Beruflich Dokumente
Kultur Dokumente
ENGINEER Vol.XLIX,
XLIX,No.
No.03,03,pp.
pp.[49-61],
[page range],
2016 2016
© The
© The Institution
Institution of
of Engineers,
Engineers, Sri
Sri Lanka
Lanka
Abstract: One of the most crucial requirements for the correct functioning of power system
protection equipment is the optimum selection of current transformers (CTs). Therefore, when
selecting CTs, the protection engineer has to pay attention to steady state performance as well as
transient performance of current transformers. The transient performance of current transformers
varies with both system parameters and current transformer parameters. System parameters vary
with the fault level and with the inductance to resistance ratio (L/R) at the fault location. In the power
system of Sri Lanka, these parameters rapidly vary due to network developments. Thus, the type of
the protection relay selected, the type of the protection function and the arrangement of the
switchgear have a huge influence on current transformer selection. This paper discusses the
development of a current transformer selection criterion for protection applications based on the
transient performance of the transformers.
In addition to analyzing the current transformer transient performance, PSCAD software has been
used in this study to simulate current transformer performance during fault conditions with a case
study done to validate the developed selection criterion.
Keywords: Current transformer, Transient factor, Primary time constant, Secondary time constant
49
1
During this 6 cycle delay, the dc component of b. Primary time constant (TP)
the fault current decays from the sub transient c. Secondary time constant (Ts)
time zone to transient time zone and this helps d. Burden of CT secondary
to minimize the effects of transient currents on e. Remanence flux of the CT core
the operation of protection relays. Old bulk oil f. Number of secondary turns and the
circuit breakers take nearly 15 cycles for a cross sectional area
tripping operation. Such delayed clearing
times do not require detailed studies on the
behavior of current transformers during the 2.2 Fault Inception Angle and Fault Loop
first few cycles of a fault. As a result, attention Impedance
was constantly focused those days on the CT's The magnitude of the DC component of the
steady state performance. fault current varies with the fault inception
angle and the power factor of fault impedance.
Power system expansions and The total fault current at any instant is defined
interconnections have been continuing at a by the equation:
very rapid rate globally along with large
𝑡𝑡
additions of generation capacity. To maintain 𝑉𝑉 ʹ −
𝑖𝑖𝑝𝑝 ൌ ሺ𝜔𝜔𝑡𝑡 𝛼𝛼 − ∅ሻ − 𝛼𝛼 − ∅ 𝑒𝑒 𝜏𝜏 𝑝𝑝
system stability under these scenarios, fault 𝑍𝑍
50
2
decaying times of the DC component of the 𝑖𝑖ʹ ൌ
ͳ 𝑅𝑅𝑡𝑡
𝐼𝐼ͳ 𝑒𝑒 − 𝐿𝐿 − 𝑐𝑐𝑜𝑜𝑠𝑠𝜔𝜔𝑡𝑡 ..…. (4)
fault current (Figure 1). 𝑁𝑁ʹ
𝑀𝑀
10000 where M is a constant.
5000 From Equations 5 and 6
0 𝑑𝑑∅ 𝑁𝑁ʹ 𝑅𝑅ʹ ∅ 𝐿𝐿ʹ 𝑑𝑑𝑖𝑖 ʹ 𝐿𝐿ʹ 𝑁𝑁ʹ 𝑑𝑑∅
𝑁𝑁ʹ ൌ 𝑖𝑖ʹ 𝑅𝑅ʹ − − …… (8)
-5000 0 0.1 0.2 0.3 𝑑𝑑𝑡𝑡 𝑀𝑀 𝑑𝑑𝑡𝑡 𝑀𝑀 𝑑𝑑𝑡𝑡
51
3
Figure 3 - Development of CT Core Flux with different TPs and a constant TS (= 1000ms)
…… (11)
3. Dimensioning of Current
Transformers
Figure 4 - Variation of Core Flux with T2
Inductance in the burden has an effect on the Protection current transformers must be
peak flux developed in the CT core. The capable of accurate performance under both
burden in electro-magnetic type protection steady state and transient state conditions. The
relays is predominantly inductive. Yet, dc component contained in the fault current
modern numerical relays have negligible during the transient period makes the flux in
inductance. The variation of peak flux in the the CT core to increase and it thus the core has
CT core and burden inductance is shown in to have sufficient cross section to avoid its
Figure 5. saturation. Optimum CT sizing, usually called
CT dimensioning, will avoid over or under
sizing. CT dimensioning calculations are based
on the transient factor (Ktf) and the transient
dimensioning factor (Ktd). Network, CT and
40
relay parameters are needed for dimensioning
35 calculations.
30
25 3.1 Transient Factor (Ktf)
0 dg angle The ratio of the theoretical total linked flux to
20
Flux (Wb)
52
4
3.2 Transient Dimensioning Factor (Ktd) Ktd= F1/F2 .......(14)
The Transient Dimensioning Factor is
introduced to indicate the transient where F1 is the secondary linked flux due to
dimensioning necessary to ensure that the the actual transient current (AC+DC) and F2 is
current transformer will be able to meet the the secondary linked peak flux of only the AC
specified performance requirements including component.
the requirements necessary under the specified
In the first half cycle, the sinusoidal
duty cycle. It defines the dimensioning
component dominates the Ktd sizing. In the
necessary to ensure that the CT will be able to
CEB transmission system, the maximum Tp is
meet the performance requirements because of
around 140ms and using Equation (13) [2].
the increase of secondary linked flux resulting
from the dc component of the primary short ʹʹ ʹʹ
circuit current. Ktd is derived from Ktf and it is −ͳ ʹ ൈ ൈ ͷͲ ൈ ͲǤͳͶ
𝑇𝑇𝑎𝑎𝑙𝑙 ͳ ൌ
a function of time which depends on selected ʹൈ
ʹʹ
ൈ ͷͲ
protection relay parameters; and network and
CT parameters. In the case of protection relay
𝑇𝑇𝑎𝑎𝑙𝑙 ͳ ൌ ͳͲǤ𝑚𝑚𝑠𝑠
based Ktd calculation, the relevant time value
is given by the protection relay manufacturer. Thusǡ ͳ just exceeds half a cycle. Tal
This defined value for the time is termed as the requested by modern numerical relays is in
required „saturation free time (Tal)‟ for the this time range and due to this reason Ktd
proper operation of the protection function required for satisfactory relay performance
and is determined during relay type tests. The becomes a very low value.
theoretical quantification of Ktd is categorized
into three time zones[1]. 2nd Time Zone (Tal1≤ Tal ≤Tal @ B max)
Tal @ Bmax is defined as the time taken for core
1st Time Zone (0 ≤ Tal ≤ Tal1) flux to reach its maximum. In this time zone,
𝜋𝜋𝜑𝜑
𝑇𝑇𝑎𝑎𝑙𝑙 ͳ ൌ ……… (13) Ktd can be quantified by Equation (15) [2].
𝜔𝜔
𝑇𝑇𝑁𝑁 𝑇𝑇𝑆𝑆 𝑇𝑇
Tal @B max ൌ 𝑙𝑙 𝑆𝑆 ..... (18)
Figure 6 - AC Flux Component and Total 𝑇𝑇𝑆𝑆 −𝑇𝑇𝑁𝑁 𝑛𝑛 𝑇𝑇𝑁𝑁
53
5
in CT sizing for differential protection with The decaying time of the DC component and
electro-magnetic and static relays (relays the fault detection time of the protection
without saturation detection.) function are the major factors that influence CT
class selection. With this information, the
If the critical fault clearing times are available maximum CT error that can be permitted
for unprotected zones by differential within the time duration starting from the fault
protection and if this critical clearing time is inception to the time that the instant relay
less than Tal @ B max, then this critical clearing makes its decision to operate has to be worked
time can be used as Tal in the Ktd calculation. In out.
general, this Ktd value is less than the value of
Ktd (max) calculated by Equation (17). The Ktd Differential Protection
calculated in this manner can be considered as The following are the key features of
the optimum. differential protection that need to be
considered in the determination of CT
4. Current Transformer Selection requirements:
54
6
tripping decisions within this time period (sub selection has a considerable influence on the
transient and transient period). Hence, CT class selection.
transient class CTs are more suitable for in
zone fault detection of static and numerical Selection of CT Classes - Different Types of
relays. Protection Relays
In distance/differential protection, the type of
In case of through faults, the protection relay protection relay plays a vital role in the CT
can take full fault period and this time zone class selection. There are three types of
may be sub transient to steady state and CT distance relays in use in the power system of
should correctly perform in this time zone. Sri Lanka. These are:
55
7
5. Conclusions the relay manufacturer. Therefore, adequate
CT selection guidelines are a must for correct
The final conclusion of this research is the CT selection. The proposed CT selection
development of a CT selection criterion for process as an outcome of this research is
protection applications. The developed shown in Figure 7 and Figure 8 and a simple
selection criterion is mainly focused on two computer program can use the given
streams. Network and CT parameter based CT algorithm and facilitate a fast selection process.
selection can be generalized to protection
applications irrespective of the type of the
protection relay. In this case, CT selection is
carried out in the first stage and the protection
relay selection is lined up after the CT
selection. The second stream of CT selection
criterion is based on the selected protection
relay and on the parameters which are given
by the relay manufacturer. This second stream
highly depends on the literature provided by
56
8
Start
Calculate primary
Calculate the fault time constant
current (Max) (consider infeeds if
any)
Type of
protection
a
Other Distance
No
Select protection relay for
b Differential lower Ktd (get defined
saturation free time by
No protection relay)
Yes
Core saturation
Core minimizing only If Relay manufacturer
selection(Details
Select Class by CT given only Tal calculate
are given
seperatly) ,TPX,TPY,TPZ,X Ktd for system , CT and
beaker parameters.
(According to the IEC
61869-2)
Yes
c
Yes
Select the CT
i accordingly f
Figure 7 - Network and CT Parameters based CT Selection Criteria (continued on next page)
57
9
c d g h
Compare standard
ALF(20,30ect) with new
ALF”
No
Select protection relay for
lower Ktd (get defined If ALF >ALF”
saturation free time)
Yes
Select the CT
accordingly
Figure 7 - Network and CT Parameters based CT Selection Criteria (continued on next page)
58
10
Select CT
with air
gapped
cores
If Yes
Select CT
No Yes installation
with air
Core saturation Select spaces is
gapped
minimizing only Transient less eg GIS
cores
by CT class )
If remenance is important No
Yes Justify minimizing If need linear
parameter for the Yes
a application (Auto reclose or effect of CT core Select type (TPX’) core(negligible
saturation remanence)
not)
No
Same as time
Select CT with
delayed protection
Co -ordinate with linear core(TPZ)
functions
No Tal , Ktd of
selected Protection
relay or Calculate
Ktd Ktd’
(Ts>>Tp)Tal=α
Select CT with Select ,Ts
air gaped
core(TPY) Ts =10900/ᵟmin
Calculate possible
Tal andTal’ must co-
ordinate with
e Ktd Ktd’ relating
protection relay or Tal at practical
Tmax maximum Ts (3s)
Calculate Tmax
calculate
Recalculate Ktd Ktd max
Recalculate possible
Ktd’ maximum Ts relating
permissible error limit
Relating Tal , Tal’ 100Ktd /2πf Ts ≤έ
for new Ts
Calculate burden co-ordinate with
resistance(Relay relay re-setting
internal, wire) time
If the selection is
based on knee point
voltage
Calculate ALF’ No
Calculate Krem (include Krem ) Yes
g f
Figure 7 - Network and CT Parameters based CT Selection Criteria (continued on next page)
59
11
Select modern numerical
No
Core saturation Relay for very low Tal
Justify Protection
b relay type
minimizing only by and Ktd
CT
Yes
Setting >>120ms
Check Relay If Relay manufacturer
time setting given only Tal, calculate
Ktd for system , CT and
breaker parameters
Setting <120ms (According to the IEC
61869-2)
Accept all
Evaluate stability
protection class of
of system
CTs
No
If the CT selection
is based on ALF
Yes
Select transient
If stability is i
class CT
crucial
Yes
No
Calculate Ktd
according to the
Accept all selected CT type, h
protection class system
CTs parameters and
breaker
parameters
Figure 7 - Network and CT Parameters based CT Selection Criteria (end of the diagram)
60
12
Start
CT core selection(According to
Justify protection scheme
the protection function)
Select protection relay with ability to saturation Justify Numerical Relay type (single
detection(Numerical relays-gives very low Tal and Ktd) function or multifunctional)
61
13
Publication Ethics and Publication Malpractice Statement for
‘ENGINEER’ - Journal of the Institution of Engineers, Sri Lanka
In order to agree upon standards of expected ethical Any statement to the effect that an observation, derivation,
behaviour for all parties involved in the act of publishing, or argument had been previously published shall be
i.e. Authors, the Editor, the Editorial Board, Reviewers and accompanied by the relevant citation. The Editor shall be
the Publisher, this journal adopted the concepts of Best informed of any substantial similarity or overlap between
Practice Guidelines for Journal Editors disseminated by the manuscript under consideration and any other
Committee on Publication Ethics (COPE). published paper of which there is personal knowledge.