1MRS756378 P Section 3

REF615 standard configurations

Section 3 REF615 standard configurations

3.1 Standard configurations

REF615 is available in twelve alternative standard configurations. The standard


signal configuration can be altered by means of the signal matrix or the graphical
application functionality of the Protection and Control IED Manager PCM600.
Further, the application configuration functionality of PCM600 supports the
creation of multi-layer logic functions using various logical elements, including
timers and flip-flops. By combining protection functions with logic function
blocks, the IED configuration can be adapted to user-specific application
requirements.

The IED is delivered from the factory with default connections described in the
functional diagrams for binary inputs, binary outputs, function-to-function
connections and alarm LEDs. The positive measuring direction of directional
protection functions is towards the outgoing feeder.

Table 9: Standard configurations


Description Std. conf.
Non-directional overcurrent and directional earth-fault protection and CB control A
Non-directional overcurrent and directional earth-fault protection, CB condition monitoring, CB
control and with the optional I/O module control of two network objects B
Non-directional overcurrent and non-directional earth-fault protection and CB control C
Non-directional overcurrent and non-directional earth-fault protection, CB condition monitoring, CB
control and with the optional I/O module control of two network objects D
Non-directional overcurrent and directional earth-fault protection with phase-voltage based
measurements, CB condition monitoring and CB control E
Directional overcurrent and directional earth-fault protection with phase-voltage based
measurements, undervoltage and overvoltage protection, CB condition monitoring and CB control F
Directional overcurrent and directional earth-fault protection, phase-voltage based protection and
measurement functions, CB condition monitoring, CB control and sensor inputs for phase currents
and phase voltages G
Non-directional overcurrent and non-directional earth-fault protection, phase-voltage and frequency
based protection and measurement functions, synchro-check , CB condition monitoring and CB control H
Directional overcurrent and directional earth-fault protection, phase-voltage and frequency based
protection and measurement functions, synchro check, CB condition monitoring and CB control J
Directional overcurrent and directional earth-fault protection, high impedance restricted earth-fault
protection, phase voltage and frequency based protection and measurements functions, synchro-
check, CB condition monitoring, CB control and fault locator (optional) K
Directional overcurrent and directional earth-fault protection, phase voltage and frequency based
protection and measurement functions and CB condition monitoring, CB control, sensor inputs for
phase currents and phase voltages and fault locator (optional) L
Directional and non-directional overcurrent and earth-fault protection, phase voltage and frequency
based protection and measurements, synchro-check, CB condition monitoring, CB control and fault
locator (optional) N

REF615 35
Application Manual
Section 3 1MRS756378 P
REF615 standard configurations

Table 10: Supported functions

Function IEC 61850 A B C D E F G H J K L N


Protection1)
Three-phase non-
directional overcurrent PHLPTOC 1 1 1 1 1 1 1 2
protection, low stage
Three-phase non-
directional overcurrent PHHPTOC 2 2 2 2 2 2 1 1
protection, high stage
Three-phase non-
directional overcurrent
PHIPTOC 1 1 1 1 1 1 1 1 1 1 1 1
protection, instantaneous
stage
Three-phase directional
overcurrent protection, low DPHLPDOC 2 2 2 1 2 2
stage
Three-phase directional
overcurrent protection, high DPHHPDOC 1 1 1 1 1 1
stage
Non-directional earth-fault
EFLPTOC 2 2) 2 2) 2 2) 2 2) 2 2)
protection, low stage
Non-directional earth-fault
EFHPTOC 1 2) 1 2) 1 2) 1 2) 1 2)
protection, high stage
Non-directional earth-fault
protection, instantaneous EFIPTOC 1 2) 1 2) 1 2) 1 2) 1 2)
stage
Directional earth-fault
DEFLPDEF 2 2)3) 2 2)3) 2 2)4) 2 2)4) 2 2)5) 2 2)4) 1 2)4) 2 6)7) 2 2)4)
protection, low stage
Directional earth-fault
DEFHPDEF 1 2)3) 1 2)3) 1 2)4) 1 2)4) 1 2)5) 1 2)4) 1 2)4) 1 2)7) 1 2)4)
protection, high stage
Admittance-based earth- (3) (3) (3) (3) (3) (3) (3) (3)
EFPADM
fault protection 8) 2)3)8) 2)3)8) 2)4)8) 2)4)8) 2)7)8) 2)4)8) 2)7)8) 2)4)8)

Wattmetric-based earth- (3) (3) (3) (3) (3) (3) (3) (3)
WPWDE
fault protection 8) 2)3)8) 2)3)8) 2)4)8) 2)4)8) 2)7)8) 2)4)8) 2)7)8) 2)4)8)

Transient/intermittent earth-
INTRPTEF 1 4)9) 1 4)9) 1 4)9) 1 4)9) 1 4)9) 1 7)9) 1 4)9)
fault protection
Harmonics-based earth- (1) (1) (1) (1) (1) (1)
HAEFPTOC
fault protection 8) 8)9) 8)9) 8)9) 8)9) 8)9) 8)9)

Non-directional (cross-
country) earth-fault
EFHPTOC 1 6) 1 6) 1 6) 1 6) 1 6) 1 6) 1 6)
protection, using calculated
Io
Negative-sequence
NSPTOC 2 2 2 2 2 2 2 2 2 2 2 2
overcurrent protection
Phase discontinuity
PDNSPTOC 1 1 1 1 1 1 1 1 1 1 1
protection
Residual overvoltage
ROVPTOV 3 3) 3 3) 3 4) 3 4) 3 7) 3 4) 34) 2 4) 3 7) 3 4)
protection
Three-phase undervoltage
PHPTUV 3 3 3 3 2 3 3
protection
Three-phase overvoltage
PHPTOV 3 3 3 3 2 3 3
protection
Positive-sequence
PSPTUV 1 1 1 1 1
undervoltage protection
Negative-sequence
NSPTOV 1 1 1 1 1
overvoltage protection
Frequency protection FRPFRQ 3 3 3 4 4
Three-phase thermal
protection for feeders,
T1PTTR 1 1 1 1 1 1 1 1 1 1 1
cables and distribution
transformers

Table continues on next page

36 REF615
Application Manual
1MRS756378 P Section 3
REF615 standard configurations

Function IEC 61850 A B C D E F G H J K L N


High impedance-based
restricted earth-fault HREFPDIF 1 10)
protection
Circuit breaker failure
CCBRBRF 1 1 1 1 1 1 1 1 1 1 1 1
protection
Three-phase inrush
INRPHAR 1 1 1 1 1 1 1 1 1 1 1 1
detector
2(5) 2 (5) 2 (5) 2 (5) 2 (5) 2 (5) 2 (5) 2 (5) 2 (5) 2 (5)
Master trip TRPPTRC 2 11) 2 11) 11) 11) 11) 11) 11) 11) 11) 11)

Arc protection ARCSARC (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3)
Multi-purpose protection 12) MAPGAPC 18 18 18 18 18 18 18 18 18 18 18 18
Fault locator SCEFRFLO (1) (1) (1)
High impedance fault
PHIZ 1 1 1 1 1 1 1
detection
Power quality
Current total demand
CMHAI (1) 13) (1) 13) (1) 13) (1) 13)
distortion
Voltage total harmonic
VMHAI (1) 13) (1) 13) (1) 13) (1) 13)
distortion
Voltage variation PHQVVR (1) 13) (1) 13) (1) 13) (1) 13)
Control
Circuit-breaker control CBXCBR 1 1 1 1 1 1 1 1 1 1 1 1
Disconnector control DCXSWI 2 2 2 2 2 2 2 2 2 2
Earthing switch control ESXSWI 1 1 1 1 1 1 1 1 1 1
Disconnector position
DCSXSWI 3 3 3 3 3 3 3 3 3 3
indication
Earthing switch indication ESSXSWI 2 2 2 2 2 2 2 2 2 2
Autoreclosing DARREC (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1)
Synchronism and
SECRSYN 1 1 1 1
energizing check
Condition monitoring
Circuit-breaker condition
SSCBR 1 1 1 1 1 1 1 1 1 1
monitoring
Trip circuit supervision TCSSCBR 2 2 2 2 2 2 2 2 2 2 2 2
Current circuit supervision CCRDIF 1 1 1 1 1 1 1 1
Fuse failure supervision SEQRFUF 1 1 1 1 1 1 1 1
Runtime counter for
MDSOPT 1 1 1 1 1 1 1 1 1 1 1 1
machines and devices
Measurement
Disturbance recorder RDRE 1 1 1 1 1 1 1 1 1 1 1 1
Load profile record LDPMSTA 1 1 1 1 1 1 1 1 1 1
Three-phase current
CMMXU 1 1 1 1 1 1 1 1 1 1 1 1
measurement
Sequence current
CSMSQI 1 1 1 1 1 1 1 1 1 1 1 1
measurement
Residual current
RESCMMXU 1 1 1 1 1 1 1 1 1 2 1 1
measurement
Three-phase voltage
VMMXU 1 1 1 2 2 2 1 2
measurement
Residual voltage
RESVMMXU 1 1 1 1 1 1 1 1
measurement
Sequence voltage
VSMSQI 1 1 1 1 1 1 1 1
measurement
Three-phase power and
PEMMXU 1 1 1 1 1 1 1 1
energy measurement
RTD/mA measurement XRGGIO130 (1) (1) (1) (1) (1) (1) (1)

Table continues on next page

REF615 37
Application Manual
Section 3 1MRS756378 P
REF615 standard configurations

Function IEC 61850 A B C D E F G H J K L N


Frequency measurement FMMXU 1 1 1 1 1 1 1 1
IEC 61850-9-2 LE (Voltage
(1) (1) (1) (1) (1) (1) (1) (1)
sharing) 14)
1, 2, ... = number of included instances
() = optional

1) The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.
2) Io selectable by parameter, “Io measured” as default
3) “Uo measured” is always used.
4) Uo selectable by parameter, "Uo measured" as default
5) Uo calculated and negative sequence voltage selectable by parameter, “Uo calculated” as default
6) Io selectable by parameter, “Io calculated” as default
7) “Uo calculated” is always used.
8) One of the following can be ordered as an option: admittance-based E/F, wattmetric-based E/F or harmonics-based E/F. The option is
an addition to the existing E/F of the original configuration. The optional E/F has also a predefined configuration in the IED. The optional
E/F can be set on or off.
9) “Io measured” is always used.
10) “IoB measured” is always used.
11) Master trip included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If the ARC
option is selected additionally, ARCSARC is connected to the corresponding master trip input in the configuration.
12) Multi-purpose protection is used, for example, for RTD/mA-based protection or analog GOOSE.
13) Power quality option includes current total demand distortion, voltage total harmonic distortion and voltage variation.
14) Only available with COM0031-COM0034

3.1.1 Addition of control functions for primary devices and the


use of binary inputs and outputs
If extra control functions intended for controllable primary devices are added to the
configuration, additional binary inputs and/or outputs are needed to complement
the standard configuration.

If the number of inputs and/or outputs in a standard configuration is not sufficient,


it is possible either to modify the chosen IED standard configuration in order to
release some binary inputs or binary outputs which have originally been configured
for other purposes, or to integrate an external input/output module, for example
RIO600, to the IED.

The external I/O module’s binary inputs and outputs can be used for the less time-
critical binary signals of the application. The integration enables releasing some
initially reserved binary inputs and outputs of the IED’s standard configuration.

The suitability of the IED’s binary outputs which have been selected for primary
device control should be carefully verified, for example make and carry and
breaking capacity. If the requirements for the primary device control circuit are not
met, using external auxiliary relays should be considered.

38 REF615
Application Manual
1MRS756378 P Section 3
REF615 standard configurations

3.2 Connection diagrams

A071288 V6 EN

Figure 11: Connection diagram for the A and B configurations [1]

[1] Additional BIO-module (X110 in the diagram) is included in the IED variant B

REF615 39
Application Manual
Section 3 1MRS756378 P
REF615 standard configurations

A071290 V5 EN

Figure 12: Connection diagram for the C and D configurations [2]

[2] Additional BIO-module (X110 in the diagram) is included in the IED variant D

40 REF615
Application Manual
1MRS756378 P Section 3
REF615 standard configurations

GUID-F7601942-ACF2-47E2-8F21-CD9C1D2BC1F0 V4 EN

Figure 13: Connection diagram for the E and F configurations

REF615 41
Application Manual
Section 3 1MRS756378 P
REF615 standard configurations

L1

L2

L3

REF615
X130 X100
Positive +
Current 1
1 0,2/1A
U aux
Direction 2 Io 2
N -
3
X131 IRF
4
4 5
IL1
5
7 PO1
U1
8
6
X132 7

4 PO2
IL2
5
8
7 9
U2
8 10
X133 SO1
11
4 12
IL3
5 13
7 SO2
U3
8 14
16
PO3
17
P1 S1 15
19
S2
TCS1 18
P2
20
X110 22
PO4
1
BI 1 2) 21
2
23
3 TCS2 24
BI 2
4

5 X110
BI 3
6 2) 14
SO1
BI 4 16
7 15
17
8
BI 5 SO2
9
19
18
BI 6 20
10
SO3
11 22
BI 7
12 21
23
BI 8 SO4
13 24

X13
1)
Light sensor input 1

X14
1)
Light sensor input 2
1) Optional
X15 2) BIO0005 Module (8BI+4BO)
1)
Light sensor input 3 Alternative Module BIO0007 (8BI+3HSO)

GUID-B70F0C14-52B2-4213-8781-5A7CA1E40451 V2 EN

Figure 14: Connection diagram for the G and L configurations

42 REF615
Application Manual
1MRS756378 P Section 3
REF615 standard configurations

GUID-E8E2F79F-3DD8-46BD-8DE7-87A30133A7AE V1 EN

Figure 15: Connection diagram for the H, J and N configurations

REF615 43
Application Manual
Section 3 1MRS756378 P
REF615 standard configurations

L1
L2
L3
A

n
N REF615
X130 X100
1 + 1
a BI 1 U aux
2
-
2
da dn
3 3
BI 2
4 IRF
4
5
BI 3 5
6
PO1
7
BI 4
8 6
60 - 7
9 210V
U12B (for SECRSYN1)
10 N PO2
60 -
11 210V
U1 8
12 N 9
60 -
13 210V
10
U2 SO1
14 N
60 -
15 210V
11
U3 12
16 N 13
60 -
17 210V SO2
Uo
18 N
14
16
PO3
X120
Positive 17
Current 1 1/5A 2) 15
not in use
Direction 19
2 N TCS1 18
3 1/5A
not in use 20
4 N 22
P1 5 1/5A PO4
S1 IoB (for HREFPDIF1)
6 N 21
P2
S2
7 1/5A 23
IL1 TCS2 24
8 N
9 1/5A
IL2
10 N X110
11 1/5A
14
IL3 3)
12 N SO1
13 1/5A
16
Io 15
14 N
17
P1 S1
SO2
X110 19
P2 S2
18
1 20
BI 1 3)
2 SO3
22
3 21
BI 2
4 23
SO4
5
BI 3 24
P1 S1 6

P2 S2 BI 4
7
8
BI 5
9

BI 6
10

11
BI 7
12

BI 8
13

X13
1)
Light sensor input 1

X14
1) 1) Optional
Light sensor input 2 2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
X15 unit is detached
1) 3) BIO0005 Module (8BI+4BO)
Light sensor input 3
Alternative Module BIO0007 (8BI+3HSO)

GUID-4288C45E-C7C8-4FB9-8821-85C58BB25D32 V1 EN

Figure 16: Connection diagram for the K configuration

3.3 Standard configuration A

3.3.1 Applications
The standard configuration for non-directional overcurrent and directional earth-
fault protection is mainly intended for cable and overhead-line feeder applications
in isolated and resonant-earthed distribution networks. The configuration also

44 REF615
Application Manual
1MRS756378 P Section 3
REF615 standard configurations

includes additional options for selecting earth-fault protection based on admittance


or wattmetric-based principles.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

3.3.2 Functions
Uo

REF615 FEEDER PROTECTION AND CONTROL IED STANDARD


CONFIGURATION
A

PROTECTION LOCAL HMI ALSO AVAILABLE


Configuration A

- Disturbance and fault recorders


System
HMI
Time
Authorization

2× - Event log and recorded data


Master Trip I
- IED self-supervision
ESC Clear

Lockout relay A
O
- Local/Remote push button on LHMI
R
L

94/86
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

IL2 0 A
- User management
- Web HMI
I ESC Clear


AND
I2> I2/I1> 3Ith>F 3I>>> O R

46 46PD 49F 50P/51P


L
OR

3× 3×
ARC 3I>/Io>BF
50L/50NL CONDITION MONITORING COMMUNICATION
51BF/51NBF
AND SUPERVISION
Protocols:
2× 2× IEC 61850-8-1 1 0 1 0 0 0 1 1 0 0 1 1 0 0
3I> 3I>> 3I2f> OPTS TCS Modbus® 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
1 1 0 0 1 1 1 0 1 1 0 1 0
51P-1 51P-2 68 OPTM TCM IEC 60870-5-103 1 0 1 1 0 1 1 0 1 1 0 1 0 0
DNP3 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
Io 1
Ethernet: TX (RJ45), FX (LC)
0 1 1 0 1 1 0 1 1 0 1 0 0

Serial: Serial glass fiber (ST),


RS-485, RS-232/485
Io>>
D-sub 9, IRIG-B
51N-2
Redundant protocols:
HSR
PRP
RSTP
Io

Io>→ Io>>→ Io>IEF→
CONTROL AND INDICATION 1) MEASUREMENT
67N-1 67N-2 67NIEF

Uo - I, Io, Uo
Object Ctrl 2) Ind 3)
3× 3× - Limit value supervision
Yo>→ Po>→ CB 1 - - Symmetrical components
21YN 32N
DC - -
OR Analog interface types 1)
ES - -
1)
Check availability of binary inputs/outputs
Current transformer 4
from technical documentation Voltage transformer 1
2)
Control and indication function for
primary object 1)
Conventional transformer inputs
3)
Status indication function for
primary object

3× 18×
Uo> MAP O→I
59G MAP 79

REMARKS
Optional 3× No. of Calculated OR Alternative
function instances value function to be
Io/Uo defined when
ordering

GUID-030C217F-7B91-4739-9DAE-90D1E053EB53 V1 EN

Figure 17: Functionality overview for standard configuration A

REF615 FEEDER PROTECTION AND CONTROL IED STANDARD


CONFIGURATION

PROTECTION LOCAL HMI


Configuration A
System
HMI
Time
Authorization

REF615 I ESC Clear 45


Application Manual
A
O R
L
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

IL2 0 A

I ESC Clear

AND
O R
L
OR

CONDITION MONITORING COMMUNICATION


AND SUPERVISION