APPENDIX - 7

PROCUREMENT, CONSTRUCTION AND COMMISSIONING SERVICES FOR ADHI GAS COMPRESSION PROJECT

SCHEDULE RATE FOR FIXED PRICE (TABLE-A)

S.No. DESCRIPTION Amount inclusive all Applicable Applicable Total Amount In


taxes & duties GST SST (Pak Rs.)*
(except GST & SST) inclusive all
applicable taxes &
duties
PROCUREMENT & SUPPLIES SUB TOTAL

Supply of Piping bulk material including Piping of different Dia Inches, Isolation Valves, Fittings etc. complete in all
A1.1 respect as per attachment Appendix 7.1 & According to technical requirement set forth in Detailed Engineering Design
Packages ITB Section-4 (Annexure-I / Part-II & Part-V)

A1
Supply, Fabrication, Pre-Commissioning, Commissioning , Installation 05 NOS Vent KO Drum at 05 Different Well Head
location (Adhi-05 / 14 / 15 / 17 & 18) as per technical requirement specified in Vent KO Drum Data Sheets (2390-PRO-
A1.2
DS-0011 / 2390-PRO-DS-0023 / 2390-PRO-DS-0038 / /2390-PRO-DS-0058 / 2390-PRO-DS-0071 ) and Project Technical
Specification ITB Section-4 (Annexure-I / Part-I, Part-II & Part-V)

Supply of Electrical & Instrumentation Items and bulk material as per attachment Appendix 7.2 & according to the
A1.3 requirement set forth in Detailed Engineering Design Documents, Drawings and Project Technical Specifications Refer to
ITB Section-4 (Annexure-I / Part-III).

NOTE: Quantities mentioned in Appended BOQs shall be essentially supplied by Contractor either Installed or Not.
Page 1 of 7

PROCUREMENT, CONSTRUCTION AND COMMISSIONING SERVICES FOR ADHI GAS COMPRESSION PROJECT

SCHEDULE RATE FOR LUMPSUMP PRICE (TABLE-B)

S.No DESCRIPTION Unit Quantity Unit Rate Amount Applicable Applicable Total Amount
(Pak Rs.)* inclusive all GST SST In (Pak Rs.)*
taxes & inclusive all
duties applicable
(except GST taxes & duties
& SST)
SUB TOTAL
CONSTRUCTION & INSTALLATION WORKS (LUMP SUM)

Fabrication, Installation, Erection, Testing of Off-Skid and installation, erection, testing of Inter Skid
Piping, Valves, and Fittings etc. for (05) different Nodal Compressor Packages as per Piping Layout
(2390PIP-PL-4802 / 2390-PIP-PL-4812 / 2390-PIP-PL-4822 / 2390-PIP-PL-4832 / 2390-PIP-PL-4842).
Works also include but not limited to Hydro testing, Testing, Radiography, Painting, Coating, Insulation etc.) JOB 05
B1.1
According to the requirement set forth in Detailed Engineering Design documents and drawings (2390-PIP-
ISO-4801~4820 / 2390-PIP-ISO-4831~4841 / 2390-PIP-ISO-4861~4871 / 2390-PIP-ISO-5101~5111 /
2390-PIP-ISO-5131~5147) and project Technical Specifications Refer to ITB Section-4 (Annexure-I /
Part-II & Part-V)

Installation, Erection, Hook Up of Compressor Package (Compressor, with Engine, Cooler, Slug Catcher,
and Blow Case etc.) as depicted in the package GA drawing (KCP101-K520-DWG-0001 / KCP101-
B1
K521DWG-0001 / KCP101-K522-DWG-0001 / KCP102-K523-DWG-0001 / KCP103-K524-DWG-0001).
B1.2 Works shall be carried out in strict compliance with Compressor Vendor advice/requirement and Company JOB 05
Safety
Guidelines and according to technical requirement of detailed Engineering Design Packages Refer to ITB
Section-4 (Annexure-I / Part-II & Part-V) Refer to ITB Section-4 (Annexure-I / Part-II & Part-V)
Installation, Erection & Hook Up of Vent K.O. Drum according to the requirement set forth in Detailed
B1.3 Engineering Design Documents, Drawings, Project Technical Specifications and Company Safety JOB 05
Guidelines Refer to ITB Section-4 (Annexure-I / Part-II & Part-V)

Construction and Installation of Earthing Materials with Earthing Cable, Pits, Bars & Other Accessories as
B1.4 per Earthing Layout (2390-EL-ELO-3402 / 2390-EL-ELO-3412 / 2390-EL-ELO-3422 / 2390-EL-ELO-3432 /
2390-EL-ELO-3442) at 05 Different NODAL Compressor Locations. According to technical requirement of JOB 05
detailed Engineering Design Packages Refer to ITB Section-4 (Annexure-I / Part-III )

Page 2 of 7
Installation, Testing, Glanding of Lighting with Lighting Fixtures, Light Poles, Pole JB, Cabling, Trenches,
Pole Foundation, Power connection & Other Accessories complete in all aspects as covered in lighting

B1.5 layout (2390-EL-ELO-3403 / 2390-EL-ELO-3413 / 2390-EL-ELO-3423 / 2390-EL-ELO-3433 / 2390-EL- JOB 05


ELO-3443) for all 05 Different NODAL Compressor Location. According to technical requirement of detailed
Engineering Design Packages Refer to ITB Section-4 (Annexure-I / Part-III )

S.No DESCRIPTION Unit Quantity Unit Rate Amount Applicable Applicable Total Amount
(Pak Rs.)* inclusive all GST SST In (Pak Rs.)*
taxes & inclusive all
duties applicable
(except GST taxes & duties
& SST)
Installation, testing and commissioning of Generator set, skid as per manufacturer provided literature
including Electric Control panels and all accessories such as batteries, engine controller, terminal box etc.

B1.6 (Installation include all internal wiring complete in all respect). Intermittent Generator 30 KW Complete in JOB 05
all aspect under Vendor supervision at 05 Different Locations (Wellhead Tk-05, Tk-14, Tk-15, Tk-17, Tk-
18). Please Refer to ITB Section-4 (Annexure-I)

Installation, testing and Commissioning of Solar Panels with Cables, Batteries Connection, Charge
Controllers, Invertors, Structures stand with Battery Room & all other Accessories Complete in all aspect
B1.7 JOB 05
under Vendor supervision at 05 Different NODAL Compressor Locations. Refer to ITB Section-4
(Annexure-I / Part-III)

Installation, testing and Commissioning & Mounting of Lightning Arrestors with cabling and proper

B1.8 Grounding connection & other Accessories Complete in all aspect under Vendor supervision at 05 Different JOB 05
NODAL Compressor Locations. Refer to ITB Section-4 (Annexure-I / Part-III)

Power Cables Installation for Bridle heat tracing, Utilities, Panels & Startup Pumps, this include Cable
laying in trenches, Glanding, Loop & break Testing & all other accessories Complete in all aspect under
B1.9 JOB 05
Vendor supervision at 05 Different NODAL Compressor Locations. Refer to ITB Section-4 (Annexure-I/
Part-III)

Installation, testing and Commissioning of 11KVA UPS System along with Cabling, Terminations all other

B1.10 accessories Complete in all aspect under Vendor supervision at Adhi Plant. Refer to ITB Section-4 JOB 01
(Annexure-I)

Installation, testing and Commissioning of Pressure Gauges 0-2500Psig, Dial size 160 mm St. St Case
Pipes/ Vessels/ Tanks with Manifold Valves & All other Accessories Complete in all aspect at 05 Different
B1.11 Nos 36
NODAL Compressor Locations (Wellhead Tk-05, Tk-14, Tk-15, Tk-17, Tk-18). Refer to ITB Section-4
(Annexure-I / Part-III )

Installation, testing and Commissioning of Temperature Gauges(Ranges Varies), Dial size 160 mm St. St

B1.12 Case on Pipes/ Vessels with All other Accessories Complete in all aspect at 05 Different Locations Nos 18
(Wellhead Tk-05, Tk-14, Tk-15, Tk-17, Tk-18). Refer to ITB Section-4 (Annexure-I / Part-III )

Page 3 of 7
Installation, testing and Commissioning Level gauges on Vessels/ Tanks with All other Accessories

B1.13 Complete in all aspect at 05 Different NODAL Compressor Locations. Refer to ITB Section-4 (Annexure-I Nos 05
/ Part-III )

Installation , checking, Loop checking, testing and Commissioning of Instrument Cables for Digital
B1.14 meter 800
Inputs/Digital Outputs from Compressor station Control System to WHCP 20 Core 2.5mm2

S.No DESCRIPTION Unit Quantity Unit Rate Amount Applicable Applicable Total Amount
(Pak Rs.)* inclusive all GST SST In (Pak Rs.)*
taxes & inclusive all
duties applicable
(except GST taxes & duties
& SST)
Cu/PVC/SWA/PVC Direct Burried along with Suitable Cable glands for both ends at 05 Different NODAL
Compressor Locations. Refer to ITB Section-4 (Annexure-I / Part-III )
Installation , testing and Commissioning of Complete SCADA/Telemetry System with Modem, Antenna,
Pole at wellhead, Antenna at Plant site, EWS and OWS, Printers, Power supplies installation with Software

B1.15 installation, Fiber Optic and Communication cable laying Converters, Cabling, Cable Laying, Trenches & all JOB 05
Other Accessories Complete in all aspect under Vendor supervision at 05 Different NODAL Compressor
Locations. Refer to ITB Section-4 (Annexure-I / Part-III )

Installation, testing and Commissioning of Fire & Gas Detectors with Pole, Testing, Checking & Calibration
B1.16 of Detectors with Cable Laying/Terminations & all other Accessories Complete in all aspect under Vendor
supervision at 05 Different Locations. Refer to ITB Section-4 (Annexure-I / Part-III ) JOB 05

Civil Construction and Steel Structural works for below listed items including supply of outsource soil (for
engineered fill, sand fill, stone solling), cement, aggregates (fine & coarse), fresh water, formworks, steel

B1.17 reinforcement, non-shrinkage EPOXY grout, bitumen for coating, steel embedded parts (lugs,anchor bolts,
hilti bolts, Ms plates, grating, checquered plates), brick masonry, steel structures as per referred drawings.
Installation and construction of structural & civil works including excavation, dewattering, levelling, grading,
laying of filling material(engineered fill, sand fill, stone solling), disposal of excess material, compaction
upto the desired density, formwork fixing, steel reinforcement(cutting, fixing), PCC & RCC works (mixing,
pouring,curing), grouting, fabrication & installation of steel embedded parts, fabrication & installation of
steel structure (lifting, shifting ,painting & erection) at five different wellhead location. All the material &
construction works shall be in compliance with project drawings & technical requirement of detailed
Engineering Design Packages Refer to ITB Section-4 (Annexure-I / Part-IV ).
Following items to be considered
Compressor Package foundation at 05 different well head location (Adhi-05 / 14 / 15 / 17 & 18) as per
B1.17.1 detailed engineering design drawings and Project Technical Specification ITB Section-4 (Annexure-I /
Part IV & Part-V ). JOB 05

Page 4 of 7
Pipe sleepers & Pipe support of Compressor Package Off-skid / Inter-skid piping at 05 Nodal Compressor
B1.17.2 Location (Adhi-05 / 14 / 15 / 17 & 18) as per Pipe Support Off-skid Layouts (2390-CIV-LO-6101 / 2390CIV-
LO-6151 / 2390-CIV-LO-6201 / 2390-CIV-LO-6251 / 2390-CIV-LO-6301) , Pipe Support schedule index
Off-skid (2390-CIV-DT-6101/6102/6151/6152/6201/6202/6251/252/6301/6302) and Project Technical JOB 05
Specification ITB Section-4 (Annexure-I / Part IV & Part-V ).

Construction works with supply of all material for Piping Crossover foundations at 05 different well head Nos 06
B1.17.3

S.No DESCRIPTION Unit Quantity Unit Rate Amount Applicable Applicable Total Amount
(Pak Rs.)* inclusive all GST SST In (Pak Rs.)*
taxes & inclusive all
duties applicable
(except GST taxes & duties
& SST)
location (Adhi-05 / 14 / 15 / 17 & 18) as per drawings (2390-CIV-DT-6103 / 6153/ 6203/ 6253 /6303) and
project technical requirement and specification refer to ITB Section-4 (Annexure-I / Part IV & Part-V ).

Construction works with supply of all material for Light Pole Civil foundations at 05 different well head
B1.17.4 location (Adhi-05 / 14 / 15 / 17 & 18) as per drawings (2390-CIV-DT-6107/6157/6207/6257/6307) and
Nos
project technical requirement and specification refer to ITB Section-4 (Annexure-I / Part IV & Part-V ).
15

Civil foundation of Flare knockout drum at 05 different well head location (Adhi-05 / 14 / 15 / 17 & 18) as
per drawings (2390-CIV-DT-6106 / 2390-CIV-DT-6156 / 2390-CIV-DT-6206 / 2390-CIV-DT-6256 /
B1.17.5 2390CIV-DT-6306) and project technical requirement and specification ITB Section-4 (Annexure-I / Part Nos 05
IV & Part-V ).

Civil construction works associated with the construction of Drain pit at 05 Different Well Head location
(Adhi-05 / 14 / 15 / 17 & 18) as per drawings (2390-CIV-DT-6105 / 2390-CIV-DT-6155 / 2390-CIV-DT6205
B1.17.6
/ 2390-CIV-DT-6255 / 2390-CIV-DT-6305) and project technical requirement and specification refer to ITB Nos 05
Section-4 (Annexure-I / Part IV & Part-V ).

Vent structure foundation at 05 Different Well Head location (Adhi-05 / 14 / 15 / 17 & 18) as per drawings
(2390-CIV-DT-6104 / 2390-CIV-DT-6154 / 2390-CIV-DT-6204 / 2390-CIV-DT-6254 / 2390-CIV-DT-6304)
B1.17.7 and project technical requirement and specification refer to ITB Section-4 (Annexure-I / Part IV & Part-V). Nos 05

Supply, fabrication & installation of steel embedded parts, fabrication & installation of steel structure (lifting,
shifting ,painting & erection) of Compressor package shed with Mechanical Crane at 05 Different Well
B1.17.8 Head location (Adhi-05 / 14 / 15 / 17 & 18) as per drawings (2390-CIV-ST-6101 / 2390-CIV-ST-6151 /
2390-CIV-ST-6201 / 2390-CIV-ST-6251 / 2390-CIV-ST-6301) and project technical requirement and Nos 05
specification refer to ITB Section-4 (Annexure-I / Part IV & Part-V ).

Generator foundation at 05 Different Well Head location (Adhi-05 / 14 / 15 / 17 & 18) as per drawing and
B1.17.9 Project Technical Specification ITB Section-4 (Annexure-I / Part IV & Part-V ). Nos 05

PRE-COMMISSIOINING & COMMISSIOINING SUB TOTAL

Page 5 of 7
Pre-commissioning & commissioning activities for (05) different NODAL Compressor at (Adhi-05 / 14 / 15 /
17 & 18) , including all operations such as, but not limited to, verification that the installation conforms to
plans, specifications and approved drawings, testing and operation of all equipment, flushing and
hydrotesting of all pipings, nitrogen purging and system leak test with process gas, calibration of
B2 B2.1 instruments, functional testing of instrumentation and control system, electrical equipment and systems,
JOB 05
F&G, etc. according to the requirement set forth in Scope of work “ITB section 4 clause 7.0” & Detailed
Engineering Design Package.

S.No DESCRIPTION Unit Quantity Unit Rate Amount Applicable Applicable Total Amount
(Pak Rs.)* inclusive all GST SST In (Pak Rs.)*
taxes & inclusive all
duties applicable
(except GST taxes & duties
& SST)
B2.2 Total Amount ( B1.1 to B2.1 ) in PKR

B2.3 Grand Total Amount ( A1 TO B2 + Table C) in PKR

NOTES:
1. The cost should include all inter connections between Units / Systems and Tie-ins with existing facilities..
2. The Supply of local equipment and material items on ex project site delivery basis.
3. All payments are subject to deduction of applicable taxes.
4. All contingent and incidental material and works must be included in the relevant item in this Price Table to ensure completeness of the PROJECT. The prices above are deemed to be full and final for the
entire scope of work inclusive of incidental and contingent Works
5. The payment terms, milestone payment schedule and bid price schedule are only for payment and not for the scope of work. Any item needed for completing the facility and not listed in ITB are to be provided
by the CONTRACTOR within the CONTRACT PRICE
6. Price against item B1.1 and B2.1 to be quoted on Lump Sum basis.
7. Quantities may increase OR decrease due to any reason. Payment to contractor shall be made as per Actual work done at site...

Page 6 of 7
PROCUREMENT, CONSTRUCTION AND COMMISSIONING SERVICES FOR ADHI GAS COMPRESSION PROJECT

SCHEDULE RATE FOR ADDITIONAL WORKS (PRICE TABLE-C)


S.No. DESCRIPTION Amount Applicable Applicable Total Amount In
inclusive all GST SST (Pak Rs.)*
taxes & duties inclusive all
(except GST &
applicable taxes
SST)
& duties
SUB TOTAL

C1.1 Fabrication , Installation and Erection Works


All additional Piping Fabrication , Piping and Equipment Installation Erection works (additional) required for completion the
project as per requirement define in attachment Appendix 7.1.1

C1.2 Testing and Installation of Electrical and Instrumentation Items


C1
All additional Testing and Installation requirement of Electrical & Instrumentation items (additional) as define in attachment
Appendix 7.2.1

C1.3 Civil and Steel Structure Works


Any Civil construction and Steel Structure works (additional) if required for successful completion of the projects as define in
Appendix 7.3.1

NOTE: Payment to contractor shall be made as per Actual work done at site
Page 7 of 7
PROJECT: ADHI GAS FIELD COMPRESSION PROJECT
PROJECT NO: 2390

PAKISTAN PETROLEUM LIMITED

BULK MATERIAL SUPPLY OF PIPING & FITTINGS


BILL OF QUANTITES

(APPENDIX - 7.1)

0 24/11/2017 ISSUED FOR TENDER AJ

Rev Date Description App’d

Doc No. 2390-PIP-BOQ-0001


PAKISTAN PETROLEUM LIMITED
ADHI GAS FIELD COMPRESSION PROJECT
BILL OF QUANTITIES
FOR PROCUREMENT

UNIT
TOTAL TOTAL
SR # ITEM DESCRIPTION UNIT SPEC RATES REMARKS
Qty. (Pak. Rs.)
(Pak. Rs)

1.0 PIPE:

Pipe,Seamless, ASTM A-106 Gr. B / API 5L Gr. B, as per


1.1 ASME B 36.10

i Dia. 8" Sch. 160 (B.E)


Dia. 8" Sch. 40 (B.E) m EA2 144
ii
Dia. 6" Sch. 160 (B.E) m AA2 702
iii
Dia. 6" Sch. 40 (B.E) m EA2 1362
iv
Dia. 4" Sch. 40 (B.E) m AA2 24
v
Dia. 3" Sch. 40 (B.E) m AA2 252
vi
Dia. 2" Sch. 160 (B.E) m AA2 342
vii
Dia. 2" Sch. 80 (B.E) m EA2 18
viii
Dia. 1 1/2" Sch. 160 (P.E) m AA2 798
ix
Dia. 3/4" Sch. 160 (P.E) m EA2 6
x
Dia. 3/4" Sch. 80 (P.E) m EA2 24
xi
m AA2 12
Pipe Nipple 100mm long THRD x PE, ASTM A-106 Gr. B
1.2 / API 5L Gr. B, as per ASME B 36.10

i Dia. 3/4" Sch.160


ii Dia. 3/4" Sch.80 m EA2 102
m AA2 98
2.0 ELBOWS:

Elbow 90° , Long Radius, B.W, ASTM A-234 Gr. WPB as


2.1 per ASME B16.9

i Dia. 8" Sch. 160 Nos. EA2 5


ii Dia. 8" Sch. 40 Nos. AA2 70

iii Dia. 6" Sch. 160 Nos. EA2 124

iv Dia. 6" Sch. 40 Nos. AA2 7

v Dia. 4" Sch. 40 Nos. AA2 27

vi Dia. 3" Sch. 40 Nos. AA2 30

vii Dia. 2" Sch. 160 Nos. EA2 16

viii Dia. 2" Sch. 80 Nos. AA2 94

Elbow 90°, Long Radius, S.W , 3000# , ASTM A-105, as


2.2
per ASME B16.11

i Dia. 3/4" Nos. - 15

Elbow 90°, Long Radius, S.W , 6000# , ASTM A-105, as


2.3
per ASME B16.11

i Dia. 3/4" Nos. EA2 33


Elbow 45° , Long Radius, B.W, ASTM A-234 Gr. WPB as
2.4
per ASME B16.9

i Dia. 8" Sch. 160 Nos. EA2 10


ii Dia. 8" Sch. 40 Nos. AA2 4

iii Dia. 6" Sch. 160 Nos. EA2 51

iv Dia. 4" Sch. 40 Nos. AA2 20

v Dia. 3" Sch. 40 Nos. AA2 8

vi Dia. 2" Sch. 80 Nos. AA2 3

PAKISTAN PETROLEUM LIMITED


ADHI GAS FIELD COMPRESSION PROJECT
BILL OF QUANTITIES
FOR PROCUREMENT

UNIT
TOTAL TOTAL
SR # ITEM DESCRIPTION UNIT SPEC RATES REMARKS
Qty. (Pak. Rs.)
(Pak. Rs)

3.0 EQUAL TEE:

Equal Tee. B.W, ASTM A-234 Gr. WPB as per ASME


3.1 B16.9

i Dia. 8" Sch. 160 Nos. EA2 10


ii Dia. 6" Sch. 160 Nos. EA2 48

iii Dia. 4" Sch. 40 Nos. AA2 16

iv Dia. 2" Sch. 80 Nos. AA2 12

3.2 Equal Tee.SW, A-105 AS PER ASME B16.11, 6000#

i Dia. 3/4" Nos. EA2 22

3.3 Equal Tee.SW, A-105 AS PER ASME B16.11, 3000#

i Dia. 3/4" Nos. AA2/BA2 18

4.0 BARRED TEE:

4.1 Barred Equal Tee. B.W, MSS SP 75 WPHY 60

i Dia. 6" Sch. 160 Nos. EA2 20

5.0 REDUCING TEE:

Reducing Tee. B.W, ASTM A-234 Gr. WPB as per ASME


5.1 B16.9

i Dia. 8" x 6" Sch 160 No. EA2 17


ii Dia. 8" x 6" Sch 40 No. AA2 3
iii Dia. 8" x 4" Sch 40 No. AA2 10

iv Dia. 4" x 2" Sch 40 x 80 Nos. AA2 16

6.0 REDUCER :

Conc. Reducer, B.W, ASTM A-234 Gr. WPB as per


6.1 ASME B16.9

i Dia. 8'' x 6'' Sch.160 No. EA2 5

ii Dia. 4" x 2" Sch 40 x 80 Nos. AA2 16

iii Dia. 2" x 1 1/2" Sch 160 Nos. EA2 16

iv Dia. 2" x 3/4" Sch 80 x 80 Nos. AA2 12

7.0 WELDOLET:

Weldolet, BW, as per ASME B 16.9 Material: ASTM A105


7.1

i Dia. 8'' x 2'' Sch.160 Nos. EA2 17


ii Dia. 8'' x 2'' Sch.40 x 80 No. AA2 6

iii Dia. 6'' x 2'' Sch.160 Nos. EA2 33

8.0 SOCKOLET:

Sockolet S.W. 3000# as per ASME B 16.11 Material:


8.1 ASTM A-105

i Dia. 6'' x 3/4'' Nos. BA2/AA2 3

ii Dia. 4'' x 3/4'' Nos. BA2/AA2 4

iii Dia. 2'' x 3/4'' Nos. BA2/AA2 16

PAKISTAN PETROLEUM LIMITED


ADHI GAS FIELD COMPRESSION PROJECT
BILL OF QUANTITIES
FOR PROCUREMENT

UNIT
TOTAL TOTAL
SR # ITEM DESCRIPTION UNIT SPEC RATES REMARKS
Qty. (Pak. Rs.)
(Pak. Rs)

Sockolet S.W. 6000# as per ASME B 16.11 Material:


8.2 ASTM A-105

i Dia. 8'' x 3/4'' Nos. EA2 6

ii Dia. 6'' x 3/4'' Nos. EA2 40

iii Dia. 2'' x 3/4'' Nos. EA2 32

9.0 BALL VALVE:

BALL VALVE 800# SW , API STD. 598, BODY-STEEL,


9.1
STEM-S.S. 316, FILLED TEFLON SEAL (SEE VB-101)
i Dia 3/4" 800# Nos. AA2/BA2 46

BALL VALVE 150# RF , ANSI B 16.34, BODY-STEEL,


9.2 STEM-13% CR. S.STEEL, FILLED TFE SEAL,TRUNION
MOUNTED BALL ABOVE 4" (SEE VB-201)

i Dia. 3" 150# No. AA2 6


ii Dia. 2" 150# Nos. AA2 34

BALL VALVE 900# RTJ , BS-2080,ANSI B 16.34, BODY-


9.3 STEEL, STEM-13% CR. S.STEEL, FILLED TFE
SEAL,TRUNION MOUNTED BALL ABOVE 4"
(SEE VB-231)

i Dia. 6" 900# Nos. EA2 74


ii Dia. 2" 900# Nos. EA2 32

BALL VALVE 900# RTJ , API 6D ,ANSI B 16.34, BODY-


STEEL, STEM-13% CR. S.STEEL, FILLED TFE
9.4
SEAL,TRUNION MOUNTED BALL,GEAR OPERATED
FULL BORE.(SEE VB-232)

i Dia. 6" 900# Nos. EA2 11

BALL VALVE 1500# SW , API STD. 598, BODY-STEEL,


9.5
STEM-S.S. 316, FILLED TEFLON SEAL (SEE VB-121)

i Dia 3/4" Nos. EA2 96

BALL VALVE 1500# THRD , API STD. 598,


BODYSTEEL, STEM-S.S. 316, FILLED TEFLON SEAL
9.6
(SEE
VB-122)

i Dia 3/4" Nos. EA2 56

10.0 CHECK VALVE:

10.1 CHECK VALVE 900# RTJ , ANSI B 16.34, BODYSTEEL,


PIN-13% CR. S.STEEL, HARD FACED13% CR.
S.STEEL SEATS , (SEE VC-231)

i Dia. 6" 900# No. EA2 35

PAKISTAN PETROLEUM LIMITED


ADHI GAS FIELD COMPRESSION PROJECT
BILL OF QUANTITIES
FOR PROCUREMENT

UNIT
TOTAL TOTAL
SR # ITEM DESCRIPTION UNIT SPEC RATES REMARKS
Qty. (Pak. Rs.)
(Pak. Rs)

11.0 GLOBE VALVE:

11.1 GLOBE VALVE 900# RTJ , ANSI B 16.34, BODY-


STEEL, STEM-13% CR. S.STEEL, HARD FACED13%
CR. S.STEEL SEATS , (SEE VGL-231)

i Dia. 2" 900# Nos. EA2 15

12.0 PRESSURE SAFTY VALVE (PSV):


12.1 Pressure Safty Valve PSV (SEE DATA SHEET)

Nos. SEE DATA SHEETS


i Dia. 1 1/2" x 2" 900# x 300# - 13

13.0 FLANGES:

Flange, WN, 150#, RF, as per ASME B 16.5, Material:


13.1 ASTM A-105

i Dia. 8" Sch. 40


Dia. 6" Sch. 40 No. AA2 28
ii
Dia. 4" Sch. 40 No. AA2 3
iii Dia. 3" Sch. 40 No. AA2 16
iv Dia. 2" Sch. 80
v Nos. AA2 18
Nos. AA2 101

Flange, WN, 300#, RF, as per ASME B 16.5, Material:


13.2
ASTM A-105

i Dia. 2" Sch. 80 Nos. AA2 16

Flange, WN, 900#, RTJ, as per ASME B 16.5, Material:


13.3
ASTM A-105

i Dia. 8" Sch. 160 Nos. EA2 22


ii Dia. 6" Sch. 160 Nos. EA2 224

iii Dia. 2" Sch. 160 Nos. EA2 110

iv Dia. 2" Sch. 80 Nos. - 16

Flange, WN, 300#, RF, as per ASME B 16.5, Material:


13.4
ASTM A-105

i Dia. 8" Sch. 160 Nos. - 2


ii Dia. 6" Sch. 160 Nos. - 2

Flange, SW, 900#, RTJ, as per ASME B 16.5, Material:


13.5
ASTM A-105

i Dia. 1 1/2" Nos. - 16

Flange, SW, 1500#, RTJ, as per ASME B 16.5, Material:


13.6
ASTM A-105

i Dia. 3/4" Nos. EA2 74

Flange, SW, 150#, RF, as per ASME B 16.5, Material:


13.8
ASTM A-105

i Dia. 3/4" Nos. AA2 52

PAKISTAN PETROLEUM LIMITED


ADHI GAS FIELD COMPRESSION PROJECT
BILL OF QUANTITIES
FOR PROCUREMENT

UNIT
TOTAL TOTAL
SR # ITEM DESCRIPTION UNIT SPEC RATES REMARKS
Qty. (Pak. Rs.)
(Pak. Rs)
Flange Blind, 150#, RF, as per ASME B16.5, Material:
13.9 ASTM A-105

i Dia. 8" No. AA2 6


ii Dia. 4" No. AA2 6

iii Dia. 2" No. AA2 6

iv Dia. 3/4" Nos. AA2 40

Flange Blind, 900#, RTJ, as per ASME B16.5, Material:


13.10
ASTM A-105

i Dia. 8" 900# Nos. EA2 16

ii Dia. 6" 900# Nos. EA2 37

Flange Blind, 1500#, RTJ, as per ASME B16.5, Material:


13.12
ASTM A-105

i Dia. 3/4" 1500# Nos. EA2 70

Flange Blind With 1/2" NPTF 1500#, RTJ, as per ASME


13.13
B16.5, Material: ASTM A-105

i Dia. 3/4" 1500# Nos. EA2 5

Flange Blind With 1/2" NPTF 900#, RTJ, as per ASME


13.14
B16.5, Material: ASTM A-105

i Dia. 2" 1500# Nos. EA2 26

Flange Blind With 1/2" NPTF 150#, RF, as per ASME


13.14
B16.5, Material: ASTM A-105

i Dia. 2" 150# Nos. EA2 7

ii Dia. 3/4" 150# Nos. AA2 6

14.0 GASKETS:

14.1 3mm Thick Compressed Graphite Filled,Spiral Wound


304 S.S Central Ring Per ASME B 16.20

i Dia. 8" RF 300#. Nos. AA2 2


ii Dia. 6" RF 300#. Nos. BA2 2

iii Dia. 8" RF 150#. Nos. AA2 30

iv Dia. 6" RF 150#. Nos. AA2 3

v Dia. 4" RF 150# Nos. AA2 16

vi Dia. 3" RF 150# Nos. AA2 18

vii Dia. 2" RF 300# Nos. BA2 16

viii Dia. 2" RF 150# Nos. AA2 102

ix Dia. 3/4" RF 150# Nos. AA2 52


14.2 Octogonal Ring Type 316L S.S

i Dia. 8" 900# R.# 49 Nos. EA2 24


ii Dia. 6" 900# R.# 45 Nos. EA2 276

PAKISTAN PETROLEUM LIMITED


ADHI GAS FIELD COMPRESSION PROJECT
BILL OF QUANTITIES
FOR PROCUREMENT

UNIT
TOTAL TOTAL
SR # ITEM DESCRIPTION UNIT SPEC RATES REMARKS
Qty. (Pak. Rs.)
(Pak. Rs)

iii Dia. 2" 900# R.#24 Nos. EA2 141

iv Dia. 1 1/2" 900# R.#18 Nos. EA2 16

v Dia. 3/4" 1500# R.#14 Nos. EA2 75

15.0 STUDS/NUTS:

15.1 Studs with 2 Nuts, as per ASME B 16.5 Stud Material : A


193 Gr. B7M Cadmium Plated and Nuts Material : A 194
Gr. 2HM,Cadmium Plated

i 1 1/8" x 225 mm Long Nos. - 101

ii 1 3/8" x 220 mm Long Nos. - 288

iii 1 1/8" x 195 mm Long Nos. - 3212

iv 7/8" x 160 mm Long Nos. - 125

v 7/8" x 145 mm Long Nos. - 749

vi 7/8" x 140 mm Long Nos. - 15

vii 7/8" x 125 mm Long Nos. - 29

viii 5/8" x 90 mm Long Nos. - 322

ix 5/8" x 85 mm Long Nos. - 408

x 3/4" x 120 mm Long Nos. - 15

xi 3/4" x 115 mm Long Nos. - 298

xii 3/4" x 110 mm Long Nos. - 240

xiii 3/4" x 100 mm Long Nos. - 20

xiv 1/2" x 65 mm Long Nos. - 207

xv 1" x 140 mm Long Nos. - 34

16.0 RESTRICTION ORIFICE


16.1 Restriction Orifice, (SEE DATA SHEET)

SEE DATA SHEET


i Dia. 2" 900# Nos. - 13

17.0 FLAME ARRESTOR

17.1 Flame Arrestor (SEE DATA SHEET)

SEE DATA SHEET


i Dia. 8" 150#
No. - 5
18.0 RUPTURE DISK

18.1 Rupture Disk Astm A 216 Gr. WCB

i Dia. 2" 900#


Nos. - 13
19.0 LEVEL GAUGE

19.1 Level Gauge (SEE DATA SHEET)

SEE DATA SHEET


i Dia. 2"
Nos. - 5
20.0 REDUCED COUPLING

20.1 Reduced Coupling M.NPT x F.NPT 6000#

i Dia. 3/4" x 1/2" M.NPT x F.NPT


Nos. - 22
21.0 HEXAGONAL HEAD PLUG

21.1 Hexagonal head plug 6000# THRD

i Dia. 3/4"
Nos. - 52

PAKISTAN PETROLEUM LIMITED


ADHI GAS FIELD COMPRESSION PROJECT
BILL OF QUANTITIES
FOR PROCUREMENT

UNIT
TOTAL TOTAL
SR # ITEM DESCRIPTION UNIT SPEC RATES REMARKS
Qty. (Pak. Rs.)
(Pak. Rs)

22.0 INSULATION KIT

22.1 Insulation Kita RTJ 900#

i Dia. 6" Nos. - 26

TOTAL(Pak. Rs.)

NOTE:
1 This BOQ also includes piping detail for Knock Out drum and Drain Pit
2 All material shall comply with NACE MR-0175 requirement.
PROJECT: ADHI GAS FIELD COMPRESSION PROJECT
PROJECT NO: 2390

PAKISTAN PETROLEUM LIMITED

FABRICATION, INSTALLTION & ERECTION FOR ADDITIONAL WORKS

BILL OF QUANTITES

(APPENDIX - 7.1.1)

0 24/11/2017 ISSUED FOR TENDER AJ

Rev Date Description App’d

Doc No. 2390-PIP-BOQ-0002


ADHI GAS FIELD COMPRESSION PROJECTS
BILL OF QUANTITIES FOR
Fabrication, Installation & Erection For Additional Mechanical Works

ESTIMATE UNIT RATE


SR# ITEM DESCRIPTION UNIT D QTY. (PKR) REMARKS

1.0 PIPING WORKS

Works include shifting from store and placing of pipes &


fittings at required location for welding or threading as
indicated in project drawings or as per site requirement.
Making weld joints / thread as per ASME B 31.3 in joining
pipe lengths and welded pipe fittings such as flanges,
bends, reducers, tees etc. The work also includes gas
cutting/cold cutting as per requirement, grinding, cutting,
beveling, welding, heat treatment, radiography, bolt
tightening(where flanges and valves are involved) etc.

Joints for different pipe sizes: (All welding to be done in


accordance with ASME Section-IX standard & as per
1.1 Sch 40 Sch 80 Sch 120 Sch 160
specified procedures. Radiography & testing also
included.)
a) ASTM A-106 Gr. B / Carbon Steel

i Dia. 10" Dia 30


Inch

ii Dia. 8" Dia 150


Inch

iii Dia. 6" Dia 150


Inch

iv Dia. 4" Dia 40


Inch

v Dia. 3" Dia 30


Inch

vi Dia. 2 1/2" Dia 10


Inch

vii Dia. 2" Dia 100


Inch

viii Dia. 1 1/2" Dia 10


Inch

ix Dia. 1" Dia 15


Inch

x Dia. 3/4" Dia 25


Inch

xi Dia. 1/2" Dia 10


Inch

xii Dia. 1/4" Dia 10


Inch

1.2 Mechanical bolt up complete in all respect as per flange 150# 300# 600# 900#
rating requirements:

i Dia. 10" Nos. 6


ii Dia. 8" Nos. 30

iii Dia. 6" Nos. 30

iv Dia. 4" Nos. 8

v Dia. 3" Nos. 6

vi Dia. 2 1/2" Nos. 2


vii Dia. 2" Nos. 20

viii Dia. 1 1/2" Nos. 2

ix Dia. 1" Nos. 3

x Dia. 3/4" Nos. 5

xi Dia. 1/2" Nos. 2

xii Dia. 1/4" Nos. 2

Instalation & Fabrication of above ground Pipe & Fittings


in all respect as per ASME B31.3 and project
1.3 Sch 40 Sch 80 Sch 120 Sch 160
specification, works include shifting from store and
placing of pipes at required location.

i Dia. 10" m 15
ii Dia. 8" m 75

iii Dia. 6" m 75

iv Dia. 4" m 20

v Dia. 3" m 15

vi Dia. 2 1/2" m 5

vii Dia. 2" m 50

viii Dia. 1 1/2" m 5

ix Dia. 1" m 8

x Dia. 3/4" m 13

xi Dia. 1/2" m 5

xii Dia. 1/4" m 5

Instalation & Fabrication of buried Pipe & Fittings in all


respect as per ASME B31.3 and project specification,
1.4 Sch 40 Sch 80 Sch 120 Sch 160
works include shifting from store and placing of pipes at
required location.

i Dia. 10" m 15
ii Dia. 8" m 75

iii Dia. 6" m 75

iv Dia. 4" m 20

v Dia. 3" m 15
ADHI GAS FIELD COMPRESSION PROJECTS
BILL OF QUANTITIES FOR
Fabrication, Installation & Erection For Additional Mechanical Works

ESTIMATE UNIT RATE


SR# ITEM DESCRIPTION UNIT D QTY. (PKR) REMARKS

vi Dia. 2 1/2" m 5

vii Dia. 2" m 50

viii Dia. 1 1/2" m 5

ix Dia. 1" m 8

x Dia. 3/4" m 13

xi Dia. 1/2" m 5

xii Dia. 1/4" m 5

2.0 INSTALLATION OF PIPING COMPONENT

Installation of valves, strainers, control Valves, safety It includes installation of


valves etc. includes the placing of component between Gate, Ball, Check, Globe
2.1 flanges and bolting up with gasket. Work also includes 150# 300# 600# 900# Needle Valves, Strainer,
Lifting and Transportation from store and unloading at control valves, safety vales
work site. etc.

i Dia. 10" Nos. 6


ii Dia. 8" Nos. 30

iii Dia. 6" Nos. 30

iv Dia. 4" Nos. 8

v Dia. 3" Nos. 6

vi Dia. 2 1/2" Nos. 2

vii Dia. 2" Nos. 20

viii Dia. 1 1/2" Nos. 2

ix Dia. 1" Nos. 3

x Dia. 3/4" Nos. 5

xi Dia. 1/2" Nos. 2

3.0 HYDROSTATIC TESTING:

Hydrostatic testing of Carbon Steel piping, as per ASME


B 31.3, for the following sizes as per project specification
3.1
and Client requirements.
Contractor shall provide
i Dia. 10" all material and
ii Dia. 8" m 15 equipment required for
iii Dia. 6" m 75 hydrostatic testing,
m 75 including supply of
iv Dia. 4"
m 20 portable water and
v Dia. 3" m 15 electricity for test.
vi Dia. 2 1/2" m 5
vii Dia. 2" m 50
m 5
viii Dia. 1 1/2"
m 8
ix Dia. 1" m 13
x Dia. 3/4" m 5
xi Dia. 1/2"

4.0 PAINTING FOR ABOVEGROUND PIPING:

Surface to be Paint: Carbon Steel and Low Temperature Refer to Specifiction for
Carbon Steel. Works include supply of all material, Painting.
application of painting system, surface preparation to
S.A. 2.5 and apply of pre-primer coat ,Primer coat &
4.1 Final Coat as per relevant specification & Client
requirement.

Painting Surface Area


i m2 4,500

5.0 COATING FOR UNDERGROUND / BURIED PIPING:

Surface to be Coated:Carbon Steel and Low Only approved Coating by


Temperature Carbon Steel. Pipe Buriel Depth : 0.2 to 2 Client is recommended.
meters buried underground. Works include supply of all
material, application of painting system, surface
preparation to S.A. 2.5 and apply of Primer Paste. Inner
Wrapping Tape. contractor to confirm that the offered
5.1
product is in full compliance to the requirements as per
relevant specification & Client requirement.

Coating Surface Area


i m2 1,000
6.0 INSTALLATION OF PIPE INSULATION:
ADHI GAS FIELD COMPRESSION PROJECTS
BILL OF QUANTITIES FOR
Fabrication, Installation & Erection For Additional Mechanical Works

ESTIMATE UNIT RATE


SR# ITEM DESCRIPTION UNIT D QTY. (PKR) REMARKS

Installation and fabrication of HOT pipe insulation as per


6.1 company's specifications. Work also includes Lifting and
Transportation from store and unloading at work site.

a) Insulation, 2" Thick,

i Dia. 10" (C.S) m 15

ii Dia. 8" (C.S) m 75

iii Dia. 6" (C.S) m 75

iv Dia. 4" (C.S) m 20

v Dia. 3" (C.S) m 15

vi Dia. 2 1/2" (C.S) m 5

vii Dia. 2" (C.S) m 50

viii Dia. 1 1/2" (C.S) m 5

ix Dia. 1" (C.S) m 8

x Dia. 3/4" (C.S) m 13

xi Dia. 1/2" (C.S) m 5

b) Insulation, 1 1/2" Thick,

i Dia. 10" (C.S) m 15

ii Dia. 8" (C.S) m 75

iii Dia. 6" (C.S) m 75

iv Dia. 4" (C.S) m 20

v Dia. 3" (C.S) m 15

vi Dia. 2 1/2" (C.S) m 5

vii Dia. 2" (C.S) m 50

viii Dia. 1 1/2" (C.S) m 5

ix Dia. 1" (C.S) m 8

x Dia. 3/4" (C.S) m 13

xi Dia. 1/2" (C.S) m 5

Installation and fabrication of COLD pipe insulation as per


6.2 company's specifications. Work also includes Lifting and
Transportation from store and unloading at work site.
a) Insulation, 1 1/2" Thick,

i Dia. 10" (C.S) m 15

ii Dia. 8" (C.S) m 75

iii Dia. 6" (C.S) m 75

iv Dia. 4" (C.S) m 20

v Dia. 3" (C.S) m 15

vi Dia. 2 1/2" (C.S) m 5

vii Dia. 2" (C.S) m 50

viii Dia. 1 1/2" (C.S) m 5

ix Dia. 1" (C.S) m 8

x Dia. 3/4" (C.S) m 13

xi Dia. 1/2" (C.S) m 5

TOTAL (PKR)
PROJECT: ADHI GAS FIELD COMPRESSION PROJECT
PROJECT NO: 2390

PAKISTAN PETROLEUM LIMITED

BULK MATERIAL SUPPLY OF ELECTRICAL & INSTRUMENTATION

BILL OF QUANTITES

(APPNEDIX-7.2)

0 24/11/2017 ISSUED FOR TENDER AJ

Rev Date Description App’d


Doc No. 2390-ELE-BOQ-3002

ADHI GAS FIELD COMPRESSION PROJECT

Document Title: BOQ FOR WELLHEAD NODAL COMPRESSION

Document No: 2390-ELE-BOQ-3002 Rev-0

INSTRUMENT AND ELECTRICAL SUPPLY


DATE 21/11/2017

UNIT TOTAL INCLUDING


S.NO. DESCRIPTION UNIT QUANTITY RATE PRICE GST REMARKS

1 ELECTRICAL SUPPLY

1.1 EARTHING PITS, EARTHING CABLES & ACCESSORIES

Supply of Earthing Materiails with Earthing Cablec, Pits, Bars & Other
Accessories Complete in all aspect.
Refer Dwg #
2390-EL-ELO-3402
2390-EL-ELO-3412 Job 5
2390-EL-ELO-3422
2390-EL-ELO-3432
2390-EL-ELO-3442

Supply of 70 mm² bare stranded Copper conductor. (For Pit to Bar & Light Pole) Mtr. 1500

Supply of 35 mm² stranded GREEN/YELLOW Cu/PVC conductor. (For Bar to


Mtr. 1000
Bar & Bar to Equipments)

25
Supply of Cable Crimp Connector ('C' Type) - 70mm² - 70mm². Nos. Approx.

50
Supply of Cable Crimp Connector ('C' Type) - 35mm² - 35mm². Nos. Approx.

75
Supply of Tin Copper Earthing Lugs for 70mm². Nos. Approx

150
Supply of Tin Copper Earthing Lugs for 35mm². Nos. Approx

Supply of Earth Pit with Cover. Nos. 37

Supply of Earth Rod Driving Stud. Nos. 37

Supply of Saddle Clamp. Nos. 37

Supply of 09 way 240x25x5T copper Earth bar. Nos. 50

Supply of 25mm dia 03m length Copper Clad Steel Earth Rod. Nos. 37

1.2 LIGHTING FIXTURES, LIGHTING CABLES & ACCESSORIES

Supply of Lighting with Lighting Fixtures, Light Poles, Pole JB, Cabling,
Trenches, Pole Foundation, Power connection & Other Asscessories
Complete in all aspect.
Refer Dwg #
2390-EL-ELO-3403 Job 5
2390-EL-ELO-3413
2390-EL-ELO-3423
2390-EL-ELO-3433
2390-EL-ELO-3443

Supply of Two step lighting pole (1250 mm length , 175mm dia of bottom end
step and 8750mm 120mm dia of fixture end step with 6" x 4" reducer b/w steps Nos. 20
)Steel hot dip galvanized height 10m round pole.
Supply of Explosion Proof Flood Lighting Fixtures type Suitable for Zone 2,
complete with 250W LED & all accessories such as 240V, 50Hz, P.F
Nos. 65
improvement capacitor and all installation material By Crouse-Hinds Australia
or equivalent.

Supply Of Explosion Proof 40A, 550V junction box for pole mounted lighting
fixtures Whitworth Rochdale make GB-5103-1221/2090 or
Nos. 20
equivalent.Enclosure With 12 Nos. Terminals For 2.5 Sq. mm. Cable Cores
Alongwith Standard Earthing Rail.

Supply Of Explosion Proof Lighting Distribution Board having 05 No of 40A,


400V Breakers for area lighting. 05 Nos. Terminals For 3C X 4 Sq. mm. Cable
Cores Alongwith Standard Earthing Rail.
Refer SLD #
2390-ELE-SLD-3401
2390-ELE-SLD-3402
2390-ELE-SLD-3403
2390-ELE-SLD-3404 Nos. 5
2390-ELE-SLD-3405
and Datasheet # 2390-
ELE-DS-3406
2390-ELE-DS-3407
2390-ELE-DS-3408
2390-ELE-DS-3409
2390-ELE-DS-3410

Supply Of Power Cable CU/XLPE/PVC/GSWA/PVC, 600/1000v Grade, 3c- 4


Sq. Mm. With Stranded Copper Conductors. Cable Type LC With Core Colors Mtr. 1500
Brown/Blue/Green-Yellow Stripe and Black Outersheath Color.

Supply Of Power Cable CU/XLPE/PVC/GSWA/PVC, 600/1000v Grade, 3c- 2.5


Sq. Mm. With Stranded Copper Conductors. Cable Type LC With Core Colors Mtr. 600
Brown/Blue/Green-Yellow Stripe and Black Outersheath Color.

SUPPLY OF FOLLOWING SIZE EEXE TYPE BRASS CABLE GLAND


2
INCLUDING STD. GLAND KIT ( E1FW / EQUI ).

M25 No. 60

M20 No. 60

3 INSTRUMENTATION SUPPLY

Supply of Pressure Gauges 0-2000Psig, Dial size 160 mm St. St Case on


Pipes/ Vessels/ Tanks with Manifold Valves & All other Accessories Complete
3.1 No. 36
in all aspect..

Supply of Level Gauge glass on Vessels/ Tanks with All other Accessories
3.2 No. 5
Complete in all aspect.

Supply of Temperature Gauges(Ranges Varies), Dial size 160 mm St. St Case


3.3 on Pipes/ Vessels/ Tanks with All other Accessories Complete in all aspect at No. 18
05 Different Locations (Wellhead Tk-05, Tk-14, Tk-15, Tk-17, Tk-18).

NOTES:
CONTRACTOR shall carry out all the tests required for the cables before procurement that shall include, Insulation Tests of all the cables, Continuity check,
1
cable resistance etc. Results of such tests shall be documented and a certificate shall be issued.
PROJECT: ADHI GAS FIELD COMPRESSION PROJECT
PROJECT NO: 2390

PAKISTAN PETROLEUM LIMITED

ELECTRICAL, INSTRUMENTATION ADDITIONAL WORKS FOR SUPPLY


& INSTALLATION
BILL OF QUANTITES

(APPNEDIX-7.2.1)

0 24/11/2017 ISSUED FOR TENDER AJ

Rev Date Description App’d

Doc No. 2390-ELE-BOQ-3003


ADHI GAS FIELD COMPRESSION PROJECT

Document Title: BOQ FOR WELLHEAD NODAL COMPRESSION

Document No: 2390-ELE-BOQ-3003 Rev-0

DATE 21/11/2017
ELECTRICAL, INSTRUMENTATION ADDITIONAL WORKS FOR SUPPLY & INSTALLATION (UNIT RATE)

TOTAL
S.NO. DESCRIPTION UNIT QUANTITY UNIT RATE PRICE REMARKS

ELECTRICAL SUPPLY ITEMS & INSTALLATION WORKS

1 Supply of Electrical Lighting Fixtures as per Datasheet #2390-ELE-DS-3401 No. 5

2 Supply of Electrical Light Pole as per Typical Drawing # 2390-ELE-DT-3401 No. 5

Supply and Construction of Earthing Pit along with Earthing material as per
3 Typical Drawing # 2390-ELE-DT-3404 Complete in all aspects. No. 5

Supply and Installation of Lightning Arrestor with Cable Complete in all


4 No. 5
aspects.

Laying of Electrical Power Cable Upto 25 Sq mm on Cable trays / ladder and


burried complete along with excavation , backfilling, supply of back fill
5 material, supply and application of tiles & markers. Mtr 50

Laying of Electrical Power cable upto 75 Sq.mm on Cable trays / ladder and
burried complete along with excavation , backfilling, supply of back fill
6 material, supply and application of tiles & markers. Mtr 50

Laying of buried cable over 75 mm Sq ; complete along with excavation ,


7 backfilling, supply of back fill material, supply and application of tiles & Mtr 50
markers.

Glanding, Testing, Loop Checking, Termination of Electrical Power Cable


8 upto 25 mmsq Each End 50

Glanding, Testing, Loop Checking, Termination of Electrical Power Cable


9 upto 75 mmsq Each End 50

Glanding, Testing, Loop Checking, Termination of Electrical Power Cable


10 upto 150 mmsq Each End 50

Installation, Testing, Glanding of Lighting with Lighting Fixtures, Light Poles,


Pole JB, Cabling, Trenches, Pole Foundation, Power connection & Other
11 Asscessories Complete in all aspect under Vendor supervision. No. 5

Supply, Installation, Termination, Testing, Glanding of Lighting Distribution


12 Board along with Breakers installation and Civil Works Complete in all No. 5
aspects.

Installation of Earthing Materials with Earthing Cables, Pits, Bars & Other
13 No. 5
Accessories Complete in all aspect under Vendor supervision.

14 Installation of Power Cable Route Markers Per Marker 50

15 Installation, Testing and Commissioning of Generator Upto 50KVA. No. 5

16 Installation, Testing and Commissioning of Generator Upto 100KVA. No. 5

17 Installation of Breakers Upto 32A in Electrical Control Panel No. 50

Installation, Testing, Glanding of Lighting with Lighting Fixture. (Separate


18 fixture) No. 5

19 Installation of Lighting pole with Lighting JB. No. 5

Cable Laying, Testing, Glanding, Power connection of lighting cable upto 16


20 Sq.mm. No. 50

21 Installation, Testing, Termination, Glanding of Lighting Distribution Board. No. 5


INSTRUMENT SUPPLY ITEMS & INSTALLATION WORKS

Supply of Instrument Gauges with all accessories as per Datasheet # 2390- -


1 5
INS DS-2001 No.

Supply of Level Gauge with all accessories as per Datasheet # 2390-INS-


2 No. 5
DS2007

Supply of Flame Detector Pole with all accessories as per Typical Drawing #
3 No. 5
2390-INS-TYP-3421.

Supply of Gas Detector Pole with all accessories as per Typical Drawing #
4 No. 5
2390-INS-TYP-3422.

5 Installation, Testing, checking of Pressure gauge. No. 5

6 Installation, Testing, checking of Temperature Gauge. No. 5

7 Installation, Testing, checking of Level Gauge. No. 5

Installation, Testing, checking, Loop checking and commissioning of


8 Pressure Transmitters. No. 5

Installation, Testing, checking, Loop checking and commissioning of


9 Temeprature Transmitters. No. 5

Installation, Testing, checking, Loop checking and commissioning of Level


12 Transmitters. No. 5

Installation, Testing, checking, Loop checking and commissioning of Flow


13 No. 5
Transmitters.

Laying, Termination, Glanding, Testing, Loop Checking of Multi Pair Cable


Upto 5 Pair 2.5sq mm Cable on Cable trays / ladder and burried complete
14 along with excavation , backfilling, supply of back fill material, supply and Mtr 50
application of tiles & markers.

Laying, Termination, Glanding, Testing, Loop Checking of Multi pair Cable


upto 20 Pair 2.5 Sq mm Cable on Cable trays / ladder and burried complete
15 along with excavation , backfilling, supply of back fill material, supply and Mtr 50
application of tiles & markers.

Laying, Termination, Glanding, Testing, Loop Checking of Multi Core Cable


Upto 20 Core 2.5 Sq mm on Cable trays / ladder and burried complete along
16 with excavation , backfilling, supply of back fill material, supply and Mtr 50
application of tiles & markers.

Laying, Termination, Glanding, Testing, Loop Checking of Multi Core Cable


Upto 40 Core 2.5 Sq mm on Cable trays / ladder and burried complete along
17 with excavation , backfilling, supply of back fill material, supply and Mtr 50
application of tiles & markers.

18 Installation of Instrument Junction Box. No. 5

19 Installation of Cable trays / cable ladder complete with supports 150x 100 mm Mtr 50

Installation of Flame Detector with Pole along with Civil Works Complete in all
20 No. 20
aspects.

Laying, Termination, Glanding, Loop checking of Multi core cable for Fire
detector Burried, complete along with excavation, backfilling, supply of back
21 fill material, supply and application of tiles & markers. Mtr 100

Installation of Gas Detector with Pole along with Civil Works Complete in all
22 No. 60
aspects.

Laying, Termination, Glanding, Loop checking of Multi core cable for Gas
detector Burried cable, complete along with excavation, backfilling, supply of
23 back fill material, supply and application of tiles & markers. Mtr 500

NOTES:
1 All the work shall be in accordance with Installation and Testing Specification.

CONTRACTOR shall carry out all the tests required for the cables that shall include, Insulation Tests of all the cables, Continuity check, cable resistance etc.
2
Results of such tests shall be documented and a certificate shall be issued.
PROJECT: ADHI GAS FIELD COMPRESSION PROJECT
PROJECT NO: 2390

PAKISTAN PETROLEUM LIMITED

CIVIL & STEEL STRUCTURE FOR ADDITIONAL WORKS


BILL OF QUANTITES

(APPENDIX - 7.3.1)

0 24/11/2017 ISSUED FOR TENDER AJ

Rev Date Description App’d

Doc No. 2390-CIV-BOQ-0001


PAKISTAN PETROLEUM LIMITED
ADHI GAS FIELD COMPRESSION PROJECT

CIVIL & STEEL STRUCTURE FOR ADDITIONAL WORKS ( BILL OF QUANTITIES)

Item. PARTICULARS Qty. Unit Rate Amount in Rs. REMARKS


No.

1.0 SITE CLEARANCE

Site clearance including sub-gade prepration, leveling, grading and compaction to achieve 95%
of maximum dry density (Proctor's value) in accordance with drawings, specification and
300 m2
Engineer's instruction and approval, including tranportation/ disposal of surplus materials.

2.0 EXCAVATION

Excavation for all type of foundations in all kinds of soil, dry or wet, hard or soft, including
dewatering of ground water, if present before or after excavation, using mechanical pumps, and
allowing proper drainage system and disposal of water by proper means of transportation with the
help of water tankers to nearest disposal site, disposal of excavated material ,earth breaking
clods, dressing, watering and consolidating by ramming in layers not exceeding 150mm depth to 220 m3 -
obtain 98% modified AASHTO desnity including lifting, shiting or as per instruction and
specification of the consultant and approval of client (Site Engineer). Contractor will carryout
compaction test as per specification with out any extra cost.

3.0 BACKFILLING

Backfilling from selected excavated materials (witin state limits or from stockpile as designated
place by engineer) lay in layers not exceeding to 150mm, including loading, unloading, spreading
and compaction as per required in specifications, filling to embankments /general any type
160 m3
structural and areas developing filling with suitable excavated material / stockpile , debris etc.
Works complete in all respect, as per drawings specifications and as directed by the Engineer.

4.0 ENGINEERED FILLING

Supply & laying Engineered filling to minimize the risk of settlement and improve the ground for
heavily loaded footings, replacement of the top 2 m of weaker material below NGL with an
engineered fill, compacted in layers no greater than 250 mm loose thickness and uniformly
compacted to the minimum dry density of 98% Standard Compaction for cohesive soils and 100%
Standard of granular material is to be used ( i.e. Sand, Crushstone, Gravel ), an additional filling
of 1 to 1.2 m of the same material will be placed on top of 2 m replaced filling to achieve FGL.
100 m3 -
Including loading, unloading, spreading, compaction, watering and consolidation as per required
in specifications. Works complete in all respect, as per drawings specifications and as directed by
the Engineer.Materials should be compacted at a placement moisture content of +/- 2% of
Standard optimum moisture content. Care should be taken not to over compact or place clayey
filling too dry of Standard optimum to minimise the effects of post construction s

5.0 COMPACTED EARTHFILLING

Supply and filling earthfill and consolidating by ramming in layers not exceeding 200mm thick to
obtain 95% modified AASHTO density.The filling material shall be coarse sand from approved
source with maximum aggregate size not exceeding 10mm and according to specification, 100 m3 -
including all lead and lift and carrying out field density tests, modified proctor tests as per
instructions and specifications of the Consultant and approval of Client (Site Engineer).

6.0 PLAIN CEMENT CONCRETE

Supply and laying Plain cement concrete of specified strength for blinding work using approved
quality 3/4" max. size graded crushed aggregate & fine aggregate of required properties
including approved Steel formwork & its removal, all operations of vibrating, levelling,
compacting and curing etc. complete as per specification & instruction of the Consultant.
Note:
1. Sulphate resistant cement should be used for all works.
2. Mix design for each type of sample will be provided by the Contractor
6.1 PCC 1:4:8 (1 cement 4 sand and 8 coarse aggregate) 30 m3 -
6.2 PCC 1:3:6 (1 cement 3 sand and 6 coarse aggregate) 30 m3 -

6.3 PCC 1:2:4 (1 cement 3 sand and 6 coarse aggregate) 300 m3 -

7.0 REINFORCED CEMENT CONCRETE

Supply and laying Reinforced cement concrete shall be developed 28 days work cubical strength
of 3000psi, using approved quality 3/4" max. size graded crushed aggregate & fine aggregate
including approved form work & its removal, all operations of vibrating, levelling, compacting and
curing etc complete but excluding the cost of steel as per specification & instruction of the
Consultant.To confirm the desired work cubical strength 3000Psi (minimum) at 28days(3+3
75 m3 -
minimum at 7 and 28 days) cube tests with (6" × 6" × 6") cube size will be carried out by contractor
from approved laboratory.
Note:
1. Sulphate resistant cement should be used for all concrete works.
2. Mix design for each type of sample will be provided by the Contractor

8.0 STEEL REINFORCEMENT

PAKISTAN PETROLEUM LIMITED


ADHI GAS FIELD COMPRESSION PROJECT

CIVIL & STEEL STRUCTURE FOR ADDITIONAL WORKS ( BILL OF QUANTITIES)

Item. PARTICULARS Qty. Unit Rate Amount in Rs. REMARKS


No.
Supply and laying hard grade ribbed deformed(min yield strength 60,000 psi) steel reinforcement
bars including the cost of straightening, cutting, bending, binding, wastage and such overlaps that
are not shown in drawings, placing in position on cement concrete 1:2:4 precast spacer block or
15 Tons -
m.s chairs,tying with binding wire (GI wire of 18 guage), including cost of chairs and wires etc in
all kinds of RCC works. Complete in all respect to the approval of Client (Site Engineer).

8.1 Deformed Steel Bars (60,000psi)

9.0 STEEL EMBEDDED PARTS

Supply, fabricating and fixing of steel embedded parts in concrete such as M.S plates, Anchor
bolts for all equipment skidsAnchor lugs, MS Rungs, Angles, Bolts with double nuts and washer
1 Tons -
etc. Material for Base Plates, Embedded plates/template shall be ASTM A-36. Complete as per
drawings, specifications and approval of Client (Site Engineer).

10.0 STEEL STRUCTURE

Supply & Installation of steel structure for sheds solar panels,pipe racks,cross overs,pipe supports
etc.the scope of work includes Supply,fabrication,painting,erection,surface preparation of steel
25 Ton
structure etc.complete in all respect as per drawing,instruction and specification of the Consultant
and approval of client.
PAKISTAN PETROLEUM LIMITED
ADHI GAS FIELD COMPRESSION PROJECT

CIVIL & STEEL STRUCTURE FOR ADDITIONAL WORKS ( BILL OF QUANTITIES)

Item. PARTICULARS Qty. Unit Rate Amount in Rs. REMARKS


No.
11.0 CEMENTITIOUS(NON-SHRINKAGE)/EPOXY GROUT

Supply & laying of 25 mm thk. cementitious(non-shrinkage)/epoxy grout, having minimum


compressive strength of 40 N/mm2 in accordance with the Company specification, as per
drawings, instruction and specification of the Consultant and approval of Client ( Site Engineer).

11.1 Cementitious Non Shrinkage Grout 60 m2 -

11.2 Epoxy Grout 30 m2 -

12.0 SAND FILLING

Supply & filling of sand for foundations and consolidating by ramming in layers not exceeding
150mm thick to obtain 95% modified AASHTO density.The infilling material with in the RCC ring
wall shall be coarse sand from approved source with maximum aggregate size not exceeding
35 m2 -
10mm and according to specification, including all lead and lift and carrying out field density tests,
modified proctor tests as per instructions and specifications of the Consultant and approval of
Client (Site Engineer).

13.0 HDPE GEOMEMBRANE

Supply and laying HDPE geomembrane for foundations and evaporation ponds with polylocks
and extrusion weld as per drawing, instruction and specification of the Consultant and approval 30 m2 -
of Client ( Site Engineer).

14.0 BITUMEN COATING

Supply & Laying 1200 micron thick 10/20 grade of bitumen for founadtions & buildings after two
coat of primer outside foundation upto finished ground level to sides of footings including cost of
85 m2 -
all material,labour,equipment etc complete as per drawing and specification and as directed by
the Engineer Incharge.

15.0 GRAVEL FILLING

Supply & filling of gravel in foundations and consolidating by ramming in layers not exceeding
150mm thick as per instructions and specifications of the Consultant and approval of Client (Site 60 m3 -
Engineer).

16.0 UPVC PIPE

Supply & Fixing 2" dia UPVC pipes for leak detectiion in foundations as per drawing, instruction 30 RM -
and specification of the Consultant and approval of Client ( Site Engineer).

17.0 SUB BASE COURSE

Supply and laying 150mm thick sub base granular aggregate in roads compacted upto max dry
density 98% AASHTO. Complete in all respect as per drawing, instruction and specification of the 500 m2 -
Consultant and approval of Client ( Site Engineer).

18.0 BASE COURSE

Supply and laying 150mm thick crushed stone base course in roads compacted upto max dry
density 98% AASHTO. Complete in all respect as per drawing, instruction and specification of the 500 m2 -
Consultant and approval of Client ( Site Engineer).
19.0 ASPHALT WEARING COURSE

Supply and laying 75mm thick asphalt wearing course in two layer over prime coat layer.
Complete in all respect as per drawing, instruction and specification of the Consultant and 500 m2 -
approval of Client ( Site Engineer).

20.0 PRIME COAT

Supply and laying prime coat over base course. Complete in all respect as per drawing, instruction 500 m2 -
and specification of the Consultant and approval of Client ( Site Engineer).

21.0 SEAL COAT

Supply and laying 1/2in thick seal coat over wearing course. Complete in all respect as per
drawing, instruction and specification of the Consultant and approval of Client ( Site Engineer). 500 m2 -

22.0 TACK COAT

Supply and laying tack coat on shoulders. Complete in all respect as per drawing, instruction and 500 m2 -
specification of the Consultant and approval of Client ( Site Engineer).

PAKISTAN PETROLEUM LIMITED


ADHI GAS FIELD COMPRESSION PROJECT

CIVIL & STEEL STRUCTURE FOR ADDITIONAL WORKS ( BILL OF QUANTITIES)

Item. PARTICULARS Qty. Unit Rate Amount in Rs. REMARKS


No.

23.0 GRAVEL CHIPPING

Supply and laying 75mm thick gravel chipping over tack coat on shoulders. Complete in all respect
as per drawing, instruction and specification of the Consultant and approval of Client ( Site 300 m2 -
Engineer).

24.0 PLASTERING

Supply & applying smooth 25mm thk. water proofing pudlo cement plaster to all internal/external
faces of brick masonary, including making champhered edges, corners at junctions recesses &
900 m2 -
racking- out-joints & curing complete i/c cost of scaffolding etc. as per specification & instruction
of the Consultant and approval of Client ( Site Engineer).

25.0 STONE SOLING

Providing and laying stone soling 6" (150 mm) thick of approved quality including hand packing
vertically and filling voids with spawels, consolidating and compacting with mechanical means, as
800 m2 -
per drawings and as per instruction and specification of the Consultant and approval Client (Site
Engineer).

26.0 RCC BUILDINGS

Providing all type of building construction material including construction of grey structure and
finishes work as per specification & instruction of the Consultant and approval of Client ( Site 200 m2
Engineer).

27.0 PAINTS

27.1 WEATHER SHIELD


Providing & applying three coats of weather shield paint over a coat of priming to internal/external
surfaces horizontal/vertical, rubbing smooth with carborandam stone, filling the depressions with
putty, apllying three coats of deluxe ICI or Berger of approved shade & colour to the wall, 750 m2
columns,coved, ceiling & projections of slab/chajja etc as per specification & instruction of the
Consultant and approval Client ( Site Engineer).

27.2 VINYL EMULSION PAINT

Providing & applying three coats of vinyl emulsion paint, over a coat of priming to internal/ external
surfaces horizontal/ vertical, rubbing smooth with carborandam stone, filling the depressions with
putty, applying three coats of Deluxe, ICI or Berger of approved shade & colour to the wall, 750 m2
columns, coved, ceiling & projections of slab/chajja etc as per specification & instruction of the
Consultant and approval of Client ( Site Engineer).

28.0 DOORS

WOODEN DOORS WITH FRAMING

Providing, laying and fixing in position 1-1/2" thick solid commercial ply single shutter wooden
flush door with 3/8" thick best quality wooden lipping all around the shutter, providing, making and
fixing 2" thick deodar wooden frame as layed at wall opening with 6 no. hold fasts cement in 1:4
cement mortor . Providing and laying 2" x 1/2" thick architrave / beading in approved quality wood
& design, providing, laying and fixing approved quality hinges, screws, tower bolts, handles, door
lock, door stoper and necessary hardwares complete in all respect as per specification &
instruction of the Consultant and approval of Client ( Site Engineer).

28.1 3'-0" X 7'-0" Wooden single leaf door 20 NO

28.2 2'-3" X 7'-0" Wooden single leaf door 20 NO

29.0 ALUMINIUM GLAZED WINDOW/VENTILATOR

Providing and fixing in position aluminium glazed windows with bronze anodized aluminium
framing as per British standard manufactured by Lucky, Alcop, Krudson, Pakistan Cables and
A.C.P (fixing through their approved fabricators) Box section, double glazed 101.6mm x 44.5 mm
and 2mm thick including the aluminium fittings with all accessories cutting holes etc. fixing and
cost of first class Belgium made 5 mm thick wire mesh glass complete as per drawings, as per
instruction and specification of the Consultant.
29.1 4'-0" X 4'-0" Aluminium glazed window 30 NO

29.2 1'-0" X 1'-6" Aluminium glazed ventilator 30 NO

30.0 2" thk C.C SCREED

Providing and laying 2" thick cc screed. finished smooth proper straight joints complete in all
respect as per drawings, specification & instruction of the Consultant and approval of Client ( Site 700 m2
Engineer)..

31.0 GLAZED CERAMIC TILES

Providing and laying Glazed Ceramic Tiles of approved quality and shades ( Shabbir or Master )
on walls and floors as shown on drawings including preparation and laying of base plaster and
base floor in 1:4 cement sand mortar, over previously constructed walls & floor, complete in all 100 m2
respect as per drawings and as per instruction and specification of the consultant and approval of
client.

32.0 TERRAZO TILES

PAKISTAN PETROLEUM LIMITED


ADHI GAS FIELD COMPRESSION PROJECT

CIVIL & STEEL STRUCTURE FOR ADDITIONAL WORKS ( BILL OF QUANTITIES)

Item. PARTICULARS Qty. Unit Rate Amount in Rs. REMARKS


No.
Providing & laying 305mm x 305mm x 13mm thick size Terrazo Tiles as shown on drawings
including preparation and laying of base plaster concrete in 1:5 cement sand mortor, grouting,
pointing in white cement as required, including curing, grinding, cutting, repairing & polishing
600 m2
(chemical polish) etc to the desired finish as per drawing and as per specification & instruction of
the Consultant and approval of Client ( Site Engineer).

33.0 BRICK MASONARY

Supply and laying 6in thick good quality burnt bricks having standard size set in 1:6 (1 cement
and 6 sand ) cement sand mortor as per instruction and specification of the consultant and
400 m2
approval of
Client (Site Engineer).

34.0 STONE PITCHING

Supply and laying 150mm thick stone pitching set in 1:6 cement sand mortar of approved material
including hand packing and filling voids, consolidating and compacting with mechanical means,
600 m2
as per drawings, specification of the Consultant, instruction and approval of Client (site Engineer).

35.0 PAVERS

Supply and laying 80mm thick good quality pavers including joint filling fine sand to fill the gaps
as per drawing, instruction and specification of the Consultant and approval of Client ( Site 600 m2
Engineer).

36.0 PIPE SLEEVES

Supply and fixing MS pipe sleeves with leak proof sealant complete in all respect and to the entire
satisfaction of Engineer incharge. The work includes supply and installation as per drawings,
15 RM
instruction and specification of the Consultant and approval of Client ( Site Engineer).

37.0 BUILDING ELECTRIFICATION

Supply, Installation ,testing and commissioning of Building electrification items including lighting
fixtures, Air Conditioners, Switch Sockets, JBs, Circuit Breakers, Fuses, internal wiring, PVC
10 No.s
Conduit, PVC Channels, clamps, and all accessories required for complete electrification of
building.