ETAP

Project: Page: 1
12.6.0H
Location: Date: 11-28-2017
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: unit6 Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR

ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

Bus load 1 20.000 95.330 -3.0 0 0 9.088 0.000 Bus5 -9.088 0.000 275.2 100.0

Bus load 2 20.000 97.991 -2.0 0 0 4.801 0.000 Bus5 -4.801 0.000 141.4 100.0

* Bus1 13.800 100.000 0.0 4.507 0.164 0 0 Coupler 4.507 0.164 188.7 99.9

* Bus2 13.800 100.000 0.0 4.507 0.164 0 0 Coupler 4.507 0.164 188.7 99.9

* Bus3 150.000 100.000 0.0 5.401 0.347 0 0 Bus5 5.401 0.347 20.8 99.8

Bus5 20.000 99.831 -1.3 0 0 0 0 Bus load 1 9.512 0.289 275.2 100.0

Bus load 2 4.891 0.061 141.4 100.0

Bus3 -5.399 -0.225 156.2 99.9

Coupler -9.005 -0.125 260.4 100.0

Coupler 20.000 99.831 -1.3 0 0 0 0 Bus1 -4.502 -0.063 130.2 100.0

Bus2 -4.502 -0.063 130.2 100.0

Bus5 9.005 0.125 260.4 100.0


* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)