SIPROTEC 4 7SJ62
Multifunction Protection Relay
Function overview
Protection functions
• Time-overcurrent protection
(definite-time/inverse-time/user-def.)
• Directional time-overcurrent protection
(definite-time/inverse-time/user-def.)
• Sensitive dir./non-dir. earth-fault
detection
• Displacement voltage
• Intermittent earth-fault protection
• Inrush restraint
LSP2299-afpen.eps
• Motor protection
– Undercurrent monitoring
Fig. 5/63 – Starting time supervision
SIPROTEC 7SJ62 – Restart inhibit
multifunction protection relay – Locked rotor
• Overload protection 5
• Temperature monitoring
• Under/overvoltage protection
• Under/overfrequency protection
• Breaker failure protection
• Negative-sequence protection
• Phase-sequence monitoring
Description
• Auto-reclosure
The SIPROTEC 4 7SJ62 relays can be used • Fault locator
for line protection of high and medium • Lockout
voltage networks with earthed (grounded), Control functions/programmable logic
low-resistance earthed, isolated or com-
pensated neutral point. For motor protec- • Commands for control of a circuit-
tion, the SIPROTEC 4 7SJ62 is suitable for breaker and of isolators
asynchronous machines of all sizes. The • Control via keyboard, binary inputs,
relay performs all functions of backup pro- DIGSI 4 or SCADA system
tection supplementary to transformer dif- • User-defined logic with CFC
ferential protection. (e.g. interlocking)
Monitoring functions
The relay provides a simple control of the
circuit-breaker and automation functions. • Operational measured values V, I, f
The integrated programmable logic (CFC) • Energy metering values Wp, Wq
allows the user to implement their own • Time metering of operating hours
functions, e. g. for the automation of • Slave pointer
switch- gear (interlocking). The user is also • Trip circuit supervision
allowed to generate user-defined messages. • Fuse failure monitor
The flexible communication interfaces are • 8 oscillographic fault records
open for modern communication architec- Communication interfaces
tures with control systems.
• System interface
– IEC 60870-5-103
– PROFIBUS-FMS/-DP
– DNP 3.0/MODBUS RTU
• Service interface for DIGSI 4 (modem)/
Temperature detection (RTD-box)
• Front interface for DIGSI 4
• Time synchronization
via IRIG B/DCF77
Hardware
• 4 current transformers
• 3 voltage transformers
• 8/11 binary inputs
• 8/6 output relays
Application
Programmable logic
The integrated logic characteristics (CFC)
allow the user to implement their own
functions for automation of switchgear
(interlocking) or a substation via a graphic
user interface. The user can also generate
user-defined messages.
Application
67, 67N Idir>, Idir>>, Ip dir Directional time-overcurrent protection (definite/inverse, phase/neutral),
IEdir>, IEdir>>, IEp dir Directional comparison protection
47 Phase sequence
79 Auto-reclosure 5
46 I2> Phase-balance current protection (negative-sequence protection)
49 >
u Thermal overload protection
Construction
Protection functions
Time-overcurrent protection
(ANSI 50, 50N, 51, 51N)
This function is based on the phase-selec-
tive measurement of the three phase cur-
rents and the earth current (four trans-
formers). Two definite-time overcurrent
protection elements (DMT) exist both for
the phases and for the earth. The current
threshold and the delay time can be set
within a wide range. In addition, inverse-
time overcurrent protection characteristics
(IDMTL) can be activated.
Protection functions
Protection functions
Breaker failure protection (ANSI 50BF) Fig. 5/70 Directional comparison protection
If a faulted portion of the electrical circuit
is not disconnected upon issuance of a trip
command, another command can be initi- Auto-reclosure (ANSI 79) For thermal protection of motors (especially
ated using the breaker failure protection the stator) a further time constant can be set
which operates the circuit-breaker, e.g., of Multiple reclosures can be defined by the
so that the thermal ratios can be detected cor-
an upstream (higher-level) protection re- user and lockout will occur if a fault is
rectly while the motor is rotating and when it
lay. Breaker failure is detected if after a trip present after the last reclosures. The fol-
is stopped. The ambient temperature or the
command, current is still flowing in the lowing functions are possible:
temperature of the coolant can be detected se-
faulted circuit. As an option it is possible • 3-phase ARC for all types of faults rially via an external temperature monitoring
to make use of the circuit-breaker position • Separate settings for phase and earth faults device (Resistance temperature detector =
indication. • Multiple ARC, one rapid auto-reclosure RTD-box, also called thermo-box). The ther-
(RAR) and up to nine delayed mal replica of the overload function is auto-
Phase-balance current protection (ANSI 46) matically adapted to the ambient conditions.
auto-reclosures (DAR)
(Negative-sequence protection) If there is no RTD-box it is assumed that the
• Starting of the ARC depends on the trip
In line protection, the two-element phase- ambient temperatures are constant.
command selection (e.g. 46, 50, 51, 67)
balance current/negative-sequence protec- • Blocking option of the ARC via binary The tripping time t is calculated for a cur-
tion permits detection on the high side of inputs rent step with static current values accord-
high-resistance phase-to-phase faults and • ARC can be initiated externally or via CFC ing to the following form:
phase-to-earth faults that are on the low
• The directional and non-directional ele- Overload protection without preload detec-
side of a transformer (e.g., with the switch
ments can either be blocked or operated tion:
group Dy 5). This provides backup protec-
non-delayed depending on the auto- 2
tion for high-resistance faults beyond the I
reclosure cycle
transformer. To detect the unbalanced
• Dynamic setting of the directional and k ⋅ I nom
load, the ratio negative-sequence cur- t = tth ⋅ ln 2
non-directional elements can be activated I
rent/rated (nominal) current is evaluated.
depending on the ready AR −1
k ⋅ I nom
Thermal overload protection (ANSI 49) Overload protection with preload detection:
2 2
For protecting cables and transformers, I I pre
−
an overload protection with an integrated k ⋅ I nom k ⋅ I nom
pre-warning element for temperature and t = tth ⋅ ln 2
I
current can be applied. The temperature is −1
calculated using a thermal homogeneous- k ⋅ I nom
body model (according to IEC 60255-8), t = Tripping time after beginning of the overload
which takes account both of the energy en-
tth = Thermal time constant
tering the equipment and the energy losses.
Ipre = Previous load current
The calculated temperature is constantly
adjusted accordingly. Thus, account is I = Overload current
taken of the previous load and the load k = k factor (acc. to IEC 60 255-8)
fluctuations. ln = Natural logarithm
Inom = Rated (nominal) current
Protection functions
n Motor protection
Starting time supervision (ANSI 48)
Starting time supervision protects the mo-
tor against long unwanted startups that
might occur when excessive load torque
occurs, excessive voltage drops occur
within the motor or if the rotor is locked.
Rotor temperature is calculated from mea-
sured stator current. The tripping time is
calculated according to the following equa-
tion:
I
tTRIP = start ⋅ t start max
I rms
I nom
for Irms > Istart, reset ratio approx. 0.94
I start
Additional functions, which are not time The switchgear or circuit-breaker can be
critical, can be implemented via the CFC controlled via:
using measured values. Typical functions – integrated operator panel
include reverse power, voltage controlled – binary inputs
overcurrent, phase angle detection, and – substation control and protection system
zero-sequence voltage detection. – DIGSI 4
Protection functions/Functions
LSP2077f.eps
dication input is blocked for a certain
ing:
period, so that the event list will not record
excessive operations. • Currents IL1, IL2, IL3, IE, IEE (67Ns)
• Voltages VL1, VL2, VL3, VL1L2, VL3L1
Filter time • Symmetrical components
All binary indications can be subjected to a I1, I2, 3I0; V1, V2, V0
filter time (indication suppression). • Power Watts, Vars, VA/P, Q, S
(P, Q: total and phase selective)
Indication filtering and delay • Power factor (cos j),
Indications can be filtered or delayed. (total and phase selective)
• Frequency Fig. 5/73
Filtering serves to suppress brief changes in • Energy ± kWh, ± kVarh, forward and NXAir panel (air-insulated)
potential at the indication input. The indi- reverse power flow
cation is passed on only if the indication
• Mean as well as minimum and maximum
voltage is still present after a set period of
current and voltage values
time. In the event of indication delay, there
is a wait for a preset time. The information • Operating hours counter
is passed on only if the indication voltage is • Mean operating temperature of overload
still present after this time. function
• Limit value monitoring
Indication derivation Limit values are monitored using pro-
grammable logic in the CFC. Commands
A further indication (or a command) can
can be derived from this limit value indi-
be derived from an existing indication.
cation.
Group indications can also be formed. The
volume of information to the system inter- • Zero suppression
face can thus be reduced and restricted to In a certain range of very low measured
the most important signals. values, the value is set to zero to suppress
interference.
Transmission lockout
Metered values
A data transmission lockout can be acti-
vated, so as to prevent transfer of informa- For internal metering, the unit can calcu-
tion to the control center during work on a late an energy metered value from the
circuit bay. measured current and voltage values. If an
external meter with a metering pulse out-
Test operation put is available, the SIPROTEC 4 unit can
obtain and process metering pulses via an
During commissioning, all indications can indication input.
be passed to an automatic control system
for test purposes. The metered values can be displayed and
passed on to a control center as an accu-
mulation with reset. A distinction is made
between forward, reverse, active and reac-
tive energy.
Fig. 5/76
Bus structure: RS485 copper conductor
1) Resistance temperature detector connection
2) In case of surface-mounting housing, please refer to the information on page 5/99
3) Under development
Communication
MODBUS RTU
LSP2163-afp.tif
MODBUS RTU is an industry-recognized
standard for communications and is sup-
ported by a number of PLC and protection
device manufacturers.
LSP2164-afp.tif
with DNP 3.0. DNP 3.0 is supported by a
number of protection device manufactur-
ers.
System solution
SIPROTEC 4 is tailor-made for use in
SIMATIC-based automation systems.
Software data management and communi-
cation is one of the strong-points of com-
bining SICAM and SIPROTEC 4.
Powerful engineering tools (SICAM plus
TOOLS on the basis of STEP7 and SICAM
WinCC) make working with SICAM con-
venient. The SIPROTEC 4 units are opti-
mally matched for use in SICAM SAS and
SICAM PCC.
With SICAM and SIPROTEC 4 continuity
exists at three central points:
Fig. 5/79
• Data management System solution/communication
• Software architecture
• Communication
1) Under development
Typical connections
n Connection of current
and voltage transformers
Standard connection
For earthed networks, the earth current is
obtained from the phase currents by the
residual current circuit.
Fig. 5/80
Residual circuit
without directional
element
5
Fig. 5/81
Sensitive earth-
current detection
without directional
element
Fig. 5/82
Residual current
circuit with direc-
tional element
Typical connections
Fig. 5/83
Sensitive directional
earth-fault detection
with directional
element for phases
5
Fig. 5/84
Sensitive directional
earth-fault detection
Fig. 5/85
Isolated-neutral or
compensated
networks
Typical applications
Typical applications
n Connection of circuit-breaker
Undervoltage releases
Undervoltage releases are used for auto-
matic tripping of high-voltage motors.
Example:
DC supply voltage of control system fails
and manual electric tripping is no longer
possible.
Automatic tripping takes place when volt-
age across the coil drops below the trip
limit. In Fig. 5/89, tripping occurs due to
failure of DC supply voltage, by automatic
opening of the live status contact upon
failure of the protection unit or by
short-circuiting the trip coil in event of
network fault.
Fig. 5/89 Undervoltage release with make contact (50, 51)
Technical data
Measuring circuits Binary outputs/command outputs
System frequency 50 / 60 Hz (settable) Version 7SJ621 7SJ622
Command/indication relay 8 6
Current transformer Contacts per command/ 1 NO / form A
indication relay (Two contacts changeable to NC/form B,
Rated current Inom 1 or 5 A (settable)
via jumpers)
Option: sensitive earth-fault CT IEE < 1.6 A
Switching capacity Make 1000 W / VA
Power consumption at Inom = 1 A < 0.05 VA per phase
Break 30 W / VA / 40 W resistive /
Power consumption at Inom = 5 A < 0.3 VA per phase 25 W at L/R £ 50 ms
For sensitive earth-fault Approx. 0.05 VA
Switching voltage £ 250 V DC
detection at 1 A
Permissible current 5 A continuous
Overload capability
30 A for 0.5 s making current,
Thermal (effective) 100 x Inom for 1 s
2000 switching cycles
30 x Inom for 10 s
4 x Inom continuous Live status contact 1 changeover contact/form C
Dynamic (impulse current) 250 x Inom (half cycle) Switching capacity Make 30 W / VA
Overload capability if equipped with Break 20 W / VA / 25 W at L/R < 50 ms
5 sensitive earth-fault current trans-
former
Switching voltage £ 250 V DC
Thermal (effective) 300 A for 1 s Permissible current 5 A continuous
100 A for 10 s 30 A for 0.2 s making current,
15 A continuous 2000 switching cycles
Dynamic (impulse current) 750 A (half cycle)
Electrical tests
Voltage transformers Specification
Rated voltage Vnom 100 V to 225 V Standards IEC 60255
Power consumption at Vnom = 100 V < 0.3 VA per phase ANSI C37.90, C37.90.1, C37.90.2,
UL508
Overload capability in voltage path
(phase-neutral voltage)
Thermal (effective) 230 V continuous Insulation tests
Standards IEC 60255-5; ANSI/IEEE C37.90.0
Auxiliary voltage Voltage test (100 % test) 2.5 kV (r.m.s. value), 50/60 Hz
Auxiliary voltage supply via integrated converter all circuits except for auxiliary
voltage and RS485/RS232 and
Rated auxiliary DC 24/48 V 60/125 V 110/250 V
time synchronization
voltage Vaux AC 115/230 V
Auxiliary voltage 3.5 kV DC
Permissible tolerance DC 19–58 V 48–150 V 88–300 V
AC 92-138 V 184–265 V Communication ports 500 V AC
and time synchronization
Ripple voltage, peak-to-peak £ 12 %
Impulse voltage test (type test) 5 kV (peak value); 1.2/50 µs; 0.5 J
Power consumption
all circuits, except communication 3 positive and 3 negative impulses
Quiescent Approx. 3–4 W
ports and time synchronization, at intervals of 5 s
Energized Approx. 7–9 W
class III
Backup time during ³ 50 ms at V ³ 110 V DC
loss/short circuit of ³ 20 ms at V ³ 24 V DC
auxiliary voltage ³ 200 ms at 115 V/230 V AC EMC tests for interference immunity
Type tests
Binary inputs/indication inputs Standards IEC 60255-6; IEC 60255-22
(product standard)
Version 7SJ621 7SJ622
EN 50082-2 (generic specification)
Number 8 11 DIN 57435 Part 303
Voltage range 24–250 V DC High-frequency test 2.5 kV (peak value); 1 MHz; t =15 ms;
Pickup threshold modifiable by plug-in jumpers IEC 60255-22-1, class III 400 surges per s; test duration 2 s
and VDE 0435 Part 303, class III
Pickup threshold 19 V DC 88 V DC
Electrostatic discharge 8 kV contact discharge;
For rated control voltage 24/48/60/ 110/125/
IEC 60255-22-2 class IV 15 kV air gap discharge;
110/125 V 220/250 V DC
and EN 61000-4-2, class IV both polarities; 150 pF; Ri = 330 W
Response time/drop-out time Approx. 3.5
Irradiation with radio-frequency 10 V/m; 27 to 500 MHz
Power consumption 1.8 mA (independent of operating voltage) field, non-modulated
energized IEC 60255-22-3 (Report) class III
Technical data
Irradiation with radio-frequency 10 V/m, 80 to 1000 MHz; Seismic vibration Sinusoidal
field, amplitude-modulated AM 80 %; 1 kHz IEC 60255-21-3, class 1 1 to 8 Hz: ± 3.5 mm amplitude
IEC 61000-4-3; class III IEC 60068-3-3 (horizontal axis)
Irradiation with radio-frequency 10 V/m, 900 MHz; repetition 1 to 8 Hz: ± 1.5 mm amplitude
field, pulse-modulated rate 200 Hz, on duration 50 % (vertical axis)
IEC 61000-4-3/ENV 50204; class III 8 to 35 Hz: 1 g acceleration
(horizontal axis)
Fast transient interference/burst 4 kV; 5/50 ns; 5 kHz; 8 to 35 Hz: 0.5 g acceleration
IEC 60255-22-4 and IEC 61000-4-4, burst length = 15 ms; (vertical axis)
class IV repetition rate 300 ms; both polarities; Frequency sweep 1 octave/min
Ri = 50 W; test duration 1 min 1 cycle in 3 perpendicular axes
High-energy surge voltages – During transportation
(Surge)
IEC 61000-4-5; class III Standards IEC 60255-21 and IEC 60068-2
Auxiliary voltage From circuit to circuit: 2 kV; 12 W; 9 µF Vibration Sinusoidal
across contacts: 1 kV; 2 W ;18 µF IEC 60255-21-1, class 2 5 to 8 Hz: ± 7.5 mm amplitude;
Binary inputs/outputs From circuit to circuit: 2 kV; 42 W; 0.5 µF IEC 60068-2-6 8 to 150 Hz; 2 g acceleration
across contacts: 1 kV; 42 W; 0.5 µF frequency sweep 1 octave/min
20 cycles in 3 perpendicular axes
5
Line-conducted HF, 10 V; 150 kHz to 80 MHz;
amplitude-modulated AM 80 %; 1 kHz Shock Semi-sinusoidal
IEC 61000-4-6, class III IEC 60255-21-2, Class 1 acceleration 15 g, duration 11 ms
IEC 60068-2-27 3 shocks in both directions of 3 axes
Power frequency magnetic field 30 A/m; 50 Hz, continuous
IEC 61000-4-8, class IV 300 A/m; 50 Hz, 3 s Continuous shock Semi-sinusoidal
IEC 60255-6 0.5 mT, 50 Hz IEC 60255-21-2, class 1 acceleration 10 g, duration 16 ms
IEC 60068-2-29 1000 shocks in both directions
Oscillatory surge withstand 2.5 to 3 kV (peak value), 1 to 1.5 MHz of 3 axes
capability damped wave; 50 surges per s;
ANSI/IEEE C37.90.1 duration 2 s, Ri = 150 to 200 W
Fast transient surge withstand 4 to 5 kV; 10/150 ns; 50 surges per s Climatic stress tests
capability ANSI/IEEE C37.90.1 both polarities; duration 2 s, Ri = 80 W Temperatures
Radiated electromagnetic 35 V/m1); 25 to 1000 MHz; Type-tested acc. to IEC 60068-2-1 -25 °C to +85 °C /-13 °F to +185 °F
interference amplitude and pulse-modulated and -2, test Bd, for 16 h
ANSI/IEEE C37.90.2 Temporarily permissible operating -20 °C to +70 °C /-4 °F to -158 °F
Damped wave 2.5 kV (peak value, polarity temperature, tested for 96 h
IEC 60694 / IEC 61000-4-12 alternating) Recommended permanent operat- -5 °C to +55 °C /+25 °F to +131 °F
100 kHz, 1 MHz, 10 and 50 MHz, ing temperature acc. to IEC 60255-6
Ri = 200 W (Legibility of display may be im-
paired above +55 °C /+131 °F)
– Limiting temperature during -25 °C to +55 °C /-13 °F to +131 °F
EMC tests for interference emission
permanent storage
Type tests – Limiting temperature during -25 °C to +70 °C /-13 °F to +158 °F
Standard EN 50081-* (generic specification) transport
Conducted interferences 150 kHz to 30 MHz Humidity
only auxiliary voltage IEC/CISPR 22 Limit class B Standards IEC 60068-2-3
Radio interference field strength 30 to 1000 MHz Permissible humidity Annual average 75 % relative humidity;
IEC/CISPR 11 Limit class B It is recommended to arrange the on 30 days a year up to 95 % relative
Units with a detached operator panel units in such a way that they are not humidity;
must be installed in a metal cubicle exposed to direct sunlight or condensation not permissible!
to maintain class B pronounced temperature changes
that could cause condensation.
1) Upon request
Technical data
Connection (with plug connectors) System interface (rear of unit)
Current terminals Only with screw-type terminals IEC 60870-5-103
(see above) Integrated interface for data trans- Port B
Voltage terminals 2-pin or 3-pin connectors mission to a master terminal
Wire size 0.5 -1.0 mm2 Transmission rate Setting as supplied: 38400 baud,
0.75 - 1.5 mm2 min. 4800 baud, max. 38400 baud
1.0 - 2.5 mm2 Transmission reliability Hamming distance d = 4
Unit version – RS232/RS485
Housing 7XP20 Connection
Dimensions See dimension drawings, part 16 For flush-mounting housing/ 9-pin subminiature connector,
Weight surface-mounting housing with mounting location “B”
Surface-mounting housing 4.5 kg detached operator panel
Flush-mounting housing 4.0 kg For surface-mounting housing At the bottom part of the housing:
with two-tier terminal at the shielded data cable
Degree of protection top/bottom part
acc. to EN 60529
Surface-mounting housing IP 51 Distance RS232 Max. 15 m/49 ft
Distance RS485 Max. 1 km/3300 ft
5
Flush-mounting housing Front: IP 51, rear: IP 20;
Operator safety IP 2x with cover Test voltage 500 V AC against earth
– Fiber optic
Connection fiber-optic cable Integrated ST connector for fiber-optic
Serial interfaces connection
Operating interface (front of unit) For flush-mounting housing/ 9-pin subminiature connector,
Connection Non-isolated, RS232; front panel, surface-mounting housing with mounting location “B”
9-pin subminiature connector detached operator panel
For surface-mounting housing At the bottom part of the housing
Transmission rate Min. 4800 baud, max. 38400 baud
with two-tier terminal at the
Distance 15 m/49 ft top/bottom part
Optical wavelength 820 nm
Service/modem interface (rear of unit) Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
Isolated interface for data transfer Port C: DIGSI 4/modem/RTD-box Distance Max. 1.5 km/0.9 miles
Transmission rate Setting as supplied 38400 baud Idle state of interface Selectable, setting as supplied “light off”
min. 4800 baud, max. 38400 baud
Transmission reliability Hamming distance d = 4 PROFIBUS-FMS/DP
– RS232/RS485 Isolated interface for data transfer Port B
Connection to a control center
For flush-mounting housing/ 9-pin subminiature connector, Transmission rate Up to 1.5 Mbaud
surface-mounting housing with mounting location “C” Transmission reliability Hamming distance d = 4
detached operator panel – RS485
For surface-mounting housing At the bottom part of the housing:
with two-tier terminal at the shielded data cable Connection
top/bottom part For flush-mounting housing/ 9-pin subminiature connector,
surface-mounting housing with mounting location “B”
Distance RS232 15 m /49.2 ft detached operator panel
Distance RS485 Max. 1 km/3300 ft For surface-mounting housing At the bottom part of the housing:
Test voltage 500 V AC against earth with two-tier terminal at the shielded data cable
top/bottom part
– Fiber optic
Distance 1000 m/3300 ft £ 93.75 kbaud;
Connection fiber-optic cable Integrated ST connector for fiber-optic 500 m/1500 ft £ 187.5 kbaud;
connection 200 m/600 ft £ 1.5 Mbaud
For flush-mounting housing/ Mounting location “C” 100 m/300 ft £ 12 Mbaud
surface-mounting housing with
detached operator panel Test voltage 500 V AC against earth
For surface-mounting housing At the bottom part of the housing – Fiber optic
with two-tier terminal at the Connection fiber-optic cable Integrated ST connector for fiber-optic
top/bottom part connection
Optical wavelength 820 nm For flush-mounting housing/ 9-pin subminiature connector,
Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm surface-mounting housing with mounting location “B”
Distance Max. 1.5 km/0.9 miles detached operator panel
Idle state of interface Settable; setting as supplied “light off” For surface-mounting housing At the bottom part of the housing
with two-tier terminal at the Important: Please refer to footnotes
1)
top/bottom part and 2) on page 5/99
Optical wavelength 820 nm
Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
Distance Max. 1.5 km/0.9 miles
Idle state of interface Settable, setting as supplied “light off”
Technical data
MODBUS RTU, ASCII, DNP 3.0 Times
Isolated interface for data transfer Port B Pickup times (without inrush
to a control center restraint, with inrush restraint
+ 10 ms)
Transmission rate Up to 19200 baud
Non-directional Directional
Transmission reliability Hamming distance With twice the setting value Approx. 30 ms 45 ms
d = 4 MODBUS RTU/ASCII With five times the setting value Approx. 20 ms 40 ms
d = 6 DNP 3.0
Dropout times
– RS485 at 50 Hz Pickup times
Connection at 60 Hz
For flush-mounting housing/ 9-pin subminiature connector, Dropout ratio Approx. 0.95 for I/Inom ³ 0.3
surface-mounting housing with mounting location “B”
detached operator panel Tolerances
For surface-mounting housing At bottom part of the housing: Pickup 2 % of setting value or 50 mA1)
with two-tier terminal at the shielded data cable Delay times T 1 % or 10 ms
top/bottom part Inverse-time overcurrent protection (directional/non-directional)
Distance Max. 1 km/3300 ft max. 32 units Setting/increments
recommended Current starting IP (phases) 0.5 to 175 A, ¥1) (in steps of 0.05 A)1)
Test voltage 500 V AC against earth IEp (earth) 0.25 to 175 A, ¥1) (in steps of 0.05 A)1)
– Tripping time characteristics according to IEC 60255-3
5
– Fiber-optic
(does not apply to the US market)
Connection fiber-optic cable Integrated ST connector for fiber-optic
connection Time multiplier for Ip, IEp TP = 0.05 to 3.20 s, ¥
For flush-mounting housing/ 9-pin subminiature connector, (IEC characteristics) (in steps of 0.01 s)
surface-mounting housing with mounting location “B” User-definable characteristics
detached operator panel Pickup threshold Approx. 1.1 x Ip for Ip/Inom ³ 0.5
For surface-mounting housing At the bottom part of the housing
with two-tier terminal at the Important: Please refer to footnotes Reset threshold Approx. 1.05 x Ip for Ip/Inom ³ 0.5
top/bottom part 1)
and 2) on page 5/99 alternatively disk emulation
Optical wavelength 820 nm Tolerances
Permissible path attenuation Max 8 dB. for glass fiber 62.5/125 µm Pickup thresholds 2 % of setting value or 1 % of Inom
Distance Max. 1.5 km/0.9 miles Timing period for 2 £ I/Ip 20 5 % of setpoint, ± 2 % current
tolerance; at least 30 ms
Idle state of interface “Light off”
– Tripping time characteristic acc. to ANSI/IEEE C37.112 (for US market)
Time dial (ANSI characteristics) TD = 0.05 to 15.0 s, ¥
Clock Pickup threshold Approx. 1.1 x M for Ip/Inom ³ 0.5
Time synchronization Port A, IRIG B-signal/DCF77, Reset threshold Approx. 1.05 x M for Ip/Inom > 0.5
binary input, communication alternatively disk emulation
Signal level 5 V, 12 V, 24 V Tolerances
Pickup thresholds 2 % of setting value, 50 mA
Dynamic parameter group Timing duration for 2 £ M £ 20 5 % of the setpoint +2 % current
Controllable function Directional and non-directional tolerance; at least 30 ms
pickup, tripping time
Start criteria Current criteria Direction detection
CB position via aux. contacts
Binary input – For phase errors
Auto-reclosure ready Type With externally generated short-circuit
Time control 3 timers tripping current
With voltage memory (memory depth
Current criteria Current threshold 2 cycles) for too small measuring volt-
(reset on dropping below threshold; ages
monitoring with timer)
Forward range Inductive: angle 45 ° ± 86 °
Resistive: angle 0 ° ± 86 °
Definite-time overcurrent protection (directional/non-directional) Capacitive: angle -45 ° ± 86 °
Setting range/increments (steps) Direction sensitivity For one and two-phase faults unlimited
For three-phase faults dynamically
Phase elements phase I 0.5 to 175 A, ¥1) (in steps of 0.05 A)1)
unlimited
Earth elements earth I 0.25 to 175 A, ¥1) (in steps of 0.05 A)1)
Steady-state approx. 7 V phase-to-phase
Delay times T 0.00 s to 60.00 s (in steps of 0.01 s), ¥
– For earth faults
Times set are pure delay times
Type With zero-sequence systems
Forward range Inductive: angle 45 ° ± 84 °
Resistive: angle 0 ° ± 84 °
Capacitive: angle -45 ° ± 84 °
Technical data
Direction sensitivity Approx. 5 V displacement voltage User-defined characteristic User-defined characteristic
(measured) defined by a maximum of 20 pairs of
Approx. 12 V displacement voltage current and delay time values
(calculated) Current pickup2)
Tolerances For sensitive input 0.001 A to 1.400 A (in steps of 0.001 A)
Phase angle error under reference For normal input 0.025 to 20.00 A1) (in steps of 0.05 A)1)
conditions ± 5 ° electrical Time multiplier 0.10 to 4.00 (in steps of 0.01 s)
For phase earth error or ¥ (deactivated)
Measuring tolerances acc. 2 % of setting value or 1 mA
Inrush blocking to DIN 57435
Influenced functions Time-overcurrent element, 50 -1, Operating time tolerances 7 % of setpoint for 2 £ M3) £ 20
50N-1; 51, 51N in the linear range +2 % current tolerance, at least 70 ms
(directional/non-directional) Dropout ratio Approx. 0.95
I>, IE>, IP, IEP – Direction detection for all types of earth-faults
Lower function limit 1.25 A 1) Direction measurement
Upper function limit (setting range) 1.5 to 125 A 1) IE, VE (measured)
Setting range T2f/I 10 to 45 %
5
3I0, 3V0 (calculated)
Crossblock (IL1, IL2, IL3) ON/OFF Measuring principle Active/reactive measurement
Measuring enable
For sensitive input 0.001 to 1.200 A (in steps of 0.001 A)
Sensitive earth-fault detection
For normal input 0.25 to 150.00 A1) (in steps of 0.05 A)1)
– Displacement voltage starting for all types of earth fault
Direction vector -45.0 ° to +45.0 ° (in steps of 0.1 °)
Displacement voltage, measured VE > 1.8 to 130.0 V (in steps of 0.1 V)
Angle correction for cable converter In 2 operating points F1 and F2
Displacement voltage, calculated 3 V0 > 10.0 to 225.0 V (in steps of 0.1 V)
(for resonant-earthed system)
Measuring time Approx. 60 ms
Angle correction F1, F2 0 ° to 5.0 ° (in steps of 0.1 °)
Pickup delay time 0.04 to 320.00 s or ¥ (in steps of 0.01 s)
Current values I1, I2
Time delay 0.10 to 40000.00 s or ¥ (in steps of 0.01 s) For sensitive input 0.001 to 1.500 A (in steps of 0.001 A)
Dropout ratio 0.95 or (pickup value -0.6 V) For normal input 0.25 to 175.00 A1) (in steps of 0.05 A)1)
Measuring tolerance Measuring tolerance acc. 2 % of the setting value or 1 mA
VE (measured) 3 % of setting value, or 0.3 V to DIN 57435
3 V0 (calculated) 3 % of setting value or 3 V Angle tolerance 2 ° for Inom = 0.2 A to 1.2 A
Operating time tolerances 1 % of setting value, or 10 ms (if VEN voltage connected) 7 ° for Inom = 0.2 A
– Phase detection for earth fault in an unearthed system Angle tolerance 3°
Measuring principle Voltage measurement (phase-to-earth)
Vph min (earth-fault phase) 10 to 100 V (in steps of 1 V) Intermittent earth-fault protection
Vph max (unfaulted phases) 10 to 100 V (in steps of 1 V) Setting ranges/increments
Measuring tolerance acc. 3 % of setting value, or 1 V Pickup value
to DIN 57435 part 303 For IE IIE> 0.25 to 175.00 A1) (in steps of 0.05 A)1)
For 3I0 IIE> 0.25 to 175.00 A1) (in steps of 0.05 A)1)
– Earth-fault pickup for all types of earth fault
For IEE IIE> 0.050 to 1.500 A (in steps of 0.001 A)
Definite-time characteristic
Pickup prolon- TV 0.00 to 10.00 s (in steps of 0.01 s)
Current pickup 50Ns2 gation time
For sensitive input 0.001 to 1.500 A (in steps of 0.001 A)
Earth-fault accu- Tsum 0.00 to 10.00 s (in steps of 0.01 s)
For normal input 0.25 to 175.00 A1) (in steps of 0.05 A)1)
mulation time
Delay time 50Ns2 0 to 320.00 s (in steps of 0.001 A)
Reset time for Tres 1 to 600 s (in steps of 1 s)
or ¥ (deactivated)
accumulation
Current pickup 50Ns1
Number of pickups for 2 to 10 (in steps of 1)
For sensitive input 0.001 A to 1.500 A (in steps of 0.001 A)
intermittent earth fault
For normal input 0.25 to 175.00 A1) (in steps of 0.05 A)1)
– Inherent operating times
Delay time 50Ns1 0 to 320.00 s (in steps of 0.01 s)
or ¥ (deactivated) Pickup times
Inherent pickup time £ 60 ms (non-directional) Current = 1.25 x pickup value Approx. 30 ms
£ 80 ms (directional) Current ³ 2 x pickup value Approx. 22 ms
Drop-off time Approx. 22 ms
(without prolongation time)
Tolerances
Pickup value IIE> 3 % of setting value, or 50 mA 1)
Times TV, Tsum, Tres 1 % of setting value or 10 ms
1) For Inom = 1 A, all limits divided by 5.
2) Available as an option.
3) Multiple of pickup.
Technical data
Thermal overload protection Maximum dead time extension 0.50 s to 320.00 s (in steps of 0.01 s) or ¥
Setting ranges/increments Action time 0.01 s to 320.00 s (in steps of 0.01 s) or ¥
Factor k acc. to IEC 60255-8 0.5 to 20 (in steps of 0.5)1) The delay times of the following protection function can be altered individu-
Time constant 1.0 to 999.9 min (in steps of 0.1 min) ally by the ARC for shots 1 to 4
Warning overtemperature 50 to 100 % with reference (setting value T = T/non-delayed T = 0/blocking T = ¥):
Qalarm/Qtrip to the tripping overtemperature 50-1, 50-2, 51, 67-1, 67-2, 67-TOC, 50N-1, 50N-2, 51N, 67N-1, 67N-2,
(in steps of 1 %) 67N-TOC
Current warning stage Ialarm 0.10 to 4.00 (in steps of 0.01) Additional functions Lockout
Co-ordination with other protection relays,
Extension factor when stopped 1.0 to 10.0 with reference to the time con- circuit-breaker monitoring,
k factor
t stant with the machine running (in steps evaluation of the CB contacts
of 0.1)
– Tripping characteristic
Breaker failure protection
( I / k ⋅ I nom ) − ( I pre / k ⋅ Inom )
2 2
t = τ th Setting ranges/increments
( I / k ⋅ I nom ) − 1
2
Pickup of current element CB I>/Inom 0.2 to 5.00
(in steps of 0.05)1)
For (I/k · Inom) £ 8 t =
Tripping time Delay time 0.06 to 60.00 s or ¥ (in steps of 0.01 s)
tth
I
=
Temperature rise time constant
=
Load current Pickup times (with internal start) is contained in the delay time 5
Ipre =
Preload current (via control) is contained in the delay time
k =
Setting factor acc. to VDE 0435 (with external start) is contained in the delay time
Part 3011 and IEC 60255-8 Dropout time Approx. 25 ms
Inom = Rated (nominal) current of the Tolerances
protection relay Pickup value 2 % of setting value (50 mA)1)
Dropout Q/Qtrip, Dropout at QAlarm Delay time 1 % or 20 ms
QAlarm Approx. 0.96
IAlarm Approx. 0.97 Negative-sequence current detection
Tolerances – Definite-time elements (46-1 and 46-2)
With reference to k x IN Class 5 acc. to IEC 60255-8
Setting range
With reference to tripping time 5 % +/- 2 s acc. to IEC 60255-8
Pickup current 2.5 to 75.00 A (in steps of 0.05 A)1) or ¥
Delay times 0 to 60.00 s, ¥ (in steps of 0.01 s)
Auto-reclosure Multiple of pickup 0.5 to 10.00 A
Number of reclosures 0 to 9 (RAR, DAR) Functional limits
Shot 1 to 4 individually adjustable Lower functional limit At least one phase current ³ 2.5 A
Upper functional limit All phase currents £ 100 A1)
Program for phase error
Start-up by Time-overcurrent elements negative Inherent operating times
sequence, binary input Pickup times Approx. 35 ms
Dropout times Approx. 35 ms
Program for earth fault Dropout ratio Approx. 0.95 for I2 /Inom > 0.3
Start-up by Time-overcurrent elements sensitive
earth-fault protection, binary input Tolerances
Pickup thresholds 3 % of the setting value or 50 mA1)
Blocking of ARC Protection functions Delay times 1 % or 10 ms
Three-phase fault detected by a protective
element – Inverse-time elements (46-TOC)
Binary input Setting range
TRIP of a protection function for which Pickup current 2.5 to 50 A 1) (in steps of 0.25 A)1)
ARC blocking is set Time dial (IEC) 0.05 to 3.20 s (in steps of 0.01 s)
TRIP command by the breaker failure or ¥ (deactivated)
protection (50BF) Time dial (ANSI) 0.05 to 15.00 s (in steps of 0.01 s)
Opening the circuit-breaker without ARC or ¥ (deactivated)
initation Functional limits
External CLOSE command Lower functional limit At least one phase current ³ 2.5 A 1)
Dead time 0.01 to 320.00 s (in steps of 0.01 s) Upper functional limit All phase currents £ 100 A 1)
(separate for phase and earth Tolerances
and individual for shots 1 to 4) Pickup thresholds 3 % of the setting value or 250 mA1)
Extension of dead time Via binary input with time monitoring Time for 2 £ M £ 20 5 % of setpoint (calculated)
Blocking duration after 0.50 s to 320.00 s (in steps of 0.01 s) +2 % current tolerance, at least 30 ms
manual close Dropout
Auto-reclosure reset time 0.50 s to 320.00 s (in steps of 0.01 s) IEC and ANSI Approx. 1.05 · I2p setting value,
(without disk emulation) which is approx. (0.95 · pickup thresh-
Safety time until AR is ready 0.01 s to 320.00 s (in steps of 0.01 s) old)
Start-signal monitoring time 0.01 s to 320.00 s (in steps of 0.01 s) or ¥ ANSI with disk emulation Approx. 0.90 · I2p setting value
Circuit-breaker supervision time 0.10 s to 320.00 s (in steps of 0.01 s)
Technical data
Starting time monitoring for motors Undercurrent monitoring
Setting ranges/increments Signal from the operational Can be generated with programmable
Start-up current of the motor 5.00 to 70.00 A (in steps of 0.05)1) measured values logic
Istart max/Inom
Pickup threshold Istart det/Inom 3.00 to 50.00 A (in steps of 0.05) 1) RTD-boxes for temperature detection
Permissible start-up time Tstart max 1.0 to 180.0 s (in steps of 0.1 s) Temperature detectors
Permissible locked rotor 0.5 to 120.0 s (in steps of 0.1 s), Connectable RTD-boxes 1 or 2
time Tlocked rotor ¥ (deactivated)
Number of temperature
– Tripping time characteristic detectors per RTD-box Max. 6
Type of measuring Pt 100 W or Ni 100 W or Ni 120 W
2
I Installation drawing “Oil” or “Environment” or “Stator” or
t = start ⋅ t start max “Bearing” or “Other”
I rms
Limit values for indications
For Irms >Istart det For each measuring detector
Istart Start-up current of the motor Step 1 -50 °C to 250 °C (in steps of 1 °C)
Irms Current actually flowing -58 °F to 482 °F (in steps of 1 °F)
Istart det Pickup threshold, from or ¥ (no indication)
5 which the motor start-up is
detected
Step 2 -50 °C to 250 °C (in steps of 1 °C)
-58 °F to 482 °F (in steps of 1 °F)
tstart max Tripping time to start-up or ¥ (no indication)
current Istart
t Actual tripping time until
current flows Undervoltage protection
– Release condition Measured quantity V 1 (positive-sequence system)
Irms > Istart det Approx. 0.95 Setting range V<, V<< 10 to 210 V
Tolerances (phase-to-earth connection)
10 to 120 V
Pickup value 2 % of setting value or 1 % of Inom
(phase-to-phase connection)
Delay time 5 % or 30 ms
Delay times 0 to 100 s (in steps of 0.01 s)
or ¥ (i.e. deactivated)
Restart inhibit for motors Pickup time £ 50 ms
Setting ranges/increments Dropout time £ 50 ms
Start-up current with reference to 15.0 to 50.0 A (in steps of 0.5)1) Dropout condition
nominal motor current IL1/IL2 V< 1.05 - 3.0 settable
Nominal motor current/ 1.0 to 6.0 A (in steps of 0.1)1) V<< 1.05
transformer nominal current IL2 Tolerances
Maximum permissible 3 to 120 s (in steps of 1 s) Voltage starting 3 % of setting value or 1 V
start-up time Tstart Delay times 1 % of setting value or 10 ms
Rotor temperature compensation 0 to 60.0 min (in steps of 0.1 min) Undercurrent blocking Yes/no
time TCOMP
Maximum permissible number 1 to 4 (in steps of 1) Overvoltage protection
of warm starts nw
Measured quantity Maximum phase-to-phase voltage
Difference between cold and 1 to 2 (in steps of 1)
Setting range V>, V>> 40 to 225 V
warm start nc - nw
(phase-to-earth connection)
Extension factor for cooling 1 to 10 (in steps of 1) 40 to 130 V
simulation of the rotor at zero (phase-to-phase connection)
speed k factor
Delay times 0 to 100 s or ¥ (in steps of 0.01 s)
– Restarting limit
Pickup time £ 50 ms
n −1 Dropout time £ 50 ms
Θ restart = Θ rot max perm ⋅ c
nc Dropout condition 0.95
Tolerances
Qrestart Temperature limit below Voltage starting 3 % of the setting value or 1 V
which restarting is possible Delay times 1 % of the setting value or 10 ms
Qrot max perm Maximum permissible
rotor overtemperature
(= 100 % in operational
measured value
Qrot/Qrot trip)
nc Number of permissible
start-ups from cold state
Technical data
Frequency protection Standard measured val-
Number of frequency elements 4 ues
Setting range 45.5 to 54.5 Hz Currents Voltages
(in steps of 0.01) at t fnom = 50 Hz IL1 in A, kA Primary VL1-L2 in kV Primary
55.5 to 64.5 Hz IL2 in A, kA Primary VL2-L3 in kV Primary
(in steps of 0.01) at t fnom = 60 Hz IL3 in A, kA Primary VL3-L1 in kV Primary
Delay times 0 to 100 s or ¥ (in steps of 0.01 s) IE in A, kA Primary VE in kV Primary
Undervoltage blocking 10 to 150 V VL1-E in kV Primary (with
(V1 positive-sequence system) phase-to-earth
connection)
Pickup times £ 150 ms VL2-E in kV Primary (with
Dropout times £ 150 ms phase-to-earth
Hysteresis Approx. 20 mHz connection)
Dropout condition 1.05 VL3-E in kV Primary (with
under voltage blocking phase-to-earth
Tolerances connection)
Frequency 10 mHz 3I0 in A, kA Primary V0 in kV Primary
Undervoltage blocking 3 % of the setting value or 1 V I1 in A, kA Primary V1 in kV Primary
Delay times 1 % of the setting value or 10 ms I2 in A, kA Primary V2 in kV Primary 5
IEE in mA, A Primary
IEE ac in mA, A Primary
Fault locator
IEE reac in mA, A Primary
Output of the fault distance In W secondary
IL1 in % or A Secondary VL1-L2 in % or V Secondary
In km / mile of line length
IL2 in % or A Secondary VL2-L3 in % or V Secondary
Starting signal With tripping, with pickup release and IL3 in % or A Secondary VL3-L1 in % or V Secondary
binary input IE in % or A Secondary VE in % or V Secondary
Setting reactance per unit length 0.005 to 6.215 W/km VL1-E in % or V Secondary (with
(secondary) or 0.01 to 10 W/mile phase-to-earth
Measuring tolerance according £ 2.5 % line length connection)
to DIN 57435 with sinusoidal (without intermediate feed-in) VL2-E in % or V Secondary (with
measured quantities 30 ° £ j £ 90 ° and Vk/Vnom ³ 0.1 phase-to-earth
connection)
VL3-E in % or V Secondary (with
Operational measured values phase-to-earth
For currents IL1, IL2, IL3 connection)
in A (Amps) primary/secondary 3I0 in % or A Secondary V0 in % or V Secondary
or in % Inom I1 in % or A Secondary V1 in % or V Secondary
Range 10 to 200 % Inom I2 in % or A Secondary V2 in % or V Secondary
Tolerance 1 % of measured value or 0.5 % Inom IEE in mA Secondary
For voltages VL1-E, VL2-E, VL3-E IEE ac in mA Secondary
Range 10 to 120 % of Vnom IEE reac in mA Secondary
Tolerance £ 1 % of measured value or 0.5 %
Measured quantities from overload protection and restarting block
Vnom
Qstat (stator) In %
For sensitive earth-current IEE, IEEac, IEEreac
detection (r.m.s., active and reactive current) Qrot (rotor) In %
In A (kA) primary, Power/work
and in mA secondary S Apparent power In kVA, MVA, GVA
Range 0 mA to 1600 mA P Active power, In kW, MW, GW
Tolerance 2 % of measured value or 1 mA total and phase-selective.
P/Watts (active power), For ^cosj^ = 0.707 to 1 typically < 3 % Q Reactive power, In kvar, Mvar, Gvar
total and phase-selective for V/Vnom, I/Inom = 50 to 120 % total and phase-selective.
Q/Var (reactive power), For ^sinj^ = 0.707 to 1 typically < 3 % cos j, total and phase-selective. -1 to +1
total and phase-selective for V/Vnom, I/Inom = 50 to 120 % Metering
S/VA (apparent power), For V/Vnom, I/Inom = 50 to 120 % + Wp kWh In kWh, MWh, GWh forward
typically < 2 % - Wp kWh In kWh reverse
Power factor cos j For ^cosj^ = 0.707 to 1 typically < 5 % + Wq kvarh In kvarh inductive
total and phase-selective - Wq kvarh In kvarh, Mvarh, Gvarh capacitive
All operational measured values and the measured values derived from them Frequency
are available for use by connected control and protection equipment. Mea- Range fn ± 5 Hz
sured-value processing is performed using programmable logic. Tolerance 20 mHz
Overload
Range 0 % to 400 %
Tolerance 5 % (acc. to IEC 60255-8)
Technical data
Optional measured values Remote control Via communication interfaces
Operating hours In h (0 to 999999 h) Control and protection
(e.g. SICAM)
Mean values 5, 15, 30, 60 minutes mean values DIGSI 4 (e.g. via modem)
Long-term mean values
IL1 dmd in A, kA Pdmd in kW
IL2 dmd in A, kA Qdmd in kvar Operating program
IL3 dmd in A, kA Sdmd in kVA DIGSI 4 under Windows 95/98/2000, Windows NT 4.0
I1 dmd in A, kA
Additional functions
Min./max. LOG (memory) Measured quantity supervision
Measured values With date and time Current balance Imax/Imin > symmetry factor,
Reset automatic Time of day (settable in minutes) for I > Ilimit
Time range (settable in days; Current sum |IL1 + IL2 + IL3 + k*IE| > limit value
1 to 365, ¥)
Current phase sequence Clockwise/counter-clockwise
Reset manual Via binary input
Limit value monitoring See operational measured values
Via keyboard
5 Min./max. values of primary currents
Via communication
Min./max. values of primary voltages
Rotating field
Fault logging
Clockwise/counter-clockwise
Technical data
Commissioning aids
Operational measured values
Circuit-breaker test
Read binary input
Set binary input
Clock
Time synchronization IRIG-B signal
Binary input
Communication
CE conformity
This product is in conformity with the Directives of the European Commu-
nities on the harmonization of the laws of the Member States relating to elec-
tromagnetic compatibility (EMC Council Directive 89/336/EEC) and
electrical equipment designed for use within certain voltage limits (Council
Directive 73/23/EEC).
This unit conforms to the international standard IEC 60255, and the Ger-
man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
5
The unit has been developed and manufactured for application in an indus-
trial environment according to the EMC standards.
This conformity is the result of a test that was performed by Siemens AG in
accordance with Article 10 of the Council Directive complying with the
generic standards EN 50081-2 and EN 50082-2 for the EMC Directive and
standard EN 60255-6 for the “low-voltage Directive”.
Unit version
For panel surface mounting, two-tier terminal top/bottom B
For panel flush-mounting, plug-in terminal, (2/3 pin connector) D
For panel flush-mounting, screw-type terminal (direct connection/ring-type cable lugs) E
Measuring/fault recording
Fault recording 1
Slave pointer, mean values, min/max values, fault recording 3
DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows (version Windows 95 and higher)
device templates, Comtrade Viewer, electronic manual included
as well as “Getting started” manual on paper, connecting cables (copper)
Basis
Full version with license for 10 computers, on CD-ROM
(authorization by serial number) 7XS5400-0AA00
Demo
Demo version on CD-ROM 7XS5401-0AA00
Professional
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00
SIGRA
5
(generally contained in DIGSI Professional, but can be ordered additionally)
Software for graphic visualization, analysis and evaluation of fault records.
LSP2090-afp.eps
0-827039-1 AMP 1)
2
Short-circuit links Crimp connector CI2 0.5 to 1 mm 4000
for other terminals taped on reel
LSP2289-afp.eps
Connection Diagram
*) For pinout of communication ports see Appendix, dimension drawings, part 16.
Connection Diagram
*) For pinout of communication ports see Appendix, dimension drawings, part 16.