Form 6 Microprocessor-Based Recloser Control
Serial Communications R280-90-18

Communications Point Data Base

Data 3026 – Revision 0

For
Serial Communications Protocol DNP3

For Use With Cooper Power Systems


Form 6 Recloser Control

January 2003 • New Issue


Printed in USA
Contents
INTRODUCTION ................................................................................................................................3

DATA DICTIONARY OVERVIEW........................................................................................................4

DNP ERROR INDICATIONS ...............................................................................................................5

UNSOLICITED REPORT BY EXCEPTION AND COLLISION AVOIDANCE ..........................................7

REFERENCES...................................................................................................................................8

APPENDIX A: FORM 6 DNP3 DEVICE PROFILE TEMPLATE .............................................................9

APPENDIX B: FORM 6 DNP3 DATA DICTIONARY ........................................................................... 16

2
Introduction

The Form 6 Recloser Control is available with the DNP3 communication protocol on any
of the serial ports. This document provides details for users that need to interface to the
control using this protocol.
The document is divided into sections that give an overview of the data dictionary for the
control, error indication definitions, and reference documents. Appendices provide the
DNP3 Device Profile Template filled out for the Form 6 control and the data dictionary
for accessing the control. Workbench and communication configuration information is
available in the online help for the Form 6.
Class 0 data polls consist of Binary Inputs (Object 1 Variation 0), Binary Counters
(Object 20 Variation 0), Analog Inputs (Object 30 Variation 0) and Binary Output Status
(Object 10 Variation 2).
Report by Exception is supported. Event Classes are configurable using the Assign Class
function or in the Workbench. On device restart, the factory or workbench defined
defaults are used for the event class content definitions until modified by the Assign Class
function. See the data dictionary for factory class definitions.
Unsolicited Report by Exception is also supported as an extension to the report by
exception capability. The implementation follows the rules defined for Unsolicited
Report by Exception, i.e., it is enabled or disabled by a configuration parameter, and
upon device reset, an unsolicited message will be sent without data. After confirmation
no further messages will be sent until DNP messages to enable unsolicited operation are
received by the control.
Data link retries and timeouts are configurable while only Unsolicited Application
timeouts are configurable.

Form 6 Communications Introduction • 3


Data Dictionary Overview

Appendix B contains a listing of the data dictionary for the Form 6 Recloser Control.
This section discusses items of interest from the data dictionary.

Class 0 and 1 Binary Inputs


1. The definition of the bit assignments depends on the workbench specified for
each control.
2. All binary input events default as Class 1 data.
3. Event data is updated immediately on every change.
Class 0 through 3 Counters
1. When an incoming request specifies 16-bit counters, only the lower 16 bits of
the 32 bit counters will be returned.
2. Counter events default to 16 bit without time.
3. Event data is updated on a 125 millisecond basis.
Class 0 through 3 Analog Inputs
1. The data dictionary section that describes the analogs includes default scale
factors (for 16 bit variation) and units to translate the raw data.
2. Analog input events default to 16 bit without time.
3. Event data is updated on a 125 millisecond basis.
Control Relay Output Block (CROB)
1. The data dictionary CROB section indicates whether the control point is self-
resetting or latched.
2. The section also specifies the default condition of a point on power-up or
reset.

Form 6 Communications Data Dictionary Overview • 4


DNP Error Indications

The Internal Indications (IIN) bits from Section 3.6 of the DNP3 Application Layer
document are defined as follows:
1st Octet

Bit 0 All stations message received.


As defined in Section 3.6.
Bit 1 Class 1 data available.
As defined in Section 3.6.
Bit 2 Class 2 data available.
As defined in Section 3.6.
Bit 3 Class 3 data available.
As defined in Section 3.6.
Bit 4 Time sync required from master.
As defined in Section 3.6.
Bit 5 Outstation is in local.
As defined in Section 3.6 for CROB points.
Bit 6 Device Trouble.
As defined by Workbench definition for this control.
Bit 7 Device restart.
As defined in Section 3.6.

Form 6 Communications DNP Error Indications • 5


2nd Octet

Bit 0 Function code not implemented.


As defined in Section 3.6.
Bit 1 Requested objects unknown.
As defined in Section 3.6.
Bit 2 Parameters in the qualifier, range or data fields are invalid or out of
range.
As defined in Section 3.6.
CROB operations when the control is in local will set this bit to indicate
the operation was not successful if the CROB point is dependent on
supervisory status.
Bit 3 Event buffer overflow.
As defined in Section 3.6.
Bit 4 Request understood but already executing.
As defined in Section 3.6.
Bit 5 Current configuration is corrupted.
Not used.
Bit 6 Reserved.
Bit 7 Reserved.

Form 6 Communications DNP Error Indications • 6


Unsolicited Report by Exception and Collision
Avoidance

Unsolicited Report by Exception


Unsolicited Report by Exception (URBE) is supported as an extension to the report by
exception capability. The implementation follows the rules defined for Unsolicited
Report by Exception and those for a Level 3 device:
1. Unsolicited reporting is enabled or disabled by a configuration parameter.
2. Upon device reset, an unsolicited message will be sent without data. After
confirmation no further messages will be sent until DNP messages to enable
unsolicited event reporting are received by the control.
3. Contents of Class 1, 2 or 3 may be assigned or de-assigned dynamically.
4. Unsolicited event reporting is enabled or disabled on a class-by-class basis.
5. The Binary input change variation is user selectable to allow time tagging of
data when requesting Class 1/2/3 information. ). The default is with time
variation.

Form 6 Communications Unsolicited Report by Exception and Collision Avoidance • 7


References

DNP30 Basic 4, Rev. 01


DNP3 Subset Definitions, Version 1.00
DNP Control Relay Output Block Minimum Implementation, 3/8/96
DNP Floating Point Analog Input Variation Recommendations, DNP User’s Group
Technical Committee meeting minutes - February 19, 1997 & April 16, 1997.
Form 6 Recloser Control Product Data - DATA XXXX

Form 6 Communications References • 8


Appendix A: FORM 6 DNP3 Device Profile
Template

Form 6 Communications Appendix A: FORM 6 DNP3 Device Profile Template • 9


Form 6 Device Profile Document

DNP V3.00
DEVICE PROFILE DOCUMENT
This document must be accompanied by a table having the following headings:
Object Group Request Function Codes Response Function Codes
Object Variation Request Qualifiers Response Qualifiers
Object Name (optional)

Vendor Name: Cooper Power Systems

Device Name: F6 Recloser Control

Highest DNP Level Supported: Device Function:


For Requests 3 ¨ Master ý Slave
For Responses 3

Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported
(the complete list is described in the attached table):

This product does not support Analog Outputs or Frozen Counters

Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted 292 Transmitted 2048
Received (must be 292) Received 2048

Maximum Data Link Re-tries: Maximum Application Layer Re-tries:


¨ None ý None
¨ Fixed at ___________________ ¨ Configurable
ý Configurable, range None to 15

Requires Data Link Layer Confirmation:


¨ Never
¨ Always
¨ Sometimes If 'Sometimes', when? ___________________________________________
ý Configurable If 'Configurable', how? Via Proview

Ver 1.0 10 (Page 1 of 6) May 3, 2001


Requires Application Layer Confirmation:
¨ Never
¨ Always (not recommended)
ý When reporting Event Data (Slave devices only)
¨ When sending multi-fragment responses (Slave devices only)
¨ Sometimes If 'Sometimes', when? ___________________________________________
¨ Configurable If 'Configurable', how? ___________________________________________

Timeouts while waiting for:


Data Link Confirm ¨ None ¨ Fixed at _________ ¨ Variable ý Configurable
Complete Appl. Fragment ý None ¨ Fixed at _________ ¨ Variable ¨ Configurable
Application Confirm ¨ None ¨ Fixed at _________ ¨ Variable ý Configurable
Complete Appl. Response ý None ¨ Fixed at _________ ¨ Variable ¨ Configurable
Others ____________________________________________________________________
Attach explanation if 'Variable' or 'Configurable' was checked for any timeout

Sends/Executes Control Operations:


WRITE Binary Outputs ý Never ¨ Always ¨ Sometimes ¨ Configurable
SELECT/OPERATE ¨ Never ý Always ¨ Sometimes ¨ Configurable
DIRECT OPERATE ¨ Never ý Always ¨ Sometimes ¨ Configurable
DIRECT OPERATE - NO ACK ¨ Never ý Always ¨ Sometimes ¨ Configurable
Count > 1 ý Never ¨ Always ¨ Sometimes ¨ Configurable
Pulse On ¨ Never ý Always ¨ Sometimes ¨ Configurable
Pulse Off ¨ Never ¨ Always ý Sometimes ¨ Configurable
Latch On ¨ Never ý Always ¨ Sometimes ¨ Configurable
Latch Off ¨ Never ¨ Always ý Sometimes ¨ Configurable
Queue ý Never ¨ Always ¨ Sometimes ¨ Configurable
Clear Queue ý Never ¨ Always ¨ Sometimes ¨ Configurable
Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation.

Ver 1.0 11 (Page 2 of 6) May 3, 2001


FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY

Expects Binary Input Change Events:


¨ Either time-tagged or non-time-tagged for a single event
¨ Both time-tagged and non-time-tagged for a single event
¨ Configurable (attach explanation)

FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES ONLY

Reports Binary Input Change Events when Reports time-tagged Binary Input Change Events when
no specific variation requested: no specific variation requested:
o Never ¨ Never
o Only time-tagged ¨ Binary Input Change With Time
¨ Only non-time-tagged ¨ Binary Input Change With Relative Time
ý Configurable to send both, one or the ý Configurable (attach explanation)
other (attach explanation)

Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:


¨ Never ý Never
ý Configurable (attach explanation) ¨ When Device Restarts
¨ Only certain objects ¨ When Status Flags Change
¨ Sometimes (attach explanation)
ý ENABLE/DISABLE UNSOLICITED No other options are permitted.
Function codes supported

Default Counter Object/Variation:


o No Counters Reported Counters Roll Over at:
ý Configurable (attach explanation) o No Counters Reported
¨ Default Object o Configurable (attach explanation)
o Default Variation ¨ 16 Bits
o Point-by-point list attached ý 32 Bits
o Other Value ___________
o Point-by-point list attached

Sends Multi-Fragment Responses: ý Yes ¨ No

Ver 1.0 12 (Page 3 of 6) May 3, 2001


Level 3 Implementation Table
This table describes the objects, function codes, and qualifiers used in a
Level 3 DNP V3.00 implementation.

OBJECT REQUEST RESPONSE


(DNP message components (DNP message components
parsed by the F6) reported by the F6)

Obj Var Description Func Qual Func Qual Codes


Codes Codes Codes (hex)
(dec) (hex) (dec)
1 0 Binary Input - All Variations 1,22 00,01,06
1 1 Binary Input 1 00,01,06 129 00,01
1 2 Binary Input with Status 1 00,01,06 129 00,01
2 0 Binary Input Change - All Variations 1 06,07,08
2 1 Binary Input Change without Time 1 06,07,08 129,130 17,28
2 2 Binary Input Change with Time 1 06,07,08 129,130 17,28
2 3 Binary Input Change with Relative Time 1 06,07,08 129,130 17,28
10 0 Binary Output - All Variations 1 01,01,06
10 1 Binary Output
10 2 Binary Output Status 1 00,01,06 129 00,01
12 0 Control Block - All Variations
12 1 Control Relay Output Block 3,4,5,6 17,28 129 Echo of request

12 2 Pattern Control Block 3,4,5,6 07


12 3 Pattern Mask 3,4,5,6 00,01
20 0 Binary Counter - All Variations 1,22 00,01,06

20 1 32-Bit Binary Counter 1 00,01,06 129 00,01


20 2 16-Bit Binary Counter 1 00,01,06 129 00,01
20 3 32-Bit Delta Counter 1 00,01,06
20 4 16-Bit Delta Counter 1 00,01,06
20 5 32-Bit Binary Counter without Flag 1 00,01,06 129 00,01
20 6 16-Bit Binary Counter without Flag 1 00,01,06 129 00,01
20 7 32-Bit Delta Counter without Flag 1 00,01,06
20 8 16-Bit Delta Counter without Flag 1 00,01,06
21 0 Frozen Counter - All Variations 1 00,01,06
21 1 32-Bit Frozen Counter 1 00,01,06
21 2 16-Bit Frozen Counter 1 00,01,06
21 3 32-Bit Frozen Delta Counter 1 00,01,06
21 4 16-Bit Frozen Delta Counter 1 00,01,06
21 5 32-Bit Frozen Counter with Time of Freeze
21 6 16-Bit Frozen Counter with Time of Freeze
21 7 32-Bit Frozen Delta Counter with Time of
Freeze
21 8 16-Bit Frozen Delta Counter with Time of
Freeze
21 9 32-Bit Frozen Counter without Flag 1 00,01,06
21 10 16-Bit Frozen Counter without Flag 1 00,01,06
21 11 32-Bit Frozen Delta Counter without Flag
21 12 16-Bit Frozen Delta Counter without Flag
22 0 Counter Change Event - All Variations 1 06,07,08
22 1 32-Bit Counter Change Event without Time 1 06,07,08 129,130 17,28
22 2 16-Bit Counter Change Event without Time 1 06,07,08 129,130 17,28
22 3 32-Bit Delta Counter Change Event without 1 06,07,08
Time
22 4 16-Bit Delta Counter Change Event without 1 06,07,08
Time
22 5 32-Bit Counter Change Event with Time 1 06,07,08 129,130 17,28
22 6 16-Bit Counter Change Event with Time 1 06,07,08 129,130 17,28
22 7 32-Bit Delta Counter Change Event with Time

Ver 1.0 13 (Page 4 of 6) May 3, 2001


OBJECT REQUEST RESPONSE
(DNP message components (DNP message components
parsed by the F6) reported by the F6)

Obj Var Description Func Qual Func Qual Codes


Codes Codes Codes (hex)
(dec) (hex) (dec)
22 8 16-Bit Delta Counter Change Event with Time
23 0 Frozen Counter Event - All Variations 1 06,07,08
23 1 32-Bit Frozen Counter Event without Time 1 06,07,08
23 2 16-Bit Frozen Counter Event without Time 1 06,07,08
23 3 32-Bit Frozen Delta Counter Event without Time
23 4 16-Bit Frozen Delta Counter Event without Time
23 5 32-Bit Frozen Counter Event with Time
23 6 16-Bit Frozen Counter Event with Time
23 7 32-Bit Frozen Delta Counter Event with Time
23 8 16-Bit Frozen Delta Counter Event with Time
30 0 Analog Input - All Variations 1,22 00,01,06
30 1 32-Bit Analog Input 1 00,01,06 129 00,01
30 2 16-Bit Analog Input 1 00,01,06 129 00,01
30 3 32-Bit Analog Input without Flag 1 00,01,06 129 00,01
30 4 16-Bit Analog Input without Flag 1 00,01,06 129 00,01
30 5 Short Floating Point Analog Input 1 00,01,06 129 00,01
30 6 Long Floating point Analog Input
30 7 Extended Floating Point Analog Input
31 0 Frozen Analog Input - All Variations
31 1 32-Bit Frozen Analog Input
31 2 16-Bit Frozen Analog Input
31 3 32-Bit Frozen Analog Input with Time of Freeze
31 4 16-Bit Frozen Analog Input with Time of freeze
31 5 32-Bit Frozen Analog Input without Flag
31 6 16-Bit Frozen Analog Input without Flag
32 0 Analog Change Event - All Variations 1 06,07,08
32 1 32-Bit Analog Change Event without Time 1 06,07,08 129,130 17,28
32 2 16-Bit Analog Change Event without Time 1 06,07,08 129,130 17,28
32 3 32-Bit Analog Change Event with Time 1 06,07,08 129,130 17,28
32 4 16-Bit Analog Change Event with Time 1 06,07,08 129,130 17,28
32 5 Short Floating Point Analog Change Event 1 06,07,08 129,130 17,28
32 6 Long Floating Point Analog Change Event
32 7 Short Floating Point Analog Change Event with 1 06,07,08 129,130 17,28
Time
33 0 Frozen Analog Event - All Variations
33 1 32-Bit Frozen Analog Event without Time
33 2 16-Bit Frozen Analog Event without Time
33 3 32-Bit Frozen Analog Event with Time
33 4 16-Bit Frozen Analog Event with Time
33 5 Short Floating Point Frozen Analog Event
33 6 Long Floating point Frozen Analog Event
33 7 Extended Floating Point Frozen Analog Event
40 0 Analog Output Status - All Variations
40 1 32-Bit Analog Output Status
40 2 16-Bit Analog Output Status
41 0 Analog Output Block - All Variations
41 1 32-Bit Analog Output Block 3,4,5,6 17,28
41 2 16-Bit Analog Output Block 3,4,5,6 17,28
50 0 Time and Date - All Variations
50 1 Time and Date 1,2 07, 129 Echo of request
quantity=1
50 2 Time and Date with Interval
51 0 Time and Date CTO - All Variations
51 1 Time and Date CTO 129,130 07, quantity=1
51 2 Unsynchronized Time and Date CTO

Ver 1.0 14 (Page 5 of 6) May 3, 2001


OBJECT REQUEST RESPONSE
(DNP message components (DNP message components
parsed by the F6) reported by the F6)

Obj Var Description Func Qual Func Qual Codes


Codes Codes Codes (hex)
(dec) (hex) (dec)
52 0 Time Delay - All Variations
52 1 Time Delay Coarse 129 07, quantity=1
52 2 Time Delay Fine 129 07, quantity=1
60 0 Not defined
60 1 Class 0 Data 1 06
60 2 Class 1 Data 1 06,07,08
20,21,22 06
60 3 Class 2 Data 1 06,07,08
20,21,22 06
60 4 Class 3 Data 1 06,07,08
20,21,22 06
70 1 File Identifier
80 1 Internal Indications 2 00, index=7
81 1 Storage Object
82 1 Device Profile
83 1 Private Registration Object
83 2 Private Registration Object Descriptor
90 1 Application Identifier
100 1 Short Floating Point
100 2 Long Floating Point
100 3 Extended Floating Point
101 1 Small Packed Binary-Coded Decimal
101 2 Medium Packed Binary-Coded Decimal
101 3 Large Packed Binary-Coded Decimal
No object (Cold Restart) 13 129
No object (Delay Measurement) 23 129

Table 1 - Level 3 Implementation (DNP-L3)

Ver 1.0 15 (Page 6 of 6) May 3, 2001


Appendix B: FORM 6 DNP3 Data Dictionary

Form 6 Communications Appendix B: FORM 6 DNP3 Data Dictionary • 16


F6 DNP 3.0 Device Profile data dictionary

Form 6 DNP 3.0 Protocol Device Profile Data Dictionary

November 20, 2002 v 1.04

THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.

Document Date Description


1.00 5/30/01 Initial release.
1.01 5/30/01 Changed wording on SGF "enable" to "block"
Made hot line tag CROBs self-resetting.
1.02 5/8/02 Added Binary Input 59 as "CCI:Control Circuit Interrupted"
1.03 10/30/02 Added CROBs 18 (Combined Trip / Close) and 19 (Sync-Check Enable)
1.04 11/20/02 Changed nomenclature of binary inputs and outputs.

17 (Page 1 of 7) Cover Page


F6 DNP 3.0 Device Profile data dictionary

INPUT SUBSYSTEM

Binary Inputs Default Static Variation Default Event Variation


Obj 02 Var 2 Binary input with time
Obj 01 Var 01 Binary input w/o status

Default
Event
Description Index Class

Mechanism is CLOSED 00 1
Mechanism is OPEN 01 1
Control is Locked Out 02 1
Any Control or System Alarm 03 1
Above minimum trip 04 1
Supervisory off 05 1
Non reclosing 06 1
Ground trip blocked 07 1
SEF Blocked 08 1
Cold load pickup blocked 09 1
Fast trips blocked 10 1
Normal profile selected 11 1
Alternate profile 1 selected 12 1
Alternate profile 2 selected 13 1
Alternate profile 3 selected 14 1
Hot line tag 15 1
Phase A Bus Voltage Present 16 1
Phase B Bus Voltage Present 17 1
Phase C Bus Voltage Present 18 1
Reverse power flow 19 1
** Battery test active 20 1
** No AC power present 21 1
** Battery Alarm 22 1
CI8:Alt1 (TB3:9-10) 23 1
CI9:Alt2 (TB3:11-12) 24 1
CI10:Alt3 (TB3:13-14) 25 1
CI11:Nrml (TB3:15-16) 26 1
CO1:aux (TB1:11-12,13) 27 1
CO2:ok (TB1:14-15) 28 1
CO3:hlt (TB1:16-17) 29 1
CO4:gtb (TB1:18-19) 30 1
SS1:lo (TB1:9-10) 31 1
CO5:nr (TB3:17-18) 32 1
CO6:alm (TB3:19-20,21) 33 1
CO7:nrm (TB4:1-2) 34 1
CO8:alt1 (TB4:3-4) 35 1
CO9:alt2 (TB4:5-6) 36 1
CO10:alt3 (TB4:7-8) 37 1
CO11:frq (TB4:9-10) 38 1
CO12:vlt (TB4:11-12,13) 39 1
Reclose retry Enabled 40 1
Phase A fault trip 41 1
Phase B fault trip 42 1
Phase C fault trip 43 1

18 (Page 2 of 7) Class 0 - 3, Binarys


F6 DNP 3.0 Device Profile data dictionary

Default
Event
Description Index Class
Ground fault trip 44 1
SEF trip 45 1
CI1:RTrip (TB1:3-4) 46 1
CI2:SClose (TB1:5-6) 47 1
CI3:STrip (TB1:7-8) 48 1
CI4:GTB (TB3:1-2) 49 1
CI5:NRecl (TB3:3-4) 50 1
CI6:TargR (TB3:5-6) 51 1
CI7 (TB3:7-8) 52 1
Ground Overcurrent alarm 53 1
Phase Overcurrent alarm 54 1
Negative Sequence Overcurrent 55 1
alarm
Hot Line tag input from Idea 56 1
Workbench
Hot Line tag input from 57 1
Communications Workbench
Hot Line tag input from Front 58 1
Panel toggle switch
CCI:Control Circuit Interrupted 59 1

** Pole Mount Version Only

19 (Page 3 of 7) Class 0 - 3, Binarys


F6 DNP 3.0 Device Profile data dictionary

INPUT SUBSYSTEM

Counters Default Static Variation Default Event Variation


Obj 20 Var 2 16 bit Counter Obj 22 Var 2 16 bitCounter w/o time

Default
Event
Description Index Class Deadband
Number of phase A operations 00 1 10000
Number of phase B operations 01 1 10000
Number of phase C operations 02 1 10000
Number of ground operations 03 1 10000
Number of SEF operations 04 1 10000
Number of trip phase operations 05 1 10000

20 (Page 4 of 7) Class 0 - 3, Counters


F6 DNP 3.0 Device Profile data dictionary

INPUT SUBSYSTEM

Analog Inputs Default Static Variation Default Event Variation


Obj 30 Var 2 16 bit Obj 32 Var 2 16 bit w/o time

Index Default Division Scale Units


Event Factor
Description Class Deadband

Instantaneous current through A phase 00 2 10 Amps 100


Instantaneous current through B phase 01 2 10 Amps 100
Instantaneous current through C phase 02 2 10 Amps 100
Instantaneous ground current 03 2 10 Amps 100

Instantaneous voltage at A phase source side 04 2 1 Volts 1000


Instantaneous voltage at B phase source side 05 2 1 Volts 1000
Instantaneous voltage at C phase source side 06 2 1 Volts 1000

Instantaneous power factor for A phase 07 2 10000 1


Instantaneous power factor for B phase 08 2 10000 1
Instantaneous power factor for C phase 09 2 10000 1

Instantaneous KVA for A phase 10 2 1 KVA 1000


Instantaneous KVA for B phase 11 2 1 KVA 1000
Instantaneous KVA for C phase 12 2 1 KVA 1000

Instantaneous KW for A phase 13 2 1 KW 1000


Instantaneous KW for B phase 14 2 1 KW 1000
Instantaneous KW for C phase 15 2 1 KW 1000

Instantaneous KVAR for A phase 16 2 1 KVAR 1000


Instantaneous KVAR for B phase 17 2 1 KVAR 1000
Instantaneous KVAR for C phase 18 2 1 KVAR 1000

Instantaneous line frequency 19 1 100 Hz 10

Demand current through A phase 20 2 10 Amps 100


Demand current through B phase 21 2 10 Amps 100
Demand current through C phase 22 2 10 Amps 100

Unloaded battery voltage 23 3 100 Volts 5


Unloaded battery current 24 3 1000 Amps 1

21 (Page 5 of 7) Class 0 - 3, Analogs


F6 DNP 3.0 Device Profile data dictionary

OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status

Default Static Variation


Conditioned by
Operation Default Supervisory State
Description Index Obj Var Desc Operation Type Mask Condition (factory default) Comments

Binary Output 00 12 01 CROB Self Resetting 0xff Off Yes * Close Mechanism
Binary Output 01 12 01 CROB Self Resetting 0xff Off Yes * Trip Mechanism
Binary Output 02 12 01 CROB Latched 0xff Off Yes Block Reclosing
Binary Output 03 12 01 CROB Latched 0xff Off Yes Block Ground Trip
Binary Output 04 12 01 CROB Latched 0xff Off Yes Block SEF
Binary Output 05 12 01 CROB Latched 0xff Off Yes Block Cold Load PU
Binary Output 06 12 01 CROB Latched 0xff Off Yes Block Fast Trips
Binary Output 07 12 01 CROB Self Resetting 0xff Off Yes * Profile:Normal
Binary Output 08 12 01 CROB Self Resetting 0xff Off Yes * Profile:Alt1
Binary Output 09 12 01 CROB Self Resetting 0xff Off Yes * Profile:Alt2
Binary Output 10 12 01 CROB Self Resetting 0xff Off Yes * Profile:Alt3
Binary Output 11 12 01 CROB Self Resetting 0xff Off Yes * Reset targets
Binary Output 12 12 01 CROB Self Resetting 0xff Off Yes * Reset demands
Binary Output 13 12 01 CROB Self Resetting 0xff Off Yes * Reset alarms
Binary Output 14 12 01 CROB Self Resetting 0xff Off Yes *, ** Test Battery
Binary Output 15 12 01 CROB Self Resetting 0xff Off No *, *** HLT Set
Binary Output 16 12 01 CROB Self Resetting 0xff Off Yes *, *** HLT Reset
Binary Output 17 12 01 CROB Latched 0xff Off Yes Enable Reclose retry
Binary Output 18 12 01 CROB Self Resetting 0xff Off Yes Combined Trip/Close
Binary Output 19 12 01 CROB Latched 0xff Off Yes Sync-Check Enable
Binary Output 20 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 21 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 22 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 23 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 24 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 25 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 26 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 27 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 28 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 29 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 30 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 31 12 01 CROB Latched 0xff Off Yes User Defined

* Momentary/Self Resetting,
always read FALSE

** Pole Mount Version Only


*** Hot Line Tag activates a
latching relay in the control
"close" circuit.

22 (Page 6 of 7) CROB
F6 DNP 3.0 Device Profile data dictionary

Default Static Variation


Conditioned by
Operation Default Supervisory State
Description Index Obj Var Desc Operation Type Mask Condition (factory default) Comments

Binary Output 00 10 02 Status * Close Mechanism


Binary Output 01 10 02 Status * Trip Mechanism
Binary Output 02 10 02 Status Block Reclosing
Binary Output 03 10 02 Status Block Ground Trip
Binary Output 04 10 02 Status Block SEF
Binary Output 05 10 02 Status Block Cold Load PU
Binary Output 06 10 02 Status Block Fast Trips
Binary Output 07 10 02 Status * Profile:Normal
Binary Output 08 10 02 Status * Profile:Alt1
Binary Output 09 10 02 Status * Profile:Alt2
Binary Output 10 10 02 Status * Profile:Alt3
Binary Output 11 10 02 Status * Reset targets
Binary Output 12 10 02 Status * Reset demands
Binary Output 13 10 02 Status * Reset alarms
Binary Output 14 10 02 Status *, ** Test Battery
Binary Output 15 10 02 Status *, *** HLT Set
Binary Output 16 10 02 Status *, *** HLT Reset
Binary Output 17 10 02 Status Enable Reclose retry
Binary Output 18 10 02 Status Combined Trip/Close
Binary Output 19 10 02 Status Sync-Check Enable
Binary Output 20 10 02 Status User Defined
Binary Output 21 10 02 Status User Defined
Binary Output 22 10 02 Status User Defined
Binary Output 23 10 02 Status User Defined
Binary Output 24 10 02 Status User Defined
Binary Output 25 10 02 Status User Defined
Binary Output 26 10 02 Status User Defined
Binary Output 27 10 02 Status User Defined
Binary Output 28 10 02 Status User Defined
Binary Output 29 10 02 Status User Defined
Binary Output 30 10 02 Status User Defined
Binary Output 31 10 02 Status User Defined

* Momentary/Self Resetting,
always read FALSE

** Pole Mount Version Only


*** Hot Line Tag activates a
latching relay in the control
"close" circuit.

23 (Page 7 of 7) CROB