Note: all length units have been converted into meter/centimeters/millimeters

Length of building = 15.14 m


Width of building = 6.834 m
c/c Roof columns = 6.834 m
c/c spacing of truss = 3.786 m
Rise of truss = 1.347 m
Self wt. of purlins = 20.67 kg/m
= 206.7 N/m

Height of columns/supports = 1.347 m


Roofings and side coverings load = 200 N/sq.m (Assumed, including bracings)

Truss configuration
Angle of inclination of roof with horizontal = 21.5 degrees
Rafter length = 3.685 meters
Length of panels
L0-U1 = 0.67 m
U1-U2 = 0.95 m
U2-U3 = 0.95 m
U3-U4 = 0.95 m
U4-U0 = 0.165 m

Self weight of truss assumed = (span/3+5)*10


= 72.78 N/sq.m
Purlin = 782.57 N

Roof load Self wt. Sum W L purlin wt(N) Total load (N) kN Unit Point
200 72.78 272.78 3.786 0.67 782.56 1474.50 1.48 kN L0
200 72.78 272.78 3.786 0.81 782.56 1619.08 1.62 kN U1
200 72.78 272.78 3.786 0.95 782.56 1763.67 1.77 kN U2,U3
200 72.78 272.78 3.786 0.64 782.56 1443.52 1.45 kN U4
Total 8.09 kN

Live load = {750N-(21.5-10)*20} N/sq.m


520 N/sq.m

Total W L Total load (N) kN Point


520 3.786 0.67 1319.042 1.32 kN L0
520 3.786 0.81 1594.663 1.6 kN U1
520 3.786 0.95 1870.284 1.88 kN U2,U3
520 3.786 0.64 1259.981 1.26 kN U4
Total 7.94 kN

Wind loads
Coefficients k1 = 1
k2 = 0.85 Class A, Category 3, building height 3m approx)
k3 = 1
Wind velocity Vb = 47.5
Design wind speed Vz = 40.375
Design wind press. Pd = 978.08 N/sqm
0.98 kN/sq.m
h= 3.3 m above ground level
w= 6.834
h/w = 0.4829 < 1/2

External wind
pressure coefficient Cpe(windward) -0.35 angle = 21.5 from table 4 IS 875-3
Cpe(leeward) -0.7 angle = 21.5 from table 4 IS 875-3
Int. wind pre. Coeff. Cpi = +/- 0.2
Wind load (Cpe-Cpi)*Pd*A length Point
-2.237299 kN 0.67 L0
-2.704794 kN 0.81 U1
-3.172289 kN 0.95 U2,U3
-2.137121 kN 0.64 U4
uplift
Loads per unit length of purlin = -0.8379 kN/m

Wind load on panel points Angle in radian 0.375245789 0.375245789


Windward side length Point Vertical comp Dir.n Horizontal comp. Dir.n
F = -1.36724 kN 0.67 L0 -1.28 up -0.51 left
-1.65293 kN 0.81 U1 -1.54 up -0.61 left
-1.93862 kN 0.95 U2,U3 -1.81 up -0.72 left
-1.30602 kN 0.64 U4 -1.22 up -0.48 left

Leeward side length Point Vertical comp Horizontal comp.


F= -2.2373 kN 0.67 L0 -2.09 up -0.82 right
-2.70479 kN 0.81 U1 -2.52 up -1 right
-3.17229 kN 0.95 U2,U3 -2.96 up -1.17 right
-2.13712 kN 0.64 U4 -1.99 up -0.79 right