Para. F.1.2.1: VECTORS AND LOADS: (Vectors are FROM the nozzle centre TO the pump centre.)
Standard API allowable loads (where applied) are extracted from table 2-1B and converted to SI units.
SUCTION: Vector X Vector Y Vector Z Force X Force Y Force Z Moment X Moment Y Moment Z
mm. mm. mm. N. N. N. Nm. Nm. Nm.
Table 4 allowable loads x factor 2.00 16012.8 13344. 10675.2 12204. 5966.4 9220.8
Status: - ok - - ok - - ok - - ok - - ok - - ok -
DISCHARGE: Vector X Vector Y Vector Z Force X Force Y Force Z Moment X Moment Y Moment Z
mm. mm. mm. N. N. N. Nm. Nm. Nm.
GLOBAL AXIS: -381 -311 7117 8674 445 678 -4882 3390
LOCAL AXIS: 0 311 -381 7117 -445 8674 678 -3390 -4882
Table 4 allowable loads x factor 2.00 13344. 10675.2 16012.8 12204. 5966.4 9220.8
Status: - ok - - ok - - ok - - ok - - ok - - ok -
__________________________________________________________________________________________________
Para. F.1
F1 = (FRSa / 1.5 FRSt4) + (MRSa / MRSt4) <= 2.00 F1 = 1.63 Within Allowable
F2 = (FRDa / 1.5 FRDt4) + (MRDa / MDSt4) <= 2.00 F2 = 1.13 Within Allowable
__________________________________________________________________________________________________
Para. F.1
F3 = 0.75 Fn (FRSt4 +FRDt4) > FRCa F3 = 34694.4 FRCa = 20022.7 Within Allowable
F5 = 0.75 Fn (MRSt4 + MRDt4) > MRCa F5 = 24814.8 MRCa = 11091.8 Within Allowable
Complies with para's F1, using the specified 'Fn' value. LOADS ARE ACCEPTABLE.
End of calculation