Truss configuration
Angle of inclination of roof with horizontal = 21.5 degrees
Rafter length = 3.685 meters
Length of panels
L0-U1 = 0.67 m
U1-U2 = 0.95 m
U2-U3 = 0.95 m
U3-U4 = 0.95 m
U4-U0 = 0.165 m
Roof load Self wt. Sum W L purlin wt(N) Total load (N) kN Unit Point
200 72.78 272.78 3.786 0.67 782.56 1474.50 1.48 kN L0
200 72.78 272.78 3.786 0.81 782.56 1619.08 1.62 kN U1
200 72.78 272.78 3.786 0.95 782.56 1763.67 1.77 kN U2,U3
200 72.78 272.78 3.786 0.64 782.56 1443.52 1.45 kN U4
Total 8.09 kN
Wind loads
Coefficients k1 = 1
k2 = 0.85 Class A, Category 3, building height 3m approx)
k3 = 1
Wind velocity Vb = 47.5
Design wind speed Vz = 40.375
Design wind press. Pd = 978.08 N/sqm
0.98 kN/sq.m
h= 3.3 m above ground level
w= 6.834
h/w = 0.4829 < 1/2
External wind
pressure coefficient Cpe(windward) -0.35 angle = 21.5 from table 4 IS 875-3
Cpe(leeward) -0.7 angle = 21.5 from table 4 IS 875-3
Int. wind pre. Coeff. Cpi = +/- 0.2
Wind load (Cpe-Cpi)*Pd*A length Point
-2.237299 kN 0.67 L0
-2.704794 kN 0.81 U1
-3.172289 kN 0.95 U2,U3
-2.137121 kN 0.64 U4
uplift
Loads per unit length of purlin = -0.8379 kN/m