Beruflich Dokumente
Kultur Dokumente
I. INTRODUCTION
Water drop at
Interfacial film Air temperature at Tw
temperature TW
Thus, cooling is accomplished by sensible heat transfer from water to air and evaporation
of a small portion of water. A generalized cooling tower system is shown in Figure 2. The hot
water which is coming from heat exchanger is sprayed at the top of the cooling tower. Air
enters through the louvers at the two opposite walls of the cooling tower. During cooling
process of water, around 2% water is evaporated. Make water is used to compensate the water
loss due to evaporation. Blowdown is there to drain a part of water containing solid deposit.
The exit cold water from the cooling tower is used in the heat exchanger or other unit operation.
Heat
Exchanger
Air
Air
Cold
Make-Up Water Water
Pump
Blowdown
Figure 2: Generalized Cooling Tower System
(NPTEL)
C. Operation
D. Classification
Induced Forced
1. Atmospheric Tower
It is a big rectangular chamber with two opposites ‘louvered’ walls. Tower is packed with
a suitable ‘tower fill’. Atmospheric air enters the tower through louvers driven by its own
velocity. Direction and velocity of wind greatly influence its performance. Figure 3 shows
the schematic of the atmospheric cooling tower.
2. Natural Draft Towers
A natural draft cooling tower has a large reinforced concrete shell of hyperbolic shape (also
called ‘hyperbolic tower’). Natural flow of air occurs through the tower; hence it is called
natural draft which is shown in Figure 4. The factors responsible for creating natural draft
are:
a. A rise in temperature and humidity of air in the column reduces its density
b. Wind velocity at the tower bottom
Fan is used to enhance the air flow rate in fan assisted natural draft tower. The typical
diameter of tower is 150 m and capacity is 5,00,000 gallons/minute.
Disadvantages:
i. Relatively dry air contacts the coldest water at the bottom of the cooling tower
ii. Humid air is in contact with the warm water and hence maximum average driving
force prevails for both heat and mass transfer.
4. Cross-current and counter-current
Cross-flow induced draft cooling tower supplies horizontal air flow along the packed
height and requires less motor horse power than the counter-flow type. Additional ‘cells’
may be added to raise the capacity. The schematic of induced draft counter-flow and cross-
flow cooling towers are presented in figure 6 and figure 7, respectively.
E. Geometric Terminology
F. Application
A closed cooling circulating water system in a thermal power plant requires 10 kg/s of cooling
water to flow through a condensation equipment for distillation which is used to cool the condenser
cooling water. The water leaves the condenser at 43.3°C. The inlet air dry bulb temperature and
wet bulb temperature are 15°C and 14°C respectively. The water is to be cooled to 10°C below the
wet bulb temperature of air and a ratio of air/steam is 1.5 times the minimum value will be used.
Water compensation will come from a dam at 10°C with a hardness of 500 ppm dissolved solids.
The circulating water cannot have a hardness greater than 2000 ppm. The speed of water is 3 kg/m2
s and the speed of air is 2.8 kg/m2 s. From the given data, calculate the dimensions of the packed
section and design a suitable cooling tower.
V. DESIGN REQUIREMENTS
A. Thermal Design
B. Mechanical Design
A. Given Data
PARAMETER VALUES
WATER FLOW RATE 10 kg/s
WATER UNIT MASS FLOW RATE 3 kg/m2s
AIR UNIT MASS FLOW RATE 2.8 kg/m2s
INLET WATER TEMPERATURE 43.3°C
OUTLET WATER TEMPERATURE 29°C
WATER COMPENSATION TEMPERATURE 10°C
DRY BULB TEMPERATURE 15°C
WET BULB TEMPERATURE 14°C
AIR TO WATER FLOW RATE 1.5
MAXIMUM COOLING TEMPERATURE 10°C
MASS TRANSFER SURFACE 500 ppm
AIR MOLECULAR MASS 28.96 kg/kmol
Table 1: Process Design Data
B. Analysis
Warm Water Air Out
Compensation
Water
C. Physical Properties
Gs
transfer units and calculate height gas-phase enthalpy transfer units, H tG as H tG
kY a
hL a
and hL a are required. A set of parallel lines (tie lines) of slope is drawn between
kY a
8. If the overall enthalpy transfer coefficient K Y is known and used, ‘tie lines’ are vertical.
For a given value of H’, value of H*’ is given by the point on the equilibrium line
H2 '
H
dH '
vertically above it. The integral of Equation
H1 '
*
H'
N t 0G
gives the number of
Approach: It is the difference between cooling water temperature leaving cooling tower and
wet-bulb temperature of inlet air which is approach to wet bulb temperature (°F), (TL1-Tas). For
getting small approach, cooling tower height must be increased. To achieve zero (0) approach
theoretically, infinite packing height is needed.
Range: ‘Cooling range’ or purely ‘range’ is the difference in the inlet hot water and outlet
cooled water temperature (°F) (TL2-TL1).
Step 1:
Specify the inlet and outlet temperatures and flow
rate of warm water
Step 2:
Select the design value of dry-bulb and wet-bulb
temperatures of air
Step 3:
Draw the equilibrium line curve
Step 4:
Locate the lower terminal of the operating line on
TL-H plane by the point (TL1, H1’)
Step 5:
Draw a tangent to the equilibrium line through the
point (TL1, H1’)
Step 6:
Locate the upper terminal of the operating line by
the point (TL2, H2’)
Step 7:
Calculate the number of gas phase enthalpy
transfer units and height gas-phase enthalpy units
Step 8:
Calculate the overall transfer unit
Step 9:
Calculate the height of a transfer unit or the
packed height
Figure 3: A Design Procedure for Cooling Tower
B. Thermal Design Calculations
STEP 1:
Specify the inlet and outlet temperatures and flow rate of warm water
PARAMETER VALUE
Inlet Water Temperature 43.3°C
Outlet Water Temperature 29°C
Table 3: Temperature of Water
STEP 2:
Selecting the design value of dry-bulb and wet-bulb temperatures of air
PARAMETER VALUE
Dry-Bulb Temperature 15°C
Wet-Bulb Temperature 14°C
Table 4: Temperature of Air
STEP 3:
From the given data in psychrometric chart, the equilibrium line curve is shown below.
250.0
200.0
150.0
100.0
50.0
0.0
20 25 30 35 40 45 50
Temperature [°C]
XII. APPENDIX
XIII. REFERENCES