Beruflich Dokumente
Kultur Dokumente
Volume IV
Sewage
Treatment Plants
Published by :
Suruhanjaya
Perkhidmatan
Air Negara (SPAN)
Ministry of
Energy, Water
and Communication
Malaysia
Foreword by the
CEO of SPAN
M
unicipal wastewater treatment technology in Malaysia has evolved through several eras. In the
past, only basic facilities were used, e.g. overhang latrines, pit privy, bucket systems and pour
flush systems. Some improvement were observed when more modern system like septic tank and
Imhoff tank systems were introduced into the country some 40 years ago. The municipal
wastewater treatment in Malaysia sees a significant improvement in the last three decades since the introduction
of new technologies in the form of oxidation ponds, aerated lagoons, activated sludge system, package systems
and a variety of mechanical plants into the country. However, sewage still remains as one of the major pollutants
of our inland waterways. In the 1900s, the emergent of new treatment technologies were mainly driven by the
basic need to treat the sewage so as to control waterborne diseases. Today, the environmental regulations are
becoming stringent with the increasing awareness toward sustainable environmental management. Allowable
effluent discharge limits are becoming lower globally. Public are also more educated and more alert on the needs
to preserve the environment. Hence the evolution of municipal wastewater treatment technologies now are even
more revolutionary and more rapid in order to meet the stricter regulators’ requirements and to compete in the
increasing competitive market.
While the nation moves towards achieving the status of a developed country, sustainability of our environment,
in particularly the Malaysian rivers and streams must be strengthened. With this vision in mind, the Sewerage
Services Department published its first edition of the guidelines for sewerage industry titled “Design and
Installation of Sewerage Systems” in January 1995. The main purpose of these guidelines is to assist the
developer and his designer to plan and design systems acceptable to the regulatory authorities which, in
turn speeds up the approval processes. The Guidelines has clearly guided the nation sewerage industry towards
achieving an improved sewerage system in the country. Subsequently, the Department further improvised the
Guidelines in its second edition titled “Guidelines for Developers” which comprise five volumes covering
specific topics.
As a continuation to the efforts by the Sewerage Services Department, the National Water Services Commission
undertake to revise and improvement the Guidelines for Developers. The product of the revision is “Malaysian
Sewerage Industry Guidelines” which also comprise five volumes. These new revisions incorporated valuable
knowledge gained by various stakeholders over a decade since the implementation of the first Guidelines for
Developers and upkeep with the aim towards sustainable environmental management.
Volume 4 is specifically designed to provide a prescriptive guide to the design and construction of sewage
treatment plants. This volume comes in 8 Sections as follows: Introduction and General Planning; Design
Overview; Effluent Discharge Standards and Requirements; Requirements for Physical Design;
Requirements for Individual Treatment Processes; Requirements for Ancillary Facilities; Special
Requirements; Package Sewage Treatment Plant. The implementation of these guidelines since 90’s has
undoubtedly achieved some levels of consistency in the design and construction of treatment plant
nationwide. Compliance to the treated effluent quality and sludge management has been elevated while the
operation and maintenance of the plants have improved significantly in terms of safety, health, operability
and robustness. Whilst the adherence to these guidelines is necessary, engineering discretion is also
required, especially for large treatment plants and/or plants with special situations. It is hoped that the
publication of the third edition of this Volume further improve the municipal wastewater treatment
facilities in this country.
National Water Services Commission and Registered Certifying Agencies employees are
permitted to copy and use the information in this publication, for internal purposes only.
i
Section 3 Sewage Characteristics and Effluent Discharge Requirements
3.1 Introduction 23
3.2 EQA Effluent Standards 23
3.2.1 Purpose of Effluent Standards 23
3.2.2 Interpretation of EQA Effluent Standards 23
3.3 Design Requirements to Achieve EQA Effluent Standards 24
3.3.1 Purpose of Design Requirements 24
3.3.2 Design Values 24
3.4 Sewage Pollutants Removal 25
3.4.1 Biochemical Oxygen Demand (BOD5) 25
3.4.2 Total Suspended Solid (TSS) 26
3.4.3 Chemical Oxygen Demand (COD) 26
3.4.4 Oil and Grease (O&G) 26
3.4.5 Nitrogenous Compound 27
3.4.6 Phosphorus Compound 27
3.5 Sludge Characteristics and Treatment Requirements 28
ii
4.4.4 Imperfect Sites 34
4.4.5 Reduced Land Areas for STPs 35
4.5 Mechanical and Electrical Requirements 45
4.5.1 Mechanical Installation 45
4.5.2 Vibration 46
4.5.3 Noise 46
4.5.4 Safety Around Equipment 47
4.5.5 Motors, Controllers and Motor Starters 49
4.5.6 Power Supply Systems 50
4.5.7 Back-up Generator 51
4.5.8 Switchgear and Control Gear Assemblies 52
4.5.9 Control Cabinets 52
4.5.10 Control Requirements 54
4.5.11 Supervisory Control and Data Acquisition Systems
(SCADA) 56
4.5.12 Early Warning System (EWS) 57
4.5.13 Instrumentation 57
4.5.14 Cables and Cabling Installation 58
4.5.15 Earthing and Lightning Protection 60
4.5.16 General Purpose Power 60
4.5.17 Manuals, Drawings and Labelling 60
4.5.18 Hazardous Areas 61
4.6 Material Requirements for STP Structures and Installations 61
4.6.1 Concrete and Reinforcement 62
4.6.2 Steel 63
4.6.3 Fibre Reinforced Plastic (FRP) 66
4.6.4 Aluminium 68
4.6.5 HDPE (High Density Polyethylene) 68
iii
Figure 4.1 STP Land Area Requirements for Planning Layout Approval for
New Development 41
Figure 4.2 STP Land Area Requirements for Structure Plans 42
Figure 4.3 Guidelines For Buffer Zone 43
Figure 4.4 Plan View of Buffer Zone Requirements 44
Figure 4.5 Clear Working Space 49
iv
5.8.3 Extended Aeration System (EA) 100
5.8.4 Rotating Biological Contactors (RBC) 103
5.8.5 Trickling Filter 105
5.8.6 Sequencing Batch Reactors (SBR) System 106
5.8.7 Design Requirements for Hybrid Systems 109
5.8.8 Design for Nutrient Removal for Sensitive Receiving
Water 109
5.9 Design of Secondary Clarifiers 111
5.9.1 Purpose 111
5.9.2 Design Requirements 111
5.9.3 Multiple Hoppers 112
5.10 Disinfection 114
5.10.1 Design Requirements 115
5.11 Design of Flow Measurement Devices 124
5.11.1 Purpose of Flow Measuring Devices 124
5.11.2 Design Requirements for Flow Devices 124
5.12 Sludge Holding, Treatment and Disposal 125
5.12.1 Introduction 125
5.12.2 Sludge Strategy in General 126
5.12.3 Provision of Sludge Holding, Treatment and Disposal 127
5.12.4 Design Criteria 128
5.13 Tertiary Treatment 133
5.13.1 Introduction 133
5.13.2 Design Requirement 133
v
Table 5.13 Design Parameters for Extended Aeration 101
Table 5.14 Design Parameters for RBC Plants 104
Table 5.15 Design Parameters for Trickling Filter 106
Table 5.16 Design Requirements for SBR System 108
Table 5.17 Design Requirement for Biological Nutrient Removal System 109
Table 5.18 Design Parameters for Secondary Clarifiers 113
Table 5.19 Requirements for Disinfection Facility 115
Table 5.20 Design Guides for Disinfection with Ultra-Violet (UV) 119
Table 5.21 Design Guide for Disinfection with Hypochlorite 122
Table 5.22 Design Guide for Intermittent Disinfection 123
Table 5.23 Design Parameters for Flow Devices 125
Table 5.24 Sludge Generation Rates 128
Table 5.25 Design Parameters for Sludge Thickening 129
Table 5.26 Design Parameters for Aerobic and Anaerobic Digestion 130
Table 5.27 Recommended Design Parameters for Sludge Treatment 131
Figure 5.1 Typical Treatment Process Flow Chart 70
Figure 5.2 Typical Elements and Process Flow Diagram of a Sewage
Treatment Plant 71
Figure 5.3 Typical Drawing of Double Penstock 73
Figure 5.4 Quantities of Screenings Collected From Primary Screens 76
Figure 5.5 Typical drawing of screen chamber based on depth. (<5m for
different PE) 77
Figure 5.6 Typical drawing of screen chamber based on depth. (>5m for
different PE) 78
Figure 5.7 Typical Dimensions of Wet-well Submersible Pump Station 81
Figure 5.8 Typical Dimensions of Dry-well Submersible Pump Station 82
Figure 5.9 Typical details of wet-well pump station 85
Figure 5.10 Typical details of dry-well pump station 86
Figure 5.11 Fine Bubble Diffuser Air – Extended Aeration System 102
Figure 5.12 Oxidation Ditch Activated Sludge System 103
Figure 5.13 Deep Shaft Activated Sludge System 104
Figure 5.14 Rotating Biological Contactor (RBC) Systems 105
Figure 5.15 Typical Process Flow Diagram for Biological Nutrient Removal
System 110
vi
Figure 5.16 Schematic illustration of ultraviolet disinfection system with stilling
plate for flow conditioning and elongated weir for level control 115
Figure 5.17 Profile schematic of lamp modules relative to inlet and outlet
structure 116
vii
Table 6.1 Minimum Number of Recommended Water Stand Pipe and
Location 138
Table 6.2 Spare Part 148
Table 6.3 Numbers of Unit and Location of Compound Lighting 149
Table 6.4 Common ventilation rates 155
Table 6.5 Painting System Index – Colour Standards 158
Figure 6.1 Standard Details for Stand Pipe 138
Figure 6.2 Typical for Administration and Mess Facilities Building 139
Figure 6.3 Typical Details of Road Pavement 140
Figure 6.4 Typical Road Section of Site Road 140
Figure 6.5 Typical Drawing of Brickwall Fencing and Gate 143
Figure 6.6 Brickwall Fencing 144
Figure 6.7 Precast Fencing 145
Figure 6.8 Masonry Fencing 146
Figure 6.9 Typical Details of Compound Lighting 150
Figure 6.10 Typical Detail of Guard Rail 159
Figure 6.11 Typical Detail of Lifting Davit 160
Figure 6.12 Typical Detail of A-Frame Lifting Facilities 160
viii
7.4.3 Specific Requirements for Covered or Buried Plants
under 5,000 PE or Less 180
7.5 Guidelines for Homestead Developments 183
7.5.1 Single Developments up to 30 Units or 150 PE in Total183
7.5.2 Single Developments Over 30 Units in Total with
Average Housing Density Greater Than Five Units per
Hectare 183
7.5.3 Single Developments Over 30 Units in Total with
Average Housing Density Less Than Five Units per
Hectare 183
7.6 Non-Compliance with Standards 184
7.6.1 Introduction 184
7.6.2 Types of Incident’s that Can Cause Treatment Plant
Failure 184
7.7 Energy Saving 187
7.8 Recycle and Reuse 187
ix
Table 8.1 Minimum Design Life Span of Package Sewage Treatment Plant
Components 190
Table 8.2 Recommended Number of Tanks and Effective Volume
Consideration for Various Unit Processes 191
Table 8.3 Technical Requirements of Pumping System 193
Table 8.4 Technical Requirements of Manhole Cover 194
x
APPENDICES
Appendix A Table
Table A.1 Contaminants of Concern in Sewage Treatment 198
Table A.2 Typical Composition of Untreated Domestic Sewage 199
Table A.3 Major Biological Treatment Processes Used for Sewage
Treatment 200
Table A.4 Interim National River Water Quality Standards for Malaysia 202
Table A.5 River Clarification 203
Table A.6 The Occupational Safety and Health Act 514, 1994 - Brief
Summary of Contents 204
Table A.7 Permissible limits for potentially toxic elements in soil 205
Table A.8 Options for disposal of Sludge and reuse of biosolids 206
Appendix B References
Malaysian Standards 207
British Standard 208
European Standard 209
ASTM Standard 211
AS Standard 212
Other Reference Materials 212
Other Guidelines in This Set 212
xi
C-12 Security 219
C-13 Scripting 219
C-14 Interfaces 220
C-15 Distributed Server Architecture 220
C-16 Web Server 220
C-17 Digital Video Monitoring 220
C-18 Integrated Maintenance Management 221
C-19 Application Report 221
C-20 Application Programming Interface 222
C-21 User Documentation 222
C-22 Specifications and Sizing 222
xii
Section 1
Introduction and General
Planning Requirements
Introduction and General Planning Requirements
This volume sets out the requirements of the National Water Services
Commission (SPAN) (referred to as the Commission in this document) for
the planning, design and construction of sewage treatment plants. This
volume contains the following:
The owner must comply with the requirements set out in this volume when
submitting an application for approval to the Commissioner.
This volume does not cover any aspect other than Sewage Treatment Plant
requirements. All internal plumbing approvals need to be approved by
Local Authorities.
This volume does not cover all aspects of design and construction of
sewage treatment plants. Where information is not covered in this volume,
the designer shall follow the requirements given in MS 1228.
a) Sufficient land area for the sewage treatment plant plus additional
area to allow for extensions to the plant, where necessary.
b) Land of suitable configuration should be provided.
c) Sufficient buffer zones.
d) The location of a sewage treatment plant in relation to a particular
catchment area. The plant unit processes shall be located at an
elevation which is not subject to flooding / wave action, or shall
otherwise be adequately protected against all flooding / wave
action.
e) Sufficient topographic features shall be included to indicate its
location in relation to streams and the point of discharge of the
treated effluent.
f) Schematic flow diagrams showing utility systems serving the plant
processes and the flow through various plant units.
g) Pipe works, including any arrangements for by-pass from
individual units. The direction of flow and the content in the pipes
shall also be clearly and permanently painted onto all exposed
piping works.
h) Hydraulic profiles showing the flow of sewage, supernatant liquor,
and sludge.
i) Location, dimensions and elevations of all existing and proposed
plant facilities.
j) Capacity of the effluent receiving drain / water course shall be able
to cater for additional discharge flow from the treatment plant.
k) Consideration for odour and noise mitigation and control through
good facility design, effective operation, containment, collection
and treatment.
Design calculation for all unit processes shall be in sequence starting from
inlet works to biological treatments and sludge treatments as shown in
Figure 5.1. The calculation shall include:
c) Influent values.
d) Design influent and effluent values in compliance with Section
3.3.2.
e) Treatment plant shall be designed based on Design Flow.
f) Hydraulic profile across the treatment units to be indicated onto to
the drawings.
g) Each unit process must comply with the design parameters set in
Section 5.
h) Calculation of PE to be based on Table 1.1.
CL CL
TWL TWL
TWL
I.L. TWL
F.F.L. I.L. TWL TWL F.G.L. FLOOD LEVEL
F.G.L. F.G.L. F.G.L. I.L. F.G.L. F.G.L. F.G.L. TWL IN RECEIVING
WATERCOURS
I.L.
SECONDARY SCREEN NORMAL WATER
LEVEL
CLARIFIER DISTRIBUTION
CHAMBER OUTFALL MEASUREMENT
PRIMARY PUMPING VALVE CHLORINE CONTACT FLUME
SCREEN STATION CHAMBER TANK
BIOLOGICAL TREATMENT CLARIFIERS
2.0m
1.8m
1.6m
1.4m
1.2m
1.0m
0.8m
0.6m
0.4m
0.2m
FGL
-0.2m
HYDRAULIC PROFILE
FE001 FE002
PI PI
GE001 GE002
GF001
GF002
GA001 GA002
PTS L001 50 DI
PTS L003 50 DI
P TS L004 100 DI
PTS L002 100 DI
M M
GF003
PC TC GE003 GA004
M M M
APR L002 80 GI APR L 001 100 GI
GA003
GF001 GF002 GF003
LD 003
LC LC
FB001 DOI
M LD 004
XXX001 D JA001
APR L005 50 G I
AP R L004 50 GI
AP R L003 50 GI
M M M
GE004 GA006
PC TC
M M M
APR L007 80 GI APR L006 100 GI
GF008 FE005 FG002
XXX001 D BA002
GA005
GF 004 GF005 GF006
LD005
FB002 DOI LC
LC
M LD006
Note:
Code numbering system for items identification:
XXX001 D JA002 1) Process equipment no. 3) Valve tag no.
XXX001 A PA001 XXX001 L005 GD001
APR L011 50 GI
A PR L010 50 GI
APR L009 50 G I
Valve sequential no .
Equipment sequential no. Valve type
Type of equipment Pipeline sequential no .
Unit process Plant identification no .
M M M
Plant identification no.
2) Pipeline no. 4) Instruments no.
RAS L003 150 DI XXX001 A FA001
Pipe material Instrument sequential no.
XXX001 D AC004 XXX001 D AC005 XXX001 D AC006 Pipe size Instrument type
Pipeline sequential no. Unit process
SEQUENCING BATCH REACTOR NO. 2 Fluid in pipeline Plant identification no.
TO CONTROL CIRCUIT
D IS T R IB U T IO N B O X F O R
L IG H T IN G A N D P O W E R
TOR
TOR
TOR
TOR
TOR
PSR
DOL
DOL
DOL
DOL
SPARE
A
A
20A SPN
20A TPN
20A TPN
16A TPN
16A TPN
6A SPN
DOL
DOL
MCB
MCB
MCB
MCB
MCB
MCB
TPN20A
TPN20A
SPN6A
MCB
MCB
MCB
R Y B
24T
3x5A
0 -5 0 0 V
R Y B
S /s w
3x5A
10A
20A
20A
6A
0 -4 0 A 0 -5 0 0 V
S /s w S /s w
U S IN G 4 C x 1 6 m m P V C /S W A P V C A R M . C A B L E U S IN G 4 C x 1 0 m m P V C /S W A /P V C A R M . C A B L E U S IN G 2 C x 6 m m P V C /S W A /P V C A R M . C A B L E
R Y B
6A 0 -50 0V
V .s .s w
3 x 6 0 /5 A 0 -6 0 A
V .s .s w
6 3 /0 .3 A 4 p R C C B
E
6 0 A T P + N 2 5 K A (4 P O L E ) M C C B
S IN G L E L IN E L A Y O U T D IA G R A M F O R
415 V S U P P LY M A IN S W IT C H B O A R D
3 PHASE
T N B M E T E R IN G
PANEL
M U L T IC O R E A R M O U R E D
C ABLE TO
T N B R E Q U IM E N T
IN C O M IN G S U P P L Y F R O M
M A IN D B 4 1 5 V
Qi =
BOD = Qe =
SS = Q = Qi + Qr + Qw
BOD = BOD =
SS = SECONDARY CLARIFIER
SS =
AERATION TANK
OVERFLOW SS CONC = OUTLET
MLSS = BOD =
Qr + Qw =
Qr, Xr BOD =
Qr = X Qi = SS =
BOD =
SS =
AEROBIC DIGESTED
SLUDGE HOLDING TANK
Qw =
BOD =
SS =
1%DS =
SLUDGE THICKENER
Qw =
BOD =
SS =
4%DS =
Qw OVERFLOW =
Classification PE
Class 1 ≤1000
Class 2 1,001 – 5,000
Class 3 5,001 – 20,000
Class 4 > 20,000
Flow Variation Most unit operation and processes work best with a
constant flow rate, although some variation can be
tolerated. If the flow variation is too great, flow
equalisation may be necessary.
Treatment Residuals The types and amounts of solid, liquid and gaseous
residuals produced must be known or estimated.
Ancillary Processes Identify the required support process and the effect
on the effluent quality, especially when they
become inoperative.
a) Biochemical characteristics
b) Physical characteristics
c) Hydraulic characteristics
d) Mechanical & engineering requirements
e) Structural requirements
f) Constructional characteristics
l) Blower room shall not share common wall and foundation with the
control and genset room
3.1 Introduction
The Environmental Quality Act (EQA) 1974 specifies two standards for
effluent discharge: Standard A for discharge upstream of any raw water
intake, and Standard B for discharge downstream of any raw water intake.
The current Third Schedule of the Environmental Quality Act 1974, under
the Environmental Quality (Sewage and Industrial Effluents) Regulations,
1979, regulations 8 (1), 8 (2) and 8 (3) has been revisited and the
Department of Environment has proposed 8th Schedule for the Act which
stipulate effluent discharge limits for parameters specific to domestic
wastewater. The effluent discharge limits in 8th Schedule are summarised
in Table 3.2. All sewage treatment plants design shall take into
consideration of the 8th Schedule and shall comply with the proposed
limits.
The need for these standards has been influenced by the fact that sewage
discharges contribute a significant amount of the biodegradable organic
matters, suspended solids and ammoniacal nitrogen to the nation's
waterways.
Value Value
Parameter
(g/capita.d) (mg/l)
Biochemical Oxygen Demand (BOD5) 56 250
Suspended Solids (SS) 68 300
Chemical Oxygen Demand (COD) 113 500
Total Nitrogen (TN) 11 50
Ammoniacal nitrogen (AMN) 7 30
Total Phosphorus (TP) 2 10
Oil and Grease (O&G) 11 50
Effluent Discharge to
Effluent Discharge to Rivers / Stream
Stagnant Water Bodies*
Parameter Standard A Standard B Standard A Standard B
Absolut
e Design Absolute Design Absolute Design Absolute Design
BOD5 20 10 50 20 20 10 50 20
SS 50 20 100 40 50 20 100 40
COD 120 60 200 100 120 60 200 100
AMN 10 5 20 10 5 2 5 2
Nitrate
Nitrogen 20 10 50 20 10 5 10 5
Total
Phosphorus N/A N/A N/A N/A 5 2 10 5
O&G 5 2 10 5 5 2 10 5
Notes:
NA = Not Applicable
All values in mg/L unless otherwise stated.
* Stagnant Water Bodies refer to enclosed water bodies such as lakes, ponds and slow
moving watercourses where dead zone occur
Sewage contains solid materials that can settle at the bottom and also give
impact on the benthic life. They can also appear in suspension solids form
that can increase turbidity and affect the light availability for aquatic life.
The amount of solids in sewage is usually measured as "total suspended
solids" or TSS. The desired solid removal in sewage treatment plants
should not exceed the absolute TSS discharge limit of 50mg/l and 100mg/l
for Standard A and Standard B, respectively.
Oil and grease that is detected in domestic sewage refers to the fraction of
organic matter that is soluble in organic solvents such as hexane.
The composition comprise primarily of wax, edible oils and fatty matter of
animal or vegetable origins. Oil and grease (mixture of tri, di and mono-
glycerides) in its liquid form results in floatable scum formation in
treatment systems whilst its solid form causes the clogging of systems.
4.1 Introduction
This section sets out the important factors and considerations associated
with the identification of proper sites to locate sewage treatment plants.
Typical workflows in the site for sewage treatment plants are illustrated in
Figures 4.1 and 4.2. It also addresses the selection of appropriate treatment
concepts and sufficient land area requirements for treatment plants in
relation to the effluent standards.
Suitable buffer distances should separate a sewage treatment plant from its
surrounding areas. Buffer Guidelines for the Siting and Zoning of
Industries as recommended by the Department of Environment (DOE)
should be referred to during the planning of suitable location for treatment
plants. The buffer distances recommended in the guidelines depend on the
category of industry being considered.
The buffer zone can be used for any purpose except permanent habitable
buildings. For example, the buffer zone may be used as a drainage reserve,
road or highway reserve, transmission reserve, utility reserve or public
park.
In the case where buffer area is to be regularly used by the residents such
as car park and playgrounds, proper precautions during design stage must
be taken to minimise nuisance such as odour, noise and unpleasant sight to
the surrounding environmental. Adequate and proper screening, odour
containment and treatment facilities must be provided at the sewage
treatment plant to address these issues.
Modular treatment plants that are designed with two (2) or more parallel
streams must be provided with pipeworks and valves to isolate each stream
of unit process during maintenance and major shut down without
interfering normal operation of the remaining stream.
a) Inlet Works/Pumps
b) Screen Facilities
c) Grit Chambers
d) Biological Treatment
e) Secondary Clarifiers
f) Sludge Facilities
The back-up capacity provided shall be such that when one unit process is
taken out of operation, the remaining units shall not be overloaded beyond
50% of their rated capacities.
The land area requirements and buffer allowance for temporary sewage
treatment plants may be reduced at the discretion of the Commission on a
case by case basis.
The recommended land area requirements for Class 1 and 2 plants (up to
5,000 PE) are given in Table 4.2 and Table 4.3 respectively. The net area
does not include the 30 m buffer zone surrounding the plant, but does
include appropriate set backs and access paths within the plant. The area
requirements given are sufficient to achieve an effluent conforming to
Standard A discharge requirements. It is important that allowance is made
for sufficient buffers in planning approvals, to avoid future complaints in
relation to the siting of the plant.
For Class 3 and 4 plants with mechanised systems, the recommended land
area requirements are given in Table 4.4 and 4.5. These systems are to be
used in normal developed and urbanised areas. The net area does not
include the 30 m buffer zone surrounding the plant, but does include
appropriate set backs and access paths within the plant. The area
requirements given are sufficient to achieve an effluent conforming to
Standard A discharge requirements. It is important that allowance is made
for sufficient buffers in planning approvals, to avoid future complaints in
relation to the siting of the plant.
Thus, the shape and elevations of the land allocated for the STP
development must be determined during planning stage so that the
configuration of the STP can be planned properly in order to allocate
adequate land for the purpose. This also enables estimates for additional
land required. It may also be required to cut or fill operations to level the
land.
The area requirements, as stipulated in Table 4.2, 4.3, 4.4, 4.5 and 4.6, must
be adhered to as strictly as possible. The required areas in these tables
include appropriate setbacks and access paths within the plant. However the
areas have not include any buffer zone surrounding each plant as indicated
in Section 4.2.1.
Note: * The required area only includes appropriate setbacks and access paths within the
plant but not the buffer zone surrounding each plant as indicated in Section 4.2.1.
Start
Determine catchment
served
Determine ultimate PE
Identified effluent
Requirement
Is development Is development
Y N
>2,000 PE? in urban area?
N Y
Use land area from Use land area from Use land area from
Table 4.2 Table 4.3,4 and 5 Table 4.6
( Class 1 plants) ( Class 2 to 4 plants) ( pond systems)
End
Start
Local Plan
Formulation
Consider multi-use of
buffer areas
End
Beautification
Property
Enclosed Plant STW Fence Boundary
Treatment Plant Site Buffer Zone 10m Min. Residential / Commercial Plot
5m Min.
Access And
Screening
Treatment Plant Site Buffer Zone 30m Min. Residential / High Rise
5m Min.
Access and
Screening
Property
Enclosed Plant STW Fence Boundary
5m Min.
Access And
Screening
Note : The buffer area can be used for roads, drains, utility reserve, agricultural or other similar
purposes.
30 m 30 m
STP LAND AREA
20 m REQUIREMENT 20 m
10 m 10 m
Volume 4
30m Surround For Residential and Commercial Note: Buffer areas can be used for roads, drains, utility reserve, public
Development parks, agricultural or similiar purposes other than permanent
Figure 4.4 Plan View of Buffer Zone Requirements
Industry Guidelines
Malaysian Sewerage
Requirements for Physical Design
(II) Installation
4.5.2 Vibration
The bare frame of rotational equipment or any equipment that may induce
vibration shall be provided with anti-vibration mount. Where rotational
equipment or equipment which may induce vibration is connected to
piping, then vibration isolator shall be provided.
4.5.3 Noise
Noise levels from machinery shall comply with the Factories and
Machinery (Noise Exposure) Regulations 1989 and Occupational Health
and Safety Act. Noise control measures and appropriate safety protection
for operators must be provided where necessary.
Noise level measurement shall be made with a sound level meter which
complies with BS EN 60651 and which is fitted with an ‘A’ weighting
network. The sound pressure level shall be measured in dB (A).
Noise level for all electronically operated electrical device such as soft
starters, variable speed drives and others shall be conform to IEC, EN.
Thus it shall fulfil all EMC Immunity requirements complying with
EN500082-1, EN50082-2, EN50082-3.
All designs and equipment shall be made and installed with safety in mind.
Nothing in this Design Guidelines shall remove the designer’s obligation
to incorporate equipment or designs that would increase the safety of the
plant.
The installation layout and equipment design shall not allow any item of
equipment to be so positioned that danger could arise to operating
personnel and equipment during normal operation and maintenance.
Particular attention shall be paid to the positioning of switch board, control
panel, cables, switch gears, lighting, small power, rotational equipment,
other electrical equipment and accessories.
All facilities shall be designed to comply with the Occupational Safety and
Health Act 514, 1994; properly designed treatment plants will enable the
operator to safely handle the treatment plant throughout its design life. The
plant shall also be designed to comply with other related Acts such as IEE,
Akta Bekalan Elektrik 1990 (Akta 448) and Peraturan –Peraturan Elektrik
1994.
Safety level for all electronically operated electrical device such as soft
starters, variable speed drive and others shall conform to IEC, EN, UL,
NFC and VDE. Thus it shall fulfill EN 50178, EN 60204- 1, EN 60950
(2000, 3rd edition), IEC 61800-5.
Where appropriate, IEE and Akta 448 (1990) and Peraturan Elektrik 1994
must be complied with in all electrical installation.
Wall 1 m or 1.5 W or
whichever greater
Equipment
Wall
1 m or 1.5 W or
whichever greater
W Equipment
1 m or 1.5 W
L or whichever
greater
(I) Motors
(II) Controllers
Sewage Treatment
Category Supply Requirements
Plant
A Single incomer with properly All Class 1, 2 and 3
design control overflow system STPs
during power failure (all electrical
control system shall be located
above design flood level)
B B1) Single incomer with diesel STP Class 4
generators for back-up supply.
B2) Single incomer with control
overflow system and genset
contribution fee.
(I) General
EWS + PC
NO. TYPE OF PLANT (monitoring) / SCADA
Data Logger
Network Pumping Station
1. < 100,000 PE ≥ 100,000 PE
(NPS)
SCADA is the acronym for Supervisory Control and Data Acquisition. The
term refers to a large-scale, distributed measurement (and control) system.
SCADA systems are used to monitor or/and to control chemical, physical
or transport processes. The following briefly describe the requirements of
SCADA while the detail requirements of SCADA are listed in Appendix
C.
The term SCADA usually refers to a central system that monitors and
controls a complete site. The bulk of the site control is actually performed
automatically by a Programmable Logic Controller (PLC). Host control
functions are almost always restricted to basic site over-ride or supervisory
level capability. Provision of SCADA system shall be in accordance with
Section 4.5.10.
− Information displayed
− Control features
b) Update times for screens to be not more than one second.
c) Nominate the alarm title to be used/displayed for each process-
generated fault input or fault generated internally by the PLC
program.
d) Nominate critical and non-critical alarms and the method of
differentiation. Examples would be: nominating an alarm on a
limit which has been reached as critical and an alarm on a limit
which is being approached as non-critical; differentiated by, for
example, red/amber lights or horn/bell).
e) At least eight variables to be displayed on a trend graph
simultaneously for ease of monitoring and comparison. This is a
measure of the level of software sophistication which should be
expected.
f) Supervisory system to log running hours for all plant items.
g) Nominate the reports to be generated for plant operation,
management and history. For example, reports to be daily, weekly
and monthly and the list of parameters to be reported on in each.
h) Alarm analysis, that is, frequency of occurrence, similar plant
faults, etc, to be provided as part of the supervising programs.
The EWS is used to monitor the status of the equipment operating inside
the treatment plants such as pumps and aeration equipment. It shall act as
the means to communicate information via Short Messaging Service
(SMS), e-mail or via other telecommunication mean to technical staff for
the fast recovery of the treatment system.
EWS system shall be able to transmit digital and analog values from the
remote module to the operator through their inputs (equipment) via SMS
and e-mail messages in text mode. The modules shall be able to interpret
SMS message from the operator to activate or deactivate long distance
machine (remote control).
4.5.13 Instrumentation
(I) General
(II) Instrumentation
(V) Conduits
a) All cabling within buildings or structures where cable trays are not
permitted, and in all external locations, shall be installed within
conduits.
b) Conduits installed externally shall be arranged to minimise their
length and exposure. PVC heavy duty conduit is permissible, where
it is protected from physical damage and UV. Otherwise, metal or
flexible conduits shall be used.
c) Use flexible steel reinforced conduit for connections, where
relative movement and removal for maintenance has to be
considered.
a) Single phase outlet rated at 10A adjacent to, or inside each control
cabinet and within 10 m of all equipment installations.
b) Three phase outlet rated at 50A within 20 m of every screen, sludge
scraper, clarifier rake, grit collector and conveyor.
c) Three (3) phase (with neutral) outlet rated at 50Amp shall be
provided at an interval of at least 20m.
d) These outlets shall be water proofed industrial type switch socket
outlets (SSO).
4.6.2 Steel
a) All areas within 5 km from the coast line or salt water bodies shall
be classified as marine environment. Sewerage facilities in marine
and corrosive environment e.g. where the atmosphere or soil
contains high levels of chloride, sulphates and corrosive chemical
elements or compounds shall be adequately designed to withstand
the corrosive actions of the chemicals prevalent in the environment.
Necessary protections shall be provided against all corrosive
actions of the environment.
b) Design requirement for facilities in marine and corrosive
environment shall include:
i) Two coats of sodium silicate shall be applied to all external
surfaces of concrete structures.
ii) Concrete shall be resistant to all chemical attacks and be
designed in accordance with BS 8110 Part 1: 1997.
c) Exposed metal shall be of corrosion resistant and of marine grade.
Proper smooth surface finishing shall be provided for the metal.
Unprotected metals acceptable for use are as follows:
i) SS316L
ii) Aluminium alloy
iii) Materials suitable for use in corrosive environment acceptable
by the Commission
d) All structural steelwork shall be thoroughly descaled to BS 7079
second quality and shall be painted with 2 coats of two pack epoxy
based red lead primer before leaving the manufacturer’s works. In
addition, all structural steelwork shall be provided with protective
paint for chloride, sulphate or the prevailing chemicals in the site
after installation.
e) Cathodic protection shall be provided for all load bearing steel
structures in marine environment for a minimum life of 50 years.
Only FRP products approved by the Commission shall be used and FRP
products shall not be used for access purposes.
FRP tanks, vessels and appurtenances for sewage treatment processes shall
be designed in accordance with BS 4994 and EN 13923. The thickness of
the structural section of the FRP tank wall shall not be less than 5 mm and
shall be at least of wall thickness as given in ASTM D 4097.
All other FRP products shall meet the requirements of ASTM C 582 for
FRP laminates.
4.6.4 Aluminium
5.1 Introduction
All new applications for sewage treatment plant approval shall follow the
design requirements as stipulated in this section. These requirements have
been formulated as a gradual change in sewage treatment methods for
Malaysia prior to enforcement of ultimate requirements as stipulated in
Sections 3 and 4 of this Guidelines.
Figure 5.2 gives an overview of the typical flow diagram and elements of a
sewage treatment plant. Figure 5.2 also shows how one facility is closely
related to another and thus has an impact upon the overall design.
The major indices are those of BOD5, Suspended Solids, COD, Oil &
Grease, Ammoniacal Nitrogen, Nitrate Nitrogen and Total Phosphorus.
Balancing
5 Tank M/O Section 5.6 Balances and equalises flow
Removes settleable
Primary Primary
6 M/O Section 5.7 solids/materials
Treatment Sedimentation
Reduces potential
Thickener detrimental effect on the
Bio Solids Stabilisation environment and converts
11 M/O Section 5.12 sludge to a form suitable for
Handling
Holding ultimate disposal
Dewatering
Sludge Disposal
Upon reaching the sewage treatment plant, sewage flows through the
primary screening facility which is the first stage of treatment. The screens
must be provided upstream of all inlet pump stations and shall be designed
to protect downstream processes and equipment. The purposes of primary
screens are:
Provision for inlet chamber before the primary screen channel is necessary
for proper operational and maintenance. The summarised requirements for
inlet chamber are as follows:
Unit
Requirements Notes
Process
Mandatory Single and
≤ 20 000 > 20 000 > 50 000 dual penstocks
Type are referring to
PE PE PE
members of
penstocks
Inlet Single Yes n/a n/a required. For
Chamber
more than 50
000 PE, the
Dual n/a Yes Yes main penstock
must be
Motorised n/a No Yes motorised.
n/a – Not applicable
CLEAR SPACING
MANUAL FINE SCREEN
OVERFLOW PIPE
DISCHARGETO DRAIN
PRIMARY
SCREEN
INLET CHAMBER
CHAMBER
450mm
1:2 IL
Design Criteria
Description Unit Manually Mechanically
Raked Raked #
Maximum clear spacing mm 25 25
Slope to the vertical
30o – 45o 15o – 45o
Maximum approach velocity at m/s 1.0 1.0
the feed channel
Notes:
* Designer shall ensure that with 50% of blockage at the face of screen, sufficient
freeboard is provided to prevent the approach channel from overflowing
# Washing and dewatering of screenings shall be provided.
In the event of the manual bypass screen being blocked, sewage must be
able to flow over the top of the screen without causing excessive backup
flooding or overflows.
Chambers design must have taken into consideration necessary health and
safety aspects. The chamber must also be hydraulically efficient to prevent
the settlement of solids in the chamber.
Shaftless screw conveyors and belt conveyors may be used where required.
The screw conveyor shall be equipped with easy to remove covers. The
frame and support of screw conveyor shall be of stainless steel grade 304
while the screw shall be of high tensile steel. The belt conveyors shall be of
heavy duty reinforced rubber belts on a protected mild steel frame.
Conveyors should normally be installed on a very slight grade to allow
drainage, with foul water returned to the inlet channel.
All screenings raked from mechanical screen shall be dropped into a skip.
100
80
Average
Maximum
Screenings, m 3/ 10 6m 3 of Sewage
60
40
20
0
0 1 2 3 4 5 6
Opening Between Bars, cm
RAMP
DOW N RAMP
DO W N
MECHANICAL COARSE
M.S GRATING COVER
SCREEN M.S GRATING COVER MANUAL COARSE
INCOMING SEW ER SCREEN
INCOMING SEW ER
CHAIN GUARD CHAIN GUARD
PENSTOCK PENSTOCK
A A
A
A R.C STAIRCASE TO DN
ENGR'S DETAIL
R.C STAIRCASE TO DN
ENGR'S DETAIL
MECHANICAL
COARSE SCREEN
PENSTOCK
PENSTOCK
SCREENINGS SCREENINGS
COLLECTION BIN COLLECTION BIN
HANDRAIL HANDRAIL
HANDRAIL HANDRAIL
> 5m
R.C PERFORATED SLAB
R.C PERFORATED SLAB
S.S PERFORATED
TROUGH
OPENINGS
OPENINGS
INCOMING SEW ER INCOMING SEW ER
CONC. APRON WP
LAID TO FALL
MECHANICAL COARSE SCREEN
RAMP
GRATING COVER DOWN
INCOMING SEWER
GRATING
COVER
INCOMING SEWER
CHAIN GUARD
PENSTOCK
CHAIN GUARD A
A R.C STAIRCASE TO A A PENSTOCK
ENGR'S DETAIL
R.C STAIRCASE TO
ENGR'S DETAIL
PLAN
(PE < 5000) PLAN
(PE > 5000)
PENSTOCK PENSTOCK
HANDRAIL
HANDRAIL
HANDRAIL HANDRAIL
< 5m
PERFORATED SLAB
< 5m
R.C STAIRCASE R.C STAIRCASE
TO ENGR'S DETAIL TO ENGR'S DETAIL
S.S PERFORATED
TROUGH
INCOMING SEWER
INCOMING SEWER
MIN 2000
QO (I/S)
INCOMING SEWER
Qi (I/S)
D2 HIGH LEVEL ALARM
CUT IN LEVEL
d
D1
Note :
Q1 = Incoming flowrate
d = Difference between stop & start level, Min 450 Max 900
IN
Qi COMI
(I/S NG
) SE
W ER
HIGH LEVEL ALARM
3
4 STANDBY CUT IN LEVEL
150
CUT IN LEVEL
D
CUT OUT LEVEL
D2 to D2
2
QO (I/S)
150
D1
D2
150 (min)
ALLOW ADDITIONAL DEPTH
FOR SOLID HEAVY OBJECTS
IN
Qi COM
(I/S I NG
) SE
WE
R
HIGH LEVEL ALARM
CUT IN LEVEL
D
CUTOUT
D2
D2 TO D2
D1 Q0 (I/S)
150
Note :
Q1 = Incoming flowrate
ALLOW ADDITIONAL DEPTH
FOR SOLID HEAVY OBJECTS
QO = Forcemain Discharge rate
D2 = Bellmouth Diameter
D = Difference between stop start level, Min 450 and Max 900
a) Either floats or ultrasonic level controller may be used for the start-
stop levels of pumps. Instrument with environmental friendly
features are recommended.
b) Ultrasonic level control is recommended due to its clog-free nature.
c) Non-mercury type floats are recommended.
d) Hollow tube electrodes are not acceptable.
e) Level controller shall be placed where they are not affected by the
turbulence of incoming flow and where they can be safely removed.
e) Valves
i) Gate valves are preferred with rising spindles operated by a tee
piece
ii) The uses of counterweights are recommended. Tapping (12 mm
BSP) shall be located upstream and downstream of check
valves
CONC. APRON
COLLECTION BIN
CLEAR SPACING
S.STEEL MANUAL OVERFLOW
FINE SCREEN CHAMBER INFLUENT PUMP
A PRIMARY SCREEN A
GRATING COVER
EXPLOSION PROOF
17 18 19 20 21 22 23 SPOT LIGHT
PUMP SUMP
CHECK VALVE
S.STEEL HANDRAIL FLEXIBLE COUPLING
STEPS
PENSTOCK GATE VALVE
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
DELIVERY PIPE
PLAN VIEW
LIFTING I-BEAM C/W
CARRIER
MECH. COARSE SCREEN
HANDRAIL
CHAIN GUARD
CHECK VALVE
CLEAR SPACING PENSTOCK
MANUAL FINE SCREEN FLEXIBLE COUPLING
GATE VALVE
OVERFLOW DELIVERY PIPE
PIPE DISCHARGE
TO DRAIN NON-EXPLOSION SPOT LIGHT
DELIVERY PIPE
GUIDERAIL
OVERFLOW
S.S PERFORATED
CHAMBER TROUGH PUMP SUMP LIFTING CHAIN
PRIMARY SCREEN
CHAMBER
CONC. SLAB
R.C WALL TO
IL ENGR'S DETAIL
STOP
SECTION A-A
OVERFLOW CHAMBER
PLAN VIEW
HANDRAIL
WET WELL
DRY WELL
PERFORATED SLAB
CAT LADDER
OPENINGS
ALARM
CHECK VALVE 2nd. STANDBY PUMP START
1st. STANDBY PUMP START
INCOMING SEWER 2nd. DUTY PUMP START
(FLOAT SWITCH) GATE VALVE 1st.. DUTY PUMP START
ALL PUMP STOP
STOP LOG
SUMP BWL
DEWATERING PUMP
DRY PIT PUMPS
SECTION VIEW
After the inlet pump station, further screening is required to reduce the
remaining floating matter and finer particles in the sewage that will disrupt
the treatment process downstream. The purposes of secondary screens are:
Plants of all sizes must be installed with secondary screens. The channel
shall be designed for Qpeak or pump flow whichever is greater. Approach
channel shall be design to ensure good contribution of velocity
A minimum of two screens are required for duty and standby. Facility for a
screened by-pass must be provided in the event of clogging. Where
mechanically cleaned screening devices are installed auxiliary manually
cleaned screen shall be provided.
Design Criteria
Description Unit Manually Mechanically
Raked Raked #
Maximum clear spacing mm 12 12
Slope to the vertical 30o – 45o 15o – 45o
Maximum approach velocity at m/s 1.0 1.0
the feed channel
Maximum flow through velocity m/s 1.0 1.0
at the screen face
Minimum freeboard mm 150* 150
Estimated volume of screenings m3 / 106 m3 See Figure 5.4
per volume of sewage
Screenings skip storage capacity day 7 7
Minimum channel width mm 500 500
Minimum channel depth mm 500 500
RC Staircase with riser detail 1 unit Anti-skid and Anti-skid and
non-corrosive non-corrosive
Notes:
* Designer shall ensure that with 50% of blockage at the face of screen, sufficient
freeboard is provided to prevent the approach channel from overflowing
# Washing and dewatering of screenings shall be provided.
This unit process is important to minimise problems associated with grit and
grease. Grit creates problems to pumps and also sludge digestion and
dewatering facilities. Grease creates problems at the clarifier and is carried
over in the final effluent.
Where manual systems are used, allow for safe and easy access to remove
grit to a storage bin.
If pump systems are used, the suction pipe shall be short and straight. Tees
and short radius bends shall be avoided, if at all possible. Flanges at
strategic locations shall be provided so that they can be dismantled to
remove any blockages.
Sand pit may be used for further dewatering of the grease removed before
ultimate disposal. The drainage from the sand pit shall be returned to the
inlet channel for further treatment.
Design Criteria
Description Unit
PE ≤ 5,000* > 5,000 > 5,000
Grease removal - Simple manual Manual interceptor Mechanical
Design Criteria
Description Unit
PE ≤ 5,000* >5.000PE >5,000PE
Grit removal - Manual Mechanical Mechanical
(tanker)
Chamber type - Horizontal Square, rotary or Aerated
flow (2 units vortex type simple
required for mechanised grit
duty and chamber
standby during
cleaning)
vortex also
acceptable
Minimum
detention time at minute 3 3 3
Qpeak
Maximum gravity
flow through m/s 0.20 0.20 0.20
velocity at Qpeak
Maximum
centrifugal flow m/s n/a <1.0 <1.0
through velocity
Head loss
- 35% of depth -
(at parshall flume)
Aeration l/s/meter
- - 10.0
requirement length of tank
Chamber
dimension:
Manufacturer’s Manufacturer’
Depth: Width - 1:2
Specification Specification
Length: Width
2:1
5.7.1 Purposes
5.8.1 Introduction
For reasons of long term whole life economics, ease of operation and
maintenance, consistent effluent standards and standardisation, the
following types of biological treatment processes are recommended for use
in Malaysia.
Mass balance calculation must be computed and submitted for all biological
treatment system and other unit processes proposed for the STP.
For the design of conventional activated sludge system, the aeration tank
shall be preceded with primary sedimentation system. An appropriate
amount of the bacteria culture, known as activated sludge must be recycled
to the upstream of the reactor while the remaining excess sludge must be
removed at secondary sedimentation system.
All conventional activated sludge system used at STPs for Class 3, Class 4
and at where requested by the Commission must be designed with anoxic
zone to achieve a total nitrogen removal in order to comply with the
requirements in Section 3 of this Guidelines, as well as to minimise
potential rising sludge at secondary sedimentation system. The anoxic zone
must be mixed without inducing dissolve oxygen. Sludge treatment and
Cu is underflow concentration
QRAS / QINFLOW 0.75-1.0
Mixed liquor suspended solids 4 – 6 of Qavg
recirculation for denitrification
purpose
RAS pump rating hrs/day 24
Organic loading kg BOD5/kg 0.25-0.5
MLSS
Volumetric loading kg BOD5/m3.d 0.3-0.6
Minimum mixing requirement W/ m3 20
⎡ VT × MLSS ⎤
† ⎢
⎢⎣ θ sludge ⎥⎦
[
⎥ − Q avg × SSeff ]
WAS =
Cu
Where:
vT = volume of reactor (m3)
MLSS = mixed liquor suspended solids (kg/m3)
θsludge = sludge age (days)
Qavg = average flow (m3/day)
SSeff = effluent suspended solids (kg/m3)
Cu = underflow concentration (kg/m3)
Refer Table D1 and D2 for aeration equipment duty / standby and also to
relevant clause of MS 1228 for more details.
The advantage of having long hydraulic retention times is that it allows the
plant to operate effectively over widely varying flow and waste loadings.
Secondary clarifiers must be designed to the variations in hydraulic
loadings and high MLSS concentrations associated with this process.
For Oxidation ditches, the minimum velocity within the channel shall be
sufficient to keep the activated sludge in suspension. The minimum velocity
within the channel shall not be less than 0.3 m/s. The tank configuration
and aeration and mixing devices shall promote unidirectional channel flow,
so that the energy used for aeration is sufficient to provide mixing in a
system with a relatively long hydraulic retention time.
Cu is underflow
concentration
RAS pump rating hours/day 24
Recirculation ratio, QRAS/QINFLOW 0.5 - 1.0
MLSS recycle ratio 4 – 6 times of Qavg
3
Volumetric loading Kg BOD5/m .d 0.1 - 0.4
Minimum mixing requirement W/m3 20
Tank dimension
Water depth m 3–5
Length:Width ratio 3:1
Max width of joined tank m <60
Notes:
#
Sludge Age = total solids in aeration tank
⎡ VT × MLSS ⎤
†
⎢
⎢⎣ θ sludge ⎥⎦
[
⎥ − Q avg × SSeff ]
excess sludge wasting/day + solids in effluen WAS =
Cu
Where:
vT = volume of reactor (m3)
MLSS = mixed liquor suspended solids (kg/m3)
θsludge = sludge age (days)
Qavg = average flow (m3/day)
SSeff = effluent suspended solids (kg/m3)
Cu = underflow concentration (kg/m3)
Refer Table D1 and D2 for aeration equipment duty / standby and also to
relevant clause of MS 1228 for more details.
Raw
Sewage
Inlet
Sewage
Pump Station
Return Sludge
Pump Station
Liquor
Chemical
Dosing
OPTIONAL
F low
M echanical Rotor Flow F inal Clarifier M easurem ent
Distribution E ffluent
S creens, G rit R em oval To River
R aw
S ewage
Inlet O xidation D itch
S ewage
P um p Station
Return S ludge
P um p S tation
Chem ical
Dosing
S ludge D rying B ed
O PTIO N AL
Units must be covered for aesthetics and odour control, and only approved
media types are accepted.
Refer also to Table D.3 for duty standby requirements and relevant clause of
MS 1228 for more details.
Rotating Biological
Contactor
Chemical
Dosing
SludgeDrying Bed
OPTIONAL
The media provides a large surface area to develop biological slime growth
which is also known as zoogleal film. The film contains living organisms
that break down organic material in the sewage.
Many variations of the trickling filters have been constructed, however the
recommended designs are given in Table 5.15.
Secondary screens (< 6mm) and flow balancing tanks to equalise the flow
must be provided before trickling filters.
Biofilter
Fine
Pump Flow
Screen
Station Distribution
Screens, Grit Removal
Final Clarifier
Filter Effluent
Raw To River
Sewage
Inlet
Sewage
Pump Station
Liquor
Chemical
Dosing
OPTIONAL
Refer also to Table D.4 for duty standby requirements and relevant clause
MS 1228 for more details.
1. Fill
2. React (Aeration)
3. Settle
4. Decant
5. Idle
In the decant stage, there shall be sufficient time to allow for mixed liquor
suspended solids (MLSS) to settle before effluent decanting begins.
Decanting time is normally much shorter than fill time. Consequently, the
effluent flow rate will also be much higher than influent flow rate. Hence
the design of the decanting weir must be capable to handle high over-flow
rate without scouring the settled sludge. Therefore, sufficient clear water
depth between the minimum water level after decant and the top of the
settled sludge blanket must be allowed for to minimise sludge carry over.
Hence the depth of water decanted must be restricted to prevent scouring of
solids.
All SBR plants must be designed to cater for peak flows. A minimum of a
two (2) tanks system is required. Proven control system in the form of
Programmable Logic Controller (PLC) with complete instruction, and
operational and training manuals must be submitted together with the
design. All SBR systems must be preceded with complete preliminary
works. Allowance shall be provided to completely empty a tank for
maintenance purposes without interrupting the operating sequence of the
plant.
Table 5.16 highlights the key design requirements for an SBR plant.
a) Biological treatment
b) Physical treatment
c) Chemical treatment
To get To get
Phosphate Nitrate back
Back
The designer shall take all necessary consideration in the design in relation
to the specific requirements of the receiving water in determining the actual
nutrient removal requirement on the case by case basis.
5.9.1 Purpose
(I) General
(II) Weirs
Multiple hoppers are not accepted. This is due to the settling characteristics
of the particles in the flow. Larger and heavier particles settle faster than
smaller and lighter particles, creating difference in the distribution of
sedimentation in different hoppers. This will present operational difficulties
because sludge removal from the hoppers is unequal. To avoid the non-
uniform withdrawal of sludge, each hopper in the multiple hopper
configuration needs a separate pipe and pump or valve on each outlet.
5.10 Disinfection
Disinfection refers to the selective destruction of disease causing organisms
in sewage effluent.
Continuous disinfection is required for those areas where the discharge from
the sewage works will cause detrimental effect onto the receiving water
course, such as bathing beaches, lakes, etc.
The Commission reserves the right to determine the need for the provision
of a continuous disinfection facility
All new STPs must have provision for disinfection infrastructure such as
contact tank and other necessary structures. The provision of the
disinfection facilities and equipment shall be in accordance to Table 5.19
below. The disinfection shall be carried out in continuous or intermittent
mode.
"A"
"A"
FLOW
PDC
TOP VIEW
(Cables removed for Clarity)
FRONT ACCESS
STILING PLATES
LEVEL PROBE
FLOW
Figure 5.17 – Profile schematic of lamp modules relative to inlet and outlet
structure
Flow
Effluent Inffluent
Channel Channel
Flow
A A
Service
Area
PLAN VIEW
Influent
Channel
Influent
Channel
CALIBRATION COLUMN
RELIEF VALVE
BACK PRESSURE
CHEMICAL CONTROL
FEED PUMP
STORAGE TANK
Operating Temperature 18 – 40 oC
Note:
*Enclosed system shall be permitted under special circumstances
Flow measuring devices are necessary for monitoring of plant operation and
process control continuously. The purposes of flow devices are:
Flow devices are mandatory for all sewage treatment plants, regardless of
size.
Design Criteria
Description
PE ≤ 5,000 PE > 5,000
Location of flow Inlet or Outlet Inlet and Outlet
meter
Type of Flow Closed Conduit or Open Closed Conduit or Open
Measurement Channel Channel
Type of flow V- notch (Outlet Only) V-notch (Outlet Only)
meter Rectangular Weir (Outlet Only) Rectangular (Outlet Only)
Flumes Flumes
Electromagnetic Electromagnetic
Ultrasonic Ultrasonic
Method of Automated or manual Automated devices linked to
measurement measurement of Staff gauge to data logging with integrator
measure height of crest with and transmitted to chart
calibration curves / tables recorder
(minimum 7 days chart time)
Measurement Continuous or Intermittent Continuous
times
5.12.1 Introduction
All sludge need to be treated for safe disposal back to the environment. The
minimum requirement for sludge treatment is to achieve stabilize sludge
with a 20% dry solid content.
For large scale development whereby the full sludge generation will only be
achieved over a certain time period, proper sizing/modulation of sludge
treatment facilities need to be provided in order to achieve the immediate
needs for sludge treatment.
Figure 5.20 shows the typical sludge treatment and disposal strategy which
consists of three main stages.
Two types of digestion facilities are available for digestion after the
thickening: aerobic and anaerobic digestion.
After the dewatering process, an on-site storage for 30 days of the treated
bio-solid shall be provided. The storage structure shall be covered with
roof and provided with partly opened walls to allow for proper ventilation.
Finally, the bio-solid is either composted and/or applied directly for land
reclamation (i.e., for ex-mining land), land application (i.e., for certain types
of agriculture land and forest land/reforestation) or used as top soil cover at
land fill site. The ultimate disposal of bio-solid is the responsibility of the
plant operator.
The Service Licensee will advise on current capacity in its existing sludge
treatment facilities, suitable sludge stabilisation, dewatering and final
disposal of the sludge shall be provided.
If the Service Licensee has the capacity to receive sludge generated from the
development, then the project proponent has the option to negotiate with the
Service Licensee to dispose off the sludge at the existing facility. In this
case, a sludge storage tank with a minimum capacity to hold for 30 days
with the sludge thickened to 1% solids is acceptable. Otherwise, the sludge
shall be stabilised, dewatered and prepared in a suitable form for disposal.
Note:
Based on the above assumptions, the quantity of waste sludge requiring treatment and disposal can be
estimated. Refer also to design guides related to each of the above individual processes.
Speed of
Backwash
% Dry Polymer Sludge
Type of Thickening water
Solids System feed
system
pump
Picket Fence Gravity
1.5
Thickener
n/a n/a n/a
Dissolved Air
2
Flotation
Belt Thickener 4 Yes with
Drum Thickener 4 appropriate
Centrifuge polymer
< 300 rpm Yes
turndown
4
ratio
Note:
a. Mechanical thickener shall be designed for 8hrs/day and 5d/week operation.
b. For belt, drum and centrifuge thickener, three polymer injection points shall be
provided
c. Potable water to be provided for polymer mixing system.
Design Criteria
Description Unit Aerobic Anaerobic
Digestion Digestion
Number of Tank, Minimum No. 2 2
Min. Solids Retention Time Days 10 18
Organic Loading Rate KgVS/m3.d 1.6 – 4.8 0.8 – 1.6
Typical Feed Solids % 2 2-6
Concentration
Type of Mixing Aerators Gas Injection
Diffusers Mechanical
Stirring
Mechanical
Pumping
Min. Water Depth, minimum m 3 7.5
Tank Shape Cylindrical Cylindrical
Rectangular Egg-Shaped
Tank Dimension, maximum m 25 diameter 25 diameter
25 length
Dissolved Oxygen mg/L 1-2 -
Design Considerations
Descriptions Unit
PE ≤ 2,000 PE > 2,000
Sludge Stabilisation
Type of stabilisation Simple anaerobic or Ambient anaerobic
process aerobic digestion digestion with good mixing
facility
Hydraulic retention time Days 30 30
(HRT) minimum
Dewatering
Type of device Belt press Belt press
Centrifuge Centrifuge
Filter press Filter press
Drying bed Drying bed *
Minimum dry solids % 20 20
(content after
dewatering)
Operating period of 5 days/week # 5 days/week #
mechanical thickening 8 hours/day 8 hours/day
and dewatering facility 250 days/year 250 days/year
Handling capacity of 4 weeks cycle on 4 weeks cycle on
drying bed 450 mm thick feed † 450 mm thick feed †
Covered storage area 1 month holding 1 month holding
Notes:
a. Access ramp of at least 1.5m wide shall be provided at all sludge drying beds
* Drying beds must be designed to support mechanical / machine lift for more
than 10,000 PE.
#
Design to be based on one full-time working shift only.
†
In computing the area requirements of a sludge drying bed, the designer may
assume a maximum 450 mm depth of sludge feed to the bed. The actual quantity
of sludge from the upstream unit processes needs to be computed before sizing
the bed. Each bed may be designed to handle a maximum of 7 days continuous
feed. The next feed to the same bed shall only be after a minimum of 21 days
from the last feed. A one-third (1/3) reduction in actual land area requirement
will be acceptable if fully covered drying beds are provided. Reduction shall only
apply to the total surface area of drying bed. No reduction is allowed for the
drying bed thickness.
Structures and materials used for the drying bed covers shall be designed to an
acceptable structural strength and of acceptable quality to withstand local weather
conditions.
Untreated Sludge
Screening
Primary Thickening
Preliminary
Treatment
and Digestion
Chemical Conditioning
Conditioning
and
Dewatering
Storage at works
To inlet of STW
Utilisation
Composting or
and
on-site Liquor Treatment Plant
Disposal
Transportation from works
Land Application
Land Reclamation Landfill Site
Forestry/Agriculture
5.13.1 Introduction
(V) Reoxygenation
a) This method is used to increase the dissolved oxygen (DO) levels in
the effluent
b) The different types of reoxygenation systems are cascade,
reoxygenation and mechanical reoxygenation
c) Cascade reoxygenation is achieved using on the hydraulic design of
structures, such as, weir overflows, flumes, spillways, etc.
d) Mechanical reoxygenation is achieved using mechanical equipment
such as surface aerators, jet diffusers or diffused air (coarse, fine
bubble, etc.)
e) Design of structures or mechanical equipment is based on the
amount of DO required for the effluent.
6.1 Introduction
Water shall be supplied to each site from standpipes and taps, to provide
for sanitary cleansing of plant areas, personal hygiene, safety, fire fighting,
process use and for equipment cooling and/or sealing. Water shall be
connected to potable supply that provides a minimum pressure of 20 m
head across the site. A ring main system shall be provided for all treatment
plants larger than 5000 PE.
The water supply system shall be sized to meet the following cases:
All water supplies and its installation (piping, tanks, air conditioning
drainpipes, gutters and etc.) must be totally isolated from all potential
contact of electrical system by means of total enclosure or suitably located
the electrical system above flood level.
Where required, wash water shall be equipped with booster pump and
where possible, obtain from reclaimed water.
Table 6.1 tabulates the minimum number and location of stand pipe
required in a sewage treatment plant. Typical drawing of stand pipe are
shown in Figure 6.1
800
76 648 76
76
8
64
100
80
76
STAND PIPE
All treatment plants shall have a minimum of one sanitary set consisting of
a toilet and wash basin. Washing facilities, toilets and showers shall be
provided for operators at all Class 3 and Class 4 plants with PE greater
Guard house with water and power supply shall also be provided for plant
more than 20,000 PE.
Covered Porch
Manager’s /
2
Engineer’s Office
1 4
Reception Area General Office
3 Supervisor's Office
5
Meeting /
Briefing Room
12
14 Control Room
Workshop
8 Sample Reception
& Preparation
7 Male
Toilet
7 Female 9 9
Toilet Clean Locker Room Dirty Locker Room
Prayer Recreation Area
6
Room 10
Pantry
9
13 11 Toilet / Shower
General Store Eating Area
Note : The numbers on the layout correspond to the numbers in Table B.1.
The layout is only for indicative purposes only and can be changed ( i.e. floor space and other arrangement)
to suit the plant’s needs and requirements.
Minimum internal floor area of mess facilities are 400 meter2. Approval
from the Commission shall be sought if smaller floor area is to be
provided. Typical arrangement of mess facilities is shown in Figure 6.2
4000
FALL FALL
The on-site road shall be able to provide safe and convenient access for
trucks or other machinery equipment used for maintenance purposes. The
Corner of junction for perimeter internal road for tankers or trucks access
shall have a minimum inside radius of 6 meter. Inside radius for perimeter
road not intended for tankers or trucks access shall be not less than 4
meter.
Cul-de-sac at the end of roads shall be provided with turning area reserve
of not less than 9 meter.
Vehicular access shall be provided to all unit processes that require daily
operation and maintenance.
6.5 Drainage
The area of the treatment plant shall be adequately drained and this shall
be arranged to prevent surface water run-off from entering the process
units.
External drainage facilities must be provided for treatment plant along the
slope area. Cut off drainage at the entrance must also be provided.
Treatment plant platform level shall be designed above flood level. If the
treatment plant is located in a flood prone area, flap gate shall be provided
to avoid back flow from the river/ main drain. The plant hydraulic must be
designed properly to ensure the discharge head is adequate to open the flap
valve at any circumstances.
The effluent discharge shall be directed to the main drain or river to avoid
discharging effluent into a drain within the residential area. Discharge to a
retention pond is not allowed unless prior approval has been granted.
The fence shall be 2.4 meter solid wall with three strands of 0.6 meter high
barbed wire. Typical details of the fence are given in Figure 6.5, 6.6, 6.7
and 6.8.
X X X
X X X X X X X X X X
900
150
225
6"x6" CONCRETE 63 x 63 x 6
COLUMN @ 3m THK. ANGLE
INTERNAL 225
600
SQ.
3200 3200
2T12
230
800
800
2T12 2T12 A
2T12
R 6 -2 0 0 R 6-20 0
600
230 x 230m m R C C O LU M N
1 0 0 x 1 2 5 m m C O P IN G B E A M 1 0 0 x 1 2 5 m m C O P IN G B E A M A T 3 .2 m IN T E R V A L S 4T12
A
D U L U X G L O S S F IN IS H L IN K S R 6 -1 5 0
400
(P A N T O N E 3 0 0 C ) C C
O R E Q U IV A L E N T
2200
2200
D U L U X G L O S S F IN IS H 1 1 5 m m T H K B R IC K W A L L
400
(P A N T O N E 3 5 4 C ) P L A S T E R E D O N B O T H S ID E
O R E Q U IV A L E N T
D U L U X T U N G S T E N (1 0 4 1 2 )
O R E Q U IV A L E N T SURFACE TO BE ROUGHENED
300
2T12
2T12 2T12 B 2T12 F IN IS H E D G R D . L E V E L F IN IS H E D G R D . L E V E L
R 6 -1 5 0 R 6-15 0
MIN. 900
MIN. 900
B
300
2T12
230
230
1 2 5 x 1 2 5 T A N A P IL E W H E R E
115 x 300m m G RO UND BEAM R E Q U IR E D T O B E D IR E C T E D B Y P .P 50m m LEAN CO NCRETE 4 T 1 2 B /W
750
T Y P IC A L R C C O L U M N D E T A IL
F R O N T V IE W O F B R IC K W A L L F E N C IN G
3 S T R A N D S P .V .C . C O A T E D B A R B E D 150 230
W IR E A T T A C H E D T O P O S T B Y 75 125
H E A V Y S P L IT P IN S
800
230
300
6 3 x 6 3 x 6 m m M .S . A N G L E
W IT H 3 S T R A N D S O F B A R B E D W IR E
45°
1 0 0 x 1 2 5 m m C O P IN G B E A M
100
S E C T IO N A -A S E C T IO N B -B S E C T IO N C -C
300
1 1 5 m m T H IC K C E M E N T / S A N D
B R IC K W A L L W IT H 2 0 P L A S T E R IN G
B O T H S ID E S NOTES :
2200
1. A LL C O N C R E TE U S E D SH A LL BE G R AD E C 25.
2 . M IN IM U M C O V E R T O R E IN F O R C E M E N T S H A L L B E 2 5 m m .
3 . A L L B R IC K S U S E D S H A L L B E F IR S T Q U A L IT Y C E M E N T / S A N D B R IC K S .
4 . B R IC K W O R K S H A L L B E R E IN F O R C E D W IT H E X P A N D E D M E T A L O R "E X M E T " A T E V E R Y F O U R T H
150 x 300m m G R O U N D BEAM
C O U R S E C O M M E N C IN G S T W O C O U R S E S A B O V E G R O U N D B E A M L E V E L .
MIN. 900
300
5 . B R IC K W O R K W A L L S S H A L L B E A N C H O R E D T O C O N C R E T E F A C E S U S IN G G A L V A N IS E D F IS H T A IL
7 5 0 x 7 5 0 x 2 3 0 m m F O O T IN G A N C H O R S T O L A P IN W IT H T H E B R IC K R E IN F O R C E M E N T A T E V E R Y F O U R T H C O U R S E
1 2 5 x 1 2 5 T A N A P IL E W H E R E C O M M E N C IN G T W O C O U R S E S A B O V E G R O U N D B E A M L E V E L .
R E Q U IR E D T O B E D IR E C T E D B Y P .P
230
6 . M O R T A R F O R B R IC K W O R K S H A L L B E S E T IN 1 :1 :5 C E M E N T -L IM E -S A N D M O R T A R .
750
7 . P L A S T E R IN G A N D R E N D E R IN G T O S U R F A C E O F B R IC K W A L L S H A L L B E F IN IS H E D T O A M IN IM U M
T Y P IC A L C R O S S S E C T IO N O F B R IC K W A L L F E N C IN G T H IC K N E R S O F 2 0 m m W IT H 1 :3 C E M E N T -S A N D N O R T A R .
P A IN T IN G
1 .) A L L E X P O S E D W A L L S H A L L B E P A IN T E D W IT H O N E U N D E R C O A T O F A P P R O V E D R E S IS T IN G P R IM E R S E A L E R A N D T W O
A P P R O V E D W E A T H E R R E S IS T A N T E M U L S IO N P A IN T .
3200 3200
800
230
800
4T12
LINKS R6-150
230 x 230mm
RC COLUMN
AT 3m INTERVALS
2200
2200
PRE-CAST CONCRETE
W ALL 75mm THICK
SURFACE TO BE ROUGHENED
230
HEAVY SPLIT PINS
800
SECTION A-A
300
PAINTING
1.) ALL EXPOSED WALL SHALL BE PAINTED W ITH ONE UNDERCOAT OF APPROVED RESISTING
PRIMER SEALER AND TWO COATS OF APPROVED WEATHER RESISTANT EMULSION PAINT.
2.) TWO BANDS OF IWK'S COLOUR WITH OVERALL HEIGHTS
OF 400mm SHALL BE PAINTED ON EXTERIOR FACE OF THE WALL.
3.) COLOUR STANDARDS
TYPICAL CROSS SECTION OF PRE-CAST FENCING A.) INTERIOR/EXTERIOR WALL - DULUX TUNGSTEN (10412) OR EQUIVALENT
B.) BANDS - BLUE - DULUX GLOSS FINISH
(PANTONE 300C) OR EQUIVALENT
- GREEN - DULUX GLOSS FINISH
(PANTONE 354C) OR EQUIVALENT
B
3 STRANDS P.V.C. COATED BARBED
WIRE ATTACHED TO POST BY
HEAVY SPLIT PINS
63 x 63 x 6mm M.S. ANGLE
WITH 3 STRANDS OF BARBED WIRE
390mmx190mmx190mm BOND BEAM BLOCK
1 NO HORIZONTAL REINFORCEMENT
ANTI-CLIMB
SECTION B-B
NOTE :-
1 NO. HORIZONTOL REINFORCEMENT 1. FOUNDATION AS PER THE DESIGN OF THE ENGINEER-IN-CHARGE
390mmx190mm190mm BOND BEAM BLOCK 2. ALL MASONRY UNITS (CONCRETE BLOCKS) USED MUST BE UNDER
SIRIM CERTIFICATION SCHEME
3. CONCRETE MIX USED FOR GROUTING TO BE GRADE 20
4. CEMENT MORTAR USED FOR JOINTS TO BE 1:3 MIX
PAINTING
390mmx190mmx114mm FULL BLOCK 1.) ALL EXPOSED WALL SHALL BE PAINTED WITH ONE UNDERCOAT
OF APPROVED RESISTING PRIMER SEALER AND TWO COATS OF
APPROVED WEATHER RESISTANT EMULSION PAINT.
2.) TWO BANDS OF IWK'S COLOUR WITH OVERALL HEIGHTS
OF 400mm SHALL BE PAINTED ON EXTERIOR FACE OF THE WALL.
1 NO HORIZONTAL REINFORCEMENT 3.) COLOUR STANDARDS
390mmx190mmx190mm BOND BEAM BLOCK A.) INTERIOR/EXTERIOR WALL - DULUX TUNGSTEN (10412)
B.) BANDS - BLUE - DULUX GLOSS FINISH OR EQUIVALENT
(PANTONE 300C) OR EQUIVALENT
- GREEN - DULUX GLOSS FINISH
(PANTONE 354C) OR EQUIVALENT
Premix or Paved area shall be provided at this zone for all class 1 treatment
plants with loading equal or less than 1,000PE or where necessary.
All Class 4 Treatment plants that exceed 20,000 PE and have a pump
station within the premises shall be provided with an active store and
workshop.
6.9 Spares
Typical spare parts requirements are provided in Table 6.2. Spare parts
shall be obtained from the original manufacturer of the equipment and
shall be packed and protected for storage to BS1133 requirement.
Minimum
Class of Population
Numbers Location
STP Equivalent
of Unit
105
290
105
6000
250 STANDARD GALVANISED
STREET LAMP POST
FRONT VIEW
SIDE VIEW
LAMP POST
All electrical equipment shall be fitted with auto restart facilities for quick
re-operation in the event of failure of power facilities.
Safe access and walkways shall be provided at all process units and
equipment (valves, penstocks, aeration tanks, etc.) that require service and
maintenance. Safety handrails shall also be installed at walkways and other
working areas with a fall greater than 2 m. Typical details of hand rail are
shown in Figure 6.10
All chemical storage facilities shall be provided with a safety shower and
eyewash as well as appropriate warning signs. Liquid chemical storage
facilities shall be bund. Access to the area shall be restricted using lockable
doors/gates.
Provision for fire detection, alarm and fire fighting equipment shall be
complying with the latest requirements in the Uniform Building Bylaws,
the Institute of Electrical Engineers (IEE) guidelines and other statutory
requirements.
Stair case and ladder exceeding 1.2m shall be provided with handrail
All plants located adjacent to earth slopes shall be provided with proper
slope protection structures. The slope protection design must be certified
by Qualified Professional Engineer.
6.14 Doors
All external doors shall be of weather proof and suitable for out-door
installation.
Power supply shall be provided to each plant from the approved source.
Drawings submitted for approval shall indicate the locations of electrical
power tapping point and schematic layout plan. Approval for power supply
tapping should be obtained from relevant authority for permanent power
supply before submitting inspection form. All related document, such as
electrical bills, transfer of ownership: to be submitted before final
inspection. Requirement of power shall be finalised prior to obtaining
design approval
All plants shall be provided with toilet. The toilet shall consist of water
tap, water closet, shower and wash basin. The area for toilet shall comply
with Uniform Building By Laws. Toilet to be located beside the control
panel building. Toilets can also be located in the mess or office building.
Safe lifting weight in unrestricted area is 16 kg. For heavier objects and/or
very tight locations, provision of crane or access for truck mounted crane
to be made.
All portable motorised hoist shall be of 230 V operating voltage and fixed
electrical hoist shall be of 415 V operating voltage.
All fixed 3 axis type gantry shall come with additional safety features such
as travel stop limit switch, hoist over run limit switch, slow & fast speed
mode and emergency stop (for all type of hoist).
All fixed type outdoor lifting facility futures shall comprise of hoist
parking bay with shade. All fixed type lifting facility shall come with
working platform and excess ladder.
Typical drawings of lifting davits and A-frame lifting facilities are shown
in Figure 6.11 and Figure 6.12.
6.19 Ventilation
6.21 Aesthetic
Unpaved area within the STP reserve shall be turfed with close turfing.
The type of grass must be “cow grass”. For slope area, turf must be pegged
to avoid grass wash away during water run-off.
Roof for control panel shall be of flat roof and shall be installed with water
proving material on the final layer. The slope of flat roof shall be 1: 20 and
gutter shall be provided.
However, for the aesthetic purpose Pitch type roof may be provided. The
slope shall be 30 degree from horizontal. Suitable material for roof such as
roof tile is recommended.
6.24 Painting
Painting shall include all plant and machinery inside buildings, including
pipework, grating, handrailing, internal walls below ground level and all
metal work including machinery.
The labels shall be stencilled on the piping in a contrasting colour with the
colour coded bands, if any, located at appropriate and strategic points.
Colour codes selected for general equipment, building and others items in
a sewage treatment plants shall be adhered to colour standards as detailed
in Table 6.5. The types of paint and surface preparation used shall be as
recommended by the paint manufacturer.
Equivalent
Item Colour
Colour Guide
General Equipment including motors (unless Dark Blue Dulux Regal Blue
come with the original manufacturer 0013
approved colour code) Par Mandarin Blue
0013
Penstocks/Valves/Manhole Covers Black Par Bituminous
Black
Machinery Yellow Dulux Lemon 2024
Guards/Railings/Runways/Overhead Par Golden Yellow
Cranes/Lifting Davit
Switchboards Light Grey Dulux Pewter 695
Par Willow Grey
00A05
Fencing poles/Gates Green Dulux A365-13449
Par Green 3666
Building and Walls – Exterior Grey Dulux BS 00A05-
(Weathersheild) 10235
Building and Walls - Interior White
Fencewall – Interior and Exterior Grey Dulux BS 00A05-
10235
Floors - Concrete Interior Green Leigh Green 3666
Building Stripes Green Dulux A910-13448
Par Green 3666
Blue Dulux A910-11482
Par Blue 2686
Indah Water Logo (where applicable) Indah Water Dulux A365-13449
Green Par Green 1006
Indah Water Dulux A365-11483
Blue Par Blue 1007
Notes:
The above painting requirements are not applicable to stainless steel, aluminium,
galvanised metal surfaces except where necessary to comply with statutory health and
safety requirement.
550
1
21/4
1100
150-250
100 33
FLAT BASE
TUBULAR STANDARDS
550
1
21/4
1100
12
100
150-250
100 36
TRIANGULAR BASE
TYPICAL RUN OF HANDRAIL AS
VIEWED FROM WALKWAY SIDE
ROUND BASE
TUBULAR STANDARDS
550
50
0
90
75
50
25
20 25 20
25
30° FL FL
6
450
30
120
6 FILLET WELDED
10
OD=98
SAFE WORKING
LOAD TO BE PLAT THICKNESS 10
INDICATED
1775
250
260
DETAIL `A'
OD = 118
DETAIL `A'
1200 2160
203x203x46Kg/m UB 1800
180
203x133x25Kg/m UB
315
203x133x
25Kg/m UB
2340
2340
1500
TO PROVIDE WITH ROLLER OR FIX TO THE CONCRETE TO PROVIDE WITH ROLLER OR FIX TO THE CONCRETE
FLOOR (TO SYSTEM SUPPLIER DESIGN) FLOOR (TO SYSTEM SUPPLIER DESIGN)
7.1.1 Definition
Temporary treatment plants refer to sewage treatment plants that are built
to operate on a temporary basis. The sewage will eventually be diverted to
a centralised sewerage system. After then, the temporary treatment plant
will be decommissioned.
Category 1
For temporary treatment of sewage during the upgrading of an existing
sewerage treatment facility
Category 2
For temporary treatment of sewage during initial stage of a new housing
development where it is not feasible to construct a plant of ultimate
capacity during initial stage or it is located within the catchment of a
centralised sewerage system.
During the upgrading of an existing treatment plant, the sewage flows into
that plant shall be directed to a temporary treatment plant for treatment
before discharge. The treatment process of the temporary plant shall be
designed and calculated based on: the duration of the project, total existing
flow and the compliance requirements. The temporary treatment shall be
monitored at regular interval. Approval from the Commission and DOE
must be obtained prior any direct discharge of the untreated sewage into
the receiving watercourse. The temporary treatment plant shall be located
within the compound of the existing site. The temporary treatment plant
shall not be built on other site area unless approval is granted by the
Commission
Filter systems may use refurbished filter material that meet the relevant
standards. However, other equipment used within the works shall be new.
Second-hand equipment is strictly prohibited.
Temporary plant shall remain as private plant. The owner must appoint a
licensed operator to operate and maintain the plant.
7.2.1 Introduction
Owners must resolve these issues at an early stage of the planning process.
The Commission should be contacted early to establish if an alternative
option is feasible.
a) Access
b) Ventilation
c) Electrical requirements for lighting system
d) Noise control
e) Process type
f) Inlet works
g) Pre-treatment
h) Confined space safety
i) Odour Control
j) Discharge systems
k) Flood mitigation measures
l) Operation and maintenance
m) General safety and health
n) Sludge handling
o) Sanitary and plumbing facilities
p) Fire Fighting Equipment
The specific guidelines and requirements for the criteria specified in 7.2.1
are listed below.
(I) Access
II) Ventilation
The type of treatment process must be limited to systems that are easy to
operate and maintain for reasons of:
a) lower sludge yield and more stable sludge characteristics
(VII) Pre-treatment
a) Operators must:
i) attend a recognised confined spaces training course,
ii) obtain training certificates, and
iii) be certified competent to operate in such an environment.
b) Confined space areas within the plant site must be clearly identified
before handover for operation.
c) Confined space areas must be demarcated and warning notices
placed.
d) Confined space procedures must be established and followed by
operatives.
e) The following must be provided:
i) rescue sets of breathing apparatus
ii) gas detection equipment, preferably electronic, and serviced
regularly
Most basement plants will lie below the level of the running drain levels.
Therefore, it is essential to:
7.3.1 Definition
Fully enclosed treatment plant shall comply with the following criteria:
When approved, fully enclosed treatment plants must comply with the
general requirements set out in Section 3, 4 and 5 of this Guidelines and
also specific requirements in this Section 7.3 for the following:
The potential for odour generation, its impact and treatment, shall be
considered in all aspects of design.
Particular problems can be found at: Inlet works, primary tanks, secondary
treatment, sites for transfer, storage and treatment of raw sludges and
leakages.
Screens, open channels and aeration tanks, where violent and turbulent
actions are encountered, may release aerosol. The design of the treatment
plant shall take into consideration any unit processes that are likely to emit
aerosol and mitigating measures shall be undertaken to counter aerosol
release to the atmosphere.
The design of a fully enclosed treatment plant shall address safety, health
and operability aspects. The guidelines given for treatment plants located
within buildings in Section 7.2 shall be followed.
The purposes of these covers are to contain odour emission at source and
to reduce visual impact.
The design requirements for treatment unit processes are outlined below.
Ventilation systems are required to supply fresh air for workers to work in
a more comfortable environment and to minimise health and safety
concerns.
All mechanical equipment that are likely to generate noise such as blowers,
compressor and pumps, shall be acoustically isolated to ensure the noise
generated are contained and reduced to below the levels stipulated by the
regulators.
If a building structure is used to house the enclosed treatment plant, then the
design of this building must comply with the requirements stipulated by the
relevant Building By-Laws.
7.4.1 Definition
Covered and buried treatment plants refer to treatment plants with covers
that are placed below ground or not more than 1.2 m above ground level.
Covers are provided to reduce the odour, noise and visual impact.
7.4.2 General
Covered and buried treatment plants have inherent hazard and restriction in
operability in their actual operation and maintenance. The requirements in
the following sections serve to highlight the minimum improvements that
must be made to these plants in addition to those set out in Section 3, 4, 5
and 6 of the Guidelines.
The design of these tanks must allow for adequate openings so that the
operator can carry out routine operation and maintenance works in a safe,
efficient and effective manner. These requirements apply to all unit
processes that are covered or buried from the inlet works to the effluent
chamber. Staggered square openings of roughly 600mm x 600mm
employed in the past for plants of this nature would not be acceptable.
These openings, as a minimum, must be opened top around the periphery of
the tank.
The designer must take into account the confined space and other related
safety issues for entry into such a tank. Provision of proper access into each
individual tank is mandatory. Where the depth exceeds 2.5 m, steps with
intermediate landings must be included. Other requirements, such as
adequate ventilation prior to tank entry, must be considered and provided in
the design.
Piping for buried plant shall be exposed and accessible for ease of
maintenance. PVC pipes are not allowed.
The aeration system (diffuser) must be retrievable from top opening without
emptying the tank.
(VI) Lighting
Hand railing provisions must be made to prevent falling into open spaces.
These hand rails must be provided on the perimeter of the open tanks and
further enhanced with kick plates.
Labeling of each treatment unit is to be provided, from the inlet works to the
secondary clarifiers, to avoid confusion with the similar geometry and sizes
used for most treatment units.
(IX) Ventilation
Adequate ventilation must be made available to allow for the safe routine
operation and scheduled maintenance of the treatment plant. During design,
this ventilation aspect must be considered. The type of ventilation, portable
or permanent, must also be determined during design stage.
The designer must account for the buoyancy effects in the design of buried
or covered tanks. This effect is of concern during high groundwater
conditions and emptying of the tank content during desludging works.
Furthermore, the designer must ensure that the design of these tanks
accounts for the hydrostatic force exerted on the floor from the outside does
not exceed the compressive strength of these covered or buried tanks. This
is to prevent any breakthrough of the floor and subsequent failure of the
tank.
The designer must ensure that the design of these tank at worse case
scenario where the tank is fully emptied. This is to prevent any
breakthrough of the floor and subsequent failure of the tank.
(XII) Covers
Covers if employed for odour, visual and noise impacts shall be subjected to
the following requirements:
a) Lifting may be unaided if the covers are hinged and weigh less 16
kg.
b) Assisted lifting is required if the covers weigh equal to or above 16
kg.
c) The cover shall comply with BSEN124 loading requirements.
d) If the cover is exposed to the environment,
i) Plastic or fibreglass cover if used, must be manufactured with
UV inhibitor and will not warp or deform due to weathering
effect.
ii) Metal covers if used, must have appropriate corrosion resistant
coating in accordance to Section 4 of this Guidelines.
iii) Where chipping might occurs at the edge of the cover,
stainless steel reinforcement frame on all sides of a plastic or
FRP cover shall be provided.
(XIII) Fencing
Adequate fencing must be provided for all plants. Adequate security shall
be provided against unauthorised access.
The owner must provide all septic tanks as part of the owner’s infrastructure
works.
For single developments over 30 units in total and with an average housing
density of less than 25 persons per hectare, a sewer reticulation and a
communal treatment plant is preferred.
iii) Developers shall ensure that home owners enter into an agreement
with the supplier of the systems or licensed contractors, to carry out
operation and maintenance of the system as per design requirements.
iv) Tanks shall be desludged by the Service Licensee as per terms of the
agreement signed between the Services Licensee and the
Commission.
v) The Commission and DOE may impose stringent conditions, if they
believe that such measures are required to ensure that the sewage
from the development will not result in an adverse impact on the
environment.
7.6.1 Introduction
This section describes the types of incidents, which are outside the control
of the operator that may cause a sewage treatment plant to fail its effluent
consent. Generally, the more sophisticated the treatment process, the more a
process is at risk of failure from one of these incidents. It would be
unreasonable to expect the operator of the treatment plants to perform
within the effluent quality standards following such incidents. However,
the operator must always use his best endeavours to rectify the situation as
soon as practicable following such an incident.
The following potential incidents are treated as special cases when meeting
absolute compliance with Standard A or Standard B.
However, the crude sewage will pass through the plant receiving only
rudimentary treatment and will probably fail to comply with Standard A
and Standard B.
On new works, all treatment plants will be fitted with auto-restart facilities
for immediate resumption of operation when power is reconnected.
(II) Lightning
During this period the plant may fail to comply with the relevant standards.
During periods of very heavy rain, areas of the local sewer network may
suffer such ingress of storm water that surcharge of the sewer system will
result, causing abnormally large flows to arrive at the sewage treatment
plant inlet.
Under these conditions, the treatment plant would receive much higher
flows than that designed for and would suffer severe hydraulic overloading.
The effect would be a rapid wash through of sewage and solids causing the
works to fail to meet standards.
All new plants must be equipped with standby units having an automatic
change over system in the event of failure.
Existing plants may be out of action for several days while repairs are
carried out to failed equipment. To help alleviate this problem, the operator
needs to carry critical spare parts to help speed the repair process.
Such discharges to the sewer system would almost always result in the
sewage treatment plant failing to comply until the effects of the discharge
have passed through the system.
A blockage in the main sewer network system often causes the sewage to
build up behind the blockage and turn septic.
The sudden release of this large volume of septic sewage by the clearance
of the blockage, may cause temporary overloading of the treatment plant
and lead to a reduction in effluent quality beyond the absolute standard for a
short period of time.
(IX) Defect
a) Minor Defect
Non-critical, do not immediately or unduly affect the performance
of the plant but nevertheless, require attention to rectify faults within
reasonable time frame.
b) Major Defect
Critical or serious and require immediate action to be taken in
rectifying faults, impair plant performance, unit processes, or system
components.
8.1 Definition
A package sewage treatment plant is a form of treatment plant both for fixed
film and suspended growth processes. It shall consist of a prefabricated
biological treatment system and be limited to the development of the sewage
treatment system between the ranges of 150 to 5,000 populations equivalent
(PE).
The package sewage treatment plant is only applicable to Class 1 and Class 2
STP as defined in Section 4 of this Guidelines. The prefabricated biological
treatment system shall have been given approval by the Commission prior to
the application.
The land area requirements for package sewage treatment plants shall
comply with those recommended for Class 1 and Class 2 Plants in Section 2
of this Guidelines.
The net area does not include the 10 m buffer zone surrounding each plant,
but does include the 5m set backs and access paths within the plant.
The physical properties of the tanks for package plants shall meet the
material requirements for STP structures as stipulated in Section 4 of this
MSIG. The prefabricated tanks shall come as complete tanks, thus no
welding, jointing, fabrication/moulding of tanks’ components is allowed at
site. The route for delivery of tanks shall be planned properly, so as not to
cause any damage to road facilities and harm to road users.
The following table provides the recommended number of tanks for each
unit process against the P.E size. The effective volume consideration is also
incorporated in the table.
Aeration Tank 2 4
Anoxic Tank 2 4
Clarifier 2 4
Sludge 2 4
Holding Tank
Note: Low water level (LWL) is the minimum submergence level of the pumps to
protect it from damage. It is dependent on the type of the pumps, thus the
low water level shall be set according to the pump’s manufacturers
requirement Top Water Level (TWL) is the normal operating water level
with adequate freeboard provided.
8.5 Appurtenances
8.5.1.1 General
All inlet and outlet pipes of the units of prefabricated biological treatment
system must be pre-fitted at the factory. On-site drilling for holes is strictly
prohibited. All jointing and pipe holes connection shall be factory
fabricated/moulded.
a) The air distribution pipe used shall be rigid and can withstand
temperatures up to 150 ºC and pressures of 25% more than the design
pressure of the blower.
b) The air pipe from the blower to the process unit shall be above
ground.
The effluent discharge piping system that passes through / by-passes the
disinfection treatment facility shall be designed so as not to cause any
nuisance.
The pumps installed in the package system shall meet the requirements as
stated in Table 8.3 below:
Sludge Transfer
Name of Pump Transfer Pump RAS/WAS Pump
Pump
Sludge Holding
Application Area Balancing Tank Clarifier
Tank
Minimum Throughlet 50 mm 50 mm 50 mm
Automatic control
Automatic control Manual control
Control by timer and
by float switch by timer
solenoid valve
1 duty for each
Number of Pump 1 duty, 1 standby 1 duty for each tank
tank
Mechanical PE < 1000 : Air lift
Mechanical
Submersible
Type of Pump Submersible
Pump or Self PE ≥ 1000 :
Pump Mechanical Pump
Priming Pump
Necessities Mandatory
All pumps shall be completely installed with duct foot, guide
Accessories
rail and lifting chain made of Grade 304 stainless steel.
Note: 1. Non-submersible pumps shall be provided with parking bay with
shade.
8.5.3 Diffuser
Note: 1. The collar of the manhole shall be raised with a minimum height of
100mm above ground level.
2. The cover shall be equipped with a frame support and hinge, and
attached to the manhole opening.
3. Each manhole cover must be properly labeled / marked for ease of
identification of the unit process of the system.
4. NA – not applicable
The tank anchor system (straps, cables, turnbuckles, etc.) shall have strength
of at least 1.5 times the maximum uplift force of an empty tank without
backfill in place. All wire straps, cables and turnbuckles must be made of
Grade 304 stainless steel.
8.5.7 Landscaping
The odour treatment shall be incorporated into the package sewage treatment
plant and shall follow the requirements stipulated in Section 7.4.
Appendix A Tables
Table A.1 Contaminants of Concern in Sewage Treatment
Table A.2 Typical Composition of Untreated Domestic Sewage
Table A.3 Major Biological Treatment Processes Used for Sewage Treatment
Table A.4 Interim National River Water Quality Standards for Malaysia
Table A.5 River Clarification
Table A.6 The Occupational Safety and Health Act 514, 1994 – Brief Summary
Table A.7 Permissible limits for potentially toxic elements in soil
Table A.8 Options for disposal of Sludge and reuse of biosolids
Table A.4 Interim National River Water Quality Standards for Malaysia
Class Uses
I ♦ Conservation of natural environment
♦ Water supply I - practically no treatment necessary
(except by disinfection or boiling only)
♦ Fishery I - very sensitive aquatic species
IIA ♦ Water supply II - conventional treatment required
♦ Fishery II - sensitive aquatic species
IIB Recreational use with body contact
III ♦ Water supply III - extensive treatment required
♦ Fishery II - common, of economic value, and tolerant
species
♦ Livestock drinking
IV Irrigation
V None of the above
Note: This data is adapted from the Water Quality Criteria and Standards
for Malaysia, Final Report July 1986, Department of Environment.
Table A.6 The Occupational Safety and Health Act 514, 1994 -
Brief Summary of Contents
The Occupational Safety and Health Act (OSHA) was enacted by the
Parliament in 1994. In general, it is an enabling law in that the duties,
responsibilities, penalties and guidelines are to be followed by each
specific industry. The following table provides an outline of OSHA.
Copper 250
Nickel 150
Cadmium 12
Lead 1000
Mercury 4
Chromium 1000
Arsenic 150
Option for
No Type of sludge/ by-product Source/Treatment Process Disposal or
Utilization
1 Liquid primary sludge and - Imhoff tanks D
septage - Primary and secondary
clarifiers
- Septic Tanks
2 Dewatered primary sludge - Drying beds C, D, I, S
and dewatered septage - Mechanical dewatering
equipment
3 Pond sludge - Oxidation ponds D, F, R
- Aerated lagoons
- Waste stabilization
ponds
4 Dewatered pond sludge - Drying beds C, D, F, I, R, S
- Mechanical dewatering
5 Digested sludge - Digesters D, F, R
- Sludge lagoons
- Anaerobic ponds
6 Dewatered digested sludge - Drying beds C, D, F, I, R, S
- Mechanical dewatering
7 Lime stabilised sludge - Lime stabilisation C, D, F, R, S
8 Compost product - Composting A, C, D, F, L, R, S
9 Thermally dried sludge - Thermal drying A, C, D, F, L, R, S,
(pellets/granules) SP
10 Incinerator ash - Incineration C, D, S, SP
NOTES:
A = Use in agriculture
C = Disposal to controlled dumpsites
D = Disposal to dedicated sludge disposal sites
F = Use in forestry/non-food crops
I = Incinerate
L = Use for landscaping at public amenity areas
S = Disposal to sanitary landfill sites
R = Use in rehabilitation of degraded
SP = Recycled into special product, e.g. building material
Malaysian Standards
♦ MS 29
Specification for aggregates from natural sources for concrete
♦ MS 144
Specification for cold reduced mild steel wire for reinforcement of concrete
♦ MS 145
Specification for steel fabric for the reinforcement of concrete
♦ MS 146
Specification for hot rolled steel bars for reinforcement of concrete
♦ MS 416
Code of practice for the use of structural steel in building
♦ MS 523
Specification for concrete including ready mixed concrete
Part 1 Guide to specifying concrete
Part 2 Methods for specifying concrete mixes
Part 3 Procedures to be used in producing and transporting concrete
Part 4 Procedures to be used in sampling, testing and assessing compliance of
concrete
♦ MS 739
Specification for hot-dip galvanised coatings on threaded fasteners
♦ MS 740
Specification for hot-dip galvanised coatings on iron and steel articles
♦ MS 822
Specification for sawn-timber foundation piles
♦ MS 1037
Specification for sulphate resisting portland cement
♦ MS 1195
Code of practice for structural use of concrete
Part 1 Design and construction
Part 2 Special circumstances
Part 3 Design charts for singly reinforced, doubly reinforced beams and
rectangular columns
♦ MS 1227
Specification for portland pulverised fuel ash cement
♦ MS 1228: 1991
Code of Practice for Design and Installation of Sewerage Systems
♦ MS 1241
Specification for fibreglass water tanks - effective capacity of less than 2000 litres
♦ MS 1292
Specification for rubber seals – water stops for sealing joints in concrete
♦ MS 1387
Specification for ground granulated blast furnace slag for use with portland cement
♦ MS 1390
Specification for glass-reinforced polyester panels and panel water tanks
British Standards
♦ BS 476
Fire tests on building materials and structures
♦ BS 1161
Specification for aluminium alloy sections for structural purposes
♦ BS 1615
Specifications for anodic oxidation coatings on aluminium.
♦ BS 3396
Woven glass fibre fabrics for plastics reinforcement
♦ BS 3532
Method of specifying unsaturated polyester resin systems
♦ BS 3749
Specification for E glass fibre woven roving fabrics for the reinforcement of polyester
and epoxy resin systems
♦ BS 4248
Specification for supersulfated cement
♦ BS 4848
Hot rolled structural steel sections
Part 2 Specification for hot finished hollow sections
♦ BS 4921
Specification for sherardized coatings on iron and steel
♦ BS 5493
Code of practice for protective coating of iron and steel structures against corrosion
♦ BS 7079
Preparation of steel substrates before application of paints and related products
♦ BS 7123
Specification for metal arc welding of steel and concrete reinforcement
♦ BS 8118
Structural use of aluminium
Part 1 Code of practice for design
Part 2 Specification for materials, workmanship and protection
European Standard
♦ EN 10088
Stainless Steel
Part 1 List of Stainless Steels
Part 3 Technical delivery conditions for semi-finished products, bars, rods,
wire, sections and bright products of corrosion resisting steels for general
purposes
♦ EN 10029
Specification for tolerances on dimensions, shape and mass for hot rolled steel plates 3
mm thick or above
♦ EN ISO 9445
Continuously cold-rolled stainless steel narrow strip, wide strip, plate/sheet and cut
lengths. Tolerances on dimensions and form
♦ EN 754
Aluminium and aluminium alloys. Cold drawn rod/bar and tube.
Part 1 Technical conditions for inspection and delivery
Part 2 Mechanical properties
Part 7 Seamless tubes, tolerances on dimensions and form
Part 8 Porthole tubes, tolerances on dimensions and form
♦ EN 755
Aluminium and aluminium alloys. Extruded rod/bar, tube and profiles.
Part 1 Technical conditions for inspection and delivery
Part 2 Mechanical properties
Part 3 Round bars, tolerances on dimensions and form
Part 4 Square bars, tolerances on dimensions and form
Part 5 Rectangular bars, tolerances on dimensions and form
Part 6 Hexagonal bars, tolerances on dimensions and form
Part 7 Seamless tubes, tolerances on dimensions and form
Part 8 Porthole tubes, tolerances on dimensions and form
♦ EN 10296
Welded circular steel tube for mechanical and general engineering purposes. Technical
delivery conditions.
Part 1 Non-alloy and alloy steel tubes.
Part 2 Stainless steel
♦ EN 10297
Seamless circular steel tubes for mechanical and general engineering purposes.
Technical delivery conditions.
Part 1 Non-alloy and alloy steel tubes.
♦ EN 10305
Steel tubes for precision applications. Technical delivery conditions.
Part 1 Seamless cold drawn tubes
Part 2 Welded cold drawn tubes
Part 3 Welded cold sized tubes
Part 4 Seamless cold drawn tubes for hydraulic and pneumatic power systems
Part 5 Welded and cold sized square and rectangular
Part 6 Welded cold drawn tubes for hydraulic and pneumatic power systems
♦ EN 14118
Reinforcements. Specification for textile glass mats. (chopped strand and continuous
filament mats).
Part 1 Designation
Part 2 Methods of tests and general requirements
Part 3 Specific requirements
♦ EN 10083
Specification for steels for quenching and tempering
Part 3 Technical delivery conditions for alloy steels
ASTM Standard
♦ ASTM D4097
Standard specification for contact-moulded glass-fibre-reinforced thermo set resin
corrosion-resistant tanks.
♦ ASTM E84
Standard test method for surface burning characteristics of building materials.
♦ ASTM C582
Standard specification for contact-moulded reinforced thermosetting Plastic (RTP)
laminates for corrosion-resistant equipment.
AS Standard
♦ AS 3750.2
Paints for steel structures – Ultra high-build paint
♦ AS/NZS 3750.12
Paints for steel structures – Alkyd/micaceous iron oxide
♦ AS/NZS 2312
Guide to the protection of structural steel against atmospheric corrosion by the use of
protective coatings.
Data acquisition begins at the Programming Logic Controller, PLC level and includes meter
readings and equipment statuses that are communicated to the SCADA as required. Data is then
compiled and formatted in such a way that a control room operator using the HMI can make
appropriate supervisory decisions that may be required to over-ride normal PLC controls. (A
SCADA system includes all the pieces, HMI, controllers, I/O devices, networks, software, etc.).
SCADA systems typically implement a distributed database which contains data elements called
tag points. A tag point represents a single input or output value monitored or controlled by the
system. Tag points can be either "hard" or "soft". A hard point is representative of an actual
input or output connected to the system, while a soft point represents the result of logic and
math operations applied to other hard and soft points. The point values are normally stored as
value-timestamp combinations; the value and the timestamp when the value was recorded or
calculated. A series of value-timestamp combinations is the history of that point.
In short, interfacing on of SCADA with PLC offers efficient monitoring and control of process
in a large installation site and with large number of distributed equipment at a site. SCADA
provide alarm notification, historical and on-line trending plots of control parameters for
effective process monitoring and control. SCADA system can also be implemented with PPM
schedule maintenance notification and reminder.
The SCADA that are installed at the remote sites can be linked to a Master Station via
communication system (Radio frequency or WIFI or other on-line communication channels).
The data from an equipment is collected via on-line data acquisition or, unless otherwise
allowed, on batch mode via data logging devices.
The SCADA software can also activate alarm messaging to inform the operator station for
exceptional event (critical alarm) reporting. Remote Access Server (RAS) features can provide
for either via Internet or other dial-up method (fixed line and/or wireless modem).
All the proposed SCADA software shall be scalable and flexible enough to allow the integration
of any additional SCADA controller in future expansion. It shall provide with many industrial
standard protocols to allow the user to integrate easily.
C-2 Purpose
This document will provide basic technical requirement for implementation of integrated
SCADA/HMI in sewerage system.
The SCADA system shall be Window based client/server system and make use of the following
technologies: -
• Dynamic data caching, alarming, human machine interface, history collection, and
reporting functions;
• Web viewable, providing secure, advanced user interface HMI capabilities based on an
open industry standard html file format and Web Browser access;
• Extensive list of communication interfaces;
• Secure Internet Browser based on-line documentation and support.
C-4 Architecture
The SCADA architecture shall be flexible and scalable to allow expansion requirements. The
basic architecture shall incorporate all but not limited to the followings:
• HMI Web – A web-based architecture that allows HMI and application data which
uses HTML display format to provide casual access of process graphic displays.
Windows, HTML and the Internet so as to minimize operator training due to familiarity of
operating environment.
Software system displays shall include but not limited to the followings: -
• Menu/navigation displays
• Alarm summary
• Event summary
• Trends
• Operating groups
• System status displays
• Configuration displays
• Loop Tuning displays
• Diagnostic and maintenance displays
• Hierarchy displays;
• Summary displays;
• Multiple log in with independent displays.
Optional Live Video integration shall provide remote viewing and viewing control features.
Security software feature shall provide restricted access, no access and full access (plant
management).
Network access shall permit authorized operator stations on a network to share a preconfigured
number of connections to the system. This allows a number of users on a network to access
production data on off-line basis.
C-7 Database
The SCADA software shall but not limited to the following real-time database:
• Analog configuration parameters
• Digital configuration parameters
• Accumulator configuration parameters
• User defined configuration parameters
Each point in the database has a number of associated configurable parameters, all of which can
be referenced relative to a single 'tag name'.
SCADA shall maintain the real time database that requires frequent high-speed access as
memory resident information and other less frequently accessed data as disk resident data.
Memory resident data is logged to data storage device every specified time frame defined by the
administrator to minimize the loss of data in the event of loss of power.
The standard Alarm Summary display shall allow operators to focus on the problem at hand by
supporting filters. Alarms may be filtered by:
Colors for the various priority levels of alarms can be configured by the user for display
purposes in the Alarm Summary and on custom graphics. The recommended color codes are
provided in Appendix 1. The software shall support configuration of alarm priority colors and
display on all process graphic displays to enables operators immediately determine critically of
the alarm.
The alarm shall annunciate in the status zone blinks with the color of the highest priority for
unacknowledged alarm. The alarms configuration shall consist but not limited to the followings:
• SPV Hi
• SPV Lo
• Transmitter Hi
• Transmitter Lo
• Trip
• Time out
With each of the configured alarms assigns a priority ranging from "Attention" - acknowledge
of non-critical alarm that required maintenance attention, "Responsive" - action required with
predefined period, "Urgent" - action required immediately.
The Alarm/Event summary shall list but not limited to the followings:
• Alarms
• Alarm Acknowledgments
• Return to normal
• Operator Control Actions
• Operator Login & Security Level Changes
C-9 Historian
Historical trend shall provide wide range of sampling frequencies in both data-point and average
formats. The history trend intervals are shall be able to but not limited to the following displays:
• second data-point of pre-defined scale
• minute data-point of pre-defined scale
• hour data-point of pre-defined scale
• minute-average of pre-defined scale
• hour-average of pre-defined scale
• day-average of pre-defined scale
• Month-average of pre-defined scale
• Alarm/Event Log reports - selectable time frame, filterable events and alarms to enable
traceability of alarm.
• Exportable Excel / Access format - able to save selected data/report format to Microsoft
Excel/Access format.
• Statistical data analysis format - generates reports of selectable statistical functions such
as Max/Min and standard deviation.
• Point Attribute Log - displaying specific attributes selectable from a list.
C-12 Security
The SCADA software shall provide configurable security levels, control levels and area
assignments. These may be configured for each individual operator or alternatively for each
operator station. The security levels shall be able to configure the following security levels:
Operator sign-on/sign-off shall be logged. Any actions initiated by an operator are logged in the
Event database with the operator identifier. In addition any control actions to a given point is
only allowed if the control level configured in the operator profile exceeds the level assigned to
the point.
Logon password shall not be less than 6 alphanumeric characters and shall be encrypted.
Operators may change own passwords; however, new password shall not be the same as the last
10 passwords used in the previous 3 months. Three unsuccessful attempts of logon shall lock the
operator out for a lock-out period. Once logged on, an operator can log off at any time or will be
automatically signed off after a defined period of inactivity.
Area assignments limit operator access to graphics, alarms and point data to assigned areas,
providing effective plant partitioning. Individual operator profiles, including security levels,
control levels and area assignments, are activated when operators sign on to the system. In
addition, area profiles can be created enabling plant areas to be enabled or disabled for control,
between certain time and date criteria.
C-13 Scripting
The software shall have the VB or VBA scripting language enable to allow user to create script
that will run when a display is active or scripts can also be attached to server objects like point
parameters, alarm events, report completion and other events.
C-14 Interfaces
SCADA software provides Data Acquisition and Control facilities to communicate with a wide
range of controllers and Remote Terminal Units (RTUs). The controllers connection type shall
comply with the following communication protocol:
The DVM shall base on open system hardware that digitizes video from standard video cameras
and transports the video to SCADA software clients anywhere on the network for real-time
viewing.
IMM enables the automated creation, assignment, tracking and closing of maintenance work
orders. If required, work orders can also be manually raised. This is all managed from either
your IMM SQL server database with full access available through the open Web-based interface
of IMM.
• Batch Report
• Downtime analysis
• Schedule maintenance
• Statistical Process & Quality Control (SPQC)
• Event archiving
• Alarm messaging (SMS or pager)
Batch Reporting –integrated reporting of batches process data, to be compiled and archived by
the SCADA software. The batch reports either as a CSV file or Microsoft Excel, if available.
Downtime Analysis –to detect, record and code any equipment breakdowns or process delays to
provide plant downtime analysis. A list of all current downtime events is maintained as well as
the history of previous downtime events, with each assigned a category and a reason code.
Downtime reports may be printed periodically or on-demand, showing downtime duration
sorted by categories and reasons.
Statistical Process & Quality Control (SPQC) - generates statistical report of average (of
specified time period) of the real-time data collected by the system.
Event Archiving –archiving events logged data by the system that based on sampling frequency
and storage capacity.
Alarm Messaging – reports the alarm messages sent designated supervisors. The report shall
incorporate summary of alarm messages by alarm type and supervisors.
Components Specifications
Basic Client/Server Workstation
Processor Processor (Latest version)
Memory 1 GB
Hard Disk Size 200 GB
Display Resolution 1024 x 768, 65K colors
Operating System (Minimum) Microsoft Windows (Latest edition)
Network Protocols TCP/IP; or other as specified in the above
documents
The SCADA software server shall perform according to the specification provided in Table C.2.
SP Low Level Light Blue (Non-Blinking) Alarm event of lower level than set
point
Transmitter Hi Yellow (Blinking) Alarm event due to transmitter high
(<=4mA) value.
Qty
AO
DO
AI
DI
Equipment)
Instrumentation Panel
Instrumentation Panel - Local Indicator 1 1
Instrumentation Panel - Remote Indicator 1 1
Instrumentation Panel - Battery Low Indicator 1 1
TNB Power (kWh meter) Data Record 1 1
PLC System
PLC (battery Low) Measure 1 1 Alarm Low (Fault Report)
Battery Charger Indicator 1 1 Alarm (Fault Report)
Penstock
Penstock Panel: Manual Switch Indicator 1 1
Penstock Panel: Auto Switch Indicator 1 1
IP open close RTU via RS-485 Serial Link
Penstock Position Actuator (%) 1
control Alarm - High torque
Penstock - Fully Open Indicator 1 1
Penstock - Fully Close Indicator 1 1
Penstock - To Open / To Close Remote Control 1 1
Penstock - UPS Low Indicator 1 1
RSP Pumps
Pump - Run Indicator 1 1 Record number of Start / stop
Pump - Trip Indicator 1 1 Alarm (Fault Report)
Pump - Off (MCCB) Indicator 1 1 Record non-operation hours
Remote Start /
Pump - To Start / Stop 1 1 Software control / PLC
Stop
Reset of Hour-
Pump - Run-hour record 0 Software counter running hours
Run meter
Pump - Ampere Reading 1 1 Record when operation
Pump - Voltage Reading 1 1 Record when operation
Pump - Soft Starter Amp/Volt Parameters
1 1 RJ45 / RS485
Comm. Setting / Review
Qty
AO
DO
AI
DI
Equipment)
Float level for RSP Pumps
Level
US Level 1 1
measurement
Float Level - L0 On/Off Indicator 1 1 Cut-off operation
Float Level - L1 On/Off Indicator 1 1 Control Start / Stop operation by diff. level
Float Level - L2 On/Off Indicator 1 1 Control Start / Stop operation by diff. level
Float Level - L3 On/Off Indicator 1 1 Control Start / Stop operation by diff. level
Float Level - L4 On/Off Indicator 1 1 Control Start / Stop operation by diff. level
Float Level - L0 Fault Indicator 1 1 For fault identification (Alarm Fault report)
Float Level - L1 Fault Indicator 1 1 For fault identification (Alarm Fault report)
Float Level - L2 Fault Indicator 1 1 For fault identification (Alarm Fault report)
Float Level - L3 Fault Indicator 1 1 For fault identification (Alarm Fault report)
Float Level - L4 Fault Indicator 1 1 For fault identification (Alarm Fault report)
Qty
AO
DO
AI
DI
Equipment)
Screenings Conveyor
Screen c/v - Run Indicator 1 1 Record number of Start / stop
Screen c/v - Trip Indicator 1 1 Alarm (Fault Report)
Screen c/v - Auto Mode Indicator 1 1
Screen c/v - Manual Mode Indicator 1 1
Screen c/v - To Start / Stop Remote Control 1 1
Reset of Hour- Software counter / Interlock with screen
Screen c/v - Run-hour record 0
Run meter operation with delay off.
Control Point
Monitoring Point (For Each SCADA Control / Monitoring
Qty
AO
DO
AI
DI
Equipment)
(For Each Equipment)
Auxiliary
LV System
Main LV Board Main Breaker : ON Indicator 1 1 Status
Main LV Board Main Breaker :
Indicator 1 1 Alarm (Fault Report)
TRIP (Earth Fault)
Main LV Board Main Breaker :
Indicator 1 1 Alarm (Fault Report)
TRIP (Over Current)
Main LV Board Main Breaker :
Reading 1 1 Record
Ampere
Main LV Board Main Breaker :
Reading 1 1 Record
Voltage
Room Temperature Monitoring /
Reading 1 1
Alarm
Bus Couple : ON Indicator 1 1
Bus Couple : OFF Indicator 1 1
kWHr Meter: Reading 1 1 Record
HT System
HT Income Panel VCB : ON Indicator 1 1 Status
HT Income Panel VCB: TRIP (Earth
Indicator 1 1 Alarm (Fault Report)
Fault)
HT Income Panel VCB: TRIP (Over
Indicator 1 1 Alarm (Fault Report)
Current)
HT Income Panel VCB: Ampere Reading 1 1 Record
HT Income Panel VCB: Voltage Reading 1 1 Record
Battery Charger Indicator 1 1 Record (Alarm fault)
Battery Low Indicator 1 1 Record (Alarm Low)
Room Temperature Monitoring /
Reading 1 1 Record / Alarm (High)
Alarm
kWHr Meter Reading 1 1 Record
Transformer System
Transformer Temperature Alarm Indicator 1 1 Record / Alarm (High)
Transformer Pressure Alarm Indicator 1 1 Record / Alarm (High)
CO2 System
TNB Room: CO2 Panel Activated Indicator 1 1 Record / Alarm (activated)
Switch Gear: CO2 Panel Activated Indicator 1 1 Record / Alarm (activated)
Transformer Room: CO2 Panel
Indicator 1 1 Record / Alarm (activated)
Activated
Main Switch Room: CO2 Panel
Indicator 1 1 Record / Alarm (activated)
Activated
MCC Room: CO2 Panel Activated Indicator 1 1 Record / Alarm (activated)
Gen Set- CO2 Panel Activated Indicator 1 1 Record / Alarm (activated)
CO2 Panel DC supply Battery Low Indicator 1 1 Record / Alarm (activated)
Qty
AO
DO
AI
DI
Equipment)
Gen Set System
Gen Set - Run Indicator 1 1 Record number of Start / stop
Gen Set - Trip Indicator 1 1 Alarm (Fault Report)
Remote Start /
Gen Set - To Start / Stop (Remote) 1 1 Software control / PLC
Stop
Remote Start /
Gen Set - To Stop (Remote) 1 1 Software control / PLC
Stop
Reset of Hour-
Gen Set - Run-hour record 1 Software counter running hours
Run meter
Gen Set -Battery Charge Indicator 1 1 Record / Alarm (Fault)
Gen Set -DC Battery Low Indicator 1 1 Record / Alarm (Low)
Gen Set -Diesel Fuel oil low Indicator 1 1 Record / Alarm (Low)
Aeration Blower
Blower - Run Indicator 1 1 Record number of Start / stop
Blower - Trip Indicator 1 1 Alarm (Fault Report)
Blower - Off (MCCB) Indicator 1 1 Record non-operation hours
Remote Start /
Blower - To Start / Stop 1 1 Software control / PLC
Stop
Blower - VSD Parameters Speed Control 1 1 RTU via RS-485 Serial Link
Reset of Hour- Software counter / software Timer control
Blower - Run-hour record 0
Run meter operation by rotation.
Blower - Ampere Measure 1 1 Record when operation
Blower - Voltage Measure 1 1 Record when operation
Qty
AO
DO
AI
DI
Equipment)
Temperature Sensor
Blower - Temperature Measure 1 1 Record & Alarm (High Temp)
Air Flow Meter
Air Flow Meter Measure 1 1 Record & Alarm (low level)
D.O. Meter
D.O. Meter Measure 1 1 Record / Control Speed & Alarm (Low)
Anoxic Mixer
Anoxic Mixer - Run Indicator 1 1 Status & counter no. of start / stop
Anoxic Mixer - Trip Indicator 1 1 Alarm (Fault Report)
Anoxic Mixer - Off (MCCB) Indicator 1 1 Record non-operation hours
Remote Start /
Anoxic Mixer - To Start / Stop 1 1 Software control / PLC
Stop
Reset of Hour-
Anoxic Mixer - Run-hour record 0 Software counter
Run meter
Anoxic Mixer - Ampere Measure 1 1 Record when operation
Anoxic Mixer - Voltage Measure 1 1 Record when operation
Qty
AO
DO
AI
DI
Equipment)
Sludge Flow Meter
RAS/WAS Flow Rate Meter Measure 1 1 Record
RAS/WAS Flow Rate Totalizer Measure 1 1 Record
14 Gravity Thickener
G. Thickener - Run Indicator 1 1 Status & counter no. of start / stop
G. Thickener - Trip Indicator 1 1 Alarm (Fault Report)
G. Thickener - Off (MCCB) Indicator 1 1 Record non-operation hours
Remote Start /
G. Thickener - To Start / Stop 1 1 Software control / PLC
Stop
Reset of Hour-
G. Thickener - Run-hour record 0 Software record of running hours
Run meter
G. Thickener - Ampere Measure 1 1 Record when operation
G. Thickener - Voltage Measure 1 1 Record when operation
Gas Blower
Gas Blower - Run Indicator 1 1 Status & counter no. of start / stop
Gas Blower - Trip Indicator 1 1 Alarm (Fault Report)
Gas Blower - Off (MCCB) Indicator 1 1 Record non-operation hours
Remote Start /
Gas Blower - To Start / Stop 1 1 Software control / PLC
Stop
Remote Start / Speed control : RTU via RS-485 Serial
Gas Blower - VSD Parameters 1 1
Stop Link
Reset of Hour-
Gas Blower - Run-hour record 0 Software record of running hours
Run meter
Gas Blower - Ampere Measure 1 1 Record when operation
Gas Blower - Voltage Measure 1 1 Record when operation
Qty
AO
DO
AI
DI
Equipment)
Temperature Sensor
Gas Blower - Temperature Measure 1 1 Record & Alarm (High)
Gas Flow Meter
Gas Flow Meter Measure 1 1 Record
Qty
AO
DO
AI
DI
Equipment)
Belt Press Compressors System
Air Compressor - Run Indicator 1 1 Record number of Start / stop
Air Compressor - Trip Indicator 1 1 Alarm (Fault Report)
Air Compressor - Auto Mode Indicator 1 1 Program Control operation
Air Compressor - Manual Mode Indicator 1 1
Air Compressor - To Start / Stop /
Remote Control 1 1 Software control / PLC
Stop
Reset of Hour-
Air Compressor - Run-hour record 0 Software counter running hours
Run meter
Qty
AO
DO
AI
DI
Equipment)
Force Ventilation: Sludge Feed &
Dewatering Room
Fan : Manual Indicator 1 1
Fan : Auto Indicator 1 1
Fan : Run Indicator 1 1 Status & counter no. of start / stop
Fan : Off Indicator 1 1 Alarm (Fault Report)
Remote Start /
Fan : To Start / Stop 1 1
Stop
Reset of Hour-
Fan : Run-Hour record 1 Software record of running hours
Run meter
Notes:
AI = Analog Input; AO = Analog Output; DI = Digital Input; DO = Digital Output
Qty = Quantity
PUMPS
(Centrifugal)
PUMPS
(Progressive Cavity)
BLOWER
SURFACE AREATOR
Valves
(General)
BUTTERFLY VALVE
AGITATOR
CONVEYORS
CONVEYORS SCREW
OTHERS
EQUIPMENT SYMBOLS
PLC CONTROLLER
WIRELESS COMMUNICATION
SCADA WORKSTATION
POWER TRANSMISSION
METER
COMPRESSOR
TANK
Fan
Rotary pump 2
Rotary compressor
Centrifugal pump
Rotary compressor 2
Positive displacement
rotary pump
Centrifugal compressor
In-line pump (axial flow)
Motorised blower
Reciprocating pump
Cetrifugal fan 2
Centrifugal pump
(submerged section)
Macerator
M
Open tank basic symbol
Rotary bridge scrapper
Open tank
SCREENS AND FILTERS
SYMBOLS DETAILS
Clarifier
Rotary screen
Closed tank basic symbol
Covered tank
Hand rake screen 2
Rotary filter
Gas holder
Water surfaces
Carrying vessel
GENERAL
SYMBOLS DETAILS SYMBOLS DETAILS
Hopper/Silo
M Aeration cone (with vibrator) 1
M
Brush aerator
Hopper/Silo
(with vibrator) 2
Diffusers X
Submersible aerator
Vibrator (with motor)
Ejector/injector
Fluid separator
CONVEYORS AND FEEDERS
Conveyor
Cyclone 2
Inclined conveyor
(with chevrons)
Centrifuge 1
Screw conveyor
Centrifuge 2
Conveyor tube
Dryer
Reversing conveyor
Scraper conveyor
Electrical motor
Spray Device
Feeder
Spray Nozzle
Screw feeder
GENERAL VALVES
Fan blade
In-line (float operated) 2
Triple fan blade
Flange
Rotary Movement
Butterfly
Cooling tower 1
Globe
Cooling tower 2
Ball
Wedge gate
Cooling tower 3
Parallel slide
Oil separator
Needle
Diaphragm 2
MIXERS
Plug 1
SYMBOLS DETAILS
Plug 2
MF
Mixer 2 Powered valve
Reducing valve
Valve manifold
PIPELINE VALVES
Power signal
Check (non-return or reflux ) 1
Statically loaded
Check (non-return or reflux ) 2
Spring loaded
Check (non-return or reflux )
screw down
Weight loaded
Stop check valve
Diaphragm
4-way
Solenoid
M
Motor
Glossary of Abbreviations