Beruflich Dokumente
Kultur Dokumente
Owner’s Manual
Transfer Switch
Models: 09227-0, 09228-0,
09229-0, and 09230-0
Read the following information carefully before attempting to install, operate or service this equip-
! ment. Also read the instructions and information on tags, decals, and labels that may be affixed to
the transfer switch. Replace any decal or label that is no longer legible.
!
DANGER! Connection of a generator to an electrical system normally supplied by an electric utility
! shall be by means of suitable transfer equipment so as to isolate the electric system from utility dis-
tribution system when the generator is operating (Article 701 Legally Required Standby Systems or !
Article 702 Optional Standby Systems, as applicable). Failure to isolate electric system by these
means may result in damage to generator and may result in injury or death to utility workers due to
backfeed of electrical energy.
Generac cannot possibly anticipate every possible cir This symbol points out important safety informa-
cumstance that might involve a hazard. The warn- ! tion that, if not followed, could endanger personal
ings in this manual, and on tags and decals safety and/or property of you and others.
affixed to the unit are, therefore, not all-inclusive. If
you use a procedure, work method or operating tech- This symbol points out potential explosion hazard.
nique Generac does not specifically recommend, you
must satisfy yourself that it is safe for you and others. This symbol points out potential fire hazard.
You also must make sure the procedure, work
method or operating technique that you choose does
not render the transfer switch unsafe. This symbol points out potential electrical shock
hazard.
Throughout this publication, and on tags and
decals affixed to the generator, DANGER, WARNING, ! GENERAL HAZARDS !
CAUTION and NOTE blocks are used to alert you to
special instruction about a particular operation that
may be hazardous if performed incorrectly or care- • Any AC generator that is used for backup power if
lessly. Observe them carefully. Their definitions are a NORMAL (utility) power source failure occurs,
as follows: must be isolated from the NORMAL (utility) power
source by means of an approved transfer switch.
Failure to properly isolate the NORMAL and
DANGER STANDBY power sources from each other may
After this heading, you can read instructions that, result in injury or death to electric utility workers,
if not strictly complied with, will result in personal due to backfeed of electrical energy.
injury or property damage. • Improper or unauthorized installation, operation,
service or repair of the equipment is extremely
dangerous and may result in death, serious per-
sonal injury, or damage to equipment and/or per-
After this heading, you can read instructions that, sonal property.
if not strictly complied with, may result in personal
• Extremely high and dangerous power voltages are
injury or property damage.
present inside an installed transfer switch. Any
contact with high voltage terminals, contacts or
wires will result in extremely hazardous, and pos-
After this heading, you can read instructions that, if sibly LETHAL, electric shock. DO NOT WORK ON
not strictly complied with, could result in damage to THE TRANSFER SWITCH UNTIL ALL POWER
equipment and/or property. VOLTAGE SUPPLIES TO THE SWITCH HAVE
NOTE: BEEN POSITIVELY TURNED OFF.
• Competent, qualified personnel should install,
After this heading, you can read explanatory
operate and service this equipment. Adhere strict-
statements that require special emphasis.
ly to local, state and national electrical and build-
These safety warnings cannot eliminate the hazards ing codes. When using this equipment, comply
that they indicate. Common sense and strict compli- with regulations the National Electrical Code
ance with the special instructions while performing the (NEC), CSA Standard; C22.1 Canadian Electric
service are essential to preventing accidents. Code and Occupational Safety and Health
Four commonly used safety symbols accompany the Administration (OSHA) have established.
DANGER, WARNING and CAUTION blocks. The type • Never handle any kind of electrical device while
of information each indicates follows: standing in water, while barefoot, or while hands
or feet are wet. DANGEROUS ELECTRICAL
SHOCK MAY RESULT.
Generac® Power Systems, Inc.
Table of Contents
14.32
19.92
00
UTILITY
SUPPLY NEUTRAL
N3, E3 AND T3 NOT CONNECTION
USED ON SINGLE PHASE E1
SYSTEMS
E2 CB2
TRANSFER
SWITCH
NEUTRAL E3
N1 N2 N3 LUG
UTILITY 1
UTILITY 2
LOAD 1
LOAD 2
194
23
UTILITY 1
E1 E2 E3 UTILITY 2
LOAD 2
NOTE:
23
POWER LEADS AND
TRANSFER SWITCH 194
LEADS MUST BE
RUN IN TWO
DIFFERENT CONDUITS.
REMOTE TEST
SWITCH (OPTIONAL)
CUSTOMER
- OPEN SWITCH TO TEST - LOAD
SWITCH TYPE, SPST AC GENERATOR
ELECTRICAL RATINGS, CONTROL PANEL
2A @ 250Vac MIN.
3.5 GENERATOR TESTS UNDER LOAD 5. When checkout under load is complete, set main
circuit breaker of the generator to its OFF or
1. Set the generator's main circuit breaker to its
OFF or OPEN position. OPEN position.
2. Manually actuate the transfer switch main con- 6. Let the generator run at no-load for several min-
tacts to their STANDBY position. utes. Then, shut down by setting the
Auto/Off/Manual switch to its OFF position.
3. To start the generator, set the Auto/Off/Manual
switch to MANUAL. When engine starts, let it sta- 7. With the manual transfer handle, move the
bilize for a few minutes. switch's main contacts back to their utility posi-
tion, i.e., load connected to utility power supply.
4. Turn the generator's main circuit breaker to its Handle and operating lever of transfer switch
ON or CLOSED position. The generator now pow- should be in down position.
ers all LOAD circuits. Check generator operation
under load as follows: 8. Turn on the utility power supply to transfer
switch, using whatever means provided (such as
• Turn ON electrical loads to the full rated a utility main line circuit breaker). The utility
wattage/amperage capacity of the generator. DO power source now powers the loads.
NOT OVERLOAD.
9. Set the generator's Auto/Off/Manual switch to its
• With maximum rated load applied, check voltage AUTO position. The system is now set for fully
and frequency across transfer switch terminals automatic operation.
E1 and E2. Voltage should be greater than 230
volts; frequency should be greater than 58 Hz.
• Let the generator run under rated load for at
least 30 minutes. With unit running, listen for
unusual noises, vibration, overheating, etc., that
might indicate a problem.
E1 E
E2
UTILITY 1
LOAD 1
LOAD 2
23
UTILITY 2
UTILITY 1
T1 T
T2 UTILITY 2
LOAD 1
NOTE:
Interconnection Diagram - Drawing No. 074106-A
N1 N1
N1
N1 N2
N2 126 A1
1
126 N1
7 A2
TR N2 B1 GTS
N1 N2
205
B2
N2
E2 T1 T2
A1 B1 T1
T1 T2
T2
205 LS1 2 3 5 6
NI
LS3
E1 E2
6 E2
TR RED 205 E2
9 126
WHITE C N2
N2 205
1 4
T2 E1
N2 126 T2
E1 LS2 T1
GTS
A2 B2 T1
1
NI B 9 6 3 TR
E2
NI
E1
205
N2 N2 E1
23
194
N2
N1
N1
23 23
LEGEND B
N2
T2
A
194
TR - RELAY, TRANSFER
NOTE:
TS - TERMINAL STRIP (CUSTOMER CONNECTION) ALL CONTACTS SHOWN WITH
TRANSFER SWITCH IN UTILITY
POSITION.
N2 126 A1
A2
N2 B1
N2
205
N1 B2 GTS
1 3 E2 T1 T2 T3
126 N1 T1
LS3 T2
T1
6 205 E1
TR RED 126
205
9 N2 NI
3-Pole Transfer Switch - Drawing No. 074499-B
WHITE C
NI 126
1 4 TR
T2
E1 LS2 T1
GTS A 7 1
B 9 6 3
A2 B2
Section 5 — Electrical Schematics and Wiring Diagrams
N2 E1
NI 205
E2 N3
E1
NI N1A 23
E1
2 1 8 7 194
N2
N3
23
N2 194
23 23 N1A
B
LEGEND TR
C - CONTACTOR ACTUATING COIL
GTS - TRANSFER SWITCH CONTACTOR A 3 4 5 6
194 194
23
N2
NI
T1
N1A
6
205 N2A
NB
A
TR (C1)
GTS
XA1
1
A
N2A
126
GTS
XA1 XB1
E2
205
A B N1A
E1 XB1
194
N2A N1A
(C2)
VR1 23 B
VR2
C1 C2
E1
E2
194
F3 N1A N2A T1A
T1A T1 T2A
T2A T2 N1A T1A T2A
E2 F4
F2
N2A N2 194
F1 F2 F3 F4
23
23 23
B
T2 194
TR N1 N2 T1
LEGEND T2
A
194 194 T1 23
C1- SOLENOID COIL (UTILITY CLOSING)
N2
C2- SOLENOID COIL (STANDBY CLOSING) N1
NOTE:
GTS - TRANSFER SWITCH CONTACTOR
ALL CONTACTS SHOWN WITH TS
TRANSFER SWITCH IN UTILITY
Transfer Switch - Drawing No. 081222-B
Section 5 — Electrical Schematics and Wiring Diagrams
TR - RELAY, TRANSFER
POSITION.
194
23
UTILITY 1
NB - NEUTRAL BLOCK
DECAL
13 31
DECAL
14
10 12
26 44
15
9 1
10 11 36
10 12
2 3 4
35
37
32 33 34 DECAL 38 39 40 41
6 7
42
22 21 5
16 DECAL
25 24 43 3 8
33 18
20
23
19
32 33
17
48
49
36 TO RETAIN COVER
33
22
22 23 16 21
9 11 12
13
23
A
7 19
3 16
21
A
8
25
DETAIL A-A
20
DECAL
28 (POWER TERMINAL LUG ASSY)
A
DECAL
35 14
15 16
47
24 (BOTTOM POWER TERMINALS)
45
40 41 42 43
34 6 4 5
11 12 31 32 1 46
TERM. STRIP
REF. ONLY
44
10 39
DECAL
30
DECAL 26
18
37
DECAL
17