for

Cliente Numero 1

Prepared By:

Esteros

domingo, 1 de abril de 2018


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Proyeccto Prueba 1
College Station, TX 77845 Page 2

Building Summary Loads


Building peaks in August at 5pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 75 0 0,00 0 136 136 0,10
Wall 135 0 0,00 0 -106 -106 -0,08
Glass 15 0 0,00 0 239 239 0,18
Floor Slab 0 0 0,00 0 0 0 0,00
Skin Loads 0 0,00 0 269 269 0,20
Lighting 83 0 0,00 0 287 287 0,22
Equipment 75 0 0,00 0 261 261 0,20
Pool Latent 0 0 0,00 0 0 0 0,00
People 1 0 0,00 204 255 459 0,34
Partition 200 0 0,00 0 1.010 1.010 0,76
Cool. Pret. 0 0 0,00 0 0 0 0,00
Heat. Pret. 0 0 0,00 0 0 0 0,00
Cool. Vent. 7.500 0 0,00 49.114 -12.066 37.048 27,81
Heat. Vent. 0 0 0,00 0 0 0 0,00
Cool. Infil. 50 0 0,00 341 -89 252 0,19
Heat. Infil. 0 0 0,00 0 0 0 0,00
Draw-Thru Fan 0 0 0,00 0 0 0 0,00
Blow-Thru Fan 0 0 0,00 0 5.153 5.153 3,87
Reserve Cap. 0 0 0,00 0 88.498 88.498 66,42
Reheat Cap. 0 0 0,00 0 0 0 0,00
Supply Duct 0 0 0,00 0 0 0 0,00
Return Duct 0 0 0,00 0 0 0 0,00
Misc. Supply 0 0 0,00 0 0 0 0,00
Misc. Return 0 0 0,00 0 0 0 0,00
Building Totals 0 0,00 49.659 83.577 133.236 100,00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0,00 49.114 -12.066 37.048 27,81
Infiltration 0 0,00 341 -89 252 0,19
Pretreated Air 0 0,00 0 0 0 0,00
Room Loads 0 0,00 204 90.580 90.784 68,14
Plenum Loads 0 0,00 0 0 0 0,00
Fan/Duct/Misc Loads 0 0,00 0 5.153 5.153 3,87
Building Totals 0 0,00 49.659 83.577 133.236 100,00

Check Figures
Total Building Supply Air (based on a 15° TD): 7.500 CFM
Total Building Vent. Air (100,01% of Supply): 7.500 CFM
Total Conditioned Air Space: 75 Sq.ft
Supply Air Per Unit Area: 99,9950 CFM/Sq.ft
Area Per Cooling Capacity: 6,8 Sq.ft/Ton
Cooling Capacity Per Area: 0,1480 Tons/Sq.ft
Heating Capacity Per Area: 0,00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 11,10 Tons

C:\Users\PRIVADO\Desktop\prueba 1.CH8 domingo, 1 de abril de 2018, 09:34 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Proyeccto Prueba 1
College Station, TX 77845 Page 3

Air Handler #1 - Uma #1 - Summary Loads


Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Z1 75 0 1.993 545 None 100/ft²
5pm August 1 0 7.500 50 0 7.500
750 0,00 100,00 0 0 7.500
Room Peak Totals: 75 0 1.993 545
Total Rooms: 1 1 0 7.500 50 0 7.500
Unique Rooms: 1 750 0,00 100,00 0 0 7.500

C:\Users\PRIVADO\Desktop\prueba 1.CH8 domingo, 1 de abril de 2018, 09:34 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Proyeccto Prueba 1
College Station, TX 77845 Page 4

Air Handler #1 - Uma #1 - Total Load Summary


Air Handler Description: Uma #1 Constant Volume - Sum of Peaks
Supply Air Fan: Blow-Thru with program estimated horsepower of 2,78 HP
Fan Input: 85% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 1,00 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 7pm in August. Method for finding peak time: Adjusted (based on percent sensible capacity)
Outdoor Conditions: Clg: 63° DB, 58° WB, 88,66 grains
Indoor Conditions: Clg: 70° DB (avg.), 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Room Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (,731 X 1,08 X 0) = 0 CFM
Winter Vent Outside Air (0,0% of supply) = 0 CFM
Room space sensible gain: 1.944 Btuh
Infiltration sensible gain: -284 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 88.498 Btuh
Total sensible gain on supply side of coil: 90.157 Btuh
Cooling Supply Air: 90.490 / (,731 X 1,1 X 15) = 7.500 CFM
Summer Vent Outside Air (100,0% of supply) = 7.500 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: -42.231 Btuh 7.500 CFM
Blow-thru fan sensible gain: 5.153 Btuh
Total sensible gain on return side of coil: -37.078 Btuh
Total sensible gain on air handling system: 53.079 Btuh
Room space latent gain: 0 Btuh
Infiltration latent gain: 350 Btuh
Outside air latent gain: 59.471 Btuh
Total latent gain on air handling system: 59.822 Btuh
Total system sensible and latent gain: 112.901 Btuh

Check Figures
Total Air Handler Supply Air (based on a 15° TD): 7.500 CFM
Total Air Handler Vent. Air (100,01% of Supply): 7.500 CFM
Total Conditioned Air Space: 75 Sq.ft
Supply Air Per Unit Area: 99,9950 CFM/Sq.ft
Area Per Cooling Capacity: 0,8 Sq.ft/Ton
Cooling Capacity Per Area: 1,3294 Tons/Sq.ft
Heating Capacity Per Area: 0,00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 99,70 Tons
Note: Tonnages are 'adjusted' tons, based on percent sensible capacity of the air handler.

C:\Users\PRIVADO\Desktop\prueba 1.CH8 domingo, 1 de abril de 2018, 09:34 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Proyeccto Prueba 1
College Station, TX 77845 Page 5

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Room 1-Z1 - Air Handler 1 (Uma #1), Zone 0 peaks (sensible) in August at 5pm.
Roof-1-4-Susp.C-L 75 0,50 5,2 0,340 133 9,792 734
Wall-1-340-C-M 135 0,83 -3,1 0,251 -104 7,229 976
Partition-2-2 150 18/0 0,275 743 0,000 0
Partition-3-2 50 18/0 0,275 248 0,000 0
Gls-340°-1-90-Tran 5,9 1,000 -9 0,900 -22 26,208 153
61%S-1-NS-Solar 5,9 0,400 122 0,590 168
SGls-340°-1-90-Tran 9,2 1,000 -9 0,900 -34 26,208 240
61%S-1-NS-Solar 9,2 0,400 42 0,790 121
Lights-Prof=4 83 1,000 282
Equipment-Prof=3 75 1,000 256 0
People-Prof=1 1,0 1,000 250 200
Cool. Infil.Direct CFM 50 -88 334
Heat. Infil.AC/hr 0 0,000 0
Sub-total 1.954 534 0
Safety factors: +2% +2% +0%
--------- --------- ---------
Total w/ safety factors: 1.993 545 0

C:\Users\PRIVADO\Desktop\prueba 1.CH8 domingo, 1 de abril de 2018, 09:34 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Proyeccto Prueba 1
College Station, TX 77845 Page 6

Room Detailed Loads (At Room Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Room 1-Z1 peaks (sensible) in August at 5pm, Air Handler 1 (Uma #1), Zone 0, 5,0 x 15,0, Construction
Type: 1 (Light), SIDB: 70°F
Roof-1-4-Susp.C-L 75 0,50 5,2 0,340 133 9,792 734
Wall-1-340-C-M 135 0,83 -3,1 0,251 -104 7,229 976
Partition-2-2 150 18/0 0,275 743 0,000 0
Partition-3-2 50 18/0 0,275 248 0,000 0
Gls-340°-1-90-Tran 5,9 1,000 -9 0,900 -22 26,208 153
61%S-1-NS-Solar 5,9 0,400 122 0,590 168
SGls-340°-1-90-Tran 9,2 1,000 -9 0,900 -34 26,208 240
61%S-1-NS-Solar 9,2 0,400 42 0,790 121
Lights-Prof=4 83 1,000 282
Equipment-Prof=3 75 1,000 256 0
People-Prof=1 1,0 1,000 250 200
Cool. Infil.Direct CFM 50 -88 334
Heat. Infil.AC/hr 0 0,000 0
Sub-total 1.954 534 0
Safety factors: +2% +2% +0%
--------- --------- ---------
Total w/ safety factors: 1.993 545 0