Sie sind auf Seite 1von 15

ENGINEER -- Vol.

ENGINEER Vol.XLIX,
XLIX,No.
No.03,03,pp.
pp.[49-61],
[page range],
2016 2016
© The
© The Institution
Institution of
of Engineers,
Engineers, Sri
Sri Lanka
Lanka

Current Transformer Performance during Transient


Conditions and the Development of a Current
Transformer Selection Criterion for Protection
Applications

W.D.A.S. Wijayapala, J. Karunanayake and R.R.T.W.M.R.A.I. Madawala

Abstract: One of the most crucial requirements for the correct functioning of power system
protection equipment is the optimum selection of current transformers (CTs). Therefore, when
selecting CTs, the protection engineer has to pay attention to steady state performance as well as
transient performance of current transformers. The transient performance of current transformers
varies with both system parameters and current transformer parameters. System parameters vary
with the fault level and with the inductance to resistance ratio (L/R) at the fault location. In the power
system of Sri Lanka, these parameters rapidly vary due to network developments. Thus, the type of
the protection relay selected, the type of the protection function and the arrangement of the
switchgear have a huge influence on current transformer selection. This paper discusses the
development of a current transformer selection criterion for protection applications based on the
transient performance of the transformers.

In addition to analyzing the current transformer transient performance, PSCAD software has been
used in this study to simulate current transformer performance during fault conditions with a case
study done to validate the developed selection criterion.

Keywords: Current transformer, Transient factor, Primary time constant, Secondary time constant

1. Introduction CT errors due to saturation or mismatch have


an adverse impact on protection functions and
Background hence on the system stability. The saturation
Current transformers (CTs) play a vital role in may be avoided by selecting an oversized CT,
the protection and measuring functions of a which however will be at an increased cost.
power system. The correct selection of current Generation and transmission expansion is a
transformers will lead to the proper operation continuing process and therefore the duties
of protection and measuring equipment. The CTs have to perform will become more and
magnetic saturation of the current transformer more demanding. Thus the utilities need
core creates undesirable problems in proper selection criteria when procuring new
protection devices and therefore a current CTs as well as when replacing existing CTs.
transformer has to be designed to activate
protection devices within the first few cycles of Objective
a fault, without letting its core to get saturated. The conventional electromagnetic relays take
nearly more than 6 cycles for the operation of
During fault conditions, the DC component of their instantaneous protection functions.
the fault current is responsible for the
saturation of current transformer cores[1]. The Eng. W.D.A.S. Wijayapala, Int.PEng(SL), CEng, FIE(Sri
L/R ratio of the system (at the fault location) Lanka), BScEng (Hons) (Moratuwa), MEng(Moratuwa),
and the L/R ratio of the secondary loop, Senior Lecturer, Department of Electrical Engineering,
University of Moratuwa.
determine the magnitude and the decaying
time of the DC component of the CT secondary Eng. J. Karunanayake, CEng, FIE(Sri Lanka), BSc Eng
current[2]. When the hardware of a (Hons), Senior Consultant Engineer.
transmission system is changed, the L/R ratio
Eng. R.R.T.W.M.R.A.I. Madawala, CEng, MIE(Sri
changes and adding up more generators to the Lanka), MSc (Moratuwa), Electrical Engineer, Ceylon
power system will increase the fault currents. Electricity Board.
These factors have considerable impacts on the
performance of the existing CTs in their
protection functions.

49
1
During this 6 cycle delay, the dc component of b. Primary time constant (TP)
the fault current decays from the sub transient c. Secondary time constant (Ts)
time zone to transient time zone and this helps d. Burden of CT secondary
to minimize the effects of transient currents on e. Remanence flux of the CT core
the operation of protection relays. Old bulk oil f. Number of secondary turns and the
circuit breakers take nearly 15 cycles for a cross sectional area
tripping operation. Such delayed clearing
times do not require detailed studies on the
behavior of current transformers during the 2.2 Fault Inception Angle and Fault Loop
first few cycles of a fault. As a result, attention Impedance
was constantly focused those days on the CT's The magnitude of the DC component of the
steady state performance. fault current varies with the fault inception
angle and the power factor of fault impedance.
Power system expansions and The total fault current at any instant is defined
interconnections have been continuing at a by the equation:
very rapid rate globally along with large
𝑡𝑡
additions of generation capacity. To maintain 𝑉𝑉 ʹ −
𝑖𝑖𝑝𝑝 ൌ •‹ሺ𝜔𝜔𝑡𝑡 ൅ 𝛼𝛼 − ∅ሻ − •‹ 𝛼𝛼 − ∅ 𝑒𝑒 𝜏𝜏 𝑝𝑝
system stability under these scenarios, fault 𝑍𝑍

clearing times have to be made much lower


and numerical relays and fast acting circuit .....(1)
breakers have been developed for this where
purpose. The advent of numerical relays and 𝑖𝑖𝑝𝑝 = Instantaneous value of fault current
high speed circuit breakers has achieved lower
𝑉𝑉 ʹ
fault clearing times as desired, but questions = IP, Peak Fault current
𝑍𝑍
have arisen on the capability of current
transformers in feeding relevant information to α = Angle of fault inception
the relays, as these CTs have been selected
based on their steady state performance. Ø = Phase angle of the fault impedance

In respect of instantaneous protection The magnitude of the DC component (•‹ 𝛼𝛼 −


functions (differential and distance), a ∅𝑒𝑒−𝑡𝑡𝜏𝜏𝑝𝑝 ) varies with the angle 𝛼𝛼−∅ and will
numerical relay operation takes place during be a maximum when 𝛼𝛼 − ∅ ൌ ∓ͻͲͲ . In the
the sub transient period. Therefore, protection case of transmission lines, typical values of ∅
engineers and CT manufacturers have focused lie around 90° as fault impedances are highly
their attention on the satisfactory transient inductive. As can be seen, the DC component
performance of CTs. IEC has also published its of the fault current is a function of the fault
standards on the transient performance of CTs. inception angle and the fault loop impedance.
This indicates that if the fault inception angle
The main objectives of this study are: equals to zero or near zero, the DC component
will also take its maximum value. However,
a. to study current transformer performance the fault inception angle will vary and cannot
under transient conditions and its impact be predicted. Hence, CT sizing is carried out
on protection functions for the worst case or by assuming that the DC
b. to revisit the present selection criteria and component is at its maximum. Equation (2)
develop a generalized current transformer gives the instantaneous fault current with a
selection criteria based on system zero inception angle and a pure inductive fault
parameters and current transformer loop impedance or when 𝛼𝛼 − ∅ ൌ −ͻͲͲ .
parameters for different protection
functions 𝑅𝑅𝑡𝑡
𝑖𝑖𝑝𝑝 ൌ 𝐼𝐼𝑝𝑝 𝑒𝑒 − 𝐿𝐿 − 𝑐𝑐𝑜𝑜𝑠𝑠𝜔𝜔𝑡𝑡 .....(2)

2. Analysis of Current Transformer 2.3 Fault Current Variation with the


Performance under Transient Primary Time Constant (TP)
Conditions The Primary Time constant (TP) is defined as
2.1 Parameters that govern CT the L/R ratio of the fault location and it
performance under transient determines the decaying time of the DC
conditions. component of the fault current. A very high
a. Fault level or fault current at the primary time constant will lead to very high
particular location

50
2
decaying times of the DC component of the 𝑖𝑖ʹ ൌ
ͳ 𝑅𝑅𝑡𝑡
𝐼𝐼ͳ 𝑒𝑒 − 𝐿𝐿 − 𝑐𝑐𝑜𝑜𝑠𝑠𝜔𝜔𝑡𝑡 ..…. (4)
fault current (Figure 1). 𝑁𝑁ʹ

From fundamentals, the secondary induced


TP makes a high impact on the flux
e.m.f. E2 will be given by
development in a CT core and plays a vital role
in CT sizing. The flux development in a closed 𝑑𝑑∅
E2 = 𝑁𝑁ʹ …… (5)
core application is given in Figure 3. 𝑑𝑑𝑡𝑡

and for the circuit in Figure 3;


Primary Current Variation
𝑑𝑑 𝑖𝑖 ʹ −𝑖𝑖 𝑀𝑀
with Tp E2= 𝑖𝑖ʹ − 𝑖𝑖𝑀𝑀 𝑅𝑅ʹ ൅ 𝐿𝐿ʹ …… (6)
𝑑𝑑𝑡𝑡
15000 𝑁𝑁
𝑖𝑖𝑀𝑀 = ʹ ∅ …… (7)
Fault current (kA)

𝑀𝑀
10000 where M is a constant.
5000 From Equations 5 and 6
0 𝑑𝑑∅ 𝑁𝑁ʹ 𝑅𝑅ʹ ∅ 𝐿𝐿ʹ 𝑑𝑑𝑖𝑖 ʹ 𝐿𝐿ʹ 𝑁𝑁ʹ 𝑑𝑑∅
𝑁𝑁ʹ ൌ 𝑖𝑖ʹ 𝑅𝑅ʹ − ൅ − …… (8)
-5000 0 0.1 0.2 0.3 𝑑𝑑𝑡𝑡 𝑀𝑀 𝑑𝑑𝑡𝑡 𝑀𝑀 𝑑𝑑𝑡𝑡

and rearranging Equation 8,


-10000
Time (s) 𝑑𝑑∅ 𝐿𝐿ʹ 𝑁𝑁ʹ 𝑁𝑁ʹ 𝑅𝑅ʹ ∅ 𝐿𝐿ʹ 𝑑𝑑𝑖𝑖 ʹ
𝑁𝑁ʹ ൅ ൅ ൌ 𝑖𝑖ʹ 𝑅𝑅ʹ ൅ …… (9)
𝑑𝑑𝑡𝑡 𝑀𝑀 𝑀𝑀 𝑑𝑑𝑡𝑡
Ip1(Tp 50ms) Ip2(Tp 120ms)
From the above equations, the solution for Ø is
obtained as (applicable 𝑓𝑓𝑜𝑜𝑟𝑟𝑡𝑡 ൐ ͺǤ͵𝑚𝑚𝑠𝑠ሻ
Figure 1 - Primary Current Variation with Tp
−𝑡𝑡 −𝑡𝑡
𝐼𝐼ͳ 𝑅𝑅ʹ 𝑇𝑇ͳ 𝑇𝑇ʹ 𝜔𝜔 ͳ
2.4 CT Flux Requirement under ∅ൌ 𝑒𝑒 𝑇𝑇 ʹ − 𝑒𝑒 𝑇𝑇 ͳ − •‹ 𝜔𝜔𝑡𝑡 ൅
𝑁𝑁ʹ ʹ𝜔𝜔 𝑇𝑇ʹ −𝑇𝑇ͳ …‘• 𝜃𝜃
Transient Conditions
𝜃𝜃 …… (10)
Consider the equivalent circuit shown in
Figure 2. 𝐿𝐿ʹ 𝜔𝜔 𝐿𝐿ʹ ൅𝑀𝑀 𝐿𝐿ͳ
L1 where𝜃𝜃 ൌ –ƒ−ͳ ,𝑇𝑇ʹ ൌ ,𝑇𝑇ͳ ൌ
R1 1/ N
2
(i2- im) 𝑅𝑅ʹ 𝑅𝑅ʹ 𝑅𝑅ͳ
i1 i2 im
R2 Thus the core flux is a function of the time,
E2 M primary current, turns ratio, primary time
constant, secondary time constant and the
burden. Figure 3 shows the flux development
L2

in a CT core having a 1000ms secondary time


constant (TS)1 and for primary time
Figure 2 - Equivalent Circuit of a CT constants(TP) of 140ms, 120ms and 60ms.

Figure 4 shows core flux variation with the


where secondary time constant and the DC current
component of the primary current. The "Flux
R1= Primary resistance of CT 3" curve in Figure 4 corresponds to a 300ms
R2 = Total secondary resistance secondary time constant (T2) and this low time
constant causes a rapid decaying of core flux
M = Magnetic inductance with the DC current component. This
L1 = Primary leakage inductance of CT characteristic is used to minimize the flux
component which is increasing due to DC
L2 = Secondary leakage inductance primary current. Gapped cores are used to
Then based on the following assumptions: reduce the secondary time constant.

1. CT is ring type with N1=1, and turns ratio


of 1/N2.
2. Fault current wave form is fully offset
(i.e.fault inception angle= 0° and fault
impedance fully inductive).
𝑡𝑡
𝑖𝑖ͳ ൌ 𝐼𝐼ͳ 𝑒𝑒 −𝑇𝑇ͳ − 𝑐𝑐𝑜𝑜𝑠𝑠𝜔𝜔𝑡𝑡 …… (3) 1
in CT sizing,1000ms can be considered as infinite

51
3
Figure 3 - Development of CT Core Flux with different TPs and a constant TS (= 1000ms)

2.5 CT Flux Requirement under


Transient Conditions with a Fully
Resistive Burden
In this case,…‘• 𝜃𝜃 ൌ ͳǡ 𝜃𝜃 ൌ Ͳ
𝐼𝐼ͳ 𝑅𝑅ʹ 𝑇𝑇ͳ 𝑇𝑇ʹ 𝜔𝜔 −𝑡𝑡 −𝑡𝑡
∅ൌ 𝑒𝑒 𝑇𝑇 ʹ − 𝑒𝑒 𝑇𝑇 ͳ − •‹ 𝜔𝜔𝑡𝑡 ൅ 𝜃𝜃
𝑁𝑁ʹ ʹ𝜔𝜔 𝑇𝑇ʹ − 𝑇𝑇ͳ

…… (11)

3. Dimensioning of Current
Transformers
Figure 4 - Variation of Core Flux with T2

Inductance in the burden has an effect on the Protection current transformers must be
peak flux developed in the CT core. The capable of accurate performance under both
burden in electro-magnetic type protection steady state and transient state conditions. The
relays is predominantly inductive. Yet, dc component contained in the fault current
modern numerical relays have negligible during the transient period makes the flux in
inductance. The variation of peak flux in the the CT core to increase and it thus the core has
CT core and burden inductance is shown in to have sufficient cross section to avoid its
Figure 5. saturation. Optimum CT sizing, usually called
CT dimensioning, will avoid over or under
sizing. CT dimensioning calculations are based
on the transient factor (Ktf) and the transient
dimensioning factor (Ktd). Network, CT and
40
relay parameters are needed for dimensioning
35 calculations.
30
25 3.1 Transient Factor (Ktf)
0 dg angle The ratio of the theoretical total linked flux to
20
Flux (Wb)

the peak instantaneous value of the ac


15 component of the flux when a current
60 dg angle
10 transformer is subjected to a specified single
5 75 dg angle energization with secondary loop time
0 constant (TS) remaining at a constant value
throughout the energization is referred to as
-5 0 0.2 0.4 0.6 the transient factor (Ktf) [4].
-10 time (sec) −𝑡𝑡 −𝑡𝑡
𝑇𝑇ͳ 𝑇𝑇ʹ 𝜔𝜔
𝐾𝐾𝑡𝑡𝑓𝑓 ൌ 𝑒𝑒 𝑇𝑇 ʹ − 𝑒𝑒 𝑇𝑇 ͳ − •‹ 𝜔𝜔𝑡𝑡𝜃𝜃 …….. (12)
Figure 5 - Variation of core flux with 𝑇𝑇ʹ −𝑇𝑇ͳ

secondary burden phase angle

52
4
3.2 Transient Dimensioning Factor (Ktd) Ktd= F1/F2 .......(14)
The Transient Dimensioning Factor is
introduced to indicate the transient where F1 is the secondary linked flux due to
dimensioning necessary to ensure that the the actual transient current (AC+DC) and F2 is
current transformer will be able to meet the the secondary linked peak flux of only the AC
specified performance requirements including component.
the requirements necessary under the specified
In the first half cycle, the sinusoidal
duty cycle. It defines the dimensioning
component dominates the Ktd sizing. In the
necessary to ensure that the CT will be able to
CEB transmission system, the maximum Tp is
meet the performance requirements because of
around 140ms and using Equation (13) [2].
the increase of secondary linked flux resulting
from the dc component of the primary short ʹʹ ʹʹ
circuit current. Ktd is derived from Ktf and it is ൅ –ƒ−ͳ ʹ ൈ ൈ ͷͲ ൈ ͲǤͳͶ
͹ ͹
𝑇𝑇𝑎𝑎𝑙𝑙 ͳ ൌ
a function of time which depends on selected ʹൈ
ʹʹ
ൈ ͷͲ
͹
protection relay parameters; and network and
CT parameters. In the case of protection relay
𝑇𝑇𝑎𝑎𝑙𝑙 ͳ ൌ ͳͲǤ͸𝑚𝑚𝑠𝑠
based Ktd calculation, the relevant time value
is given by the protection relay manufacturer. Thusǡ ƒŽ ͳ just exceeds half a cycle. Tal
This defined value for the time is termed as the requested by modern numerical relays is in
required „saturation free time (Tal)‟ for the this time range and due to this reason Ktd
proper operation of the protection function required for satisfactory relay performance
and is determined during relay type tests. The becomes a very low value.
theoretical quantification of Ktd is categorized
into three time zones[1]. 2nd Time Zone (Tal1≤ Tal ≤Tal @ B max)
Tal @ Bmax is defined as the time taken for core
1st Time Zone (0 ≤ Tal ≤ Tal1) flux to reach its maximum. In this time zone,
𝜋𝜋൅𝜑𝜑
𝑇𝑇𝑎𝑎𝑙𝑙 ͳ ൌ ……… (13) Ktd can be quantified by Equation (15) [2].
𝜔𝜔

where −𝑇𝑇 𝑎𝑎𝑙𝑙 −𝑇𝑇 𝑎𝑎𝑙𝑙


𝑇𝑇ͳ 𝑇𝑇ʹ 𝜔𝜔
𝜑𝜑 ൌ –ƒ −ͳ
𝜔𝜔𝑇𝑇𝑝𝑝 𝐾𝐾𝑡𝑡𝑑𝑑 ൌ 𝑒𝑒 𝑇𝑇 ʹ  − 𝑒𝑒 𝑇𝑇 ͳ ൅ͳ …(15)
𝑇𝑇ʹ −𝑇𝑇ͳ

In the case of electromagnetic relays and static


protection relays, the defined saturation free
AC time lies in this second time zone.
component
of core flux 3rd Time Zone (Tal≥Tal @ B max)
During the period beyond Tal @ Bmax, core flux
begins to decay. The mathematical expression
Total core for the maximum flux in the CT core is given
flux ,Tp by Equation (16) and the time taken to reach
Flux (wb)

=120ms the maximum flux (Tal@ B max) is given by


Equation (18) [2].

Total core 𝐵𝐵 𝑇𝑇ͳ 𝑇𝑇ʹ 𝜔𝜔


−𝑡𝑡 −𝑡𝑡

flux,Tp =140 𝐾𝐾𝑓𝑓𝑡𝑡 ൌ 𝑒𝑒𝑇𝑇ʹ  − 𝑒𝑒𝑇𝑇 ͳ ൅ ͳ ..... (16)


𝐵𝐵𝑎𝑎𝑐𝑐 𝑇𝑇ʹ −𝑇𝑇ͳ
ms 𝐵𝐵𝑚𝑚𝑎𝑎𝑥𝑥 𝑇𝑇
𝑇𝑇 ʹ

Time (s) ൌ 𝐾𝐾𝑡𝑡𝑑𝑑 ሺ𝑚𝑚𝑎𝑎𝑥𝑥 ሻ  ൌ ͳ ൅ 𝜔𝜔𝑇𝑇ʹ ሾ ͳ ሿ 𝑇𝑇 ʹ −𝑇𝑇 ͳ …… (17)


𝐵𝐵𝑎𝑎𝑐𝑐 𝑇𝑇ʹ

𝑇𝑇𝑁𝑁 𝑇𝑇𝑆𝑆 𝑇𝑇
Tal @B max ൌ 𝑙𝑙 𝑆𝑆  ..... (18)
Figure 6 - AC Flux Component and Total 𝑇𝑇𝑆𝑆 −𝑇𝑇𝑁𝑁 𝑛𝑛 𝑇𝑇𝑁𝑁

Flux Development of the CT Core.


This time zone is more important in CT sizing
Figure 6 shows the total flux development and for maximum possible core flux or highest
ac flux development of the CT core in the first saturation free time. In the case of static and
few cycles. Figure 6 shows the flux electromagnetic relays used in differential
development in the first few cycles and the protection applications, due to sizing
flux relationship of Ktd is given below: requirements of through fault conditions, a CT
must provide a saturation free current input to
the protection relay during the entire fault
period. Therefore, Tal @B max must be considered

53
5
in CT sizing for differential protection with The decaying time of the DC component and
electro-magnetic and static relays (relays the fault detection time of the protection
without saturation detection.) function are the major factors that influence CT
class selection. With this information, the
If the critical fault clearing times are available maximum CT error that can be permitted
for unprotected zones by differential within the time duration starting from the fault
protection and if this critical clearing time is inception to the time that the instant relay
less than Tal @ B max, then this critical clearing makes its decision to operate has to be worked
time can be used as Tal in the Ktd calculation. In out.
general, this Ktd value is less than the value of
Ktd (max) calculated by Equation (17). The Ktd Differential Protection
calculated in this manner can be considered as The following are the key features of
the optimum. differential protection that need to be
considered in the determination of CT
4. Current Transformer Selection requirements:

a. No time delays are involved as the


Oversized CTs may facilitate accurate
operation is instantaneous. Hence, the
protection operations, but such selections
relay is required to do its fault detection
cannot be economically justified. Once the
within the first few cycles of the fault,
optimum selection of CTs is done at the
which is within the transient period.
planning stage, the protection system will
b. Protection is based on the circulating
operate satisfactorily, but power system
current principle. Hence at any instant,
parameters will keep on changing with system
secondary currents from two or more CTs
expansions. Hence, all transmission and
are evaluated to make the tripping
distribution system operators are required to
decision.
study and analyze each and every protection
c. To accomplish (b), the protection relay will
relay operation and determine the causes of
need real time secondary currents with
mal-operations if any.
errors at levels lower than the stipulated
4.1 CT Selection Criteria levels to determine primary circuit current
CT selection criteria largely depend on the differences.
following main parameters: d. Biased curve setting is used to mitigate CT
errors. This curve setting is used to
1) CT class mitigate effects which originate from CT
2) Core construction and network mismatches for through
3) CT capacity faults. In case of transformer differential
protection, the transformer magnetizing
CT Class current component dominates to some
CT class selection depends on the following extent. The tripping value of the
parameters: differential current of the protection relay
is set to follow the biased curve.
a) Protection function
b) Type of protection relay In the case of in-zone faults, the protection
c) Required limit of unit or system relay operation has been categorized as
stability instantaneous operation. However, the relay
takes time to detect the fault and make the
Protection Functions
tripping decision. This delay time depends on
The protection function determines the
required delay for the relay operation. the type of relay and numerical relays are very
Differential protection needs high speed fast in this process. Static and electro-magnetic
operation or even operation without a delay. relays take more time than numerical relays.
First zone operation of distance also needs The fastest numerical relay takes nearly 25ms
high speed fault detection. In this research, it for in zone faults and this lies in the sub
has been identified that the categorization of transient time zone. According to network
instantaneous or non-delayed tripping parameters of Sri Lanka and magnetic
functions are more appropriate for CT class characteristics of CTs, saturation starts after ½
selection.
cycle and remains until around 400ms and
numerical relays and static relays make their

54
6
tripping decisions within this time period (sub selection has a considerable influence on the
transient and transient period). Hence, CT class selection.
transient class CTs are more suitable for in
zone fault detection of static and numerical Selection of CT Classes - Different Types of
relays. Protection Relays
In distance/differential protection, the type of
In case of through faults, the protection relay protection relay plays a vital role in the CT
can take full fault period and this time zone class selection. There are three types of
may be sub transient to steady state and CT distance relays in use in the power system of
should correctly perform in this time zone. Sri Lanka. These are:

If the protection scheme guarantees protection a. Electromagnetic (electro-mechanical)


relay operation within the first ½ cycle for in- relays
zone faults and if the protection system also b. Static relays
guarantees a critical fault clearing time less c. Digital relays
than ½ cycle for through faults, the use of class d. Numerical relays
P CTs can be accepted.
CT Core Selection
Distance Protection CT core selection is based on the following:
To maintain system stability, faulty sections of
a power system must be isolated from the a. Type of CT installation
healthy system within the critical clearing load b. The Value of acceptable Ktd
angle and critical clearing time. Thus, the relay for any given protection relay
has to operate fast. In a distance relay's first c. Cost of CT
zone, operation is instantaneous and the relay
operates within the transient period. When Type of CT Installation
secondary current distortions are present due The CT size is not a major issue in outdoor
to inaccurate transformation by CTs, the fault type CT installations where generally
location as measured by the relay can differ sufficient space is available for switchgear
from the actual location. For a first zone fault installation. This environment allows for the
close to the boundary between the first zone use of CTs with large cross sections, such as
and the second zone, secondary current closed core CTs in which remanence flux
distortions may make the relay to see it as a mitigation will take place.
second zone fault and hence will result in
delayed tripping. If this delay exceeds the In the case of indoor substations (Gas
critical clearing time of this particular location Insulated Substations (GIS)), the installation
it will cause system instability. space becomes an important parameter. In GIS,
CTs are encapsulated with the circuit breaker
In the power system of Sri Lanka, the and isolator units. Therefore, smaller size CTs
maximum primary time constant (TP) is are more suitable for GIS. Gapped core CTs
around 140ms. In a closed core CT have relatively low cross sections. Class TPZ
construction, the DC current component will CTs have approximately only 60% of the cross
take more than 300ms to decay and the section of closed core CTs and 40% of that of
maximum saturation may occur in the second class PR and class TPX cores.
cycle. The grading time (delay time) in
The Value of Acceptable Ktd for a Given
distance schemes is 250-300ms. This implies
Protection Relay
that the 2nd zone operation also may take place
Alow Ktd means a low cross section for a CT. If
before the complete decay of the DC transient
a protection relay can operate accurately with
component. Therefore, the transient class is the
lower Ktd, then a closed core CT in which
preferred option for distance protection. As
accurate DC component transformation is
discussed above, 1st and 2nd zone operations of
possible can be selected.
differential relays lie within the 10ms to 400ms
region and the exact operation time varies with
the type of the relay and therefore, the relay

55
7
5. Conclusions the relay manufacturer. Therefore, adequate
CT selection guidelines are a must for correct
The final conclusion of this research is the CT selection. The proposed CT selection
development of a CT selection criterion for process as an outcome of this research is
protection applications. The developed shown in Figure 7 and Figure 8 and a simple
selection criterion is mainly focused on two computer program can use the given
streams. Network and CT parameter based CT algorithm and facilitate a fast selection process.
selection can be generalized to protection
applications irrespective of the type of the
protection relay. In this case, CT selection is
carried out in the first stage and the protection
relay selection is lined up after the CT
selection. The second stream of CT selection
criterion is based on the selected protection
relay and on the parameters which are given
by the relay manufacturer. This second stream
highly depends on the literature provided by

56
8
Start

Obtain fault level and


X,R values at
selected location

Calculate primary
Calculate the fault time constant
current (Max) (consider infeeds if
any)

Type of
protection
a

Other Distance

No
Select protection relay for
b Differential lower Ktd (get defined
saturation free time by
No protection relay)

Yes

Core saturation
Core minimizing only If Relay manufacturer
selection(Details
Select Class by CT given only Tal calculate
are given
seperatly) ,TPX,TPY,TPZ,X Ktd for system , CT and
beaker parameters.
(According to the IEC
61869-2)
Yes

Calculate Ktd (Ts >>Tp -closed


core)

for total saturation free


transformation Tal=α Justify rated burden and
,approximately National grid Tp
specify CT internal
resistance of CT
max =120ms,hence dc
decaying nearly takes 200ms.
e
Calculate actual
Tal Should co-ordinate with burden (relay ,wire
Tp. loop)

Calculate actual ALF (Ips/Ipn*)Ktd


For Through fault
Calculate knee point voltage
currents should be
and check (> Kss*Ktd*(Rct No
checked for Ktd(max)
+Rb)*Is )
If selection is X

c
Yes

Select the CT
i accordingly f

Figure 7 - Network and CT Parameters based CT Selection Criteria (continued on next page)

57
9
c d g h

Calculate ratio of Actual


Calculate new secondary impedance to
ALF(ALF*secondary secondary rated impedance
impedance ratio)
Rs(act)/Rs(n)

Compare standard
ALF(20,30ect) with new
ALF”

No
Select protection relay for
lower Ktd (get defined If ALF >ALF”
saturation free time)

Yes

Calculate ALF new Ktd is ok

Select the CT
accordingly

Figure 7 - Network and CT Parameters based CT Selection Criteria (continued on next page)

58
10
Select CT
with air
gapped
cores

Yes If Relay manufacturer


has given only Tal , Calculate ’Ktd
Select modern calculate Ktd for
If installation and size
numerical Relay system , CT and d
for very low Tal spaces is less breaker parameters. CT(Burden ,Knee
eg GIS ) (According to the IEC point voltage, ALF)
and Ktd Select CT
61869-2)
Closed cores
No

If Yes
Select CT
No Yes installation
with air
Core saturation Select spaces is
gapped
minimizing only Transient less eg GIS
cores
by CT class )

If remenance is important No
Yes Justify minimizing If need linear
parameter for the Yes
a application (Auto reclose or effect of CT core Select type (TPX’) core(negligible
saturation remanence)
not)

No

Same as time
Select CT with
delayed protection
Co -ordinate with linear core(TPZ)
functions
No Tal , Ktd of
selected Protection
relay or Calculate
Ktd Ktd’
(Ts>>Tp)Tal=α
Select CT with Select ,Ts
air gaped
core(TPY) Ts =10900/ᵟmin
Calculate possible
Tal andTal’ must co-
ordinate with
e Ktd Ktd’ relating
protection relay or Tal at practical
Tmax maximum Ts (3s)
Calculate Tmax

calculate
Recalculate Ktd Ktd max
Recalculate possible
Ktd’ maximum Ts relating
permissible error limit
Relating Tal , Tal’ 100Ktd /2πf Ts ≤έ
for new Ts
Calculate burden co-ordinate with
resistance(Relay relay re-setting
internal, wire) time

If the selection is
based on knee point
voltage
Calculate ALF’ No
Calculate Krem (include Krem ) Yes

Calculate CT internal Calculate knee point


resistance(Take 50% voltage (Eal )
of burden R)

g f

Figure 7 - Network and CT Parameters based CT Selection Criteria (continued on next page)

59
11
Select modern numerical
No
Core saturation Relay for very low Tal
Justify Protection
b relay type
minimizing only by and Ktd
CT

Yes

Setting >>120ms
Check Relay If Relay manufacturer
time setting given only Tal, calculate
Ktd for system , CT and
breaker parameters
Setting <120ms (According to the IEC
61869-2)

Accept all
Evaluate stability
protection class of
of system
CTs

No
If the CT selection
is based on ALF
Yes
Select transient
If stability is i
class CT
crucial

Yes

No

Calculate Ktd
according to the
Accept all selected CT type, h
protection class system
CTs parameters and
breaker
parameters

Figure 7 - Network and CT Parameters based CT Selection Criteria (end of the diagram)

60
12
Start

Get fault level and X,R values


from transmission/generation
sections at selected location

Calculate primary time constant (consider


Calculate fault current (Max)
infeeds if any)

CT core selection(According to
Justify protection scheme
the protection function)

Select protection relay with ability to saturation Justify Numerical Relay type (single
detection(Numerical relays-gives very low Tal and Ktd) function or multifunctional)

Specify CT parameters according


to the protection relay(ALF, Knee
Point voltage, Turn ratio, Ts)

Figure 8 - Relay based CT Selection Criteria

61
13
Publication Ethics and Publication Malpractice Statement for
‘ENGINEER’ - Journal of the Institution of Engineers, Sri Lanka

In order to agree upon standards of expected ethical Any statement to the effect that an observation, derivation,
behaviour for all parties involved in the act of publishing, or argument had been previously published shall be
i.e. Authors, the Editor, the Editorial Board, Reviewers and accompanied by the relevant citation. The Editor shall be
the Publisher, this journal adopted the concepts of Best informed of any substantial similarity or overlap between
Practice Guidelines for Journal Editors disseminated by the manuscript under consideration and any other
Committee on Publication Ethics (COPE). published paper of which there is personal knowledge.

Scope of the Journal Disclosure and Conflict of Interest


The journal ‘ENGINEER’ is intended for the publication of Information or ideas obtained through peer review shall
full length research/technical papers related to not be used by reviewers for personal advantage.
Engineering, filtered through double blind peer review Manuscript where known conflict of interest resulting from
process. competitive, collaborative, or personal connections shall not
be accepted by a reviewer for review.
Eligibility for Publication
The journal is fully funded by the Institution derived from Duties of Authors
membership fees and the publication is free of charge for
successful authors. Consequently, eligibility for publication Reporting standards
is limited to all categories of members of the Institution. Authors of original research papers shall present an
However, the Editor may, in consultation with the Editorial accurate account of the work performed as well as an
Board accept any relevant submission on individual merit. objective discussion of its significance. A research paper
shall contain sufficient detail and references to permit
Decision for Publication others to replicate the work. Fraudulent or knowingly
The Editor of the journal is responsible for deciding which inaccurate statements constitute unethical behavior and are
of the articles submitted to the journal should be published. deemed unacceptable.
The Editor shall be guided by the policies of the Editorial
Board and constrained by such legal requirements as shall Data Access and Retention
then be in force regarding copyright infringement and Authors shall provide raw data in connection with a paper
plagiarism. if requested for editorial review, and shall be prepared to
retain such data for a reasonable time after the publication.
Equity
Decision for publication shall be based on intellectual Originality Acknowledgement and Plagiarism
content without bias to race, religion, ethnic origin, The authors shall ensure that their manuscripts are original
citizenship, gender or political philosophy of the authors. except for included extracts from acknowledged works of
others appropriately cited or quoted. Authors are
Confidentiality, Disclosure and conflicts of interest encouraged to cite publications which influenced their
The Editor and any editorial staff shall not disclose any work. Plagiarism in any form shall be desisted by authors.
information about a submitted manuscript to anyone other
than the corresponding author, reviewers, potential Multiple or Concurrent Publication
reviewers and the publisher, as appropriate, nor shall they In general, an author shall not publish manuscripts
use material contained in such a manuscript for their own describing essentially the same work in multiple
research without the expressed written consent of the publications. Concurrent submission of the same
author. manuscript to multiple publishers is unacceptable as it
constitute unethical practice.
Preclusion of Plagiarism
The Journal does not tolerate any form of plagiarism and Authorship of the Manuscript
shall disqualify a manuscript from publication if detected. Individuals who have made significant contributions in
concept, formulation, execution and interpretation of the
Duties of Reviewers reported study as well as compilation of the manuscript
shall be made co-authors. Other significant contributors
Contribution to Editorial Decisions shall be appropriately acknowledged. The corresponding
Peer review assists the Editor in making editorial decisions author shall ensure that all appropriate co-authors are
and through the editorial communications with the author included and they have agreed with the final version of the
may also assist the author in improving the paper. manuscript for publication.

Promptness Disclosure and Conflicts of Interest


Financial or any substantive conflict of interest that might
Any notified reviewer who feels unqualified to review the be construed to influence the results or interpretation of the
reported manuscript or knows that its prompt review will work to be published shall be disclosed in the manuscript.
not be impossible shall notify the Editor and withdraw.
Significant errors in published papers
Confidentiality It is the duty of an author to immediately inform the Editor
Manuscripts received for review shall be treated as if a significant error is discovered in either a published
confidential documents. paper or a manuscript being processed for publication and
assist in the correction process.
Standards of Objectivity
Reviews should be conducted objectively with views clearly
described with supporting arguments.
Identification of Sources

Das könnte Ihnen auch gefallen