Sie sind auf Seite 1von 23

VECO Doc. No.

20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 2 of 23
TABLE OF CONTENTS
1.0 INTRODUCTION.............................................................................................................3
1.1 General ...........................................................................................................................3
1.2 Scope ..............................................................................................................................3
1.3 Definitions .......................................................................................................................4
1.4 Abbreviations...................................................................................................................4
1.5 Environmental Conditions................................................................................................5
1.6 Device Protection ............................................................................................................6
2.0 CODES, REGULATIONS AND STANDARDS ................................................................6
2.1 General ...........................................................................................................................6
2.2 Units of Measurement .....................................................................................................7
2.3 Order of Precedence .......................................................................................................8
3.0 OVERALL SCOPE..........................................................................................................8
3.1 Scope of Supply ..............................................................................................................9
4.0 SPECIFICATION...........................................................................................................10
4.1 General .........................................................................................................................10
4.2 Pressure / Differential Pressure Transmitters ................................................................12
4.3 Temperature Transmitters .............................................................................................12
4.4 Gas Chromatograph ......................................................................................................12
4.5 Dew Point Analyzer .......................................................................................................17
4.6 Flow Computer ..............................................................................................................18
4.7 Analyzer House .............................................................................................................21
5.0 INSPECTION AND TESTING .......................................................................................21
6.0 CERTIFICATION OF COMPLIANCE ............................................................................22
7.0 SITE SERVICES ...........................................................................................................22
8.0 SPARE PARTS AND SPECIAL TOOLS.......................................................................22
9.0 TRAINING .....................................................................................................................22
10.0 Documentation ............................................................................................................23

ATTACHMENT 1: P&ID-Sales Gas Metering

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 3 of 23

1.0 INTRODUCTION

1.1 General

PETRONAS CARIGALI (Pakistan) Ltd. (PCPL) is undertaking the development of Mehar


Gas Field in Mehar Block (Block 2767-1) located in Sindh and Balochistan Provinces of
Pakistan.

PCPL intends to develop the Mehar Field by installing a Gathering System, Gas
Processing Facility (GPF) and Product Storage & Loading Facilities. The field facilities
will be developed in two phases, Phase-I and Phase-2. Phase-1 development will cater
to 55 MMSCFD of gas productions and Phase-2 will cater to 80 MMSCFD of gas
productions. The expected condensate production rate is 6600 BPD for Phase-I and
7000 BPD for Phase-2. From GPF, treated sales gas will be exported through a new
pipeline to existing SSGCL/SNGPL gas pipeline. Stabilized condensate and produced
LPG will be exported by road tankers.

Mehar Block is located in the Kirthar Fold belt area, in the Middle Indus Basin. Mehar
field is located about 190 km west of Sukkur and 400 km north of Karachi in Sindh
province. The environment is arid and the terrain is mountainous. Mazarani gas field,
operated by PPL is situated about 25 km to the north, while Zamzama gas field operated
by BHP is situated about 70 km to the north of Mehar Field.

Mehar field consists of Pab and Ranikot formations. The wells will be connected to the
new GPF through a Gathering System. There will be a total of 8 wells (4 in Pab & 4 in
Ranikot) in Phase-1 and 3 additional wells (2 in Pab & 1 in Ranikot), totaling 11, in
Phase-2 of the Mehar field development.

1.2 Scope

This specification covers the minimum technical requirements for the design,
manufacture, testing and supply of Sales Gas Metering Package suitable for
installation in MEHAR Gas Development Project.

This specification shall not be considered all-inclusive. The VENDOR shall submit full
technical details of its well-proven standard equipment, which meet the project
requirements herein. Aspects of the requirements, which cannot meet, shall be identified
and variances explained.

The sales agreement for gas is not finalized at this stage. CONTRACTOR and VENDOR
shall be fully responsible to incorporate changes that may be proposed by the potential
buyer / Government regulation.

CONTRACTOR shall be responsibly for compliance to Government regulation regarding


sales gas.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 4 of 23
Compliance with the specification, codes and standards does not relieve the VENDOR
of the responsibility for supplying equipment of proper design and construction, fully
suitable for all specified operating conditions.

The Sales Gas Metering Package with the Analyzers shall be complete, tested, pre-
commissioned, and commissioned so that it shall ensure a trouble-free start-up and
operations of the new facilities.

1.3 Definitions

COMPANY Petronas Carigali Pakistan Limited (PCPL) or any Third Party


assigned by the COMPANY
ENGINEER Party which carries all or part of the design, engineering of
the PROJECT. VECO Engineering, Abu Dhabi is the
ENGINEER.
EPCC CONTRACTOR Party which carries out all or part of the design, engineering,
procurement, construction, commissioning or management, of
the PROJECT. EPCC CONTRACTOR includes his approved,
MANUFACTURERS, SUPPLIERS, VENDORS and
SUBCONTRACTORS.
MANUFACTURER/ Party/ies, which manufacture and/or supply materials,
SUPPLIER/VENDOR equipment and services to perform the duties as specified by
the CONTRACTOR in the scope of supply.
PROJECT MEHAR GAS DEVELOPMENT PROJECT

1.4 Abbreviations

AGA American Gas Association

API American Petroleum Institute

ASME American Society of Mechanical Engineers

ASTM American Society for Testing and Materials

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 5 of 23

FM Factory Mutual

GC Gas Chromatograph

GSA Gas Sales Agreement

IEC International Electrotechnical Commission

IEEE Institute of Electrical and Electronics Engineers

IP Institute of Petroleum

ISO International Organization for Standardization

NFPA National Fire Protection Association

UL Underwriter’s Laboratory

WGM Working Gas Mixture

1.5 Environmental Conditions

Wellhead facilities, Gathering stations and GPF area has been tentatively selected at a
location about 190 km west of Sukkur and 300 km north of Karachi in Sindh Province.
The environment is arid the terrain is mountain.

The Environmental conditions are:

Maximum Ambient Temperature : 55ºC

Minimum Ambient Temperature : 0.5ºC

Wet bulb temperature (design) : 30ºC

Relative humidity (max / nor /min) : 90 / 65 / 20 %

Direction of prevailing wind : From south to north

Wind Velocity (max / normal) : Hold / 2.9 knots

Elevation above Mean Sea Level (GPF) : 54m (Site-IV) / 56m (Site-l)

Average barometric pressure : 1001.2 mbara (29.56 inches of Mercury)

Ice / Snow : None

Seismic zone : Zone 2B, upper moderate with ground


acceleration of 0.2 (Hold)

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 6 of 23
Annual rainfall min. : 63.3 mm (year 2006)

Annual rainfall max. : 139.9 mm (year 2005)

1.6 Device Protection

All instruments/ electrical equipment installed in hazardous area shall be certified as


EEx‘i’ IIA / IIB, T3. EEx’d’ is acceptable if EEx‘i’ is not available or can not be provided.

All electrical installation materials shall be suitable and certified for use in this area
classification. All field devices, installation material shall have weather protection to IP 65
as minimum.

2.0 CODES, REGULATIONS AND STANDARDS

2.1 General

Codes, specifications and standards referred to within this specification, form a part of
the requirements of this specification in a manner and to the extent specified within
those codes and standards.

Unless otherwise specified, the latest edition or revision to these codes specifications,
and standards in force at the time of request for quotation and/or Purchase Order shall
apply.

No deviations from the Codes and Standards listed in this document will be allowed
unless such deviations are clearly identified in the bids, with the reasoning. In addition,
they must be approved in writing by COMPANY.

2.1.1 Codes and Standards

AGA – 3/2000 : Orifice metering of Natural Gas

AGA - 8 : Compressibility factors of Natural Gas and other


related Hydrocarbon gases.

ISO 9001:2000 : Quality Management Systems- Requirements

ISO 10474 : Steel and Steel Products – Inspection Document


ASME Sec. VIII Div. 1 : Pressure Vessel

ASME Sec. IX : Welding and Bogging Qualification

ASME B 31.8 : Gas Transmission and Distribution Piping


System

ASTM 3588 : Heat Value, Compressibility Factor and Relative


Density of Gaseous Fuels
BS 5345 : Code of Practice for the Selection, Installation

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 7 of 23
and Maintenance of Electrical Apparatus for use
in Potentially Explosive Atmosphere

EN 50014 to 20 : Electrical Apparatus for Potentially Explosive


Atmosphere

IEC 60801 : Electromagnetic Compatibility for Industrial


Process Measurement & Control Equipment

IEC 60529 : Classification for Degree of Protection Provided


by Enclosures

IEC 60079 : Electrical Apparatus for Explosive Gas


Atmosphere

API RP 554 : Process Instrumentation and Control

API RP 551 : Process Measurements Instruments

2.2 Units of Measurement

The Sales Gas Metering Package shall support any unit of measure where appropriate,
however, the units of measurement to be used on this project shall be:

Liquid Density: : API and kg/m3


Flow Rate: : m3 / hr, MMSCFD (gas), BPD (condensate), BWPD
(Water)
Power, Duty: : kW

Heat Transfer : W / m2 K
Coefficient:
Thermal Conductivity: : W / m.K

Heat Capacity : kJ/ Kg °C

Viscosity: : cP

Kinematic Viscosity : : centistokes (cSt)

Area : m2

Length : Metre (m), Km, mm

Pressure : Bar (g), Bar (a), Psi (g)

Temperature : °F

Volume : m3

Pipe Diameter : mm

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 8 of 23

Instrument : Inch
Tubings/Fittings
Stress : Mpa, Kg/cm2, Psi
Weight : Kg

2.3 Order of Precedence

In case of conflicting requirements amongst any of the specified Standards, the


Standard having the most stringent requirement shall be governing.

In the event of contradictions, the order of precedence of various specifications shall be


as follows:

1. Government Legislations
2. Gas Sales Agreement
3. This Specification
4. Project Specification
5. COMPANY Standards
6. International Codes and Standards;
7. Vendor Standards.

In the event that CONTRACTOR is faced with conflicting information, Owner shall be
contacted directly for a clarification. Owner’s interpretation shall be final.

3.0 OVERALL SCOPE

VENDOR scope includes the design, engineering, manufacturing, assembly, FAT,


supply, installation, testing, commissioning, training and documentation of the Sales Gas
Metering Skid and Analyzers/Analyzer House.

VENDOR overall scope shall include the following as a minimum:

• Supply of Metering Skid including as per section 3.1;

• Metering Skid construction and assembly;

• Supply of GC and Dew point analyzer including Analyzer house (this analyzers will
be supplied by Vendor separate of metering skid);

• Factory Acceptance Test (FAT) at VENDOR’S works;

• Packing, transportation and delivery;

• Site Acceptance Test (SAT);

• Training to the plant operators & engineers (at VENDOR’S works or at site);

• Supply of start-up and commissioning spares, special tools;

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 9 of 23
• Drawing and Documentation;

• Recommended spare part list for 2 years continuous operation.

3.1 Scope of Supply

The scope of supply for metering skid shall include three (03) metering runs (02 in
continuous operation and one standby, in 2 X 100% configuration) with following details
of each run. For additional information refer to P&ID, 12-MEGP-B-4028.

• One (1) upstream section with straight length of 18 D up to primary device with flow
conditioner. The inlet side shall be flanged and the outlet side shall be welded to
orifice fitting. Final requirement shall be base on AGA 3.

• One (1) double chamber orifice fitting with 316 SS square edge orifice plate. The
inlet side shall be welded to upstream section and the outlet side shall be flanged.
The orifice assembly must include supply of plates, flanges, Stud Bolts, Nuts, Jack
Screws, Gasket / Plate holder & Plugs;

• One (1) downstream section having DN50 flanged connection for vent with straight
length of 7 D up to outlet flange. Both sides shall be flanged;

• The various accessories for senior orifice assemblies for operation under
pressurized line condition. Ball valves, equalizer valves, bleeder valves, plate carrier,
sealing and guide brackets etc. shall be as per VENDOR standard to suit not sour
natural gas custody transfer requirement. Manual sampling point with isolation valve
shall be provided. Refer to P&ID for valve sizes.

• The installation, tubing, cabling and testing at site shall be carried out by the EPCC
CONTRACTOR. The following instrumentations (but not limited) shall be provided
and shall form part of the metering skid:

1. Two (2) Flow Indicating Transmitters (high and low range-pay) and One (1) Flow
Indicating Transmitter (high range – check), for each run shall be provided.
Transmitter ranges for high range shall be 0-2500 mm H2O and 0-500 mm H2O
for low range. (Total of 9 FITs)

2. One (1) Pressure Indicating Transmitter and Pressure Gauge on each run.

3. One (1) Temperature Indicating Transmitter, One (1) Temperature Gauge and
one (1) Thermowell for transmitter calibration on each run.

4. Two (2) Densitometer for each meter run if not provided by GC.

• One (1) Flow Control Valve

• Six (6) Motor Operated Valves

• Automatic Sampling facilities in the inlet manifold

• One (1) flow computer for each meter run to be installed on a cabinet panel.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 10 of 23
• The supervisory flow computer shall be supplied with all necessary configuration
software required. The supervisory flow computer shall form part of gas flow
metering package. Supervisory flow computer location is in the control room. The
configuration software shall run on Microsoft Windows XP; The supervisory flow
computer shall communicate to the PMCS via serial link. A high availability
supervisory computer with RAID 5, redundant hard disk as minimum.

• Dedicated PC shall be provided with software installed such as Kelton, Flo cal or
better;

• Two (2) GC (1-working, 1 standby) and One (1) Dew point Analyzer, separate from
Sales gas metering skid shall be supplied in Analyzer house. F&G Detection for the
Analyzer house shall be provided. Preferred GC manufacturer in Daniel Industries.

• Master Meter for proving.

• Calibration tools for Analyzers and metering package.

• Any validation and calibration software required for the flow computers.

4.0 SPECIFICATION

4.1 General

The intent of this section is to describe the minimum acceptance parameters for the
design, manufacture and supply of sales gas metering systems.

Unless otherwise specified the enclosure Ingress Protection of the metering system
transmitters (pressure, differential pressure and temperature), located in field, shall be at
least IP65 as per IEC 60529.

The junction boxes shall be in 316SS and cable trays shall be hot dip galvanized. The
painting colour of Junction Box, cable trays etc shall be RAL 9010.

The actual gas flow rate shall be measured by means of a 316SS square edge orifice
plate installed in a double chamber senior orifice fitting of a meter-run. All shall be in
accordance with AGA-3 and AGA-8 for custody transfer measurement unless otherwise
specified in the GSA.

The double chamber orifice fitting shall permit orifice plate replacement with line under
pressure and flowing condition.

Orifice diameter shall be calculated for square edge orifice with flange taps (½” NPT).

Redundant flow computers shall be provided interfaces with GC, Moisture Analyzer,
Control System and Field instruments.

230 VAC power supply shall be for GC, Dew point analyzer and flow computer.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 11 of 23
VENDOR shall use volumetric as well as Gross Calorific value calculations of the sales
gas based on standard conditions of 60ºF and 14.73 psi as per AGA 3.

The unit of measurement for volumetric calculations would be (1) standard cubic foot.

The units of volume and calorific value for billing purpose would be MCF and MMBtu
respectively.

Flow computer software shall be in compliance with AGA 3 and AGA 8 unless otherwise
specified in the GSA.

4.1.1 Meter Tubes

The meter tube (18D) at the inlet of the orifice assembly, the meter tube (7D) at the
outlet of the meter assembly, shall be designed as per AGA 3.

Pipe Material : ASTM A106 Gr. B, Seamless

Size & Thickness : DN150 NB, SCH. 80

End Connections : Flanged

Material : ASTM A 105 N

Size : DN150 Weld Neck

Rating / Face : CL600, RF

Finish : Smooth to 125 AARH (as per ASME B 16.5)

Bolt Material : ASTM A 193 B7

Nut Material : ASTM A 194 Gr. 2H

4.1.2 Minimum Straight Lengths

Down stream length : 7D (D is the nominal diameter of the line)

Upstream length : 18 D

Thermowell connection shall be 2" flanged and located as close as possible to the meter
tube discharge flange. However the installation of the thermowell in the metering tube
shall not affect the accuracy of the meter.

4.1.3 Basis of Sizing and Accuracy

VENDOR shall provide calculations for all orifice plates. Calculations shall be in
accordance with AGA-3, based on "beta" close to but not exceeding 0.6. The normal
flow rate of the orifice meter shall be between 60 and 80 percent of the meter flow
capacity. The anticipated maximum and minimum flow rate shall be 95 and 30 percent of
meter flow capacity, respectively.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 12 of 23

The meter run uncertainty should be +/- 1% of mass flow rate @ 95% confidence level.
Uncertainty calculation shall be submitted to COMPANY for review and approval.

Switching between high range and low range differential pressure as the flow fluctuates
shall be automatic.

The thickness of the orifice shall be 6 mm (0.236”) for pipelines for DN150 line.

The normal differential pressure range for flow metering orifice plate shall be 0 to 2500
mm-H2O. If this normal range is not practical, the standard range shall be 0 to 500 mm
H2O, 0 to 5000 mm H20.

VENDOR shall size the orifice plates as per process data sheet. All calculations shall be
submitted to COMPANY for approval.

4.1.4 Sampling System

Gas samples are required to determine gas composition, relative density and BTU
content. Samples shall be collected at least once a month using automatic gas
samplers. Minimum 3 samples of 500 cc are needed. Additional samples if required shall
be advised by the COMPANY.

Sample collection control system shall be by time based or by flow proportional mode
selectable by the Operator. The sample rates or volume shall be unaffected by variances
in pipeline or sample pressures or temperatures. Constant pressure sample cylinders
shall be used.

Manual sample points shall also provided in the metering skid with isolation valves.
Samples shall be collected in bottles for analysis in a laboratory.

4.2 Pressure / Differential Pressure Transmitters

For detail specification refers Doc # 12-MGDP-I-1024, Specification for General


Instruments.

4.3 Temperature Transmitters

For detail specification refers Doc # 12-MGDP-I-1024, Specification for General


Instruments.

Wake frequency analysis for thermowell shall be submitted to COMPANY for review and
approval.

4.4 Gas Chromatograph

The GC shall be used to give continuous quantitative composition analysis of natural gas
from a process stream.

The analysis is normally limited to the following main components and concentration:

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 13 of 23

COMPONENTS CONCENTRATION RANGE IN MOLE %


(DRY BASIS-VAPOR)
H2S 0.0014
CO2 2.1761
Nitrogen 5.4281
Methane 77.7527
Ethane 5.6500
Propane 3.0980
Iso-butane 0.9214
Normal-butane 1.5551
Iso-pentane 0.7753
Normal-pentane 0.7460
Mcyclopentane 0.0992
n-Hexane 0.8204
Benzene 0.0628
Cyclohexane 0.1155
n-Heptane 0.4064
3-Mhexane 0.0857
Toluene 0.0637
n-Octane 0.1590
E-Benzene 0.0039
p-Xylene 0.0194
o-Xylene 0.0069
n-Nonane’s and heavier 0.0377
Notes:

1. The H2S content may increase to 35 ppm (wt) and shall be considered in the design.
2. The CO 2 content may increase to 5% mole in the future and design shall be
considered in this aspect.

The GC shall quantify the concentrations of the main components in the gas composition,
for the purpose of gas accounting, calculation of calorific value and reference density in
fiscal applications. The gas composition shall also be used for check of gas quality
conformity with gas quality specifications defined by commercial gas agreements, and as
a base for calculation of the operating density. The calculation of the operating density
will normally be handled by the flow computers using live input values of the gas
composition from the gas chromatograph. For this purpose serial interface shall be
provided to the Flow Computer.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 14 of 23
Calculation of flow weighted average composition will normally be handled by the fiscal
measurement computer system. The concentration given in mole % shall be converted to
mass % for such calculations.

The analytical results shall be traceable regarding sample point, time and date,
calibration gas cylinder, calibration table, and time of last calibration.

Recognized method for gas chromatograph analysis is ASTM 3588 and AGA 3.

The daily and hourly averages of the sample gas as well as calibration gas analysis
reports are required for at least 30 days.

GC shall communicate via serial with PMCS to view some vital outputs i.e. BTU value,
Wobbed Index and unnormalized mole %. Maintenance and calibration mode alarms of
GC should be monitored on PMCS.

GC shall be controlled from PMCS for Auto / manual operation. GC shall provide daily
auto / manual generation of calibration reports.

4.4.1 Technical Requirements

4.4.1.1Sample Handling System

The sample handling system shall collect a representative gas sample.

The transport time through the sample handling system shall be less than 2 min.

The sampling probe shall be installed so that a representative sample of the gas can be
collected. The sampling probes shall be supplied with the analyzers. The distance to the
nearest upstream disturbance, shall be at least 20 ID.

Conditioning equipment is required to reduce pressure to a level suitable for the analyzer.
Adequate protective filtering and coalescer have to be installed after the pressure
reduction system to remove dirt and liquid entrainments if such contamination will be
present.

The temperature in all parts of the sample lines including sample conditioning equipment
shall be kept at a temperature minimum 10 °C above the hydrocarbon dew point
temperature. The dew point temperature shall be calculated by well recognized methods
for every pressure level in the system. The temperature and pressure at critical points in
the sampling system shall be indicated.

Slope of at least 1:12 should be maintained along the sample line from the probe to the
pressure reduction system in order to avoid liquid traps.

The sampling probe should be designed so it is possible to be retracted under operating


pressure by method accepted by the operator.

All manually controlled shut off valves in the cabinets shall have a proper open/close
indication.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 15 of 23

Waste samples from the analyzer shall be vented via a separate vent line specially
designed in order to minimize influence from ambient conditions. Waste bypass gas from
the cabinets can be vented to a common vent system.

GC stream shall be selectable i.e the selection of calibration gas and sample gas for
analysis of the stream. This shall be done by using tee or valve manifold. Calibration
gases shall be supplied by Vendor, sufficient until final testing.

4.4.1.2 Analytical Unit

The time required for a full analysis cycle shall be less than 10 min. The oven
temperature shall be controlled to obtain required stability and accuracy of the analysis.

The chromatograph shall use carrier gas in accordance with requirement given by the
application. Pressure and flow rate of carrier gas shall be controlled with sufficient
accuracy. Necessary equipment for safe operation in case of failure in carrier gas supply
shall be installed if applicable.

The chromatograph shall use thermal conductivity detector or equivalent.

4.4.1.3 Computer Unit

Communications between the analytical unit and the computer unit should be according
to the VENDOR’S standard protocol.

The following functions shall all be available for the operator and should also be
available from the supervisory computer:

• Start and stop the analysis cycle;

• Change the alarm limits;

• Acknowledge alarms;

• Define and/or read component table, retention time retention time tolerance,
response factor and valve switching;

• Sequence, calibration frequency and WGM concentration;

• Password protected program modifications;

• Define and/or read time, peak height, peak area, peak start time, peak end time (for
each component) and total area;

• Select override analysis.

GC shall be configured that it does have an option to store at least 260 alarms and
events.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 16 of 23
The computer unit shall have functions that give an alarm and inhibit the use of
calibration tables containing response factors that are outside pre-set limits of
acceptable values. The response factors for those components not present in the
calibration gas shall either be manually entered or automatically calculated by using a
mathematical relation to other components, i.e. calculate response factors for the
hexane plus fraction from the response of pentanes or butanes.

The chromatograms should be displayed in real time and also stored digitally with the
possibility of later visual inspection. Start and stop of peak integration event marks and
electronic baseline should be possible.

A main report to the main network shall contain names of components, normalized mole
% of each component rounded to the nearest 0,001 %.

A quality control report for printouts and electronic transmission should contain
information about retention time, peak height, peak width, peak area, response factor,
and mole % before and after normalization.

A control function in the software should give alarm if one or more components are
missing from the report or that the sums of non-normalized values are outside pre-set
limits. This alarm shall inhibit the transmission of potential erroneous results onto the
main computer network.

The following requirements for displaying items should be considered:

• Alarm status;

• Historical analysis data for a single component in chart form;

• Historical analysis data in report format, average, maximum and minimum values
for each component and calculated values;

• The last measured concentration value for each component and calculated
values;

• Real time chromatogram and valve status.

Alarm generation shall be standardized.

Communication with the main metering computer should be via serial data link.

4.4.1.4 Calibration equipment

The calibration gas bottles cabinet shall be electrically heated to prevent condensation.
It should be possible to enter, store and change the composition of the calibration gas.
The VENDOR of the WGM shall provide relevant documentation for the uncertainty
calculations.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 17 of 23
4.4.1.5 Power Supply

The chromatograph shall be powered by an uninterruptable power supply (240 VAC).


Back-up facilities in each chromatograph shall additionally ensure that its data is not lost
under any circumstances.

4.5 Dew Point Analyzer

On-line Dew Point Analyzers shall monitor process gas and hydrocarbon liquid for water
content. Sample stream composition and conditions shall be shown on Instrument Data
Sheets.

The moisture analyzer shall have a high sensitivity and shall not be affected by the
presence of olefins.

The analyzer and all equipment shall be suitable for use in the electrical area
classification as shown on Instrument Data Sheets.

Moisture Analyzer shall consist of but not limited to the following:

• Sensor (Thin Films Aluminum Oxide);

• Analyzer indicator to indicate the water content;

• Interconnecting cable.

The analyzer shall be provided with automatic switching for sample sensor selection and
a manual switch for range and calibration selection.

The analyzer shall provide an isolated DC output current signal of 4-20 mA for each
stream to the flow computer. The output signal shall be linearly proportional to the ranges
as specified on the data sheets.

Interconnecting cable between sample probes and analyzer shall be provided.

Analyzer shall be equipped with self-moisture generator.

The input of Moisture Analyzer shall be communicated to control system and it should be
used for the re-normalization of gas composition with moisture content as per ASTM
standard.

Dew Point Analyzer shall have the following Service Parameters;

• Accuracy shall be + 3.6 ºF;

• Power supply shall be 240VAC;

• Daily auto-calibration feature.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 18 of 23
4.6 Flow Computer

4.6.1 Hardware Requirements

Flow computer shall be provided and able to handle differential pressure inputs for flow
under process conditions, temperature, pressure and molecular weight. Flow computer
will be in a cabinet located in the marshalling cabinet room.

Flow computer hardware and software calculation blocks for flow computing shall be
certified as suitable for use in custody transfer application by independent certification
body e.g. NMI or PTB.

Differential pressure (high and low range pressure), temperature and pressure values
are acquired by the flow computer as 4-20 mA signals.

The overall uncertainty of the metered standard volume flow rate, calculated in
accordance with AGA 3/2000, shall not exceed ±1% (of mass flowrate) over the full
operating range.

Gas composition and molecular weight are acquired by flow computer via RS 485
physical interface MODBUS RTU protocol to Gas Chromatograph.

Flow computer shall be provided with an internal printer and suitable interface.

The flow computer shall also be able to provide as a minimum the following:
• RS 485 MODBUS RTU serial interface or Ethernet communication to control
system;
• Four 4 - 20 mA isolated analogue signal outputs for compensated volume flow
rate, mass flow rate, temperature and pressure as repeat signal for others;
• Flow computer should also give two digital output signals for flow computer
healthy status, flow computer fault status.
The flow computer shall be supplied with dedicated supervisory computer and all
necessary configuration software required. The configuration software shall run on
Microsoft Windows XP or latest.

4.6.2 Accessibility Levels

The flow computer will have at least 2 access levels:


• Random access (engineering level);
• Restricted access (operator level).
The random access must be protected by means of a hardware switch-off facility and
gives special access to the following data:
• Engineering units;
• Scaling factors;
• Correction factors;

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 19 of 23
• Calibration factors;
• Programming;
• Constants;
• The switch-off facility must be inside the computer housing.
The restricted access level gives only access to the various displayed values such as:
• Differential pressure;
• Pressure;
• Temperature;
• Corrected flow rate;
• Mol % N2;
• Mol % CO2 etc.;
• Molecular weight;
• Accumulative corrected quantity;
• All data where a change of data does not affect the accumulated quantity.

4.6.3 Display

The LCD type display presents alphanumeric data in at least 2 lines with a minimum of
16 characters each.

4.6.4 Key Pad

The integrated key-pad serves the purpose of selecting the information to be displayed
and of entering the alphanumeric values of data as described above in "Accessibility
levels" Section.

4.6.5 Memory Back-up

No data shall be lost including the totaled values, by an external power supply failure.

4.6.6 Software Requirements

4.6.7 Input Conditioning

The input signals, for flow computer, from the differential pressure transmitters shall be
linearised by the flow computer.

4.6.8 Selection of Flow Inputs

Where two differential pressure transmitters shall be used, the selection of the low or
high flow range transmitter shall be done automatically base on the flow rate. At the end
of the low flow range of the transmitter for low flow, the computer switches over to the
transmitter for high range by increasing flow. The reverse sequence is followed on
decreasing flow.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 20 of 23
4.6.9 Computation

The actual compensated gas flow must be calculated at reference conditions 60ºF at
14.73 psi absolute and in accordance with AGA-3 / 2000.

4.6.10 Error Handling

Input errors (transmitter failure) must be displayed on the display and will activate the
flow computer trouble alarm output.

System errors shall be handled in the same way.

Below an output of 10% for a period of up to 4 minutes, an alarm will be generated. Also
at an output above 100% the system will generate an alarm "out of limit" on the system
display and via the digital output flow computer trouble. Also an alarm message will be
printed on the printer. The flow computer shall also generate Flow Computer healthy
indication.

The start and end time of every error will be stored in the system memory.

4.6.11 Print Reports

Flow computer shall be able to produce a print report on manual command. A print
report consists of the following information:
• Year, Month, Day and Time;
• Total cumulative corrected quantity in MMSCF;
• Cumulative corrected quantity for the previous day in MMSCF.
And if an error or hold state has been detected in the previous day:
• Alarm or hold state numbers;
• Time when the error or hold state has been detected;
• Time when the end of error or hold state has been detected;
• Type of error or hold state;
• Corrected quantity during error conditions for the previous day in MMSCF as
cumulative total from begin to end of error.

4.6.12 Operating Status

The normal operating status is without an input or position frozen.

For testing and for calibrating of the computers or field instruments several inputs or
positions can be frozen from the key pad as following:
• Hold State 1
This hold state will be used for testing and/or calibration of the transmitters only.

During the hold state 1 the input signals are frozen on the last value;

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 21 of 23
• Hold State 2
This hold state will be used only for testing and calibration of the flow computers
themselves.

During the time this hold state is activated the flow totalling will be blocked.

After resetting this hold state the totalling starts again with the last totalized value
before the hold state.

4.6.13 Power Supply

Flow computer shall be powered by an uninterruptable power supply (240 VAC). Back-
up facilities in flow computer shall additionally ensure that fiscal figures are not lost
under any circumstances.

4.7 Analyzer House

The pre-engineered packaged analyzer system shall include the pre-fabricated shelter,
sampling system, analyzers, ventilation, electrical services and other utilities. Pre-
engineered shelters shall be supplied by a specialist system fabricator to offer the best
option in terms of convenience, cost, system responsibility and final product quality.

Analyzer shelter shall provide a controlled environment for the operation and
maintenance of the analyzer packages and shall protect the analyzers against extreme
ambient conditions.

Pre-engineered shelters shall be shipped with analyzers installed and all systems (air
conditioners, ventilators, purge system, lighting & power supply systems) in place and
tested before shipment.

The shelter floor shall be sealed to prevent the ingress of vapour or gas.

Analyzer shelter shall be large enough to allow adequate access and space for
maintenance work and shall have two (2) exits located at opposite ends.

5.0 INSPECTION AND TESTING

The COMPANY reserves the right for inspection of material, manufacturing process,
testing, etc. Such inspection does not relieve the VENDOR of the responsibility of
suitable design and workmanship.

VENDOR shall submit a detailed Inspection and Test Plan (ITP) for approval with all
activities and acceptance criteria.

Sales Metering Skid shall be subjected to factory acceptance test.

Following are the requirement for Factory Acceptance Test:


• Performance;

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 22 of 23
• Hydro Test;
• Review of NDTS;
• Review of Material and Calibration Certificate;
• Physical and Dimensions;
• Access for Individual Equipment for Maintenance Purpose.

6.0 CERTIFICATION OF COMPLIANCE

The gas flow meter skid package shall be certified by a suitable authority of the country
of origin for AGA 3/2000 requirements.

7.0 SITE SERVICES

The gas metering VENDOR / CONTRACTOR shall be responsible for the delivery, off-
loading and installation at site. VENDOR shall provide the services of an experienced
ENGINEER to assist the CONTRACTOR for the following site activities:

• Mechanical completion: assistance for skid installation and site preliminary tests;

• Power-up, functional testing and commissioning;

• Site Acceptance Test.

8.0 SPARE PARTS AND SPECIAL TOOLS

VENDOR shall supply special tools, if any required for configuration and maintenance of
the system.

The VENDOR shall include with the bid the recommended spare parts list as per the
following and the material requisition:

• One (1) orifice plate similar to the one installed in the provided meter runs.

• Itemized recommended spare part list for start-up and commissioning;

• Itemized recommended spare parts list for two (2) years operation in SPIR forms.

9.0 TRAINING

The scope shall include training for the operators, maintenance personnel & engineers
as per the terms and conditions in the Purchase Order. Training shall cover the following
areas as a minimum:

• Operation;

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc


VECO Doc. No. 20298-01-EJ12-005
Project Title

MEHAR GAS DEVELOPMENT PROJECT


Area Location Discipline Document No Rev. Page
12 MGDP I 1025 0 23 of 23
• Maintenance / Troubleshooting;

• Configuration.

Training for the complete system shall be provided for COMPANY operations for 1 day
and for maintenance / engineers for 3 days at VENDOR factory.

For each trainee who will attend a training course, a copy of the complete training
course, notes and drawing shall be provided to the COMPANY.

The copies shall be retained by the trainees on completion of the training course and
shall be the property of the COMPANY.

10.0 DOCUMENTATION

Manuals provided shall be in English, written in a simple, clear and concise manner.
A comprehensive set of manuals shall be supplied including but not limited to:

• General system description;

• Equipment specification;

• Application software documentation;

• Test and commissioning procedures;

• Meter Validation Manual

• Operations Manual.

Vendor shall also comply the requirements of documentation specified in PCPL


procedure CSP-03.

C:\Documents and Settings\shaikhb\Desktop\Bahuddin\20298-01-EJ12-005 Rev 0 Specification Sales Gas Metering (12.05.08).doc

Das könnte Ihnen auch gefallen