Technical Review Report

SR Ref: CEDSR-37788 Submission Count: 1 Report Date: 04-Feb-2018

Applicant Information
Client Name NASSER ABDULLA MOHAMMED BIN HAFEZ ALJANAHI
Trakhees ID P-0-091526

Consultant Name EMSQUARE ENGINEERING CONSULTANTS


Trakhees ID C-0010-039196

Contractor Name ANMOL PILING &STEEL STRUCTURES (L.L.C.)


Trakhees ID C-0016-037889

Project Information
Developer/BU Nakheel
Project Location Palm Jumeirah
Plot No. PJFRN050_52
Project ID (if any) P16174
Project Description
Subject APPLICATION FOR SHORING NOC

Service Request Reference


Service Requested Shoring - New
Service Request # CEDSR-37788 Requested on 24-Jan-2018

Review Comments
Reviewer wael.mohamed
TKS Structure Comments
Review Status RESUBMIT
1. Valid Trakhees concept approval or Re-validated Building Permit shall be provided. ... [To be responded]
2. Please submit De-watering documents and drawings, otherwise submit the undertaking letter as per the template attached to
the circular ref. - CEDGR-3-Circular dated on 15-April-15 for issuing conditional Shoring NOC for the same. ... [To be responded]

Final Status

RESUBMIT

Note:
● This is a system generated Technical Report and doesn’t require signatures.
● Refer comments marked as [To be responded] and provide relevant response for Trakhees Review.
● Pending Re-submission requests will be cancelled if not responded in time.
● Applicants submitting/resubmitting documents or drawings without implementing previous comments OR
submitting/resubmitting drawings, data, calculations or information that are incomplete, without sufficient details,
unclear, incorrect, not in agreement with other area or disciplines (Architectural/Structural/Services) OR
submitting drawings for works already executed at site without mentioning the status of such work etc., will be
subject to imposing relevant penalties in compliance with Trakhees CED violation procedures.

Page 1 of 1