The IED is delivered from the factory with default connections described in the
functional diagrams for binary inputs, binary outputs, function-to-function
connections and alarm LEDs. The positive measuring direction of directional
protection functions is towards the outgoing feeder.
REF615 35
Application Manual
Section 3 1MRS756378 P
REF615 standard configurations
Wattmetric-based earth- (3) (3) (3) (3) (3) (3) (3) (3)
WPWDE
fault protection 8) 2)3)8) 2)3)8) 2)4)8) 2)4)8) 2)7)8) 2)4)8) 2)7)8) 2)4)8)
Transient/intermittent earth-
INTRPTEF 1 4)9) 1 4)9) 1 4)9) 1 4)9) 1 4)9) 1 7)9) 1 4)9)
fault protection
Harmonics-based earth- (1) (1) (1) (1) (1) (1)
HAEFPTOC
fault protection 8) 8)9) 8)9) 8)9) 8)9) 8)9) 8)9)
Non-directional (cross-
country) earth-fault
EFHPTOC 1 6) 1 6) 1 6) 1 6) 1 6) 1 6) 1 6)
protection, using calculated
Io
Negative-sequence
NSPTOC 2 2 2 2 2 2 2 2 2 2 2 2
overcurrent protection
Phase discontinuity
PDNSPTOC 1 1 1 1 1 1 1 1 1 1 1
protection
Residual overvoltage
ROVPTOV 3 3) 3 3) 3 4) 3 4) 3 7) 3 4) 34) 2 4) 3 7) 3 4)
protection
Three-phase undervoltage
PHPTUV 3 3 3 3 2 3 3
protection
Three-phase overvoltage
PHPTOV 3 3 3 3 2 3 3
protection
Positive-sequence
PSPTUV 1 1 1 1 1
undervoltage protection
Negative-sequence
NSPTOV 1 1 1 1 1
overvoltage protection
Frequency protection FRPFRQ 3 3 3 4 4
Three-phase thermal
protection for feeders,
T1PTTR 1 1 1 1 1 1 1 1 1 1 1
cables and distribution
transformers
36 REF615
Application Manual
1MRS756378 P Section 3
REF615 standard configurations
Arc protection ARCSARC (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3)
Multi-purpose protection 12) MAPGAPC 18 18 18 18 18 18 18 18 18 18 18 18
Fault locator SCEFRFLO (1) (1) (1)
High impedance fault
PHIZ 1 1 1 1 1 1 1
detection
Power quality
Current total demand
CMHAI (1) 13) (1) 13) (1) 13) (1) 13)
distortion
Voltage total harmonic
VMHAI (1) 13) (1) 13) (1) 13) (1) 13)
distortion
Voltage variation PHQVVR (1) 13) (1) 13) (1) 13) (1) 13)
Control
Circuit-breaker control CBXCBR 1 1 1 1 1 1 1 1 1 1 1 1
Disconnector control DCXSWI 2 2 2 2 2 2 2 2 2 2
Earthing switch control ESXSWI 1 1 1 1 1 1 1 1 1 1
Disconnector position
DCSXSWI 3 3 3 3 3 3 3 3 3 3
indication
Earthing switch indication ESSXSWI 2 2 2 2 2 2 2 2 2 2
Autoreclosing DARREC (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1)
Synchronism and
SECRSYN 1 1 1 1
energizing check
Condition monitoring
Circuit-breaker condition
SSCBR 1 1 1 1 1 1 1 1 1 1
monitoring
Trip circuit supervision TCSSCBR 2 2 2 2 2 2 2 2 2 2 2 2
Current circuit supervision CCRDIF 1 1 1 1 1 1 1 1
Fuse failure supervision SEQRFUF 1 1 1 1 1 1 1 1
Runtime counter for
MDSOPT 1 1 1 1 1 1 1 1 1 1 1 1
machines and devices
Measurement
Disturbance recorder RDRE 1 1 1 1 1 1 1 1 1 1 1 1
Load profile record LDPMSTA 1 1 1 1 1 1 1 1 1 1
Three-phase current
CMMXU 1 1 1 1 1 1 1 1 1 1 1 1
measurement
Sequence current
CSMSQI 1 1 1 1 1 1 1 1 1 1 1 1
measurement
Residual current
RESCMMXU 1 1 1 1 1 1 1 1 1 2 1 1
measurement
Three-phase voltage
VMMXU 1 1 1 2 2 2 1 2
measurement
Residual voltage
RESVMMXU 1 1 1 1 1 1 1 1
measurement
Sequence voltage
VSMSQI 1 1 1 1 1 1 1 1
measurement
Three-phase power and
PEMMXU 1 1 1 1 1 1 1 1
energy measurement
RTD/mA measurement XRGGIO130 (1) (1) (1) (1) (1) (1) (1)
REF615 37
Application Manual
Section 3 1MRS756378 P
REF615 standard configurations
1) The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.
2) Io selectable by parameter, “Io measured” as default
3) “Uo measured” is always used.
4) Uo selectable by parameter, "Uo measured" as default
5) Uo calculated and negative sequence voltage selectable by parameter, “Uo calculated” as default
6) Io selectable by parameter, “Io calculated” as default
7) “Uo calculated” is always used.
8) One of the following can be ordered as an option: admittance-based E/F, wattmetric-based E/F or harmonics-based E/F. The option is
an addition to the existing E/F of the original configuration. The optional E/F has also a predefined configuration in the IED. The optional
E/F can be set on or off.
9) “Io measured” is always used.
10) “IoB measured” is always used.
11) Master trip included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If the ARC
option is selected additionally, ARCSARC is connected to the corresponding master trip input in the configuration.
12) Multi-purpose protection is used, for example, for RTD/mA-based protection or analog GOOSE.
13) Power quality option includes current total demand distortion, voltage total harmonic distortion and voltage variation.
14) Only available with COM0031-COM0034
The external I/O module’s binary inputs and outputs can be used for the less time-
critical binary signals of the application. The integration enables releasing some
initially reserved binary inputs and outputs of the IED’s standard configuration.
The suitability of the IED’s binary outputs which have been selected for primary
device control should be carefully verified, for example make and carry and
breaking capacity. If the requirements for the primary device control circuit are not
met, using external auxiliary relays should be considered.
38 REF615
Application Manual
1MRS756378 P Section 3
REF615 standard configurations
A071288 V6 EN
[1] Additional BIO-module (X110 in the diagram) is included in the IED variant B
REF615 39
Application Manual
Section 3 1MRS756378 P
REF615 standard configurations
A071290 V5 EN
[2] Additional BIO-module (X110 in the diagram) is included in the IED variant D
40 REF615
Application Manual
1MRS756378 P Section 3
REF615 standard configurations
GUID-F7601942-ACF2-47E2-8F21-CD9C1D2BC1F0 V4 EN
REF615 41
Application Manual
Section 3 1MRS756378 P
REF615 standard configurations
L1
L2
L3
REF615
X130 X100
Positive +
Current 1
1 0,2/1A
U aux
Direction 2 Io 2
N -
3
X131 IRF
4
4 5
IL1
5
7 PO1
U1
8
6
X132 7
4 PO2
IL2
5
8
7 9
U2
8 10
X133 SO1
11
4 12
IL3
5 13
7 SO2
U3
8 14
16
PO3
17
P1 S1 15
19
S2
TCS1 18
P2
20
X110 22
PO4
1
BI 1 2) 21
2
23
3 TCS2 24
BI 2
4
5 X110
BI 3
6 2) 14
SO1
BI 4 16
7 15
17
8
BI 5 SO2
9
19
18
BI 6 20
10
SO3
11 22
BI 7
12 21
23
BI 8 SO4
13 24
X13
1)
Light sensor input 1
X14
1)
Light sensor input 2
1) Optional
X15 2) BIO0005 Module (8BI+4BO)
1)
Light sensor input 3 Alternative Module BIO0007 (8BI+3HSO)
GUID-B70F0C14-52B2-4213-8781-5A7CA1E40451 V2 EN
42 REF615
Application Manual
1MRS756378 P Section 3
REF615 standard configurations
GUID-E8E2F79F-3DD8-46BD-8DE7-87A30133A7AE V1 EN
REF615 43
Application Manual
Section 3 1MRS756378 P
REF615 standard configurations
L1
L2
L3
A
n
N REF615
X130 X100
1 + 1
a BI 1 U aux
2
-
2
da dn
3 3
BI 2
4 IRF
4
5
BI 3 5
6
PO1
7
BI 4
8 6
60 - 7
9 210V
U12B (for SECRSYN1)
10 N PO2
60 -
11 210V
U1 8
12 N 9
60 -
13 210V
10
U2 SO1
14 N
60 -
15 210V
11
U3 12
16 N 13
60 -
17 210V SO2
Uo
18 N
14
16
PO3
X120
Positive 17
Current 1 1/5A 2) 15
not in use
Direction 19
2 N TCS1 18
3 1/5A
not in use 20
4 N 22
P1 5 1/5A PO4
S1 IoB (for HREFPDIF1)
6 N 21
P2
S2
7 1/5A 23
IL1 TCS2 24
8 N
9 1/5A
IL2
10 N X110
11 1/5A
14
IL3 3)
12 N SO1
13 1/5A
16
Io 15
14 N
17
P1 S1
SO2
X110 19
P2 S2
18
1 20
BI 1 3)
2 SO3
22
3 21
BI 2
4 23
SO4
5
BI 3 24
P1 S1 6
P2 S2 BI 4
7
8
BI 5
9
BI 6
10
11
BI 7
12
BI 8
13
X13
1)
Light sensor input 1
X14
1) 1) Optional
Light sensor input 2 2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
X15 unit is detached
1) 3) BIO0005 Module (8BI+4BO)
Light sensor input 3
Alternative Module BIO0007 (8BI+3HSO)
GUID-4288C45E-C7C8-4FB9-8821-85C58BB25D32 V1 EN
3.3.1 Applications
The standard configuration for non-directional overcurrent and directional earth-
fault protection is mainly intended for cable and overhead-line feeder applications
in isolated and resonant-earthed distribution networks. The configuration also
44 REF615
Application Manual
1MRS756378 P Section 3
REF615 standard configurations
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
3.3.2 Functions
Uo
Lockout relay A
O
- Local/Remote push button on LHMI
R
L
94/86
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
- User management
- Web HMI
I ESC Clear
2×
AND
I2> I2/I1> 3Ith>F 3I>>> O R
3× 3×
ARC 3I>/Io>BF
50L/50NL CONDITION MONITORING COMMUNICATION
51BF/51NBF
AND SUPERVISION
Protocols:
2× 2× IEC 61850-8-1 1 0 1 0 0 0 1 1 0 0 1 1 0 0
3I> 3I>> 3I2f> OPTS TCS Modbus® 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
1 1 0 0 1 1 1 0 1 1 0 1 0
51P-1 51P-2 68 OPTM TCM IEC 60870-5-103 1 0 1 1 0 1 1 0 1 1 0 1 0 0
DNP3 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
Io 1
Ethernet: TX (RJ45), FX (LC)
0 1 1 0 1 1 0 1 1 0 1 0 0
Uo - I, Io, Uo
Object Ctrl 2) Ind 3)
3× 3× - Limit value supervision
Yo>→ Po>→ CB 1 - - Symmetrical components
21YN 32N
DC - -
OR Analog interface types 1)
ES - -
1)
Check availability of binary inputs/outputs
Current transformer 4
from technical documentation Voltage transformer 1
2)
Control and indication function for
primary object 1)
Conventional transformer inputs
3)
Status indication function for
primary object
3× 18×
Uo> MAP O→I
59G MAP 79
REMARKS
Optional 3× No. of Calculated OR Alternative
function instances value function to be
Io/Uo defined when
ordering
GUID-030C217F-7B91-4739-9DAE-90D1E053EB53 V1 EN
IL2 0 A
I ESC Clear
AND
O R
L
OR