Beruflich Dokumente
Kultur Dokumente
Moist air can be made to flow over a battery of cooling coils which may be of the direct-expansion type, or
may carry chilled-water or brine as the secondary refrigerant (Fig. 42). Sensible or simple cooling of air takes
place when it flows over dry cooling coil whose surface temperature tS is lower than dry bulb temperature of the
air.
There is no method by which one can obtain simple dehumidification of air. Dehumidification processes
are accompanied with simultaneous cooling or heating of air. Dehumidification will take place along with
cooling if moist air flows over a cooling coil, whose mean surface temperature tS is below the dew point
temperature tdp of the entering air. This temperature tS of the cold surface is named apparatus dewpoint of the
coil, or simply as coil ADP or tADP.
In Figure 42 shows the air enters at 1 and leaves at 2 when the surface is maintained at S. In the transfer of
heat and water vapour, in any conditioning process, the particles of air stream come in contact with a surface.
The state of contacted air mCS is that of saturated air at the temperature of the surface tS. The uncontacted air
or bypass air mB1 remains at the entering state 1. The end state of the air is the same as that produced by the
complex mixing of contacted and uncontacted particles, viz., 2 as shown in Figure 43.
where: mB1 = mass of bypass air (or wise air) which remains at temperature t1.
mCS = mass of contacted air (or saturated air at surface temperature, ts)
m2 = total mass
– ratio of the mass of by-passed air, mB1 (also called wise air) to the total mass m2.
– fraction of air that by-passed the cooling unit and is not affected at all thus, it leaves the air conditioning
unit (ACU) at the same temperature, t1
– vital parameter signifying the performance of air-conditioning equipment.
– ratio of the mass of contacted air, mc on the cooling coil or plate to the total mass of air, m2.
– fraction of air that touches the cooling coil and leaves air at temperature equal to mean surface
temperature of the cooling coil or Apparatus Dew Point of the coil.
Following equations apply to the mixture of bypass air and uncontacted air:
m2 = mB1 + mcs
therefore,
mB1 = t2 – ts = BPF
m2 t1 – ts
also
mB1 = W2 – Ws = h2 – hs = BPF
m2 W1 – Ws h1 – hs
therefore, mcs = t1 – t2 = h1 – h2 = W1 – W2 = CF
m2 t1 – ts h1 – h2 W1 – Ws
also, BPF + CF = 1
Note:
If Bypass Factor (BPF) is not given or equal to zero, then RH2 = 100% or air leaves the ACU as
saturated air. That is td2 = ts (mean surface temperature of coil or Apparatus Dew Point temperature,
tADP).
Sample Problem
1.) Three pounds per second of air enters and leaves the coil at 80oF and 60oF respectively, the coil
temperature is 50oF. Determine (a) the contact factor (b) the bypass factor (c) apparatus dew point and
(d) the amount of bypassed air in one minute. Ans: (a) 66.67% (b) 33.33% (c) 50oF (d) 60 lbs
Solution:
(d) mB1 = m2 x BPF x Δtime = m2 x mB1 x Δtime = 3 lbs/sec x 0.3333 lbs (bypassed) x 60 sec
m2 lbs (total)
mB1 = 60 lbs
COOLING-LOAD AIR QUANTITIES
If a building or conditioned space to be air conditioned receives heat due to transmission or other means, it
is supposed to have sensible heat load. Heat gain in buildings require the conditioning of supply air to lower
temperature causing a cooling load on the air-conditioning equipment.
Illustrations:
Qs = m cp (t2 – t1)
If the building gains moisture, it is supposed to have a latent heat load. A gain of moisture will require the
condensation of moisture for the dehumidification of supply air in the conditioning apparatus hence cooling
load.
Illustrations:
QT = Qs + QL
SHR = Qs . = Qs .
QT Qs + QL
A SHR of 0.78 to 0.8 is quite common in air conditioning practice in a normal dry climate. A lower
value of SHR such as 0.65, implies a high latent heat load which is quite common in a humid
climate.
Sample Problems:
1.) An auditorium is to be maintained at a temperature of 25 oC dry bulb and 19oC wet bulb temperatures. The
sensible heat load is 88 kW and 58 kg/hr of moisture must be removed. Air is supplied to the auditorium at
18oC. Determine (a) the mass flow rate of supply air, (b) the relative humidity, dew point, and wet bulb
temperatures of the supply air, (c) the latent heat, and (d) the sensible heat ratio.
Solution: Given: t2 = 25oC; tw2 = 19oC; Qs = 88 kW; t1 = 18oC; Rate of moisture pick up = 58 kg/hr
(b) From the psychrometric chart at t2 = 25oC and tw2 = 19oC the W2 = 0.0114 kg/kgd.a
2.) An auditorium is to be maintained at 25oC dry bulb temperature and 50 percent relative humidity. The
supply air enters the auditorium at 17oC. The sensible and latent heat loads are 150 kW and 61 kW,
respectively. Determine the wet bulb temperature, relative humidity, and volume flow rate of the supply
air. Ans: 14oC, 72%, 15.54 m3/sec