Sie sind auf Seite 1von 8

724 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO.

4, OCTOBER 2001

Benchmark Systems for Digital Computer


Simulation of a Static Transfer Switch
IEEE PES TF on Simulation of FACTS and Custom Power Controllers
of
IEEE PES WG on Modeling and Analysis of System Transients Using Digital Systems

Abstract—This paper presents two benchmark systems for


time-domain simulation of a thyristor based Static Transfer
Switch (STS). The objectives are 1) to provide guidelines for
digital simulation of STS systems, 2) to provide a basis for perfor-
mance evaluation of simulation programs used for STS analysis
and 3) to benchmark performance of various detection/control
strategies adopted for STS systems. Each benchmark system is
composed of 1) supply system, 2) STS, and 3) sensitive load. The
two benchmark systems are referred to as STS-1 and STS-2.
Simulated performances of the two systems, based on the use
of PSCAD/EMTDC software package are provided. Simulation
results corresponding to STS-2 are also compared with the
corresponding measurement results.
Index Terms—Custom power, digital simulation, FACTS, static
transfer switch.

I. INTRODUCTION

T HE STS has been widely used in low-voltages applica-


tions. Availability of reliable semiconductor switches
and stringent voltage quality requirements of sensitive loads
Fig. 1. STS system structure.

II. PRINCIPLES OF OPERATION OF STS


have led to medium-voltage applications of STSs during the
The basic structure of a STS system is shown in Fig. 1. The
last few years [1]–[5]. Design and performance evaluation of
system is composed of:
a STS system require detailed analysis of the supply system,
STS and sensitive load. Such studies are best carried out by • a load which is sensitive to variations of utility supply,
means of digital time-domain simulation tools. This paper is to • two independent sources one of which is the preferred one
provide: 1) general guidelines for simulation of STS systems, and the other is the alternate one,
2) a benchmark for performance evaluation of various digital • two thyristor blocks and which connect the load to
time-domain software programs for simulation of STS systems, the power sources, and
and 3) a benchmark for evaluation of various detection/control • a control logic to monitor voltage quality of both sources,
approaches and strategies for STS systems. detect voltage fluctuations in the system (detection
Section II briefly describes principles of operation of a STS process), compare the two sources, and perform a load
[6], [7]. Sections III and IV introduce two benchmark systems transfer from one source to the other one if needed
STS-1 and STS-2. STS-1 is a medium-voltage system in which (transfer process).
the sensitive load is composed of a passive and a motor load. STS blocks and each contain three thyristor modules cor-
STS-2 is a low voltage system with a passive sensitive load. responding to the three phases of the system. Each thyristor
The PSCAD/EMTDC is used to simulate performance of both module includes two anti-parallel thyristor switches (
systems. The simulation results corresponding to STS-2 are also and ).
compared with experimental results. A discussion of the studies Under normal operating conditions, i.e., when the preferred
is reported in Section V. source meets load voltage requirements, the control logic trig-
gers only the thyristors of . If the preferred source cannot meet
voltage requirements, the control logic will transfer the load to
Manuscript received December 27, 1999.
Task force members: M. R. Iravani (Co-Chair), K. Sen (Co-Chair), A. Gole, the alternate source if it is in a better condition than the preferred
G. Irwin, B. Johnson, A. Keri, P. Lehn, J. Mahseredjin, J. A. Martinez, H. one. This is achieved by removing gating signals from thyris-
Mokhtari, M. Sedighy, and D. A. Woodford tors and triggering thyristors. In case of voltage recovery, the
Contributors: H. Mokhtari, M. R. Iravani, S. B. Dewan, P. Lehn, and J. A.
Martinez load is transferred back to the preferred source. Input signals in
Publisher Item Identifier S 0885-8977(01)08505-3. Fig. 1 are those required for controlling the STS operation.
0885–8977/01$10.00 © 2001 IEEE
TASKFORCE ON SIMULATION OF FACTS AND CUSTOM POWER CONTROLLERS: BENCHMARK SYSTEMS FOR DIGITAL COMPUTER SIMULATION 725

voltages into a synchronously rotating frame ( -to- ) based


on (1):

(1)

where:

Fig. 2. Power circuit of STS-1 benchmark system.


and:

where
, , and preferred-source line voltages;
, , and components of the preferred-
Fig. 3. Block diagram of the voltage detection scheme. source voltages in the rotating frame;
angular frequency of the rotating frame;
initial value of .
To offer ride-through capability, the load must be transferred The peak value of and is calculated as:
within the shortest possible time. Therefore, the STS must meet
the following requirements: (2)
• It must detect voltage fluctuations in the system as fast as
possible. The output of the transformation block, i.e., , is compared to
• In case the preferred source fails, it must perform a fast a dc reference, i.e., . The error is passed through a first-
load transfer to the alternate source. order low-pass filter which attenuates impact of voltage tran-
• The gating strategy, which controls the transfer process, sients. The filter introduces a delay to the error signal which is
must prevent paralleling the two sources. determined by the filter cut-off frequency ( ). The filter output
• Detection and transfer logic must function properly for all is then compared to a voltage-change tolerance limit ( ).
possible operating conditions. Output of the comparator is a transfer signal which initiates a
• Detection scheme must not be sensitive to temporary transfer process if the preferred source fails.
voltage transients, e.g., capacitor switchings. 2) Gating Strategy: The gating strategy is composed of
three identical sets of logic for the three phases of the system.
III. STS-1 BENCHMARK SYSTEM It provides selective gating patterns to thyristor switches which
results in a fast load transfer process and prevents source paral-
Fig. 2 shows a schematic diagram of STS-1 benchmark
leling. The selective gating strategy is based on the direction of
system which is composed of a power circuit and a control
line current flow. Fig. 4 shows the gating logic structure which
logic.
is composed of the following blocks:
A. Power Circuit 1) Current direction and zero-crossing detection logic
is responsible for detecting the status of the thyristor
Power circuit of STS-1 benchmark system is composed of switches, i.e., on/off state, and selecting the right switch
two 12 kV distribution feeders as preferred (p) and alternate (a) to trigger to prevent source paralleling during the transfer
sources. The sources are represented by ideal voltage sources in process. To avoid multiple zero-crossing detection, line
series with lumped resistances and inductances. The combina- currents are passed through a smoothing first-order
tion of the load and load transformer is connected to the sources low-pass filter. Output of the filter is an input to a hys-
through thyristor blocks and . teresis comparator which detects the direction of current
flow. The hysteresis comparator is used to make sure that
B. Control Logic current direction can be detected and the transfer process
Control logic of STS-1 is composed of a voltage detection can begin for all possible loading conditions. The hys-
and a gating strategy section. teresis comparator compares its input to a zero-current
1) Voltage Detection: Fig. 3 depicts a block diagram of the threshold limit ( ) and preserves its output status as
voltage detection scheme. The logic is based on transforming ac long as the line current is within .
726 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO. 4, OCTOBER 2001

Fig. 5. Load transformer magnetizing curve.

Fig. 4. Gating logic structure.

2) Gating-pattern generation logic generates selective


gating signals for both and thyristor switches
according to the direction of current flow. For example,
if (outgoing switch) is conducting at the time a
disturbance is detected, the transfer process begins with
triggering (incoming switch). The other thyristor,
i.e., , will be gated when both and are
turned off. During the transfer operation, two scenarios
may occur in each phase. The first scenario is when
commutation begins as soon as the incoming thyristor,
e.g., , is gated. In this case, is triggered when the
preferred-source current drops below, and the alternate-
source current exceeds, the zero-current threshold limit
. The second scenario occurs when commutation
fails between the incoming and outgoing thyristors. In
this case, the outgoing thyristors continue conducting
until a zero crossing is reached and commutation begins.
A turn-off time is also considered before gating to
make sure that the outgoing thyristors have regained their
blocking capability.
3) Line voltage to phase voltage conversion and
zero-voltage back-up transfer logic transfers the
load at the zero crossing of the phase voltage if the
change of current direction and current zero-crossing Fig. 6. RL Load, 35% three-phase under voltage disturbance.
cannot be detected. This may occur for low values of line
currents, e.g., no load conditions, when the line current is • Each pair of thyristor valves has a snubber circuit com-
within . The zero-voltage back-up transfer circuit posed of M and F (Impact of
optimizes transfer time if the transfer process based on snubber circuit on the STS system is insignificant).
current direction does not succeed. • Load system is composed of a three-phase RL load in par-
allel with an induction motor. The series RL load has the
C. Parameters of STS-1 Benchmark System
following parameters:
With respect to Fig. 2, parameters of STS-1 benchmark ,
system are as follows: The motor load is rated at:
• Preferred and alternate source systems: 480 V, 500 kVA, 60 Hz, 3528 rpm
12 kV, 60 Hz Other parameters of the motor are:
, Inertia Constant H 1 s
• Three-phase load transformer stator resistance 0.33 p.u.
12 kV/480 V, 1 MVA, 60 Hz first cage resistance 0.2 p.u.
Leakage Reactance = 12% second cage resistance 0.018 p.u.
Resistance representing winding losses = 1.5%, stator unsaturated leakage reactance 0.098 p.u.
Resistance representing core losses = 0.5% mutual unsaturated reactance 3.1 p.u.
Transformer magnetizing curve is shown in Fig. 5. rotor unsaturated mutual reactance 0.1 p.u.
TASKFORCE ON SIMULATION OF FACTS AND CUSTOM POWER CONTROLLERS: BENCHMARK SYSTEMS FOR DIGITAL COMPUTER SIMULATION 727

Fig. 7. RL load, single-phase-to-ground fault. Fig. 8. RL + motor load, 35% three-phase under voltage disturbance.

second cage unsaturated reactance 0.105 p.u. Case 1: RL Load, Three-Phase Under Voltage: Fig. 6 shows
mechanical damping 0.008 p.u. a case in which a 35% three-phase under voltage occurs in
• Control circuit parameters: the system at ms when phase-a voltage angle is
kV ( ). The disturbance is detected at
voltage-change tolerance limit % ms [Fig. 6(b)] which results in a detection time of
filter cut-off frequency Hz 1.39 ms. Commutation in phase-b and phase-c is completed
line current smoothing filter cut-off frequency 1 kHz with no delay [Fig. 6(d) and (e)] but fails in phase-a [Fig. 6(c)].
zero-current threshold limit A At , phase-a current direction is positive and, therefore, is
thyristor turn-off time 1 ms gated. However, the voltage drop across the incoming thyristor
sampling rate 6660 Hz. is negative and it cannot be turned on. The disturbance
instant is such that the detection occurs at the zero crossing
D. Case Studies of phase-a voltage ( ) which results in maximum transfer
time. The control logic allows phase-a current to cross zero
Figs. 6–11 show simulated performance of STS-1 benchmark by re-gating . After 1 ms, i.e., at 8.49 ms, is forward
system. The simulations are performed by PSCAD/EMTDC biased and gated to successfully transfer phase-a to the alternate
package. Under voltage disturbances are created by reducing source. The maximum transfer time, which occurs in phase-a, is
the amplitude of the preferred source voltage. Faults are created 3.05 ms. The total load-transfer time is 4.44 ms. Load voltages
at the preferred source terminals. Fault resistance of 0.01 are shown in Fig. 6(a).
is considered. Definitions of detection, transfer and total Case 2: RL Load, Single-Phase-To-Ground Fault: Case 2
load-transfer times are as follows: presents the simulation results when phase-a of the preferred
detection time: The difference between the time at which source is subjected to a single-phase-to-ground fault. The wave-
a disturbance occurs and the time it is detected. forms are shown in Fig. 7. The fault occurs at ms
transfer time: The difference between the time at which a ( ) and is detected after 4.38 ms, i.e., at ms
disturbance is detected and the time at which the last faulty [Fig. 7(c)]. At this time, phase-a line current is negative, and
phase is transferred. the incoming thyristor is positively biased. Therefore, the
total load-transfer time: The sum of detection time and transfer process in this faulty phase is completed with almost
transfer time. no delay [Fig. 7(d)]. The transfer time is only the commutation
728 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO. 4, OCTOBER 2001

Fig. 9. RL + motor load, 80% three-phase under voltage disturbance. Fig. 10. RL + motor load, phase-to-phase fault.

time which is negligible, and the total load-transfer time is equal cannot conduct. Commutation in phase-b fails, and the load
to the detection time, i.e., 4.38 ms. becomes regenerative feeding the preferred source through .
Case 3: RL Motor Load, 35% Three-Phase Under Commutation cannot begin until the incoming thyristor is
Voltage: In this case, the preferred source is subjected to a positively biased. This occurs at the zero crossing of phase-b
35% three-phase under voltage disturbance when the load is voltage. The transfer is completed at 11.41 ms. Therefore, the
a combination of an RL load and a motor load. The system maximum transfer time (8.23 ms) occurs in phase-b. The total
behavior is shown in Fig. 8. This disturbance scenario is load-transfer time is 8.69 ms.
similar to Case 1 where only an RL load was employed. The Case 5: RL Motor Load, Phase-To-Phase Fault: Fig. 10
disturbance occurs at ms ( ) and is detected at shows the STS performance for the same regenerative load
ms (detection time of 1.39 ms). Phase-b and phase-c when a phase-to-phase fault occurs at ms between
are transferred to the alternate source as soon as the fault is phase-a and phase-b of the preferred source. It is detected
detected. Phase-a has to wait for the current zero-crossing at ms. The detection time is 2.85 ms. Commu-
which is reached at ms (including thyristor turn-off tation in both faulty phases fails. The transfer is completed
time). The transfer time and the total load-transfer time are at ms when both incoming thyristors ( for
3.25 ms and 4.64 ms, respectively. phase-a and for phase-b) are positively biased. The transfer
Case 4: RL Motor Load, 80% Three-Phase Under time and total load-transfer time are 5.83 ms and 8.68 ms,
Voltage: Fig. 9 shows the system behavior for a condition respectively.
where the load becomes regenerative. The system is subjected Case 6: RL+Motor Load, Cross Current Phenomenon: The
to a disturbance which results in a three-phase 80% under cross current phenomenon may occur when current direction
voltage. The load is the same as that of Case 3. The distur- is not correctly detected. This is due to the inaccuracy of cur-
bance occurs at ms ( ) and is detected at rent measurement devices when line currents are within .
ms corresponding to a detection time of 0.46 ms. Fig. 11 shows the impact of the cross current phenomenon on
Commutation in phase-a and phase-c begins as soon as the the STS performance. The zero-current threshold limit is
fault is detected, and these two phases are transferred to the set to 1% of the load nominal current, i.e. 4.8 A. Therefore, if
alternate source with no delays. However, in phase-b, due to the line current is within 4.8 A, the detected current directions
the opposite signs of line current direction and phase voltage may not be correct. Fig. 11(a) shows a phase-to-phase fault be-
polarity, the incoming thyristor is negatively biased and tween phase-a and phase-b at ms. As Fig. 11(c) shows,
TASKFORCE ON SIMULATION OF FACTS AND CUSTOM POWER CONTROLLERS: BENCHMARK SYSTEMS FOR DIGITAL COMPUTER SIMULATION 729

Fig. 11. RL + motor load, cross current phenomenon. Fig. 13. 35% three-phase under voltage disturbance (STS-2).

Therefore, resistor is inserted in the preferred feeder path to


practically decouple the two feeders. Variac compensates for
voltage drop across . The fault circuit is composed of a fault
resistance which is used for creating under voltage distur-
bances. Switch is also used to bypass for creating faults
to ground. Thyristor switch is employed to create timed fault.

A. Parameters of STS-2 Benchmark System


Parameters for STS-2 benchmark system are as follows:
Fig. 12. Single-line diagram of STS-2 benchmark system. • Main source: 120 V, 60 Hz, ,
• Decoupling resistance
in phase-a, the wrong incoming thyristor is gated at the time the
• Thyristor switches , , and : 50 A, 500 V snubber
fault is detected resulting in a cross current.
resistance , snubber capacitance F
• Load Transformer:
IV. STS-2 BENCHMARK SYSTEM , 4 kVA, 220 V/120 V, ,
Fig. 12 shows a single-line diagram of the three-phase STS-2 HV and LV sides are connected to the system and load,
benchmark system. An experimental set-up corresponding to respectively.
the system of Fig. 12 is developed and the simulation and ex- • Load: ,
perimental results corresponding to the STS behavior are pro- • Fault resistance
vided. A digital control system including voltage detection and • Variac: represented by an ideal lossless transformer
transfer logic, is adopted for STS-2 benchmark system. The con- • Control circuit parameters:
trol system is realized based on a UHP40 platform [8] which sampling frequency 6660 Hz
utilizes a floating-point TMS320C40 digital signal processor. V
The control system is analogous to the one used for the STS-1 voltage-change tolerance limit %
benchmark system. filter cut-off frequency Hz
Due to limitations in the laboratory, the preferred and al- line current smoothing filter cut-off frequency 1 kHz
ternate feeders are output feeders of a single transformer. The zero-current threshold limit A
preferred and alternate feeders are not completely independent. thyristor turn-off time 1 ms
730 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 16, NO. 4, OCTOBER 2001

Fig. 15. Phase-to-phase fault (STS-2).


Fig. 14. Single-phase-to-ground fault (STS-2).

TABLE I
B. Case Studies STUDY RESULTS SUMMARY—STS-1 BENCHMARK SYSTEM

Figs. 13–15 show performance of STS-2 benchmark system


under different operating conditions and compare corre-
sponding simulation and experimental results.
Case 1: RL Load, Three-Phase Under Voltage: This case
studies the STS performance when the preferred source is sub-
jected to a 35% three-phase under voltage disturbance. The dis-
turbance is created by gating fault thyristor at 14.5 ms (
open). Fig. 13(a) and (c) show load voltages obtained from ex- Case 3: RL Load, Phase-To-Phase Fault: Case 3 studies
periment and simulation respectively. The maximum transfer the performance of STS-2 benchmark system when a
time occurs in phase-a. Phase-b and phase-c are transferred to phase-to-phase fault, at ms ( ), occurs be-
the alternate source immediately after fault detection. Fig. 13(b) tween phase-a and phase-b of the preferred source. The results
and (d) show line current in phase-a. From the simulation wave- are shown in Fig. 15. Load voltages are shown in Fig. 15(a)
forms, the detection and transfer times are 1.4 ms and 2.9 ms, re- and (c). Phase-a line current is shown in Fig. 15(b) and (d).
spectively. The experimental waveforms show a detection time Fig. 15(a) and (b) indicate detection and transfer times of 4.4
of 1.65 ms and a transfer time of 3.3 ms. The total load-transfer and 3.6 ms for the experiment. Fig. 15(c) and (d) show detection
time is 4.3 for the simulation and 4.95 ms for the experiment. and transfer times of 4.45 and 3.35 ms for the simulation. The
Case 2: RL Load, Single-Phase-To-Ground- total load-transfer time is 7.8 and 8.00 ms for the simulation
Fault: Fig. 14(a)–(d) provide the simulation and experimental and experiment, respectively.
waveforms in the case of a single-phase-to-ground fault in
phase-a of the preferred source at ms ( ). V. DISCUSSION OF RESULTS
Fig. 14(a) and (c) show detection times of 4.65 ms and 4.45 ms
for the experiment and simulation, respectively. Fig. 14(b) A. Performance of Control Strategy
and (d) show that the transfer time is negligible for the given Tables I and II summarize the study results for STS-1 and
disturbance. Therefore, the total load-transfer time is almost STS-2 benchmark systems respectively. Characteristics, e.g.,
equal to the detection time. fault type and fault instant, as well as the detection logic. The
TASKFORCE ON SIMULATION OF FACTS AND CUSTOM POWER CONTROLLERS: BENCHMARK SYSTEMS FOR DIGITAL COMPUTER SIMULATION 731

TABLE II are not completely independent, and in some cases due to


STUDY RESULTS SUMMARY—STS-2 BENCHMARK SYSTEM line impedances, they become slightly out of phase. This
affects the commutation process which in turn impacts the
transfer time.
• Thyristors that are used for the STS and the fault circuit in
the experimental set-up and the load transformer are not
ideal components.
• The voltage and current sensors in the experimental set-up
are not ideal.
• In the simulation studies, the system voltages are assumed
to be clean 60 Hz sinusoidal signals. However, as the ex-
perimental waveforms show, the real voltage waveforms
have noticeable harmonic contents.
detection time is shorter for a more severe fault. The response
of the voltage detection logic is mainly determined by the filter VI. CONCLUSION
cut-off frequency . The higher the , the faster the detection
circuit and the shorter the detection time. However, increasing This paper introduces two benchmark systems for time-
makes the logic more sensitive to voltage transients, e.g., domain simulation of the Static Transfer Switch (STS). The
capacitor switchings. Therefore, a trade-off needs to be made first system, STS-1, is a medium-voltage system in which
between the speed of the detection logic and its sensitivity to the sensitive load is composed of a passive component and a
voltage transients. motor load. The second system, STS-2, is a low voltage system
The transfer time is determined by gating strategy, load type, with a passive sensitive load. The PSCAD/EMTDC is used to
fault type, fault instant and system configuration. Each phase simulate performance of both systems. Experimental results
has its own transfer time, and the maximum transfer time occurs corresponding to STS-2 are also verified.
in the phase for which the commutation process fails. Commu-
tation fails when the voltage drop across the incoming thyristor REFERENCES
is negative. The worst case scenarios occur for a regenerative
[1] R. W. De Doncker, W. T. Eudy, J. A. Maranto, H. Mehta, and J. W.
load when the load feeds the fault through thyristors, and the Schwartzenberg, “Medium voltage subcycle transfer switch,” Power
transfer cannot be completed until the polarity of voltage drop Quality Assurance, pp. 46–51, July/Aug. 1995.
across the incoming thyristor changes. [2] T. Musaki, Y. Kataoka, M. Ono, and Y. Yokoi, “Development of static
transfer switching equipment for different distribution systems,” in
Since the selective gating strategy is based on detecting line IPEC, Yokohama, 1995, pp. 1588–1593.
current direction, the structure of the direction detection logic [3] J. W. Schwartzenberg and R. W. De Doncker, “15 kV medium voltage
plays an important role in the performance of STS. The more static transfer switch,” in IEEE IAS 30th Annual Meeting, Oct. 1995, pp.
2515–2520.
accurate the current direction detection circuit, the better the [4] M. Takeda, H. Yamamoto, and G. F. Reed, “Development of a novel
performance of STS. Erroneous current direction detection may hybrid switch device and application to a solid-state transfer switch,” in
result in a cross current between the two sources. Proceeding of IEEE—PES Winter Meeting, New York, USA, Jan.–Feb.
1999.
[5] G. F. Reed, M. Takeda, and I. Iyoda, “Improved power quality solutions
B. Comparison of Simulation and Experimental Results using advanced Solid-state switching and static compensation technolo-
gies,” in Proceeding of IEEE-PES Winter Meeting, New York, USA,
Table II shows that the simulation and experimental results Jan.–Feb. 1999.
are in close agreement for STS-2 benchmark system. The slight [6] D. C. Griffith, Uninterruptible Power Supplies: Marcel Deckker, 1989.
differences are due to the following reasons: [7] H. Mokhtari, “High speed silicon controlled rectifier static transfer
switch,” Ph.D. dissertation, Dept. of Electrical and Computer Engi-
• In the experimental set-up, the sources are not ideal and neering, University of Toronto, 1999.
decoupled by a decoupling resistor. Therefore, the sources [8] S. Krebs, “UHP40 User’s Manual,” University of Toronto, Dec. 1995.

Das könnte Ihnen auch gefallen