Beruflich Dokumente
Kultur Dokumente
Abstract - A variety of models has been developed rated current. The 25 MVA transformer with 110/44/4
to represent transformers in switching surge studies. kV Y/Y/A windings was available to us for an extended
However, there is a paucity of data on the character- period and provided most of the results presented
istics of large power transformers to provide parame- here. An evaluation of the accuracy of several equiv-
ters for utilization in the models. This paper des- alent circuits has resulted. At lower currents, the
cribes a low power field method of saturating large described method also permitted observation of the be-
transformers and plotting the instantaneous magnetiza- haviour of minor hysteresis loops through reversals of
tion curve. Results on a 25 MVA unit allowed the ac- the excitation. The results show that hysteresis
curacy of several equivalent circuits to be compared. curves tend to follow a certain simple relationship
Minor hysteresis loops were observed to obey simple from which two models will be derived.
relationships from which two magnetizing inductance
models were developed. 2.0 TEST METHOD FOR MEASUREMENT
OF TRANSFOMER CHARACTERISTICS
1.0 INTRODUCTION
From Faraday's law, the induced voltage in a coil
Switching surge and other types of overvoltage with changing flux linkage is:
studies have been carried out for many years using
model networks (TNAs). More recently digital computer dk
programs have been developed for the purpose[l]. As a v =
dt
(1)
consequence, physical and analytical models have been
developed for the various elements of a power system.
These include generators, circuit breakers, and trans- therefore A fvdt
mission lines, with frequency-dependent losses if
required. Transformers, too, have been represented, That is, the change in flux linkage of a coil can
often by linear networks for simulations not involving be measured by integrating the induced voltage. This
saturation, ie, where the magnetizing branches could is the basis of the classical ballistic galvanometer
be neglected. method of measuring flux and of flux-meters. The
principle can be applied with modern instrumentation
There are, however, many studies in which trans- utilizing an electronic integrator[6].
former saturation effects are crucial, for example,
the overvoltages resulting from loss of load at the The application of this method to tranisformers
end of a long line with radial generation. Nonlinear requires that a changing current be applied to one
ferromagnetic effects including possible ferroreson- winding and the transient voltage appearing across a
ance predominate in such situations. Saturation ef- second winding be integrated to determine the flux
fects are ?lso important in protective relay applica- linkage. In fact, if a reversible dc supply is used,
tions as affected by inrush currents, and in problems the method can be regarded as excitation by very low
connected with generation of harmonics and with Tran- frequency ac, whereby high flux levels can be obtained
sient Interference Factor (TIF). For these studies, a with the application of low voltage and low power.
variety of models has been developed[l-51 whose va-
lidity has been verified by comparison with perform- 2.1 Measuring Mutual Inductance
ance of miniature model transformers, or by simulation
of power system disturbances. Very little data on The basic circuit of the instrumentation is shown
saturation characteristics of large power transformers in Fig. 1. The dc source S supplies varying current
has been available because it was assumed that this to the winding N1 of the transformer. As the flux 02
would require energization from a high power source at changes, the voltage v2 appearing at the terminals of
voltages considerably exceeding their rating. coil N2 is integrated by the operational amplifier A2
with the integrating time constant R4C2. In fact, the
In this paper we shall discuss a low power test flux linkage is proportional to the integrator output:
method which has been used in the field to obtain the
instantaneous magnetization characteristics of large J v2 dt
transformers. Using this method, a 250 MVA autotrans-
former, and two independent winding units rated 83.3
vA2 =( (2)
and 25 MVA have been tested to levels approaching
where R2 << R4 and may be neglected.
A signal proportional to current ij, is obtained
across the shunt Rs in the primary circuit. This
signal, vil, together with the flux-linkage signal vA2
can be fed to an X-Y recorder which plots flux linkage
against supply current. By reversal of the supply a
F 80 244-4 A paper recommended and approved by the complete hysteresis loop can be plotted between posi-
IEEE Transmission & Distribution Committee of the IEEE tive and negative current limits determined by the
Power Engineering Society for presentation at the IEEE supply power, source impedance and winding resistance
PES Winter Meeting, New York, NY February 3-8,1980. R1.
Manuscript submitted September 4, 1979; made available
for printing November 16, 1979.
COMPARISON OF TEST AIR-CORE INDUCTANCE AND INDUCTANCE CALCULATED FOR THREE EQUIVALENT CIRCUITS
3.2 Saturation - Three Phases Paralleled DC offset in neutral current increases apparent
power requirements, and could operate transformer pro-
On a core-type transformer, flux associated with tection. For shell-type and single phase transformers
neutral current returns outside the windings through the flux shift caused by neutral current directly in-
an air gap, structural steel and the tank. Fig. 5 creases the positive sequence magnetizing current.
shows the magnetization curve at high neutral current For a core-type transformer, the flux shift resulting
with the three HV windings paralleled. In contrast, from a given neutral current may be noted on Fig. 5.
to the results of Fig. 3 (same scales), the maximum The increase in positive sequence magnetizing current
inductance at the origin has greatly decreased to 5.20 for this flux shift may then be seen on Fig. 3. For
pu. At about 0.1 pu current per phase, part of the example, a dc neutral current (HV) of 270 A (0.5 pu
iron flux path saturates - evidently the iron tank - per phase) in the core-type transformer shifts the
leaving 1.33 pu inductance. Test current was limited average flux by 1.0 pu. Fig. 3 shows that a similar
to 0.6 pu with three phases energized. However, the shift in a shell-type transformer would require only
results of Fig. 3 predict further saturation (induct- about '0.01 pu current (5.4 A in neutral). Thus a
412
Pu 4A
Lm = 1700
1 .2 ii-*
o = 0.59 0.8.
i.
-0.06 -0.04 -0.02 -1.0 -0.5 0 0.5 1.0 x
pu
10o
ih = 0. 0007
legs and yokes. The outside phases have additional The numerical values for the inductances (Fig.
reluctance resulting from the core yokes between a1 10) werecalculated from both short circuit and dc
and a2, etc. Zero sequence flux flows from a to b test results (Fig. 4). An iterative approach was used
outside the windings through end frames, air and since equivalent circuits of this size are difficult
tank. Leakage flux may experience higher reluctance to synthesize. Air-core inductances derived from Fig.
between a and c due to flux shields which protect the 10 are listed in Table I for comparison with other
end frames. The detail shows the breakdown of flux equivalent circuits. The number of elements makes
paths assumed between, and distributed within, each of this circuit too cumbersome for most studies.
the three windings.
4.3 Modified Star-Equivalent Circuit
The topological dual of the magnetic equivalent
circuit is the required electric equivalent circuit, The detailed equivalent circuit had shown that
one phase of which is shown in Fig. 10. The induct- the magnetizing inductance should be connected near
ances may be related to physical geometry in the the inner (tertiary) winding and the zero sequence in-
transformer as follows: ductance near the outer (HV) winding. As illustrated
in Fig. 11, the star-equivalent circuit could be modi-
1. The negative inductances -Lh h6, -Lx . 6,p -L fied without increasing the number of elements. Table
~~~~y
6 result from the distribution of leakage flux I shows this change reduces the error significantly.
through the finite winding section. They are
approximately proportional to winding radial
thickness.
x
2. The leakage inductances Lhx and Lxy are propor-
tional to the distance between winding mean
radii.
A A
4
ol
0
Fig. 16 details the flux linkage - current plane -The transients program was modified with the as-
for a single backlash element. In region II the sistance of Dr. H.W. Dommel at the University of
switch must be closed since current is less than ih or British Columbia. About 50 Fortran statements were
flux linkage exceeds A In order to perform a major changed or added. The switch and current source were
loop, a to f, it is necessary to have the switch open implemented as a new two-terminal element labelled a
in reg'ions I and III. However, when -performing a flux switch with parameters As, Ar, and ih. The pa-
minor loop, g to j, the switch must be closed in rameter Ar Specifies an initial remanent flux.
regions I and III when the excitation reverses at g
and i. This may be recognized by a negative change in The flux switches were tested by modelling the
flux linkage AA in region III or a positive AA in magnetization characteristic of the 25-MVA transformer
region L. '- mentioned in section 3. Four flux switches connected
to appropriate inductances were used per phase. Fig.
At point i, a further condition must be taken 17 shows the result of simulating several minor loops
into account. As shown by the detail, AA was detected of increasing amplitude with current supplied to one
negative at point 3 followed ,by the switch closing. phase. Close inspection of the curves reveals at
At point 4, which could still be in region III, AA is least 7 distinct slopes. The flux switches present in
no longer strictly negative. To prevent the switch the other two phases were coupled through the three-
from opening, this situation is recognized from the limb core effect and provided the additional break-
points.
417
,'
Minor hysteresis loops were observed to obey
.0 simple relationships which describe the shape of the
curves and the significance of the reversal points.
These observations led to the construction of a tem-
I REMANENCE
-i m-
plate model with the storage of reversal points in a
INAL stack-type memory. This model assumes that hysteresis
.i
i:
77 I
and saturation are independent. In contrast, the de-
composition method assigns hysteresis and saturation
I :,.i
--7
]-,, T
parameters to each backlash element. The decomposi-
tion method was implemented into the transients pro-
_I.
gram of reference[l] and minor hysteresis loops were
_
Li
--I -f-
simulated.
-aLLL REFERENCES
Fig. 17. Magnetization Curve Resulting from Decompos-
ition Method [1] "Electromagnetic Transients Progam (EMTP) User's
Manual", Bonneville Power Administration,
The same model was also used to simulate the Revised November, 1977.
results of Fig. 4 and tests involving 60 Hz short cir-
cuits, closing/tripping onto an infinite bus, and a [2] H.W. Dommel, "Transformer Models in Simulation
ferroresonant study. The initial results show there of Electromagnetic Transients", 5th Power
may be a problem in choosing a small enough step size Systems Computation Conference, Cambridge
to accomodate both hysteresis and high current satura- (England), September 1-5, 1975, Paper No 3.1/4.
tion accurately. The tow magnetizing inductance fol-
lowing an excitation reversal tends to produce large [3] N. Germay, S. Mastero and J. Vroman, "Review of
current changes per time step. The. flux switches do Ferroresonance Phenomena in High-Voltage Power
not have time to open before the hysteresis intercept System and Presentation of a Voltage Transformer
has been overshot. Several thousand time steps per Model for Predetermining Them", CIGRE, 1974
power system cycle appear necessary when using a five- Session Paper 33-18.
slope model.
[4] A. Semlyen and A. Castro, "A Digital Transformer
6.0 -CONCLUSIONS Model for Switching Transient Calculations in
Three-Phase Systems" , PICA Conf, 9th, Proc, New
The paper has described a field method of satur- Orleans, LA, June 2-4, 1975, p. 121-126.
ating large transformers and plotting the magnetiza-
tion curve. Several advantages and limitations of [5] H.. Yamashita, E. Nakamae, M.S.A.A. Hammam and K.
using dc to energize the transformer were shown: Wakisho, "A Program to Analyze Transient
Phenomena of Circuits Including Precisely
1. Transformers rated 25-250 MVA.have been saturation Represented Transformers", IEEE PES Summer
tested at currents approaching their thermal Meeting, July, 1975, A 75 403-6.
rating. The power source supplies only small
resistive losses - typically 0.1% of the [6] G.W. Swift, "Power Transformer Core Behaviour
transformer rating. Under Transient Conditions", IEEE Transactions
PAS-90, No 5, September/October, 1971, p. 2206.
2. The plotted magnetization curve is instantaneous,
ie, does not require conversion from rms quanti- [7] G.R. Slemon, "Magnetoelectric Devices, Trans-
ties. ducers, Transformers and Machines", John Wiley
and Sons, 1966, p. 168.
3. The current reversals can be easily controlled to
investigate minor hysteresis loops. [8] G. Kron, "Equivalent Circuits of Electric
Machinery", John Wiley and Sons, 1951, p. 26.
418
Discussion
Adam Semlyen (University of Toronto): This paper contains important Phase c
and useful new information and basic knowledge related to core type
transformer modelling. It addresses basically the problem of producing
a simplified but sufficiently accurate transformer equivalent with cor-
rect representation of leakage, non-linear iron, and zero sequence in-
ductances. Special attention is given to hysteresis modelling with startl-
ing, new results regarding the effect of past history on minor loops.
While the losses associated with hysteresis are relatively small in large
transformers, hysteresis is very important to establish the remanence
conditions in the iron. Is the hysteresis model described in the paper
valid for a wider class of core material?
The transformer equivalent of Fig. 10 appears to be quite general for
a network with five terminals. This general condition is reemphasized in fo 1HX fXY tm
Fig. A, where the terminals are H, X, Y, 0, and 1, corresponding to
those in Fig. 10. The complete polygon between these terminals will
have ten branches. The authors have eleven. I assume that topological
considerations may produce such redundancies, just as they produce
simplifications, as shown in Fig. 11. Is this correct?
The simplified equivalent circuit of Fig. 11 is conceptually and prac-
tically important. The authors have retained only those branches bet-
ween terminals (Fig. A) where fluxes can topologically be identified. Fig. B Transformer model for building the simple equivalent circuit of
First two branches between H-X and X-Y to account for the two basic Fig. A. The path of +. may be ferromagnetic
leakage fluxes (between high and medium, and between medium and
low voltage windings). Then a corrective branch between H-Y, to ac- transformer representation of Fig. B. Fluxes are represented by double
count for the complexity produced by incomplete flux linkages. Zero- line arrows in air and in saturable parts of the core, where, for nonzero
sequence fluxes and core leg fluxes are clearly on opposite sides of the reluctances, non-infinite inductances appear in the equivalent circuit.
three windings: they are represented by the branches L. and Lm. All Since the sum of all fluxes represented in Fig. B is zero, the respective
other branches have been omitted. It is important to note that the resul- inductances in Fig. A form a loop. It is interesting to note that, if the
tant simplified model (Fig. 11) is still almost as good as the comples yoke saturates Lk#oo], the zero-sequence current is not the magnetizing
equivalent of Fig. 10, while the conventional model of Fig. 8 is incorrect current of L..
and useless (Table I). The latter has connected the magnetizing bran-
ches to the starpoint of the leakage inductances: L. should instead be Manuscript received February 4, 1980.
connected to the high-voltage terminal, and Lm to the low-voltage
terminal.
If the yoke can saturate, then it may be represented by a single non-
linear branch Lk, connected in the simplified equivalent in the way
shown in Fig. 10, or between 0 and 1 in Fig. A. In the case of five limb
cores, often met at large powers, L. is non-linear for the external phases
and so is Lk, because of reduced iron cross-section.
pu
0.,
0.
i
0.1
0 0.2 0.4 0.6 0.8 pu
FIGURE C
NON-LINEAR INDUCTANCES FOR
3 AND 5-LIMB TRANSFORMERS