DESIGN OF TOWER SUPPORTING STRUCTURE

S.NO. DENOTION OF STRUCTURE 30m 400 33

1 TOWER SIZE 1600X1600 mm

2 NUMBER OF CHIMNEYS 4

3 DIA OF EXHAUST PIPE 400 mm

4 THE HEIGHT OF TOWER 30m

5 THE HEIGHT OF EXHAUAT 1m


PIPE ABOVE THE TOP LEVEL
OF TOWER.

The above details are as shown in the enclosed drawing.

The tower is critical in the axis parallel to 1600mm side which is perpendicular to one
pipe common axis. Therefore the tower is analysed (using staad programme ) along this
critical axis, since the maximum wind force(because maximum surface area) acts along
this critical axis. The same bracing is provided along the other perpendicular axis also.

WIND PRESSURE CALCULATIONS.

BASIC WIND SPEED = Vb = 33 m /sec

RISK COEFFICIENT = K1 = 1.00

RISK COEFFICIENT = K2 = 1.17

TOPOGRAPHY FACTOR = K3 = 1.0

DESIGN WIND VELOCITY = VZ =VB.K1.K2.K3 = 33X1X1.17X1.0 =38.61m/sec

DESIGN WIND PRESSURE = 0.6VZ2 = 0.6 X 38.612 = 894.4 N /M2

SAY 90Kg/M2