents are decaying. This results in a decaying total rms current
protection devices’ coordination, three time intervals are shown which decreases to around 1.4 p.u. in 0.2 s. Therefore, when
in Fig. 13. Typically, instantaneous OC devices operate in in- field discharge is applied, the generator has smaller contribu-
terval 1, extremely inverse-time and short time-delay OC de- tions to total fault current, and higher DG capacity can be em-
vices operate in interval 2, and inverse and very inverse time bedded without causing any miscoordination in comparison to
OC devices operate in interval 3 [22][23]. As Fig. 13 shows, the cases in which the DG utilizes the traditional excitation con-
the maximum reduction in the generator’s contribution due to trol during the fault.
the field discharge operation is 0.15 p.u in interval 1. It means
IV. FIELD DISCHARGE TRIGGER MECHANISM
that the field discharge is not effective enough to prevent misco-
ordination when instantaneous devices are involved. In interval In the above sections, it was supposed that there is a mecha-
2, the maximum reduction is 1 p.u. which means that the field nism which accurately and quickly detects the fault occurrence
discharge can be an effective mechanism to prevent miscoor- in the network, and triggers the field discharge circuit. In fol-
dination when extremely inverse-time and short time-delay OC lowing, this mechanism will be described.
devices are involved. Finally, in interval 3, the maximum reduc- The first and the most important step in trigger mechanism
tion in the generator’s contribution can be up to 1.4 p.u. which is fault detection. To do so, one of the generator’s local voltage
means that field discharge is a very effective mechanism when or current signals should be selected and monitored. To be an
inverse and very inverse time OC devices are involved. appropriate grid fault indicator, this signal should have the fol-
The aforementioned analysis was based on the assumption lowing properties:
that the OC relays measure the ac component of current. How- 1) Its variation due to grid faults should be so fast that fault
ever, fuses and some old electromechanical relays operate based occurrence is detected as quickly as possible.
on the total current. In such cases, the total rms current of the 2) This signal should have distinctive levels for different grid
synchronous generator should be considered. For phase , this disturbances so that close grid faults can be distinguished
current can be obtained as follows: from other disturbances.
Considering these necessary properties, derivative of the
(44) field’s current is an appropriate indicative signal. Fig. 15 shows
YAZDANPANAHI et al.: NOVEL FAULT CURRENT CONTROL SCHEME 549

TABLE III
RELAYS’ SETTINGS

TABLE IV
Fig. 15. Field’s current derivative for three different grid disturbances. OVERCURRENT DEVICES’ CURRENT AND OPERATION TIMES FOR VARIOUS
FAULT LOCATIONS WHEN THERE IS NO DG UNIT

TABLE II
LOADS IN FIG. 2

Each breaker is associated with two OC relays: one short time


delay and one inverse time. The short time-delay relays are set to
the derivative of the field’s current for the generator with the protect 80% of their sections, and the inverse-time relays are set
parameters tabulated in Table I, for three different disturbances: to coordinate with next protection elements and act as backup.
three-phase fault in the generator’s neighbourhood, one-phase The pickup current of short time-delay relay of B2 is set equal
fault at one of the generator’s terminals, and a large sudden to the fault current at F2, and the pickup current of the short
load change at the generator’s node. As Fig. 15 shows, these time-delay relay of B1 is set equal to the fault current at F1. In
signals have three distinguished levels in the first cycle after the addition, the TSM of the inverse-time relay of B2 is set so that
disturbances. As a result, by appropriately defining thresholds, B2 acts as backup for the fuse at L3 in case of a fault at F4.
the type of disturbance can be easily and accurately deter- Similarly, the TSM of the inverse-time relay of B1 is set to act
mined. In addition, it can be seen that for three-phase faults in as a backup for the short time-delay relay of B2 in case of a fault
which the DG unit has the most contribution, and has the most at F3. Table III shows the relays’ settings, and Table IV shows
probable impact on coordination, the indicative signal has an their operation times for different fault locations when no DG
almost instantaneous jump which help detect the fault in few is in the system.
milliseconds. After fault detection, control unit closes S2 and When a synchronous-machine DG unit (with the parameters
opens S1. tabulated in Table I) is added to the substation, its contribution
It should be noted that when this method is implemented, the to the fault increases the fault current flowing through protection
generator’s overcurrent protection is set so that it protects the devices. Such an increase may cause miscoordination between
generator from damages due to overcurrent/overload. In other B1 and B2. As an example, consider the fault at F3. When there
words, when field discharge circuit is implemented, the DG’s is no DG, the current through B2 is 4187A. This result leads to
overcurrent relay is set similar to those of the generators con- operation of its short time-delay relay, while the current through
nected to the transmission system, and there is no conflict be- B1 is 4190A. This result causes the operation of its inverse-time
tween generator’s overcurrent protection and field discharge ap- relay. However, when the DG is added, if it increases the fault
plication. IEEE Standard C.37.102-2006 can be followed in this current at F3 above 4440 A (the pickup current of B1’s short
case [25]. time-delay relay), both B1 and B2 operate simultaneously, and
The last step is detecting the fault clearance and disabling the the entire feeder is de-energized. Fig. 16 shows the fault current
field discharge circuit which can be detected by monitoring the at F3 for the case with 5 MW DG. As this figure reveals, for
generator’s terminal voltages. DG’s with higher capacities, the coordination between B1 and
B2 will be lost. As an example, Fig. 17 shows how a 6.5 MW
V. CASE STUDY DG moves the protection operation points from “A” to “B” and
Consider Fig. 2 again. In this 25 kV distribution system, the causes miscoordination.
upstream network is represented by a Thevenin equivalent of a Nevertheless, the field discharge circuit operation can main-
voltage source and a series impedance tain the coordination between B1 and B2 for DG units larger
p.u., and the feeder is composed of four-wire overhead ACSR than 5 MW. Consider that a 6.5 MW DG is connected to the sub-
conductors represented by series impedance station through a transformer with MVA equal to 130% of the
p.u./km ( 25 kV, 100 MVA). As Fig. 2 DG’s, and 6% series impedance. Also, imagine that the DG’s
shows, the feeder has four sections. The lengths of all sections field’s rated voltage is 220 V. According to Section II, the max-
are 500 m, except for the length of CD’, which is 1 km. This imum-allowable is 3.7. For this system, Fig. 18 shows the
system also has four three-phase laterals, and the total load of fault current at F3. As this figure shows, when a field discharge
each lateral is shown in Table II. resistance is applied to the DG during the fault, it reduces the
As Fig. 2 reveals, the feeder is protected by two breakers, DG’s contribution, so that the fault current is decreased below
B1 and B2, and the laterals L1 to L4 are protected by fuses. 4440 A in less than 0.1 s which blocks the operation of the short
550 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 2, APRIL 2014

The operation of the field discharge circuit was explained, and


its effects on the generator’s output current during the fault were
analyzed. It was shown that the first effect is the removal of the
steady-state part of the generator’s current. The second effect
is the reduction of the -axis transient principal time constants.
Next, the ac component of the generator’s current was specifi-
cally analyzed, and the reduction in the rms of this component
was demonstrated for different time intervals. It was shown that
applying the field discharge circuit could sufficiently reduce the
Fig. 16. Fault current at F3 when a 5 MW SMDG is added at the substation.
generator’s contribution to fault current and, as a result, prevent
miscoordination when short time-delay and/or inverse-time OC
relays were involved. Finally, a case study was presented to con-
firm the previous conclusions.

REFERENCES
[1] W. El-Khattam and T. S. Sidhu, “Restoration of directional overcur-
rent relay coordination in distributed generation systems utilizing fault
current limite,” IEEE Trans. Power Del., vol. 23, no. 2, pp. 576–585,
Apr. 2008.
[2] J. C. Gómez and M. M. Morcos, “Coordination of voltage sag and over-
Fig. 17. Impact of a 6.5 MW SMDG on the relays’ operation points. current protection in DG system,” IEEE Trans. Power Del., vol. 20, no.
1, pp. 214–218, Jan. 2005.
[3] W. El-Khattam and T. S. Sidhu, “Resolving the impact of distributed
renewable generation on directional overcurrent relay coordination: A
case study,” IET Renew. Power Gen., vol. 3, no. 4, pp. 415–425, 2009.
[4] C. J. Mozina, “A tutorial on the impact of Distributed Generation (DG)
on distribution systems,” in Proc. Protective Relay Eng. Annu. Conf.,
2008, pp. 591–609.
[5] R. A. Walling, R. Saint, R. C. Dugan, J. Burke, and L. A. Kojovic,
“Summary of distributed resources impact on power delivery system,”
IEEE Trans. Power Del., vol. 23, no. 3, pp. 1636–1644, Jul. 2008.
[6] S. Chaitusaney and A. Yokoyama, “Prevention of reliability degra-
dation from recloser—Fuse miscoordination due to distributed gener-
atio,” IEEE Trans. Power Del., vol. 23, no. 4, pp. 2545–2554, Oct.
2008.
Fig. 18. Effect of field discharge circuit on eliminating the impact of a 6.5 MW
[7] J. Chen, R. Fan, X. Duan, and J. Cao, “Penetration level optimiza-
synchronous-machine DG.
tion for DG considering reliable action of relay protection device con-
strains,” in Proc. Int. Conf. Sustain. Power Gen. Supply, 2009, pp. 1–5.
[8] T. K. Abdel-Galil, A. E. B. Abu-Elnien, E. F. El-saadany, A. Girgis, Y.
TABLE V A.-R. I. Mohamed, M. M. A. Salma, and H. H. M. Zeineldin, “Protec-
RELAYS’ CURRENTS AND OPERATION TIMES FOR A FAULT AT F3 AND tion coordination planning with distributed generation,” Canmet En-
6.5 MW DG AT THE SUBSTATION ergy Technol. Ctr., Varennes, QC, Canada, CETC-Varennes 2007-149
(TR), 2007.
[9] H. B. Funmilayo and K. L. Buyler-Purry, “An approach to mitigate the
impact of distributed generation on the overcurrent protection scheme
for radial feeders,” in Proc. IEEE Power Syst. Conf. Expo., 2009, pp.
1–11.
[10] F. A. Viawan, D. Karlsson, A. Sannino, and J. Daalde, “Protection
scheme for meshed distribution systems with high penetration of dis-
time-delay relay at B1, and consequently, maintains the coordi- tributed generation,” in Proc. Pow. Sys. Conf. Advanced Meter., Pro-
tect. Control, Commun., Distrib. Recources, 2006, pp. 99–104.
nation. Table V shows the protection devices’ operation times [11] I. M. Chilvers, N. Jenkins, and P. A. Crossley, “The use of 11 kV dis-
for the fault at F3, and a for a 6.5 MW DG at the substation. In tance protection to increase generation connected to the distribution
fact, the field discharge application increases the maximum-al- network,” in Proc. Int. Conf. Develop. Power Syst. Protect., 2004, vol.
2, pp. 551–554.
lowable capacity of DG from 5 MW (equal to 48% of the total [12] D. Uthitsunthorn and T. Kulworawanichpong, “Distance protection of
load in the distribution system), to 6.5 MW (equal to 63% of the a renewable energy plant in electric power distribution systems,” in
total load). Note that in the simulation, a detailed model of the Proc. Int. Conf. Power Syst. Technol., 2010, pp. 1–4.
[13] H. Wan, K. K. Li, and K. P. Wong, “An adaptive multiagent approach to
prime mover is used. protection relay coordination with distributed generators in industrial
power distribution system,” IEEE Trans. Ind. Appl., vol. 46, no. 5, pp.
VI. CONCLUSION 2118–2124, Sep./Oct. 2010.
[14] J. Ma, J. Li, and Z. Wang, “An adaptive distance protection scheme for
In this paper, the idea of applying a field discharge circuit to distribution system with distributed generation,” in Proc. 5th Int. Conf.
the synchronous-machine DG to mitigate its impact on the OC Crit. Infrastruct., 2010, pp. 1–4.
[15] M. Baren and I. El-Markabi, “Adaptive overcurrent protection for
protection coordination (by reducing its contribution to fault) distribution feeders with distributed generators,” in Proc. Power Syst.
and, consequently, to increase its compatibility with the dis- Conf. Expo., 2004, vol. 2, pp. 715–719.
tribution system, was proposed. Next, through a detailed anal- [16] W. El-Khattam and T. S. Sidhu, “Restoration of directional overcur-
rent relay coordination in distributed generation systems utilizing fault
ysis, the effect of operating a field discharge circuit on the syn- current limiter,” IEEE Trans. Power Del., vol. 23, no. 2, pp. 576–585,
chronous generator’s current during the fault was investigated. Apr. 2008.
YAZDANPANAHI et al.: NOVEL FAULT CURRENT CONTROL SCHEME 551

[17] H. Yamaguchi and T. Kataoka, “Current limiting characteristics of Wilsun Xu (F’05) received the Ph.D. degree in power engineering from the
transformer type superconducting fault current limiter with shunt University of British Columbia, Vancouver, BC, Canada, in 1989.
impedance and inductive load,” IEEE Trans. Power Del., vol. 23, no. From 1989 to 1996, he was an Electrical Engineer with BC Hydro, Vancouver,
4, pp. 2545–2554, Oct. 2008. BC, Canada. Currently, he is a Research Chair Professor with the University of
[18] Y. Zhang and R. A. Dougal, “Novel dual-FCL connection for adding Alberta, Edmonton, AB, Canada. He also works in areas, such as power mea-
distributed generation to a power distribution utility,” IEEE Trans. surements, distributed generation, and voltage stability. His current research in-
Appl. Superconduct., vol. 21, no. 3, pp. 2179–2183, Jun. 2011. terests are power quality and power disturbance analytics.
[19] C. A. Gross, Electric Machines. Boca Raton, FL: CRC, 2007.
[20] Standard Enclosed Field Discharge Circuit Breakers for Rotating Elec-
tric Machinery, ANSI/IEEE Standard C37.18.1979.
[21] B. Adkins and R. C. Harley, The General Theory of Alternating Current Yun Wei Li (S’04–M’05–SM’11) received the B.Sc. degree in electrical engi-
Machines. London, U.K.: Chapman & Hall, 1975. neering from Tianjin University, Tianjin, China, in 2002, and the Ph.D. degree
[22] IEEE Recommended Practice for Protection and Coordination of In- in electrical engineering from Nanyang Technological University, Singapore, in
dustrial and Commercial Power Systems, IEEE Standard 242-2001. 2006.
[23] A. Sallaem and O. Malik, Protection of Electric Distribution Sys- In 2005, he was a Visiting Scholar with the Aalborg University, Aalborg,
tems. Hoboken, NJ: Wiley-IEEE, 2011. Denmark. From 2006 to 2007, he was a Postdoctoral Research Fellow at
[24] “Network Protection and Automation Guidline,” Alstom GRID, 2011. Ryerson University, Toronto, ON, Canada. In 2007, he was also with Rockwell
[25] IEEE Guid For AC Generator Protection, IEEE Standard. C37.102- Automation Canada, Cambridge, ON, Canada, before he joined the University
2006. of Alberta, Edmonton, AB, Canada, in the same year. Currently, he is an
Associate Professor at the University of Alberta. He is an Associate Editor for
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS and a Guest Editor for
Hesam Yazdanpanahi (S’11) received the B.Sc. and M.Sc. degrees in electrical the IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS SPECIAL SESSION ON
engineering from Amirkabir University of Technology, Tehran, Iran, in 2007 DISTRIBUTED GENERATION AND MICROGRIDS. His research interests include
and 2009, respectively, and is currently pursuing the Ph.D. degree in electrical distributed generation, microgrid, renewable energy, high-power converters,
and computer engineering at the University of Alberta, Edmonton, AB, Canada. and electric motor drives.
His research interests are distributed generation (DG) and power system Dr. Li received the Richard M. Bass Outstanding Young Power Electronics
protection. Engineer Award of the IEEE Power Electronics Society in 2013.

Das könnte Ihnen auch gefallen