ESQUEMA LINEA COMPUTO


TRAMO CENTRO TRANF. CARGA No. DE CONDUCTOR KVA-KM AV (%)
DESIGNA. LON(K-M) No. KVA TOT. KVA FASES CALIBRE KVA-KM PARCIAL TOTAL
1 2 3 4 5 6 7 8 9 10 11
REFERENCIA : APENDICE A - 12 - E
___
__%
FORMATO TIPO PARA COMPUTO DE CAIDA DE TENSION
CIRCUITOS SECUNDARIOS

NOMBRE DEL PROYECTO:___________________________ CENTR. DE TRANSF. No.______________________KVA


TIPO DE INSTALACION : __________________________ USUARIO TIPO __________________________________
TENSIÓN ________________V No. FASES______________ D M Up ______________________________________KVA
LIMITE DE CAIDA DE TENSION_______________________ CIRCUITO No. ___________________________________
FECHA: _______________________________________ MATERIAL DEL CONDUCTOR ______________________

ESQUEMA

ESQUEMA DEMAN CONDUCTOR COMPUTO


TRAMO NUMERO KVA (d) CALIBRE KVA(LT) KVA-M KVA-M AV (%)
DESIGNA. LONG.(M) USUARIOS PARCIAL
1 2 3 4 5 6 7 8 9
REFERENCIA : APENDICE A - 11 - D
APENDICE A - 12 - C
ON

_________KVA
____________
_________KVA
_____________
____________

V (%)
TOTAL
10
DEMANDA
usuarios d max lamp perdidas demanda
11 8.60 0.90 0.31 10.33
5 4.70 0.90 0.17 6.07
2 2.80 0.90 0.10 4.00
6 5.40 0.90 0.19 6.84
5 4.70 0.90 0.17 6.07
4 4.20 0.90 0.15 5.53
2 2.80 0.90 0.10 4.00
1 1.60 0.90 0.06 2.69
0.00 0.00
4 4.20 0.90 0.15 5.53
CALCULO DEMANDA DISEÑO TRANSFORMADOR KVA

Usuarios Dem. Máx A/P Perd. Fp DD Calculado Seleccionado

42 42.7 3.00 1.54 0.95 49.72 40 50

CALCULO DEMANDA DISEÑO TRANSFORMADOR KVA


Usuarios Dem. Máx A/P Perd. Fp DD Calculado Seleccionado
22 15.8 0.90 0.57 0.95 18.18 15 25
CALCULO DE CAIDA DE TENSION
NOMBRE DEL PROYECTO: WPAA CENTR. DE TRANSF. No. 50 KVA
TIPO DE INSTALACION : Aeréa USUARIO TIPO:D
TENSIÓN ________________V No. FASES 1 D M Up KVA
LIMITE DE CAIDA DE TENSION 3.5% CIRCUITO No.
FECHA: 7-Apr-10 MATERIAL DEL CONDUCTOR _ASC
ESQUEMA

ESQUEMA DEMAN CONDUCTOR COMPUTO


TRAMO NUMERO KVA (d) CALIBRE KVA(LT) KVA-M KVA-M AV (%)
DESIGNA. L.(M) USUARIOS PARCIAL TOTAL
1 2 3 4 5 6 7 8 9 10
0-1 10 26 20.9 2/0 766 208.9 0.27 0.27
1 - 2. 30 16 14.3 1/0 655 430.4 0.66 0.93
2 - 3. 20 14 12.9 1/0 655 258.6 0.39 1.32
3 - 5. 25 5 6.5 1/0 655 162.3 0.25 1.57
5 - 6. 30 2 4.4 1/0 655 132.7 0.20 1.77
3 - 7. 10 9 9.4 1/0 655 94.4 0.14 1.92
7 - 8. 40 7 7.9 1/0 655 316.5 0.48 2.40
8 -9. 40 3 5.2 1/0 655 207.4 0.32 2.72
1 - 10. 25 8 8.7 2/0 766 216.9 0.28 3.00
10 - 11. 30 4 5.9 2/0 766 178.5 0.23 3.23
1 - 14. 20 2 4.4 2/0 766 88.4 0.12 3.35

0 - 12. 40 12 17.4 2/0 766 696.0 0.91 0.91


12 - 13. 40 4 5.9 2/0 766 237.9 0.31 1.22
REFERENCIA : APENDICE A - 11 - D
APENDICE A - 12 - C
CALCULO DE CAIDA DE TENSION
NOMBRE DEL PROYECTO: WPAA CENTR. DE TRANSF. No. 25 KVA
TIPO DE INSTALACION : Aeréa USUARIO TIPO:D
TENSIÓN ________________V No. FASES 1 D M Up ________________________KVA
LIMITE DE CAIDA DE TENSI 3.5% CIRCUITO No. ______________________
FECHA: 7-Apr-10 MATERIAL DEL CONDUCTOR _ASC

ESQUEMA

ESQUEMA DEMAN CONDUCTOR COMPUTO


TRAMO NUMERO KVA (d) CALIBRE KVA KVA-M KVA-M AV (%)
DESIGNA. L.(M) USUARIOS PARCIAL TOTAL
1 2 3 4 5 6 7 8 9 10
0-1 20 11 10.3 2/0 429 206.5 0.48 0.48
1 - 2. 15 5 6.1 2/0 429 91.1 0.21 0.69
2 - 3. 40 2 4.0 2/0 429 160.0 0.37 1.07
1 - 5. 25 6 6.8 2/0 429 170.9 0.40 1.47
5 - 6. 25 5 6.1 2/0 429 151.8 0.35 1.82
6 - 7. 20 4 5.5 2/0 429 110.6 0.26 2.08
7 - 8. 30 2 4.0 2/0 429 120.0 0.28 2.36
6 -9. 12 1 2.7 2/0 429 32.3 0.08 2.43

0 - 10. 30 4 5.5 2/0 429 165.8 0.39 0.39


REFERENCIA : APENDICE A - 11 - D
APENDICE A - 12 - C
Potencia Voltaje MT Intensidad Fusible ( A )
VA V Calculado Seleccionado
25000 13800 3.623 4

Potencia Voltaje MT Intensidad Fusible ( A )


VA V Calculado Seleccionado
50000 13800 7.246 8

Potencia Voltaje MT Intensidad Fusible ( A )


VA V Calculado Seleccionado
75000 13800 10.870 12

Potencia Voltaje BT Intensidad Fusible ( A )


VA V Calculado Seleccionado
25000 240 83.333 100

Potencia Voltaje BT Intensidad Fusible ( A )


VA V Calculado Seleccionado
50000 240 166.667 200
CALCULO DE CAIDA DE TENSION
NOMBRE DEL PROYECTO: WPAA CENTR. DE TRANSF. No.
TIPO DE INSTALACION : Subterranea USUARIO TIPO:B
TENSIÓN ________________V No. FASES 1 D M Up KVA
LIMITE DE CAIDA DE TENSION 3.5% CIRCUITO No.
FECHA: 7-Apr-10 MATERIAL DEL CONDUCTOR _ASC
ESQUEMA

ESQUEMA DEMAN CONDUCTOR COMPUTO


TRAMO NUMERO KVA (d) CALIBRE KVA(LT) KVA-M KVA-M AV (%)
DESIGNA. L.(M) USUARIOS PARCIAL TOTAL
1 2 3 4 5 6 7 8 9 10
0-1 20 20 11.4 350 1850 228.0 0.12 0.12
1-2 60 16 11.4 350 1850 684.0 0.37 0.49
2-3 100 12 11.4 350 1850 1140.0 0.62 1.11
3-4 140 8 11.4 350 1850 1596.0 0.86 1.97
4-5 180 4 11.4 4/0 1410 2052.0 1.46 3.43
REFERENCIA : APENDICE A - 11 - D
APENDICE A - 12 - C
CALCULO DEMANDA DISEÑO TRANSFORMADOR KVA

Usuarios Dem. Máx A/P Perd. Fp DD Calculado Seleccionado

40 55.3 0.70 1.99 0.95 61.04 49 50

CALCULO DEMANDA DISEÑO TRANSFORMADOR KVA


Usuarios Dem. Máx A/P Perd. Fp DD Calculado Seleccionado
22 15.8 0.90 0.57 0.95 18.18 15 25
Potencia Voltaje MT Intensidad Fusible ( A )
VA V Calculado Seleccionado
50000 13800 7.246 8

Potencia Voltaje BT Intensidad Fusible ( A )


VA V Calculado Seleccionado
50000 120 333.333 350