Sie sind auf Seite 1von 2

FSSFC5060 SERIES

The FSSFC5060 series frequency converters are designed to supply 3 phase AC critical loads with
high stability 60Hz frequency and voltage from a 50Hz input power source. The FSSFC5060 version
converts 60Hz to 50Hz.

The frequency converter design is based upon the standard rectifier and inverter sub-assemblies
and the logic as used in our S40 Series of UPS systems. This compact dimensioned product range is
ideally suitable for industrial applications in military and civil aviation, shore to ship services, avionics
workshops and where USA market products have to operate from 50Hz power supplies when high
performance and reliability is demanded.

Batteries can be added to this frequency converter to provide autonomy and power security for the
users who need continuous power at times when there is the risk of input mains degradation or
failure.

A mimic status and alarm panel with either digital or analogue metering is provided on the front
door of the frequency converter. A remote alarm signal interface facility is available as an optional
feature.

The basic mechanical construction is in vertical format with ingress protection IP31 with optional IP41
and IP54, there is a horizontal version available for mounting on a mobile trolley, trailer or on floor
stands.

>
FREQUENCY CONVERTERS

Analogue supplementary metering

> 50Hz or 60Hz input frequency

> Output 50 or 60Hz flexible cable

> Remote monitoring by interface PCB


50 & 60HZ SOLID STATE

> RS485 remote monitoring by computer

> Ingress protection from IP20 up to IP54

> Special paint colours and finish, available upon request


TECHNICAL SPECIFICATIONS
INPUT:
Input Voltage 115V / 230V / 440V +/-10% 3ph
Input Frequency 50 or 60Hz , +/- 6%
Input Current Harmonics IEC 1000-3-4
Input Power Factor >0.95
Rectifier Inrush 10 second walk-in, max current < In x 1.2
Input Connections IEC or EN60309/2 connectors
Input Protection Circuit breaker, rear panel

OUTPUT:
Output Voltage 230V or 115V 3 ph
Output Voltage Regulation Steady-state: +/-2%, dynamic 0-100% step load:
+/-5% recovering to steady- state within 10mS
Total Harmonic Distortion <3% linear load
Output Frequency 50Hz or 60Hz +/- 0.1%, quartz generated
Permissible Load Power Factor -0.6 to 1
Output is galvanically isolated from input - the output neutral may be bonded to earth.

SECURITY:
Permissible Overload 110% @ 10 min, 150% @ 10 s, 200% @ 1 s
FREQUENCY CONVERTERS

Output Overvoltage Cutout Nominal voltage +15%


Output Undervoltage Cutout Nominal voltage -15%
Thermal Overload Thermal sensors located in rectifier, inverter and
output transformer.
50 & 60HZ SOLID STATE

ENVIRONMENT & EQUIPMENT:


Ambient Temperature Range -10 to 40 deg C
Humidity <90%, non-condensing
Altitude All specifications quoted at < 2000m above sea level
Acoustic Noise < 45dBA @ 1m
Overall Efficiency 85 to 91% model dependant
EMC Better than EN55-022B
Cabinet Zinc plated steel, powder coated RAL 7032
Cabinet Protection IP31
Meters Digital voltmeter and ammeter for output
CE marked a

CONNECTIONS:
2m input lead, with correct EN30906/2 inlet socket. Output via Green EN30906/2 or terminals or
choice.

DIMENSIONS:
2 to 5KVA H380 W300 D510mm
6 to 8 KVA H770 W450 D620mm

OPTIONS:
Other input and output voltages and frequencies

> Military variants

> Marine variants

1.5KVA 2KV 3KVA 4KVA 5KVA 6KVA 7kVA 8KVA


A

30Kg 34K 38Kg 40Kg 42Kg 44Kg 46Kg 48Kg


g

Das könnte Ihnen auch gefallen