Beruflich Dokumente
Kultur Dokumente
Product description................................................................................................. 3
Technical data.......................................................................................................... 4
Accessories.............................................................................................................. 7
2
Product description of Bosch Compress 3000 AWS heat pumps
AWBS or AWES
Compress 3000 AWS outdoor units indoor unit
Reversible split air-to-water heat pump for heating, cooling and domestic hot water production
Bosch split heat pumps meet the quality requirements the EHPA quality seal and guarantee efficient seasonal perfor-
mance factors
The outdoor and the indoor unit must be connected with pipes suitable for a cooling circuit and the system must be
filled with R410A refrigerant gas
High energy efficiency, COP up to 4.8* due to modulating compressor using inverter technology
Wide range of portfolio: 4 power output variants from 8 to 15 kW with single-phase or three-phase power supply
Two different indoor units that can be connected hydraulically to the outdoor unit:
- AWBS hybrid: hybrid system combined with any auxiliary heat generator
- AWES Electric: mono-energetic system with integrated electrical backup heating
Equipped with high-efficiency pump and anti-condensate insulation (AWES unit).
New pre-configured HPC400 control on board in the indoor unit featuring graphical user interface. Control and set the
parameters of the system like: climate control; cooling parameters; operating limits; adjusting and / or excluding elec-
trical heating (AWES unit); energy rate in case operating in bivalent system (AWBS unit); parameters for the DHW
production. Possibility of remote management via mobile application in case the IP Module accessory is installed and
connected to the internet
The outdoor units having single fan can be installed on the wall with fixing brackets or as the same way like units ha-
ving double fan on a stand
Indoor units are supplied with the outside temperature sensor, flow temperature sensor, temperature sensor for dome-
stic hot water (AWBS and AWES units) and shut-off valve with filter
Special reduced electricity tariffs are applicable thanks to the high efficiency these units provide
3
Outdoor unit ODU Split for Bosch Compress 3000 AWS split heat pump systems.
Reversible with inverter compressor working with refrigerant R410A.
Technical data
Product data for energy consumption - according to the requirements ODU ODU ODU ODU
of EU Regulations 811/2013 and 812/2013 on completion of Directive Split 8 Split 11s Split 13s Split 15s
2010/30/EU
Rated thermal output at average climatic conditions [kW] 6 9 10 11
Rated thermal output at average climatic conditions in a low temperature sys-
7 10 11 13
tem [kW]
Product data for energy consumption - according to the requirements ODU ODU ODU
of EU Regulations 811/2013 and 812/2013 on completion of Directive Split 11t Split 13t Split 15t
2010/30/EU
Rated thermal output at average climatic conditions [kW] 9 10 11
Rated thermal output at average climatic conditions in a low temperature sys-
10 11 13
tem [kW]
Technical data
Nominal ventilator air flow m3/h 3600 2 x 3600 2 x 3600 2 x 3600
Sound pressure level (LpA) at 1 m distance (3)
dB(A) 52 55 55 55
Refrigerant (4)
- R410A R410A R410A R410A
Weight of refrigerant kg 1.6 2.3 1.6 2.3
Maximal delivery water temperature in º
C 55 55 55 55
heating without electric backup heating
Operating boundaries for heating º
C -20 / 35 -20 / 35 -20 / 35 -20 / 35
(min/max outside air temperature)
Minimal delivery water temperature in cooling º
C 10 10 10 10
Operating boundaries for cooling º
C 10 / 45 10 / 45 10 / 45 10 / 45
(min/max outside air temperature)
950 x 330 x
Dimensions W x D x H mm 950 x 330 x 1380
834
Weight of appliance kg 60 94 94 94
Electrical data
Supply 230 V / 50 Hz
Maximal absorption working at +7 ºC air and 35 ºC delivery water
kW 2.25 3 3.5 3.75
temperature
Maximal performance of the fan motor W 124 2 x 124 2 x 124 2 x 124
Electrical protection class IPX4
(1) Measured in a laboratory accredited according to EN ISO / IEC 17025 in accordance with EN 14511
(2) Measured laboratory accredited according to EN ISO / IEC 17025 in accordance with EN 14825
(3) Sound pressure level LpA in accordance with EN 12102 (rated power with 40% inverter for A7/W55)
4
ODU ODU ODU
Three-phase outdoor units
Split 11t Split 13t Split 15t
Heating performance
At +7 ºC air and 35 ºC delivery water (1)
Maximal heat output kW 15.0 16.2 17.4
At -7 ºC air and 35 ºC delivery water (2) Nominal heat output kW 10.0 11.0 12.5
With 100% load of the inverter COP - 2.7 2.7 2.7
At +2 ºC air and 35 ºC delivery water (2) Nominal heat output kW 7.5 8.5 9.5
With 60% load of the inverter COP - 3.6 3.5 3.5
At +7 ºC air and 35 ºC delivery water (2) Nominal heat output kW 12.2 14.4 15.8
With 40% load of the inverter COP - 4.4 4.4 4.41
Cooling performance
Nominal cooling
kW 12 14 15
At +35 ºC air and 18 ºC delivery water (2) performance
EER - 3.3 3.3 3.3
Technical data
Nominal ventilator air flow m3/h 2 x 3600 2 x 3600 2 x 3600
Sound pressure level (LpA) at 1 m distance (3)
dB(A) 55 55 55
Refrigerant (4)
- R410A R410A R410A
Weight of refrigerant kg 2.3 1.6 2.3
Maximal delivery water temperature in º
C 55 55 55
heating without electric backup heating
Operating boundaries for heating º
C -20 / 35 -20 / 35 -20 / 35
(min/max outside air temperature)
Minimal delivery water temperature in cooling º
C 10 10 10
Operating boundaries for cooling º
C 10 / 45 10 / 45 10 / 45
(min/max outside air temperature)
Dimensions W x D x H mm 950 x 330 x 1380
Weight of appliance kg 96 96 96
Electrical data
Supply 400 V / 50 Hz
Maximal absorption working at +7 ºC air and 35 ºC delivery water
kW 3 3.5 3.75
temperature
Maximal performance of the fan motor W 2 x 124 2 x 124 2 x 124
Electrical protection class IPX4
Indoor unit AWBS and AWES for Bosch Compress 3000 AWS split heat pump
systems with HPC400 control
Technical data
5
Compress 3000 AWS sets
Product data for energy consumption - according to the requirements of EU Regulations 811/2013 and 812/2013 on
completion Directive 2010/30 / EU: set of equipment for heating and / or mixed with the temperature control device.
ODU Split 8 room heating with 35 ºC flow temperature
Possible auxiliary
Nominal heating
Heating System
Supply phases
Supply phases
Ordering code
Ordering code
Description
heating
Variant
Variant
Price
Compress 3000
Hybrid Optional boiler 1 AWBS 8-15
ODU AWS 8 - BS
9 Split 8 1
Mono- Integrated elec- Compress 3000
1/3 AWES 8-15
energetic tric heating rod AWS 8 - ES
Compress 3000
Hybrid Optional boiler 1 AWBS 8-15
ODU AWS 11s - BS
12 Split 1
11s Mono- Integrated elec- Compress 3000
1/3 AWES 8-15
energetic tric heating rod AWS 11s - ES
Compress 3000
Hybrid Optional boiler 1 AWBS 8-15
ODU AWS 13s - BS
14 Split 1
13s Mono- Integrated elec- Compress 3000
1/3 AWES 8-15
energetic tric heating rod AWS 13s - ES
Compress 3000
Hybrid Optional boiler 1 AWBS 8-15
ODU AWS 15s - BS
16 Split 1
15s Mono- Integrated elec- Compress 3000
1/3 AWES 8-15
energetic tric heating rod AWS 15s - ES
Compress 3000
Hybrid Optional boiler 1 AWBS 8-15
ODU AWS 11t - BS
12 Split 3
11t Mono- Integrated elec- Compress 3000
1/3 AWES 8-15
energetic tric heating rod AWS 11t - ES
Compress 3000
Hybrid Optional boiler 1 AWBS 8-15
ODU AWS 13t - BS
14 Split 3
13t Mono- Integrated elec- Compress 3000
1/3 AWES 8-15
energetic tric heating rod AWS 13t - ES
Compress 3000
Hybrid Optional boiler 1 AWBS 8-15
ODU AWS 15t - BS
16 Split 3
15t Mono- Integrated elec- Compress 3000
1/3 AWES 8-15
energetic tric heating rod AWS 15t - ES
6
Accessories for Bosch Compress 3000 AWS heat pumps
Ordering
Name Description Price
number
Floor standing rack Floor standing mounting kit for outdoor units 7716161065
7
Compress 3000 AWS sets
Bosch bivalent DHW tanks with solar coil and high surface coil for heat pump systems
Ordering ErP Coil size
Name Description
number class m2
Enameled steel cylinders with insulated ma-
WS 400-5 B
gnesium anode. Volume of 400 or 500 liter. 7735500306 B 3.3/1.3
Featuring 2 coils, temperature sensor sockets,
WS 500-5 B 2 inspections ports (1 in front, 1 on top), 7735500309 B 5.1/1.8
socket for e-heater. Maximal operating pressu-
re is 8 bar.
WS 400-5 C -4 00/500l – B Class – 100 mm insolation - hard foam 7735500305 C 3.3/1.3
and foil mantle+ 40 mm fleece
WS 500-5 C - 400/500l – C Class – 80 mm insolation - hard foam 7735500308 C 5.1/1.8
and foil mantle
Comfort buffer tanks with solar coil, stratification plate and separating plates and dispersion tube
Ordering ErP
Name Description Price
number class
BHS 750-6 ERZ C Comfort buffer tanks featuring e-heater con- 7735501107 C 2.1
nection, stratification plate, separating plates,
solar coil and dispersion tube. Variants with
BHS 1000-6 ERZ C 750 and 1000 liter volume. Importance for 7735501111 C 2.5
differentiation of temperature zones.
BHS 750-6 ERZ E -7 50/1000l – C Class, Hard foam half shells 70 mm + 7735501105 E 2.1
5 mm PVC foil mantle with soft foam
- 750/1000l – E Class, Fleece insulation 80 mm with
BHS 1000-6 ERZ E PVC foil mantle 7735501109 E 2.5
Enameled indirect DHW tanks for heat pump systems – non branded
Ordering ErP Coil size
Name Description
number class m2
HP300UNO High quality enameled indirect DHW tank with B 2.1
1 coil, maximal operating pressure of 8 bar.
HP400UNO Variants with 300, 400 and 500 liter of volume. C 2.55
Featuring socket for e-heater.
HP500UNO - 300/400/500 l – PU Insulation 50 mm C 3.4
Legend
ODU Split 11s, 13s, 15s, 11t, 13t, 15t main dimensions
Legend
9
Main dimensions and clearance AWBS 8-15 indoor unit
[1] C
able bushings for sensor, CAN-BUS and [5] Auxiliary heater return
EMS 2 BUS [6] Overpressure discharge of the pressure
[2] Cable bushing for power supply relief valve
[3] P
rimary output, liquid side, 3/8" (to out- [7] Flow to the heating system
door unit ODU) [8] Flow to the auxiliary heater
[4] P
rimary input, gas side, 5/8" (from out- [9] Pressure gauge
door unit ODU) [10] Return from the heating system
[1] Return from the heating system [5] Primary input, gas side, 5/8“ (from out-
[2] Cable bushings for sensor, CAN-BUS and door unit ODU)
EMS 2 BUS [6] Supply to the heating system
[3] Cable bushing for power supply [7] Pressure gauge
[4] Primary output, liquid side, 3/8“ (to out- [8] Overpressure discharge of the pressure
door unit ODU) relief valve
10
Basic installation advices for Bosch Compress 3000 AWS heat pumps*
Legend
[1] Outdoor unit
[2] Electrical cables
[3] Refrigerant lines 3/8 „and 5/8“
[4] Concrete foundations
[5] Condensate pipe, central connection to drain pan
(accessory)
[A] Distance of the foundations
[B] Length of foundations
A heating cable for the drain (accessory) is required when using the condensate collection pan!
*Information in this document is not complete! One must always read and follow the instruc-
tions of the attached manuals!
11
Installation on the ground
Legend
▶▶Make sure that heat radiation (cooling mode) from the heat exchanger is not restricted if a sunroof is built over the
unit to prevent direct sunlight or rain exposure.
▶▶Do not place the outdoor unit at the northern side of the house. Doing this can lead to lower efficiencies in operation.
▶▶Make sure that the clearances indicated by arrows at the front, back and side of the unit are observed.
▶▶Do not place plants in the path of the air flow.
▶▶Take the weight of the outdoor unit into account and select a place where noise and vibration are minimum.
▶▶When choosing a suitable location, make sure that the maximum sound pressure level will not disturb the neighbors.
Legend
Legend
[1] Inside
[2] Wall
[3] External
12
Refrigerant lines and electrical connections between indoor and outdoor unit
Before installing the refrigerant pipe, observe the constraints in relation to pipe lengths and gradients. After resolving all
constraints, some preparations are required to proceed. Then start installing the refrigerant pipe at the outdoor unit.
The rated output of the product is based on the specified standard lengths. It is important not to exceed the maximum
allowable length to ensure that the product operates reliably. Improper refrigerant charge may result in abnormal opera-
tion.
Make additional charge of the refrigerant as required according to the below table if the pipe length is longer than 7.5 m.
The single pipe length without necessary additional filling is 7.5 m. Additional filling of refrigerant is not required up to
this length. Example: if the split unit with a single pipe length of 50 m is installed, fill with an additional 1700 g refrige-
rant. The following applies: (50-7.5) x 40 g = 1700 g.
Outdoor model Pipe diameter [inch] Distance, single pipe Elevation B [m] Additional
length A [m] refrigerant [g/m]
Gas Liquid Standard Max. Standard Max. (single pipe length)
ODU Split 8
ODU Split 11s/t
5/8”(1) 3/8”(2) 7.5 50 0 30 40
ODU Split 13s/t
ODU Split 15s/t
1) Adapters will be included to make the 9.52mm (3/8”) and 15.88mm (5/8”) fit to the smaller connections at the outdoor unit.
2) Adapters will be included to make the 9.52mm (3/8”) and 15.88mm (5/8”) fit to the smaller connections at the outdoor unit.
ODU Split 8
[1] Forward
[2] Sideways
[3] Backward
Legend
[1] Continuous
[2] Torque wrench
[3] Outdoor unit
[4] Liquid side piping
[5] Gas side piping
[6] Connect wiring
[7] Drain hose (if necessary)
[8] Connection pipe
[9] Putty or insulating material
(produced locally)
14
Electrical connections of outdoor and indoor units
Legend
(1) When using the power-OFF signal an additional 230 V line to the indoor unit must be installed so that the control,
despite Power-OFF permanently remains in operation.
15
Basic system design advices*
Heating system with an unmixed and a mixed heating circuit without buffer
To ensure sufficient energy for defrosting cycle make sure that in the unmixed circuit at least 4 radiators each with at least 500 W power
are installed. The thermostatic valves must be fully opened if there is any. It is also necessary to install into the largest room (reference
room) a temperature controller (CR10 or CR10H, please see the accessories section). The measured value will be communicated to the
main controller and will be taken into account for the calculation of the required flow temperature. (Weather compensated control with
room temperature control.) Depending on the water content of the installed radiators it can happen that for a complete defrost cycle
the auxiliary heater will be activated.
If both heating circuits have different operating hours, each heating circuit must be able to ensure sufficient energy for defrost cycle.
Therefore beside the above conditions one must ensure that at least 22 m2 of heated floor area is installed in the mixed heating circuit.
In this case in both heating circuits should have a reference room where a temperature controller is installed.
If both heating circuits have identical operating times, there is no requirement for minimum area in the mixed heating circuit because
with the 4 radiators the proper functioning of the heat pump is ensured.
Heating system with only mixed heating circuit (also applies to heating circuit with fan coils)
To ensure sufficient energy for defrosting cycle a buffer tank is needed. The minimum volume for a system with ODU Split 8 is 50 liters,
while for a system with ODU Split 11s/t, 13s/t or 15s/t is 120 liters.
General information
To start the cooling operation, the CR10H room controller (with humidity sensor) is required (see the accessories section) to avoid
condensation with ensuring a flow temperature higher than the current dew point. When using fan assisted convectors (e.g. fan coils)
with dehumidifying function a CR10 room controller is needed. To ensure a proper dehumidifying function the heat pump must be able
to provide flow temperature that is lower than the current dew point of the reference room. To protect against corrosion all pipes and
connections must be fitted with a suitable insulation.
The indoor units AWES are already featuring a vapor diffusion-tight thermal insulation as factory standard. The indoor units AWBS are
not insulated and therefore they are not suitable for cooling where flow temperature below the dew point is needed (e.g. fan coil system
with dehumidifying function).
Cooling through radiators is not allowed! The cooling operation is controlled by the first heating circuit (via flow temperature sensor T0
and remote control CR10H). Cooling only in the second heating circuit is therefore not possible. The block of cooling function in circuit
1 will also block the cooling in heating circuit 2.
In both cases a dew point sensor must be installed on the flow pipe of the indoor unit! In case of using a buffer tank without suita-
ble thermal insulation a second dew point sensor must be installed and placed right before the tank! Maximum 5 pcs of dew point
sensors can be connected to protect other critical areas as well.
*Information in this document is not complete! One must always read and follow the instructions of the attached manuals! These
advices do not substitute the professional planning of the systems!
16
Considering the sound effect of the heat pump
For a sound technical assessment of the installation location of the heat pump, the expected sound pressure level at the
affected areas can computationally be estimated. These sound pressure levels are calculated from the sound power level
of the device, the installation situation (directivity Q) and their distance from the heat pump by means of the following
formula: , where
Q is the directivity (takes into account the spatial radiating conditions on the sound source, e.g. house walls);
r is the distance between the receiver and sound source (in meters).
Freestanding external installation of the heat pump, radiation into the half-space: Q = 2.
Expected sound pressure level of an ODU Split 11s/t outdoor unit considering the type
of installation and a distance (r) of 10 meters.
Heat pump (or air inlet / outlet) on a house wall, radiation into the neighborhood area:
Q = 4.
Expected sound pressure level of an ODU Split 11s/t outdoor unit considering the type
of installation and a distance (r) of 10 meters.
Heat pump on a house wall in reentrant corner facades, radiation in the eighth space: Q
= 8.
Expected sound pressure level of an ODU Split 11s/t outdoor unit considering the type
of installation and a
distance (r) of 10 meters.
Effect on sound pressure level in dB (A) depending on the distance of the sound source and the receiver and
the type of installation
Directivity (Q)
1m 2m 4m 5m 6m 8m 10 m 12 m 15 m
2 -8 -14 -20 -22 -23.5 -26 -28 -29.5 -31.5
4 -5 -11 -17 -19 -20.5 -23 -25 -26.5 -28.5
6 -2 -8 -14 -16 -17.5 -20 -22 -23.5 -25.5
17
Choosing the right output variant for heating
An exact calculation of the heat load can be done with following the instructions of the EN 12831 standard. However
rough estimating methods are also commonly used with which one can perform a quick calculation. Note that these
estimations cannot replace the proper calculation!
The heat demand is calculated from
- the heated area A;
- the specific heat loss ;
- and the temperature difference of the mean outside temperature and the designed room temperature of the
reference room
as follows: .
As a further simplification we will consider the temperature difference given in the specific heat loss and therefore the
formula will not contain it: .
Typical values for respecting the type of the building. Please note that these values may vary depending on the climatic
conditions of the different geolocations. Values in the table refer to a ΔT of 35 K.
Old building without insulation, wall thickness up to 30 cm. Typical year of building is < 1982. 100 - 150
Old building without insulation, wall thickness up to 35 cm. Typical year of building is 1982 – 1995. 80 - 100
Old building with poor insulation. Typical year of building is 1995 – 2005. 60 - 80
Existing building with average insulation. Typical year of building is 2005 – 2013. 30 - 60
Energy efficient building with thick insulation, very low heat loss. Year of building is > 2013. 15 - 30
Passive house 10
Output power depending on external temperature and ODU variant providing 45 ºC flow temperature
Legend
Output heating power [kW] at 45ºC flow temperature
[1] Split 8
[2] Split 11s/t
[3] Split 13s/t
[4] Split 15s/t
19
Basic installations for Compress 3000 AWS heat pumps
System configuration with heat pump and AWBS indoor unit with mixing valve for additional auxiliary
heater. Operating a direct heating or cooling circuit.
Legend
SEC20 Installer module integrated in the indoor unit T1 Outside temperature sensor
HPC400 System controller (HMI) MK2 Humidity sensor (accessory)
CR10H Room controller with air humidity sensor T0 Flow temperature sensor
(accessory) [1] Placed in the heating/cooling source
CU-EM1 Controller of the external auxiliary heater [2] Placed in the indoor unit
EM1 Additional heat source [5] Placed on the wall
20
System configuration with heat pump and AWES indoor unit with integrated immersion heater. DHW pro-
duction via connected storage tank. Operating a direct heating or cooling circuit.
Legend
SEC20 Installer module integrated in the indoor unit MK2 Humidity sensor (accessory)
HPC400 System controller (HMI) T0 Flow temperature sensor
CR10H Room controller with air humidity sensor TW1 Cylinder temperature sensor (in the scope of
(accessory) delivery)
CW1 DHW cylinder (accessory) PW2 DHW circulation pump (accessory
VW1 3-way valve (accessory) [3] Placed in the indoor unit
T1 Outside temperature sensor [5] Placed on the wall
21
Advanced installations with Bosch Compress 3000 AWS heat pumps
Mono-energetic system with AWES indoor unit featuring integrated electric heater. DHW production via con-
nected storage tank. Operating a direct and a mixed heating or cooling circuit.
Legend
SEC20 Installer module integrated in the indoor unit MK2 Humidity sensor (accessory)
HPC400 System controller (HMI) T0 Flow temperature sensor
CR10H Room controller with air humidity sensor TW1 Cylinder temperature sensor (in the scope of
(accessory) delivery)
CW1 DHW cylinder (accessory) PW2 DHW circulation pump (accessory
VW1 3-way valve (accessory) VC1 Mixing valve (accessory)
T1 Outside temperature sensor TC1 Temperature sensor for the mixed circuit (ac-
PC1 Pump for heating or cooling circuit (accessory) cessory)
MM100 Module for mixed heating or cooling circuit [4] Placed in a unit or on the wall
(accessory) [5] Placed on the wall
22
Bivalent system featuring an auxiliary gas-fired condensing boiler. DHW production via connected storage
tank. Operating a direct heating or cooling circuit.
Legend
SEC20 Installer module integrated in the indoor unit MK2 Humidity sensor (accessory)
HPC400 System controller (HMI) T0 Flow temperature sensor
CR10H Room controller with air humidity sensor TW1 Cylinder temperature sensor (in the scope of
(acces sory) delivery)
CW1 DHW cylinder (accessory) PW2 DHW circulation pump (accessory
VW1 3-way valve (accessory) [1] Placed in the indoor unit
T1 Outside temperature sensor [3] Placed in the heating/cooling source
EM1 Additional heat source [5] Placed on the wall
CU-EM1 Controller of the external auxiliary heater
23
Bivalent system featuring a gas-fired condensing boiler with AWBS indoor unit. DHW production via con-
nected storage tank. Operating direct and a mixed heating or cooling circuits.
Legend
SEC20 Installer module integrated in the indoor unit MK2 Humidity sensor (accessory)
HPC400 System controller (HMI T0 Flow temperature sensor
CR10H Room controller with air humidity sensor (accessory) TW1 Cylinder temperature sensor (in the scope of delivery)
CW1 DHW cylinder (accessory) PW2 DHW circulation pump (accessory
VW1 3-way valve (accessory) VC1 Mixing valve (accessory)
T1 Outside temperature sensor TC1 Temperature sensor for the mixed circuit (accessory)
PC1 Pump for heating or cooling circuit (accessory) [1] Placed in the indoor unit
MC1 Temperature limiter (accessory) [3] Placed in the heating/cooling source
MM100 Module for mixed heating or cooling circuit (accessory) [5] Placed on the wall
EM1 Additional heat source CU-EM1 Controller of the external auxiliary heater
V Variable (up to 4 circuits in total)
24
Bivalent system featuring a gas-fired condensing boiler and buffer tank. DHW production via connected
storage tank. Operating direct and mixed heating or cooling circuits.
Legend
SEC20 Installer module integrated in the indoor unit MK2 Humidity sensor (accessory)
HPC400 System controller (HMI) T0 Flow temperature sensor
CR10H Room controller with air humidity sensor (accessory) TW1 Cylinder temperature sensor (in the scope of delivery)
CW1 DHW cylinder (accessory) PW2 DHW circulation pump (accessory
VW1 3-way valve (accessory) VC1 Mixing valve (accessory)
T1 Outside temperature sensor TC1 Temperature sensor for the mixed circuit (accessory)
PC1 Pump for heating or cooling circuit (accessory) BW1 Buffer tank (accessory)
MC1 Temperature limiter (accessory) CU-EM1 Controller of the external auxiliary heater
MM100 Module for mixed heating or cooling circuit (accessory) [1] Placed in the indoor unit
V Variable (up to 4 circuits in total) [3] Placed in the heating/cooling source
EM1 Additional heat source 5] Placed on the wall
25
Bivalent system featuring a gas-fired condensing boiler and buffer tank with AWBS indoor unit. DHW pro-
duction via connected storage tank with thermal solar support. Operating direct and a mixed heating cool-
ing circuits.
Legend
SEC20 Installer module integrated in the indoor unit PS1 Pump for solar circuit (accessory)
HPC400 System controller (HMI) MS100 Module for thermal solar circuit (accessory)
CR10H Room controller with air humidity sensor (accessory) MK2 Humidity sensor (accessory)
CW1 DHW cylinder (accessory) T0 Flow temperature sensor
VW1 3-way valve (accessory) TW1 Cylinder temperature sensor (in the scope of delivery)
T1 Outside temperature sensor PW2 DHW circulation pump (accessory
PC1 Pump for heating or cooling circuit (accessory) VC1 Mixing valve (accessory)
MC1 Temperature limiter (accessory) TC1 Temperature sensor for the mixed circuit (accessory)
MM100 Module for mixed heating or cooling circuit (accessory) BW1 Buffer tank (accessory)
V Variable (up to 4 circuits in total) [1] Placed in the indoor unit
TS1 Solar panel temperature sensor (accessory) [3] Placed in the heating/cooling source
TS2 Cylinder temperature sensor (accessory) [4] Placed on the wall
KS01 Solar station (accessory) [5] Placed on the wall or in to a unit
EM1 Additional heat source CU-EM1 Controller of the external auxiliary heater
26
Mono-energetic system with buffer tank and AWES indoor unit. DHW production via connected storage tank
with thermal solar support. Operating direct and mixed heating or cooling circuits.
Legend
SEC20 Installer module integrated in the indoor unit PS1 Pump for solar circuit (accessory)
HPC400 System controller (HMI) MS100 Module for thermal solar circuit (accessory)
CR10H Room controller with air humidity sensor (accessory) MK2 Humidity sensor (accessory)
CW1 DHW cylinder (accessory) T0 Flow temperature sensor
VW1 3-way valve (accessory) TW1 Cylinder temperature sensor (in the scope of delivery)
T1 Outside temperature sensor PW2 DHW circulation pump (accessory
PC1 Pump for heating or cooling circuit (accessory) VC1 Mixing valve (accessory)
MC1 Temperature limiter (accessory) TC1 Temperature sensor for the mixed circuit (accessory)
MM100 Module for mixed heating or cooling circuit (accessory) BW1 Buffer tank (accessory)
V Variable (up to 4 circuits in total) [1] Placed in the indoor unit
TS1 Solar panel temperature sensor (accessory) [4] Placed on the wall
TS2 Cylinder temperature sensor (accessory) [5] Placed on the wall or in to a unit
KS01 Solar station (accessory
27
Bosch Thermotechnik GmbH
www.bosch.com