Sie sind auf Seite 1von 30

0739DB9901R11/03

June 2004
Data Bulletin Cedar Rapids, Iowa, USA

International Miniature Circuit Breakers


with QO® Plug-on and Bolt-on Connections
Class Number 0739
Retain for future use.

GENERAL DESCRIPTION The following topics are covered in this bulletin.


■ Characteristics on page 2
■ Circuit Breaker Operating Characteristics on page 3
■ Main Circuit Breakers on page 5
■ QO-MBGX main circuit breakers with residual current protection on
page 7
■ Main Switch Disconnectors and Main Lugs on page 10
■ QOE200 Main Switch with Residual Current Protection on page 12
■ QOE Circuit Breakers on page 14
■ QOE-RCBO Circuit Breakers with Residual Current Protection on
page 17
■ QOH-X Circuit Breakers on page 20
■ QOH-RCDX Circuit Breakers with Residual Current Protection on
page 24
■ QOXD Circuit Breakers on page 27
In 1955 Square D Company introduced the QO® Plug-on System and
revolutionized the way electrical contractors install miniature circuit breakers
in the United States. Today, as part of Schneider Electric, we offer the same
Plug-on System technology around the world. A full line of IEC Certified QO
products are available for residential, commercial and industrial
applications.

Table 1: International Miniature Circuit Breaker Description

Single-phase Three-phase
Circuit
Description Consumer Distribution
Breaker
Units Boards
QO-MBX Main circuit breakers —
Main circuit breakers with residual
QO-MBGX —
current protection
QO-M/QO-L Main switches and lugs
Main switches with residual current
QOE200 —
protection
QOE Branch circuit breaker
Branch circuit breaker with residual
QOE-RCBO
current protection
QOH-X Branch circuit breaker
Branch circuit breaker with residual
QOH-RCDX
current protection
QOXD Branch circuit breaker

© 2000-2004 Schneider Electric All Rights Reserved 1


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

CHARACTERISTICS • Circuit breakers are rated 240 Vac single-phase and 415 Vac three-
phase, 50/60 Hz, 3–100 A.
• Circuit breakers are available in 1-, 2- or 3-pole construction.
• Thermal trip elements are factory calibrated to 40°C (IEC 947-2) and
30°C (IEC 898) ambient temperature.
• RCBO devices available with 10 mA, 30 mA and 100 mA residual
current protection.
• Trip-free handle ensures tripping even when the circuit breaker is held or
locked in the ON position.
• Circuit breakers are in compliance with international standards set by
the International Electrotechnical Commission (IEC).
• The CE marking is located on each circuit breaker in accordance with
the low-voltage directive of the European Union.
• The entire QO circuit breaker family provides the advantage of a plug-on
connection. (Bolt-on connections also available.)

Advantages of the Plug-on System • A 50% reduction on installation time compared to a lug/lug (DIN)
alternative.
• No link bars to fit and tighten.
• Contact jaws automatically align the circuit breakers in the equipment.
• High short circuits result in an increase in jaw pressure reducing the
potential for hazardous arcs on the line side of the circuit breaker.

Figure 1: Plug-on System


07393011

2 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

Table 2: Accessories
Circuit Breaker Catalog Number

Accessory

QOE-RCBO

QOH-RCDX
QO-MBGX
Accessory Description Catalog

QOE-200
QO-MBX

QOH-X
Number

QOXD
QOE
Converts any two adjacent 120/240 Vac single-pole circuit breakers to independent-
Handle Tie QO1HT — — — — —
trip 2-pole.
Clamp for holding QO single-pole circuit breaker handle in ON or OFF position. QO1LO — — — — —
Handle
Clamp Clamp for holding QO either 1-, 2- or 3-pole circuit breaker handles in ON or OFF
HLO-1 — — —
position.
Attaches to 1-, 2- and 3-pole circuit breaker handles (removable). QOEPLA — — — — — —
Attaches to single-pole circuit breaker handles (removable). QOE-1PL — — — — — — —
For padlocking single-pole QO circuit breaker in ON or OFF position (fixed). QO1PA — — — — —
For padlocking single-pole QO circuit breaker in ON or OFF position. For 2- and 3-
pole QO circuit breakers which require padlocking in either ON or OFF position QO1PL — — — — —
(fixed).
Handle
For padlocking single-pole QO circuit breaker in ON or OFF position (removable). QOHPL — — — — —
Padlock
Attachment For padlocking single-pole QO circuit breaker in ON or OFF position. For 2- and 3-
pole QO circuit breakers which require padlocking in either ON or OFF position QO1HPL — — — —
(removable).
For padlocking 2-pole QO-MBGX circuit breaker in either ON or OFF position
GFI2PA — — — — — — —
(removable).
For padlocking single-pole QO circuit breaker in the OFF position only (fixed). QO1PAF — — — — —
For padlocking 2- and 3-pole QO circuit breakers in the OFF position only (fixed). QO2PAF — — — — —

CIRCUIT BREAKER OPERATING


CHARACTERISTICS

Table 3: Main Circuit Breakers

Circuit Breaker Continuous IEC 60947-2 Service Rating Icu (Ics) Residual Trip
Catalog Number Prefix Number of Poles Ampere
Current BS4293
Plug-on Bolt-on Rating 240 V 415 V
QO-MBX N/A 2 10–100 10 000 (25%) — —
QO-MBGX30 N/A 2 16–63 10 000 (25%) — 30 mA

Table 4: Branch Circuit Breakers

Circuit Breaker
Catalog Number Prefix Number of Continuous Ampere IEC 898 Service Rating Icn Tripping
Poles Rating Characteristics
Plug-on Bolt-on 240 V 415 V
QOXD QOBXD 1, 2, 3 10–32 3 000 3 000 Type D (10–20 In)
QO-EB6 N/A 1 3–63 6 000 — Type B (3–5 In)
QO-EC6 N/A 1, 3 6–63 6 000 6 000 Type C (5–10 In)
QO-ED6 N/A 1 6–63 6 000 — Type D (10–20 In)
QO-EB10 N/A 1 3–63 10 000 — Type B (3–5 In)
QO-EC10 N/A 1, 2, 3 6–63 10 000 10 000 Type C (5–10 In)
QO-ED10 N/A 1, 2, 3 6–63 10 000 10 000 Type D (10–20 In)

© 2000-2004 Schneider Electric All Rights Reserved 3


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

Table 5: Branch Circuit Breakers

Circuit Breaker
Continuous Ampere IEC 947-2 Service Rating Icu (Ics)
Catalog Number Prefix Number of Poles
Rating
Plug-on Bolt-on 240 V 415 V
1, 2, 3 10–32 3 000 (100%) 3 000 (100%)
QOXD QOBXD 1 40–63 3 000 (50%) —
2, 3 40–100 3 000 (50%) 3 000 (50%)
1, 2, 3 10–63 5 000 (25%) 5 000 (25%)
QOH-X QOBH-X 1, 2, 3 70–100 6 000 (25%) 6 000 (25%)
4 100 — 6 000 (25%)

Table 6: Residual Current Circuit Breakers

Circuit Breaker Continuous IEC 898 Service Residual Trip


Catalog Number Prefix Number Rating Icn
Ampere Current
of Poles
Plug-on Bolt-on Rating 240 V 415 V BS4293

QOE-B01 N/A 1 6–40 10 000 — 10 mA


QOE-B03 N/A 1 6–40 10 000 — 30 mA
QOE-C01 N/A 1 6–40 10 000 — 10 mA
QOE-C03 N/A 1 6–40 10 000 — 30 mA
QOE-C100 N/A 1 6–40 10 000 — 100 mA

Table 7: Residual Current Circuit Breakers

Circuit Breaker IEC 947-2 Service


Catalog Number Prefix Number Continuous Ampere Rating Icu (Ics)
of Poles Rating
Plug-on Bolt-on 240 V 415 V
QOH-RCDX10 QOBH-RCDX10 1 10–32 5 000 (25%) —
QOH-RCDX30 QOBH-RCDX30 1 10–32 5 000 (25%) —

4 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

MAIN CIRCUIT BREAKERS QO-MBX main circuit breakers are designed for use as incoming main
devices for single-phase consumer unit applications.
Figure 2: QO-MBX Circuit Breaker
• Compliance with International Standards: Certified to IEC 60947-2,
10 kA at 240 Vac when used as a main incomer on single-phase
07393002

systems, 50/60 Hz, CE marked.


• ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
• Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
Table 8: QO-MBX Circuit Breaker

Circuit Breaker
Continuous Ampere Rating
Catalog Number

2-Pole Circuit Breaker


16 QO216MBX
20 QO220MBX
32 QO232MBX
45 QO245MBX
63 QO263MBX
70 QO270MBX
80 QO280MBX
100 QO2100MBX
• Trip Indication: Indication of a tripped circuit breaker on overload or
short circuit is by location of the handle in the center position. The circuit
breaker is also equipped with the Square D exclusive Visi-Trip® indicator
(a luminescent red trip indicator on the front of the circuit breaker).
• Thermal Trip Element: Thermal trip elements are factory calibrated at
40°C ambient temperature.
• Endurance (Switching Operations):
— 1,500 full-load operations
— 8,500 no-load operations
• Mounting: Plug-on connection.

Accessories • Handle Clamp (HLO-1)


The handle clamp accessory fastens the handle in the ON or OFF
Figure 3: QO-MBX Circuit Breaker position. This handle clamp cannot be padlocked.
Accessories • Handle Padlock Attachments (QO1PL, QO1HPL)
Handle padlock attachments allow padlocking the circuit breaker
07393026

07393043

handles in the ON or OFF position. They are available in two styles:


Fixed and removable. The fixed style (QO1PL) is intended to be a
permanent device. The padlock can be removed to resume normal
operation. The removable style (QO1HPL) is intended to be a temporary
HLO-1 Handle Clamp device and must be removed to resume normal operation. (Padlock is
QO1HPL Removable
Padlock Attachment
not included.)
07393042

— Removable attachment: QO1HPL


— Fixed attachment: QO1PL

QO1PL Fixed
Padlock Attachment

© 2000-2004 Schneider Electric All Rights Reserved 5


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

Lugs

Figure 4: QO-MBX Circuit Breaker Lugs Table 9: QO-MBX Circuit Breaker Lugs
Continuous Wire Wire Size Tempera- Torque Value
07393015

Ampere Type 2 AWG ture N•m lb-in


(1)
Rating mm Rating
10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36

(2) 10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36

10–32 A Lugs 45–63 A Lugs 70–100 A Lugs 45–63 Al/Cu (1) 10–25 (1) #8–#2 75°C 5 45
70–100 Al/Cu (1) 25–50 (1) #4–#2/0 75°C 6 50

Dimensions
Figure 5: QO-MBX Circuit Breaker Dimensions

Dim. A: 3.0 in. (76 mm), 10–32 A


07393030

0.94 Dim. B: 3.125 in. (79 mm), 45–63 A


(24) Dim. C: 3.5 in. (89 mm), 70–100 A

1.48 26°
(38)
1.34
(34) 2 1°

Tripped
°
0.16 22

F
0.53

set
OF
(4)

ON
(13)

Re
Dim. 0.25
2.91
Dim. C (6) 2.92
(74) (74)
Dim. B
2.31
A (59)

0.75 in.
2.75 Dual Dimensions:
(19) (mm)
(70)

6 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

QO-MBGX MAIN CIRCUIT BREAKERS QO-MBGX main circuit breakers with residual current protection are
WITH RESIDUAL CURRENT designed for use as incoming main devices for single-phase consumer unit
PROTECTION applications.
• Compliance with International Standards: Certified to IEC 61009-1
Figure 6: QO-MBGX Circuit Breaker 10 kA at 240 Vac when used as a main incomer on single-phase
07393009 systems, 50/60 Hz, CE marked.
• ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
• Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
• Trip Indication: Indication of a tripped circuit breaker on overload, short
circuit or residual current ground fault is by location of the handle in the
center position. The circuit breaker is also equipped with the Square D
exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the
front of the circuit breaker).
• Push-to-test Function: A yellow push-to-test button is positioned on
the front of the device for testing the residual current electronic trip
circuit and mechanical tripping interface.
• Thermal Trip Element: Thermal trip elements are factory calibrated at
40°C ambient temperature
• Residual Current Protection: Residual ground-fault trip currents are
factory set at 30 mA.
Table 10: QO-MBGX Circuit Breakers
• Endurance (Switching Operations):
Continuous Circuit Breaker
Ampere Rating Catalog Number — 1,500 full-load operations
— 8,500 no-load operations
Residual Trip
2-Pole • Mounting: Plug-on connection.
Current 30 mA
16 QO216MBGX30
20 QO220MBGX30
32 QO232MBGX30
45 QO245MBGX30
63 QO263MBGX30

Accessories
• Handle Clamp (HLO-1)
Figure 7: QO-MBGX Circuit Breaker The handle clamp accessory fastens the handle in the ON or OFF
Accessories position. This handle clamp cannot be padlocked.
• Handle Padlock Attachments (GFI2PA, QO1HPL)
07393026

Handle padlock attachments allow padlocking the circuit breaker


handles in the ON or OFF position. They are available in two styles:
fixed (GFI2PA) and removable (QO1HPL). The fixed style is intended to
HLO-1 Handle Clamp be a permanent device. The padlock can be removed to resume normal
operation. The removable style is intended to be a temporary device and
07393042

07393043

must be removed to resume normal operation. (Padlock is not included.)

GFI2PA Fixed QO1HPL Removable


Padlock Attachment Padlock Attachment

© 2000-2004 Schneider Electric All Rights Reserved 7


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

Lugs

Figure 8: QO-MBGX Circuit Breaker Lug Table 11: QO-MBGX Circuit Breaker Lug
Continuous Lug Wire Size Torque Value
07393016

Wire Temperature
Ampere
Type Rating
Rating mm2 AWG N•m lb-in

16–63 Al/Cu (1) 2.5-16 (1) #14–#6 75°C 5 45

16–63 A Lug

Dimensions

Figure 9: QO-MBGX Circuit Breaker Dimensions

0.94
07393031

(24)

26°

22 ° Tripped 21
°

set
OF
ON

Re

2.91
(74)
2.31
(59)

1.49
(38) 4.12 in.
Dual Dimensions:
(103) (mm)

8 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

Connections

Figure 10: QO-MBGX Circuit Breaker Connections in 240 Vac Single-phase Consumer Unit
07393029

240 Vac Source Branch Circuit Breakers

N L
240 V

Load
Load
QO-MBGX 240 V
Main Circuit Breaker

Load

S/N

GND

© 2000-2004 Schneider Electric All Rights Reserved 9


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

MAIN SWITCH DISCONNECTORS AND QO-M main switch disconnectors and QO-L main lugs are designed for use
MAIN LUGS as incoming main devices in single-phase consumer unit and three-phase
distribution panelboard applications.
Figure 11: QO-M Main Switch Disconnector
• Compliance with International Standards: QO-M switches are
certified to IEC 60947-3 at 240 Vac single phase and 415 Vac three
07303008

phase, 50/60 Hz, CE marked.


— Duty category AC21-A (125 A) and AC22-B (100 A).
• ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
• Handle Operation: Over-center toggle mechanism. ON-OFF isolator
switch disconnector.
• Mounting: Plug-on connection.
• Accessories: A padlocking feature is incorporated into the design of the
switch disconnector.

Figure 12: QO-L Main Lug


Table 12: QO-M/QO-L Main Switch Disconnect and Main Lug
07303014

Ampere
Catalog Number
Rating

Main Switch
1-Pole 2-Pole 3-Pole 4-Pole
Units
100 N/A QO1100M — —
125 N/A N/A QO3100M —
125 (4-pole) N/A N/A QO4100M QO4100M
125 (4-pole
with solid N/A N/A QO4100MN QO4100MN
neutral)

Main Lug
Units
100 QO1100L N/A N/A —
125 N/A N/A QO3100L —
125 (4-pole) N/A N/A QO4100L QO4100L

Lug

Figure 13: QO-M/QO-L Lug Table 13: Table 11: QO-M/QO-L Lug
Continuous Lug Wire Size Torque Value
07393020

Wire Temperature
Ampere
Type mm2 AWG Rating N•m lb-in
Rating
100–125 Al/Cu (1) 10–50 (1) #12–#2/0 75°C 6 50

100–125 A Lug

10 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

Dimensions
Figure 14: QO-M Main Switch Disconnector Dimensions

2.25
07393032

(57)
0.25
(6.3) 1.62
(41)
0.34
(8.7)

0.20
(5)

60°

0.29 0.56
(7.5) (39)

0.25 0.43
(6.3) (11)

3.20
(81)

3.0 2.25 1.50 0.75


(76) (57) (38) (19)

3.36
(85)

0.55
(14)

in.
Dual Dimensions:
(mm)

© 2000-2004 Schneider Electric All Rights Reserved 11


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

QOE200 MAIN SWITCH WITH RESIDUAL QOE200 main switches with residual current protection are designed for
CURRENT PROTECTION use as incoming main devices in single-phase consumer unit applications.

Figure 15: QOE200 Main Switch


• Compliance with International Standards: Certified to BS 4293 at 240
Vac single-phase, 50/60 Hz, CE marked.
• ON/OFF Indication: ON/OFF markings are on the face of the circuit
07393004

breaker along with the international I/O markings.


• Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
• Trip Indication: Indication of a tripped circuit breaker on residual
current ground fault is by location of the handle in the OFF position. The
circuit breaker is also equipped with a red trip indicator on the front of the
device.
• Push-to-test Function: A yellow push-to-test button is positioned on
the front of the device for testing the residual current electronic trip
circuit and mechanical tripping interface.
• Residual Current Protection: Residual ground-fault trip currents are
factory set at 30 mA, 100 mA or 300 mA. They are sensitive to ac
currents.
• Mounting: Plug-on connection.

Continuous Circuit Breaker


Ampere Rating Catalog Number (2-Pole)

Residual Trip Current 30 mA


63 QOE200R30
100 QOE20030

Residual Trip Current 100 mA


63 QOE200R100
100 QOE200100
100 with time delay QOE200100S

Residual Trip Current 300 mA


63 QOE200R300
100 QOE200300

Accessory Handle Padlock Attachment (QOEPLA)

Figure 16: QOEPLA Handle Padlock The handle padlock attachment allows padlocking of the main switch
Attachment handles in the ON or OFF position. The padlock attachment is intended to
be a temporary device and must be removed to resume normal operation.
(Padlock is not included.)
07393023

12 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

Lug

Figure 17: QOE200 Circuit Breaker Lug Table 14: QOE200 Circuit Breaker Lug
Continuous Lug Wire Size Torque Value
07393019

Wire Temperature
Ampere
Type Rating
Rating mm2 AWG N•m lb-in

63–100 Cu (1) 10–50 (1) #8–#1/0 75°C 3.5 32

63–100 A Lug

Dimensions
Figure 18: QOE200 Circuit Breaker Dimensions

1.45
(37)
07393033

1.40
(35)
0.49 0.45
0.19
(12) (11)
(5)

85°
4.13 0.35 0.19
105 2.68 (8.8) (5)
(68)

in.
Dual Dimensions:
(mm)

Connections
Figure 19: QOE200 Circuit Breaker Connections

Line Power QOE-200 Load Switches


07393040

2-pole Circuit Breaker


N L
240 V Load Power

Load 1

Load 2
240 V
Load Neutral

Load 3

S/N

GND

© 2000-2004 Schneider Electric All Rights Reserved 13


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

QOE CIRCUIT BREAKERS QOE current-limiting branch circuit breakers are designed for use in single-
phase consumer unit and three-phase distribution panelboard applications.
Figure 20: QOE 1-Pole Circuit Breaker • Compliance with International Standards: Certified to IEC 60898,
6 kA and 10 kA at 240 Vac single-phase and 415 Vac three-phase,
50/60 Hz, CE marked.
07393077

• ON/OFF Indication: ON/OFF markings are on the handle of the circuit


breaker along with the international I/O markings.
• Handle Operation: Trip-free handle that ensures tripping even when
held or locked in the ON position.
• Trip Indication: Indication of a tripped circuit breaker on overload or
short circuit is by location of the handle in the OFF position.
• Thermal Trip Element: Thermal trip elements are factory calibrated at
30°C ambient temperature (50°C calibration available: Contact your
local sales office).
Instantaneous-trip level types B, C and D:
— Type B—(3–5 In) Overcurrent protection for sensitive equipment
Figure 21: QOE 3-Pole Circuit Breaker
— Type C—(5–10 In) Overcurrent protection for all application types
— Type D—(10–14 In) Overcurrent protection for loads with high inrush
currents
07393005

• Mounting: Plug-on connection.

Accessory Handle Padlock Attachment (QOEPLA)


The handle padlock attachment allows padlocking the circuit breaker
Figure 22: Handle Padlock Attachment handles in the ON or OFF position. The padlock attachment is intended to
(QOEPLA) be a temporary device and must be removed to resume normal operation.
(Padlock is not included.)
07393023

Lugs
Table 15: QOE Circuit Breaker Lugs
Figure 23: QOE Circuit Breaker Lugs
Continuous Torque
Lug Wire Size
Wire Temperature Value
07393018
07393017

Ampere
Type Rating
Rating mm2 AWG N•m lb-in
3–25 Cu 1–25 (1) #18–#14 75°C 3.5 32
32–63 Cu 2.5–35 (1) #14–#2 75°C 3.5 32

3–25 A Lug 32–63 A Lug

14 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

Thermal-magnetic Plug-on Circuit


Breakers 240/415 Vac, 10–63 A, Certified
to IEC 898
Table 16: QOE Circuit Breakers (10 kA) and QOE Circuit Breakers (6 kA)

QOE Circuit Breakers (10 kA) QOE Circuit Breakers (6 kA)


Ampere Rating Circuit Breaker Catalog Number Ampere Rating Circuit Breaker Catalog Number

Type B Type B
Instantaneous Trip 1-Pole 2-Pole 3-Pole Instantaneous Trip 1-Pole 2-Pole 3-Pole
Circuit Breakers Circuit Breakers
3 QO103EB10 N/A N/A 3 QO103EB6 N/A N/A
6 QO106EB10 N/A N/A 6 QO106EB6 N/A N/A
10 QO110EB10 N/A N/A 10 QO110EB6 N/A N/A
16 QO116EB10 N/A N/A 16 QO116EB6 N/A N/A
20 QO120EB10 N/A N/A 20 QO120EB6 N/A N/A
25 QO125EB10 N/A N/A 25 QO125EB6 N/A N/A
32 QO132EB10 N/A N/A 32 QO132EB6 N/A N/A
40 QO140EB10 N/A N/A 40 QO140EB6 N/A N/A
50 QO150EB10 N/A N/A 50 QO150EB6 N/A N/A
63 QO163EB10 N/A N/A 63 QO163EB6 N/A N/A

Type C Instantaneous-trip Circuit Breakers Type C Instantaneous-trip Circuit Breakers


6 QO106EC10 QO206EC10 QO306EC10 6 QO106EC6 N/A QO306EC6
10 QO110EC10 QO210EC10 QO310EC10 10 QO110EC6 N/A QO310EC6
16 QO116EC10 QO216EC10 QO316EC10 16 QO116EC6 N/A QO316EC6
20 QO120EC10 QO220EC10 QO320EC10 20 QO120EC6 N/A QO320EC6
25 QO125EC10 QO225EC10 QO325EC10 25 QO125EC6 N/A QO325EC6
32 QO132EC10 QO232EC10 QO332EC10 32 QO132EC6 N/A QO332EC6
40 QO140EC10 QO240EC10 QO340EC10 40 QO140EC6 N/A QO340EC6
50 QO150EC10 QO250EC10 QO350EC10 50 QO150EC6 N/A QO350EC6
63 QO163EC10 QO263EC10 QO363EC10 63 QO163EC6 N/A QO363EC6

Type D Instantaneous-trip Circuit Breakers Type D Instantaneous-trip Circuit Breakers


6 QO106ED10 QO206ED10 QO306ED10 6 QO106ED6 N/A N/A
10 QO110ED10 QO210ED10 QO310ED10 10 QO110ED6 N/A N/A
16 QO116ED10 QO216ED10 QO316ED10 16 QO116ED6 N/A N/A
20 QO120ED10 QO220ED10 QO320ED10 20 QO120ED6 N/A N/A
25 QO125ED10 QO225ED10 QO325ED10 25 QO125ED6 N/A N/A
32 QO132ED10 QO232ED10 QO332ED10 32 QO132ED6 N/A N/A
40 QO140ED10 QO240ED10 QO340ED10 40 QO140ED6 N/A N/A
50 QO150ED10 QO250ED10 QO350ED10 50 QO150ED6 N/A N/A
63 QO163ED10 QO263ED10 QO363ED10 63 QO163ED6 N/A N/A

© 2000-2004 Schneider Electric All Rights Reserved 15


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

Dimensions
Figure 24: QOE Circuit Breaker Dimensions

3.20
07393034

81

2.24
(57) 0.5
(14)
82°

0.11
(2.8)

2.03
(51)

3.2
(81)

2.21 1.47 0.73


(56) (37) (18)

2.91
(74)
2.31
(59)

in.
Dual Dimensions:
(mm)

16 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

QOE-RCBO CIRCUIT BREAKERS WITH QOE-RCBO branch circuit breakers with residual current protection and
RESIDUAL CURRENT PROTECTION integral overcurrent protection are designed for use in single-phase
consumer unit and three-phase distribution panelboard applications.
Figure 25: QOE-RCBO Circuit Breaker
• Compliance with International Standards: Certified to IEC 60898 and
BS4293, 10 kA at 240 Vac, 50/60 Hz, CE marked.
07393013

• ON/OFF Indication: ON/OFF markings are on the face of the circuit


breaker along with the international I/O markings.
• Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
• Trip Indication: Indication of a tripped circuit breaker on overload or
short circuit is by location of the handle in the OFF position. Indication of
a tripped circuit breaker on residual current ground fault is by location of
the handle in an intermediate position.
• Push-to-test Function: A yellow push-to-test button is positioned on
the front of the device for testing the residual current electronic trip
circuit and mechanical tripping interface.
• Thermal Trip Element: Thermal trip elements are factory calibrated at
30°C ambient temperature.
• Instantaneous trip level types B and C:
— Type B—(3–5 In) Overcurrent protection for sensitive equipment
— Type C—(5–10 In) Overcurrent protection for all application types
• Residual Current Protection: Residual ground-fault trip currents are
factory set at 10 mA, 30 mA or 100 mA: Type A.
• Trip Mechanism: Device will trip on loss of neutral. Device is sensitive
to both ac and pulsating dc fault current. Device will trip on voltage
between neutral and earth greater than 50 Vac.
• Mounting: Plug-on connection.

© 2000-2004 Schneider Electric All Rights Reserved 17


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

Table 17: QOE-RCBO Circuit Breakers with Instantaneous Trip and Residual Trip Current

Type B Type C Type D


Circuit Breaker Circuit Breaker Ampere Circuit Breaker
Ampere Ampere Rating Catalog
Catalog Catalog
Rating Rating Number
Number Number

10 mA 1-Pole 10 mA 1-Pole 10mA 1-Pole

6 QOE106B01 6 QOE106C01
10 QOE110B01 10 QOE110C01
16 QOE116B01 16 QOE116C01
20 QOE120B01 20 QOE120C01
32 QOE132B01 32 QOE132C01
40 QOE140B01 40 QOE140C01

30 mA 30 mA 30 mA

6 QOE106B03 6 QOE106C03 6 QOE106D03


10 QOE110B03 10 QOE110C03 10 QOE110D03
16 QOE116B03 16 QOE116C03 16 QOE116D03
20 QOE120B03 20 QOE120C03 20 QOE120D03
32 QOE132B03 32 QOE132C03 32 QOE132D03
40 QOE140B03 40 QOE140C03

100 mA 100 mA 100 mA

6 QOE106C100 6 QOE106D10
10 QOE110C100 10 QOE110D10
16 QOE116C100 16 QOE116D10
20 QOE120C100 20 QOE120D10
32 QOE132C100 32 QOE132D10

Accessory
Handle Padlock Attachment (QOE1PL)
Figure 26: QOE1PL Handle Padlock The handle padlock attachment allows padlocking the circuit breaker
Attachment handles in the ON or OFF position. The padlock attachment is intended to
be a temporary device and must be removed to resume normal operation.
07393023

(Padlock is not included.)

Lugs

Figure 27: QOE-RCBO Circuit Breaker Lug Table 17: QOE-RCBO Circuit Breaker Lug
Continuous Wire Lug Wire Size Temperature Torque Value
Ampere Type Rating
07393021

mm2 AWG N•m lb-in


Rating
6–40 Cu (1) 1–10 (1) #18–#8 75°C 1.0 9

6–40 A Lug

18 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

Dimensions
Figure 28: QOE-RCBO Circuit Breaker Dimensions

0.68 0.17 0.34


(17) (4.5) (8.8)
0.19 0.27
07393035

0.73 (5) (7)


(18)
60°

0.37
(9.5) 60°

0.35
(9)
4.36
2.53
(110)
(64)

0.15
(4)
0.59
0.29 (5)
(7.3)
in.
Dual Dimensions:
(mm)

Connections
Figure 29: QOE-RCBO Circuit Breaker Connections

A—Load Power
Line Power QOE-RCBO 1-pole Circuit Breaker B—Load Neutral
07393041

C—Panel Neutral Wire Blue


N L
D—Panel Earth Wire Yellow/Green
A

B
Load 1
C
Load 2

© 2000-2004 Schneider Electric All Rights Reserved 19


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

QOH-X CIRCUIT BREAKERS QOH-X branch circuit breakers are designed for use in single-phase
consumer unit and three-phase distribution panelboard applications.
Figure 30: QOH-X 1-Pole Circuit Breaker
• Compliance with International Standards: Certified to IEC 60947-2, 5
kA (10–63 A) and 6 kA (70–100 A) at 240 Vac single-phase and 415 Vac
07393006

three-phase, 50/60 Hz, CE marked.


• ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
• Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
• Trip Indication: Indication of a tripped circuit breaker on overload or
short circuit is by location of the handle in the center position. The circuit
breaker is also equipped with the Square D exclusive Visi-Trip® indicator
(a luminescent, red trip indicator on the front of the circuit breaker).
• Thermal Trip Element: Thermal trip elements are factory calibrated at
Figure 31: QOH-X 4-Pole Circuit Breaker 40°C ambient temperature.
• Endurance (Switching Operations):
07393007

— 1,500 full-load operations


— 8,500 no-load operations
• Mounting: Plug-on and bolt-on connection available.

QOH-X and QOBH-X Circuit Breakers Thermal-magnetic, 240/415 Vac, 10–63 A Certified to IEC 947-2 at 5 kA,
70–100 A Certified to IEC 947-2 at 6 kA

Table 18: QOH-X and QOBH-X Circuit Breakers

QOH-X Plug-on Circuit Breakers QOBH-X Bolt-on Circuit Breakers

Continuous Circuit Breaker Catalog Number Continuous Circuit Breaker Catalog Number
Ampere Rating 1-Pole 2-Pole 3-Pole Ampere Rating 1-Pole 2-Pole 3-Pole
10 QOH110X QOH210X QOH310X 10 QOBH110X QOBH210X QOBH310X
16 QOH116X QOH216X QOH316X 16 QOBH116X QOBH216X QOBH316X
20 QOH120X QOH220X QOH320X 20 QOBH120X QOBH220X QOBH320X
32 QOH132X QOH232X QOH332X 32 QOBH132X QOBH232X QOBH332X
45 QOH145X QOH245X QOH345X 45 QOBH145X QOBH245X QOBH345X
63 QOH163X QOH263X QOH363X 63 QOBH163X QOBH263X QOBH363X
70 QOH170X QOH270X QOH370X 70 QOBH170X QOBH270X QOBH370X
80 QOH180X QOH280X QOH380X 80 QOBH180X QOBH280X QOBH380X
100 QOH1100X QOH2100X QOH3100X 100 QOBH1100X QOBH2100X QOBH3100X
100 (4-pole) N/A N/A QOH4100X 100 (4-pole) N/A N/A QOBH4100X

20 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

Accessories
• Handle Tie (QO1HT)
Figure 32: QOH-X Circuit Breaker The handle tie accessory converts any adjacent 1-pole QO circuit
breaker to one independent-trip, multi-pole circuit breaker.
07393025

07393027
• Handle Clamps (QO1LO and HLO-1)
The handle clamp accessories fasten the circuit breaker handle in the
ON or OFF position. These handle clamps cannot be padlocked.
— 1-pole circuit breaker handle clamp: QO1LO
QO1HT Handle Tie QO1LO Handle Clamp
— 1-, 2- and 3-pole circuit breaker handle clamp: HLO-1
• Handle Padlock Attachments
07393028

07393043

(QOHPL, QO1PA, QO1PL and QO1HPL)


The handle padlock attachments allow padlocking the circuit breaker
handles in the ON or OFF position. They are available in two styles:
fixed and removable. The fixed style is intended to be a permanent
QO1PA Fixed QO1HPL Removable device. The padlock can be removed to resume normal operation. The
Padlock Attachment Padlock Attachment removable style is intended to be a temporary device and must be
removed to resume normal operation. Padlock is not included.
— 1-pole circuit breaker removable attachment: QOHPL
07393026

— 1-pole circuit breaker fixed attachment: QO1PA


— 2- and 3-pole removable attachment: QO1HPL
— 2- and 3-pole fixed attachment: QO1PL
HLO-1 Handle Clamp
07393042

07393044

QO1PL Fixed
Padlock Attachment QOHPL Removable
Padlock Attachment

Lugs

Figure 33: QOH-X Circuit Breaker Lugs Table 19: Table 19: QOH-X Circuit Breaker Lugs

Continuous Lug Wire Size Torque Value


07393016
07393022

Wire Temperature
Ampere
(1) Type mm2 AWG Rating N•m lb-in
Rating
10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36
10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36
(2)
45–100 Al/Cu (1) 25–50 (1) #4–#2/0 75°C 6 50
10–32 A Lugs 45–100 A Lug

© 2000-2004 Schneider Electric All Rights Reserved 21


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

Dimensions NOTE: QOBH-X circuit breaker dimensions are the same as the QOH-X
circuit breaker dimensions except as shown

Figure 34: QOH-X Circuit Breaker Dimensions


07393036

Dim. A: 3.5 in. (88.9 mm), 45–100 A for 1-, 2- and 3-pole
Dim. B: 3.00 in. (76.2 mm), 10–32 A for 1-, 2- and 3-pole

2.25
Dim. A
(57)
Dim. B

0.94
24

26°
2.23 1.48 0.73 0.18
(57) (38) (19) (4)
2.09 1.34 0.59 22° 21°

Tripped
(53) (34) (15) 0.16

set
0.38

F
0.53 0.53 (4)

Re
OF
ON
(13) (13) (10)

2.91 0.25
(74) (6) 2.92
(74)
2.31
(59)

0.94 0.94 2.75


24 24 (70)

in.
Dual Dimensions:
(mm)

22 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

Figure 35: QOBH-X Circuit Breaker Dimensions


07393036

0.38
(10)

0.75 0.75 0.75


(19) (19) (19) 2.94
(75)
in.
Dual Dimensions:
(mm)

© 2000-2004 Schneider Electric All Rights Reserved 23


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

QOH-RCDX CIRCUIT BREAKERS WITH QOH-RCDX branch circuit breakers with residual current protection and
RESIDUAL CURRENT PROTECTION integral overcurrent protection are designed for use in consumer unit and
three-phase distribution panelboard applications.
Figure 36: QOH-RCDX Circuit Breaker
• Compliance with International Standards: Certified to IEC 60947-2
and BS4293, 5 kA at 240 Vac, 50/60 Hz, CE marked.
07393001

• ON/OFF Indication: ON/OFF markings are on the face of the circuit


breaker along with the international I/O markings.
• Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
• Trip Indication: Indication of a tripped circuit breaker on overload, short
circuit or residual current ground fault is by location of the handle in the
center position. The circuit breaker is also equipped with the Square D
exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the
front of the circuit breaker).
• Push-to-test Function: A yellow push-to-test button is positioned on the
front of the device for testing the residual current electronic trip circuit
and mechanical tripping interface.
Thermal Trip Element: Thermal trip elements are factory calibrated at
40°C ambient temperature.
• Residual Current Protection: Residual ground-fault trip currents are
factory set at 10 or 30 mA.
• Endurance (Switching Operation):
— 1,500 full-load operations
— 8,500 no-load operations

Table 20: QOH-RCDX and QOBH-RCDX Circuit Breakers with Instantaneous Trip and Residual Trip Current

QOH-RCDX Circuit Breaker QOBH-RCDX Circuit Breaker

Continuous Circuit Breaker Continuous Circuit Breaker


Ampere Catalog Number Ampere Catalog Number
Rating (1-Pole) Rating (1-Pole)

Residual Trip Current Residual Trip Current


10 mA 10 mA
10 QOH110RCDX10 10 QOBH110RCDX10
16 QOH116RCDX10 16 QOBH116RCDX10
20 QOH120RCDX10 20 QOBH120RCDX10
32 QOH132RCDX10 32 QOBH132RCDX10

Residual Trip Current Residual Trip Current


30 mA 30 mA
10 QOH110RCDX30 10 QOBH110RCDX30
16 QOH116RCDX30 16 QOBH116RCDX30
20 QOH120RCDX30 20 QOBH120RCDX30
32 QOH132RCDX30 32 QOBH132RCDX30

24 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

Accessories • Mounting: Plug-on and bolt-on connections available.


• Handle Tie (QO1HT)
QOH-RCDX Circuit Breaker
Figure 37: Accessories • The handle tie accessory converts any adjacent 1-pole QO circuit
breaker to one independent-trip, multi-pole circuit breaker.
• Handle Clamps (HLO-1 and QO1LO)
07393025

• The handle clamp accessories fasten the handle in the ON or OFF


position. These handle clamps cannot be padlocked.
QO1HT Handle Tie • Handle Padlock Attachments (QO1PA and QOHPL)
The handle padlock attachment allows padlocking the circuit breaker
07393027

handles in the ON or OFF position. They are available in two styles:


07393026

fixed and removable. The fixed style is intended to be a permanent


device. The padlock can be removed to resume normal operation. The
removable style is intended to be a temporary device and must be
HLO-1 Handle Clamp QO1LO Handle Clamp removed to resume normal operation. Padlock is not included.
— Fixed padlock attachment: QO1PA
07393028

07393044

— Removable padlock attachment: QOHPL

QO1PA Fixed QOHPL Removable


Padlock Attachment Padlock Attachment

Lugs
Table 21: QOH-RCDX Circuit Breaker Lugs
Figure 38: QOH-RCDX Circuit Breaker Lugs
Continuous Torque
Lug Wire Size Temperature Value
Ampere Wire Type
07393022

Rating
(1) Rating mm2 AWG N•m lb-in
10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36
10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36
(2)

10–32 A Lugs

© 2000-2004 Schneider Electric All Rights Reserved 25


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

Dimensions
Figure 39: QOH-RCDX Circuit Breaker Dimensions
07393037


26°

22° 21°

Tripped

F
set
OF
ON

Re

2.91
(74)
2.31
(59)

4.12
(108)

0.74
(19)

in.
Dual Dimensions:
(mm)

Connections
Figure 40: QOH-RCDX Circuit Breaker Connections

240 Vac Source


07393039

N L
Load Power 250 V Duplex
Receptacle

240
Vac

240 V

Load Neutral
S/N

Equipment Ground
GND

26 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

QOXD CIRCUIT BREAKERS QOXD branch circuit breakers are designed for use in single-phase
consumer unit and three-phase distribution panelboard applications.
Figure 41: QOXD Circuit Breaker
• Compliance with International Standards: Certified to IEC
947-2 (3 kA [10–63 A]) and IEC 898 (3 kA [10–32 A]) at 240 Vac single
07393010

phase and 415 Vac three phase, 50/60 Hz, CE marked.


• ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
• Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
• Trip Indication: Indication of a tripped circuit breaker on overload or
short circuit is by location of the handle in the center position. The circuit
breaker is also equipped with the Square D exclusive Visi-Trip® indicator
(a luminescent, red trip indicator on the front of the circuit breaker).
• Thermal Trip Element: Thermal trip elements are factory calibrated at
40°C ambient (IEC 947-2) and 30°C ambient (IEC 898) temperature.
• Endurance (Switching Operations):
— IEC 947-2: 1,500 full-load operations
— IEC 947-2: 8,500 no-load operations
— IEC 898: 4,000 full-load operations

Table 21: Thermal-Magnetic Circuit Breakers

QOXD Plug-on Circuit Breakers QOBXD Bolt-on Circuit Breakers

Continuous Circuit Breaker Catalog Number Continuous Circuit Breaker Catalog Number
Ampere Ampere
Rating 1-Pole 2-Pole 3-Pole Rating 1-Pole 2-Pole 3-Pole
10 QOXD110 QOXD210 QOXD310 10 QOBXD110 QOBXD210 QOBXD310
16 QOXD116 QOXD216 QOXD316 16 QOBXD116 QOBXD216 QOBXD316
20 QOXD120 QOXD220 QOXD320 20 QOBXD120 QOBXD220 QOBXD320
25 QOXD125 QOXD225 QOXD325 25 QOBXD125 QOBXD225 QOBXD325
32 QOXD132 QOXD232 QOXD332 32 QOBXD132 QOBXD232 QOBXD332
40 QOXD140 QOXD240 QOXD340 40 QOBXD140 QOBXD240 QOBXD340
45 QOXD145 QOXD245 QOXD345 45 QOBXD145 QOBXD245 QOBXD345
50 QOXD150 QOXD250 QOXD350 50 QOBXD150 QOBXD250 QOBXD350
63 QOXD163 QOXD263 QOXD363 63 QOBXD163 QOBXD263 QOBXD363
70 — QOXD270 QOXD370 70 — QOBXD270 QOBXD370
80 — QOXD280 QOXD380 80 — QOBXD280 QOBXD380
100 — QOXD2100 QOXD3100 100 — QOBXD2100 QOBXD3100

© 2000-2004 Schneider Electric All Rights Reserved 27


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

Accessories Mounting: Plug-on and bolt-on connection available.

QOXD Circuit Breaker • Handle Tie (QO1HT)


Figure 42: Accessories The handle tie accessory converts any adjacent 1-pole QO circuit
breaker to one independent-trip multi-pole circuit breaker.
• Handle Clamps (HLO-1 and QO1LO)
07393025

The handle clamp accessories fasten the circuit breaker handle in the
ON or OFF position. These handle clamps cannot be padlocked.

QO1HT Handle Tie — 1-pole circuit breaker handle clamp: QO1LO


— 1-, 2- and 3-pole circuit breaker handle clamp: HLO-1
07393026

07393027

• Handle Padlock Attachments


(QOHPL, QO1PA, QO1HPL and QO1PL)
The handle padlock attachments allow padlocking the circuit breaker
HLO-1 Handle Clamp
handles in the ON or OFF position. They are available in two styles:
QO1LO Handle Clamp
fixed and removable. The fixed style is intended to be a permanent
07393028
07393044

device. The padlock can be removed to resume normal operation. The


removable style is intended to be a temporary device and must be
removed to resume normal operation. (Padlock is not included.)
— 1-pole circuit breaker removable attachment: QOHPL
QOHPL Removable QO1PA Fixed — 1-pole circuit breaker fixed attachment: QO1PA
Padlock Attachment Padlock Attachment
— 2- and 3-pole removable attachment: QO1HPL
— 2- and 3-pole fixed attachment: QO1PL
07393042
07393043

QO1HPL Removable QO1PL Fixed


Padlock Attachment Padlock Attachment

Lugs

Figure 43: QOXD Circuit Breaker Lug Table 23: QOXD Circuit Breaker Lugs
Continuous Wire Lug Wire Size Temperature Torque Value
07393022

07393016

Ampere Type Rating


mm2 AWG N•m lb-in
(1) Rating
10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36
10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36
(2)
45–100 Al/Cu (1) 25–50 (1) #4–#2/0 75°C 6 50
10–32 A Lugs 45–100 A Lug

28 © 2000-2004 Schneider Electric All Rights Reserved


0739DB9901R11/03 International Miniature Circuit Breakers
June 2004

Dimensions NOTE: QOBX-D circuit breaker dimensions are the same as the QOXD
circuit breaker dimensions except as shown.

Figure 44: QOXD Circuit Breaker Dimensions

Dim. A: 3.5 in. (89 mm), 70–100 A for 1-, 2- and 3-pole
Dim. B: 3.125 in. (79 mm), 45–63 A for 1-, 2- and 3-pole
07393036

Dim. C: 3.0 in. (76 mm), 10–32 A for 1-, 2- and 3-pole

Dim. A 2.25
Dim. B (57)
3.00
Dim. C
(76)

0.94
(24)

0.73 26°
2.23 1.48
(19)
(57) (38)
2.09 1.34 0.59

Tripped
(53) (34) (15) 21
0.16 22° °

set
F
0.53 0.53

OF
ON
0.38 (24)

Re
(13) (13) (10)

2.91 0.25
(74) (6)
2.92
2.31 (74)
(59)

0.75 0.75 0.75 2.75


(19) (19) (19) (70)

in.
Dual Dimensions:
(mm)

© 2000-2004 Schneider Electric All Rights Reserved 29


International Miniature Circuit Breakers 0739DB9901R11/03
June 2004

Figure 45: QOBX-D Circuit Breaker Dimensions


07393036

0.38
(10)

0.75 0.75 0.75 2.94


(19) (19) (19) (75)
in.
Dual Dimensions:
(mm)

30 © 2000-2004 Schneider Electric All Rights Reserved

Das könnte Ihnen auch gefallen