Sie sind auf Seite 1von 4

ELECTRONICALLY REPRINTED FROM MARCH 2015

inside process

Inspecting instruments
installed in hazardous locations
A difficult, time-consuming, and expensive task is made much simpler with wireless instruments
to relay information from flow, pressure, temperature, level, and other field transmitters.

A
major trend in process indus-
tries is the increasing use of wire-
less flow, pressure, temperature,
level, and other field transmitters.
While these instruments are wide-
ly used to provide inexpensive, easy-to-install
measurements in unclassified areas of process
plants, they can also be used in hazardous loca-
tions (Figure 1). This article explains the diffi-
culty, time, and expense involved when installing
and maintaining traditional two-wire or fieldbus
transmitters, and shows how wireless transmit-
ters avoid almost all those problems.

Hazardous requirements
Many strategies exist for safety in process
installations. The simplest strategies to minimize
risk in a hazardous area are to keep instrumenta- Figure 1: Installing and maintaining wired instruments in a hazardous loca-
tion out of the area altogether, or make the area tion can be difficult and expensive. Wireless transmitters can solve these
less hazardous through process improvements. problems. All graphics courtesy: Emerson Process Management
But when instruments must be installed
in hazardous areas, all of the wiring must be requires that an initial inspection must be car-
installed and maintained to the relevant stan- ried out when the equipment is first installed.
dards to prevent an ignition of explosive envi- IEC 60079-17 says the interval between inspec-
ronments. The costs of protecting wired 4 to 20 tions shall not exceed three years without seek-
mA and fieldbus instruments in hazardous areas ing expert advice.
are significant. Although complete inspections have to be
Field transmitter wiring requires wiring, con- done at least every three years, the grade of
Key
duits, cable trays, field junction boxes, and mar- inspection and the interval between inspections
concepts
shalling cabinets. If the instrument is 4-wire, it should take into account the type of equipment; n Installing traditional
must have separate power wiring. All wiring sys- that is, some devices may need to be inspected instrumentation in hazard-
tems must meet the requirements of IEC 60079 more often than every three years depending on ous areas involves wiring
for the type of protection that the circuit is cer- the environmental conditions of the installation. infrastructure that can be
very expensive.
tified for. This could be “EX ia” for intrinsically Continuous and visual inspections, as defined
safe, “Ex d” for explosion-proof, or one of the below, should be done on a regular basis, or n Many wireless field
instruments are suitable
other types of protection permitted. whenever maintenance work is done in the area.
for installation in hazard-
Installing these wiring systems can be quite Close and detailed inspections may require open- ous areas, without that
expensive, but costs don’t stop with installation ing enclosures and using specialized tools so infrastructure.
as initial and periodic maintenance are required such inspections can be done during shutdowns
n Wireless devices also
to ensure that the protection level is being main- or when the area is safe. avoid the need for regular
tained. IEC 60079 covers inspection of electri- There are four grades of inspections defined wiring inspections.
cal equipment in hazardous areas. IEC 60079-14 in IEC 60079-17:
inside process

Table: EC 60079-17 Inspection Schedule 1. Continuous supervision—defined


for EX “i,”“iD,” and “nL” as frequent attendance, inspection, ser-
vice, care and maintenance of the electri-
Check That: Grade of inspection
cal installation by skilled personnel who
A Equipment Detailed Close Visual have the knowledge and skills to main-
tain the equipment in accordance with
Circuit and / or equipment documentation is appro-
1
priate to the EPL/Zone requirements of the location
X X X IEC 60079-17 Clause 4.5.
Equipment installed is that specified in the docu-
2
mentation - Fixed equipment only
X X 2. Visual inspection—an inspection
(Figure 2) that identifies, without use of
3
Circuit and / or equipment category and group are
X X access equipment or tools, defects that
correct
would be apparent to the eye, such as
4 Equipment temperature class is correct X X missing bolts or damaged cables.
5 Installation is clearly labelled X X
3. Close inspection—defined as an
Enclosure, glass parts, and glass-to-metal sealing
6
gaskets and / or compounds are satisfactory
X X inspection that encompasses aspects cov-
ered by a visual inspection and identifies
7 There are no unauthorized modifications X defects that are apparent only by the use
8 There are no visible unauthorized modifications X X of equipment and tools, such as loose
bolts or damaged cable glands.
Safety barrier units, relays, and other energy-lim-
iting devices are of the approved type, installed in
9 X X X
accordance with the certification requirements, and 4. Detailed inspection—defined as
securely earthed when required an inspection that encompasses every-
10 Electrical connections are tight X thing covered by a close inspection and
identifies defects that are only apparent
11 Printed circuit boards are clean and undamaged X
by opening the enclosure and using tools
B Installation and test equipment. Detailed inspections
can find loose terminations or incorrect
Cables are installed in accordance with the
1
documentation
X grounds.
Cables are screened and earthed in accordance
2
with the documentation
X These inspections include all equip-
ment located in the hazardous area, and
3 There is no obvious damage to the cables X X X any protection device located in the safe
Sealing of trunks, ducts, pipes and / or conduits is area (in the case of “EX ia”). In practice,
4 X X X
satisfactory this is difficult and expensive to achieve.
5 Point-to-point connections are all correct X Some wiring systems may be routed
in such a manner as to make inspec-
Earth continuity is satisfactory (e.g. connections are
6 tight, conductors are of sufficient cross-section) for X
tion very difficult. Process plants have
non-galvanically isolated circuits internal permitting procedures that must
be followed when entering hazardous
Earth connections maintain integrity of the type of
7
protection
X X X areas, adding further costs. And there
is, of course, the time required to make
Intrinsically safe circuit earthing and insulation
8 X inspections, to document work done, and
resistance are satisfactory
to keep required records.
Separation is maintained between intrinsically safe It’s important to verify that an instal-
9 and non-intrinsically safe circuits in common distri- X
bution boxes or relay cubicles
lation conforms to a detailed equipment
list and circuit diagrams. These and any
As applicable, short-circuit protection of the power other documentation listing specific con-
10 X
supply is in accordance with the documentation
ditions of use must be made available
11
Compliance with specific conditions of use (if
X for the inspector. Often the equipment
applicable)
list has not been updated with equipment
12 Cables not in use are correctly terminated X changes as plant modifications are car-
ried out, due to either failed equipment
C Environment
being replaced with alternatives, or new
1
Equipment is adequately protected against corro-
X X X
wiring additions.
sion, weather, vibration, and other adverse factors If clarification has to be sought
2 No undue external accumulation of dust and dirt X X X regarding the installation and associat-
ed documentation, this adds to the time
‘  ireless devices that
W
have been certified to the
relevant protection level
for the hazardous area
can reduce the amount of
equipment installed in the
hazardous area, such as
the wiring and supporting
infrastructure needed with a


wired installation.

wireless sensors and transmitters in


enclosures to protect the instruments
from the environment. Because these
instruments are rated for use in the area,
no special protective measures were
required.

Figure 2: Instruments and wiring systems in hazardous locations must be inspected Cutting costs with wireless
regularly. During a visual inspection, a certified technician looks for obvious faults. devices
Adoption of wireless equipment can
taken to carry out the inspection. Reduc- the hazardous area can reduce the amount have significant impact on both CAPEX
ing the number of equipment items of equipment installed in the hazardous (capital expenditures) and OPEX (oper-
reduces the burden of keeping equip- area, such as the wiring and supporting ating expenses).
ment lists updated, and wireless instru- infrastructure needed with a traditional In the CAPEX phase, the design of a
ments are one of best ways to address wired installation. Wireless process trans- circuit using a wireless device achieves
this issue. mitters (Figure 3) are typically battery cost savings. By removing the wires,
Typical issues found during inspec- powered, which eliminates the need for conduit, cable tray, field junction boxes,
tions include: power wiring, and battery power is safe and marshalling cabinets, equipment
n Incorrect or damaged cable gland for use in most hazardous areas. costs are reduced and savings are real-
n Damaged cables For example, a refinery in Mexi- ized in creating drawings and equip-
n Non-IS (intrinsically safe) circuits co was having problems with its cool- ment schedules. This also reduces space
installed with IS circuits ing towers. The wired cooling tower and weight requirements, which can be
n Incorrect segregation of IS and instrumentation was old, and most mea- very important in some industries where
non-IS circuits suring devices were out of service. Mea- space is limited and weight is a factor.
n Wrong zener barrier or galvanic surements were difficult because the The cost of installation must also
isolator fitted process environment was corrosive to be considered, as not having to install
n No earth on zener barrier wiring, mainly due to hazardous chemi- equipment required for wired instru-
n Non-IS earths connected to IS cal vapors. As a result, these areas were ments reduces labor costs and can speed
earth, and poorly instrumented. Consequently, up installation and commissioning times.
n Equipment not as scheduled. control was poor, operations were inef- This also allows for a reduction of facil-
ficient, and the towers required a great ities required to support this type of
The table on page P9 describes the deal of maintenance. work, such as cabins, access equipment,
types of inspections typically required Installing wired instruments was and more.
for traditional instruments and their asso- deemed too expensive because of the Wireless field devices also reduce
ciated wiring systems, and as can be seen cost of equipment and its supporting OPEX, especially the cost of hazard-
they are quite extensive. But there is a infrastructure, and because the corrosive ous area inspections, because much
simplifying solution, one that eliminates environment would degrade the instru- less equipment has to be inspected.
wires and their associated equipment. mentation and raise maintenance costs. Only the instruments themselves have
Required inspections would add further to be inspected, and possibly the wire-
Installing wireless instruments costs, making wired instrument installa- less gateways if they are installed in the
Wireless devices that have been cer- tion impractical. hazardous area. But in many instances,
tified to the relevant protection level for Instead, the refinery installed 122 gateways can be installed outside the
inside process

using a hardwired solution, the inspection ply is in accordance with the


would generally require: documentation.

1. Instrument (equipment) for condi- Looking over the list, it’s clear that
tion, type and certification match- most inspection tasks relate to cables
es equipment schedule and associated equipment, so removing
2. Cable gland at instrument type that equipment from the circuit reduces
and condition the number of inspection tasks.
3. Cable gland at field junction box So if that wired device was replaced
type with a wireless transmitter, such as a
and condition WirelessHART device, the inspection
4. Cable between instrument and list would be somewhat shorter:
field
junction box type and condition 1. Instrument (equipment) for condi-
Figure 3: Battery-powered field devices, 5. Terminals in field junction box tion, type and certification match-
such as this WirelessHART level sen- tightness and compliance with es equipment schedule
sor, can be used in hazardous environ- installation requirements That’s it. The other 14 points are no
ments, including tanks containing flam- 6. Cable gland for main cable from longer applicable as no cables are used
mable materials. safe area to connect the device to the safe area.
7. Cable to main safe area condition Of course this assumes that the gateway
and type is mounted in a safe area, as is the nor-
hazardous area. For the same reason— 8. Safety barrier unit, relays, and mal practice. But even if the gateway is
fewer pieces of supporting devices—the other mounted in the hazardous area, it is still a
number of repairs will be reduced. energy-limiting devices to ensure reduction in the quantity of wired circuits
their condition, type, and cer- to inspect. ce
Wired vs. wireless inspections tification matches equipment
The cost of installing, inspecting, schedule - Ian MacDonald, MBCS, MIDGTE,
and maintaining wired 4 to 20 mA or 9. Cable screens are earthed in is a wireless solution architect at Emer-
fieldbus process instruments in a haz- accordance with documentation son Process Management. He is certi-
ardous area is very high because of the 10. Sealing
 of trunks, ducts, pipes, or fied for hazardous area inspections.
need to support those instruments with conduits is satisfactory
infrastructure including power supplies, 11. P oint-to-point connections are
wires, conduit, and marshalling cabi- correct
nets. All of these items need to be pro- 12. IS
 circuit earthing and insulation Go Online
tected to avoid igniting a flammable or resistance are satisfactory The two main wireless device protocols are:
explosive atmosphere, all the equipment 13. Separation
 is maintained between ISA-100.11a:
needs to be inspected on a regular basis, IS and non-IS circuits www.isa100wci.org
WirelessHART:
and repairs are often required to keep the 14. C ompliance with specific condi- www.hartcomm.org
entire system safe. tions of use For more information, visit:
If we look at a typical intrinsically 15. As applicable, short-circuit www.emersonprocess.com
safe DP (differential pressure) transmitter protection of the power sup- www.controleng.com/wireless

Posted with permission from March 2015. Control Engineering, www.controleng.com CFE Media. Copyright 2015. All rights reserved.
For more information on the use of this content, contact Wright’s Media at 877-652-5295

118481

Das könnte Ihnen auch gefallen