Form 6 Microprocessor-Based Recloser Control
Serial Communications R280-90-18
For
Serial Communications Protocol DNP3
REFERENCES...................................................................................................................................8
2
Introduction
The Form 6 Recloser Control is available with the DNP3 communication protocol on any
of the serial ports. This document provides details for users that need to interface to the
control using this protocol.
The document is divided into sections that give an overview of the data dictionary for the
control, error indication definitions, and reference documents. Appendices provide the
DNP3 Device Profile Template filled out for the Form 6 control and the data dictionary
for accessing the control. Workbench and communication configuration information is
available in the online help for the Form 6.
Class 0 data polls consist of Binary Inputs (Object 1 Variation 0), Binary Counters
(Object 20 Variation 0), Analog Inputs (Object 30 Variation 0) and Binary Output Status
(Object 10 Variation 2).
Report by Exception is supported. Event Classes are configurable using the Assign Class
function or in the Workbench. On device restart, the factory or workbench defined
defaults are used for the event class content definitions until modified by the Assign Class
function. See the data dictionary for factory class definitions.
Unsolicited Report by Exception is also supported as an extension to the report by
exception capability. The implementation follows the rules defined for Unsolicited
Report by Exception, i.e., it is enabled or disabled by a configuration parameter, and
upon device reset, an unsolicited message will be sent without data. After confirmation
no further messages will be sent until DNP messages to enable unsolicited operation are
received by the control.
Data link retries and timeouts are configurable while only Unsolicited Application
timeouts are configurable.
Appendix B contains a listing of the data dictionary for the Form 6 Recloser Control.
This section discusses items of interest from the data dictionary.
The Internal Indications (IIN) bits from Section 3.6 of the DNP3 Application Layer
document are defined as follows:
1st Octet
DNP V3.00
DEVICE PROFILE DOCUMENT
This document must be accompanied by a table having the following headings:
Object Group Request Function Codes Response Function Codes
Object Variation Request Qualifiers Response Qualifiers
Object Name (optional)
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported
(the complete list is described in the attached table):
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted 292 Transmitted 2048
Received (must be 292) Received 2048
Reports Binary Input Change Events when Reports time-tagged Binary Input Change Events when
no specific variation requested: no specific variation requested:
o Never ¨ Never
o Only time-tagged ¨ Binary Input Change With Time
¨ Only non-time-tagged ¨ Binary Input Change With Relative Time
ý Configurable to send both, one or the ý Configurable (attach explanation)
other (attach explanation)
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
INPUT SUBSYSTEM
Default
Event
Description Index Class
Mechanism is CLOSED 00 1
Mechanism is OPEN 01 1
Control is Locked Out 02 1
Any Control or System Alarm 03 1
Above minimum trip 04 1
Supervisory off 05 1
Non reclosing 06 1
Ground trip blocked 07 1
SEF Blocked 08 1
Cold load pickup blocked 09 1
Fast trips blocked 10 1
Normal profile selected 11 1
Alternate profile 1 selected 12 1
Alternate profile 2 selected 13 1
Alternate profile 3 selected 14 1
Hot line tag 15 1
Phase A Bus Voltage Present 16 1
Phase B Bus Voltage Present 17 1
Phase C Bus Voltage Present 18 1
Reverse power flow 19 1
** Battery test active 20 1
** No AC power present 21 1
** Battery Alarm 22 1
CI8:Alt1 (TB3:9-10) 23 1
CI9:Alt2 (TB3:11-12) 24 1
CI10:Alt3 (TB3:13-14) 25 1
CI11:Nrml (TB3:15-16) 26 1
CO1:aux (TB1:11-12,13) 27 1
CO2:ok (TB1:14-15) 28 1
CO3:hlt (TB1:16-17) 29 1
CO4:gtb (TB1:18-19) 30 1
SS1:lo (TB1:9-10) 31 1
CO5:nr (TB3:17-18) 32 1
CO6:alm (TB3:19-20,21) 33 1
CO7:nrm (TB4:1-2) 34 1
CO8:alt1 (TB4:3-4) 35 1
CO9:alt2 (TB4:5-6) 36 1
CO10:alt3 (TB4:7-8) 37 1
CO11:frq (TB4:9-10) 38 1
CO12:vlt (TB4:11-12,13) 39 1
Reclose retry Enabled 40 1
Phase A fault trip 41 1
Phase B fault trip 42 1
Phase C fault trip 43 1
Default
Event
Description Index Class
Ground fault trip 44 1
SEF trip 45 1
CI1:RTrip (TB1:3-4) 46 1
CI2:SClose (TB1:5-6) 47 1
CI3:STrip (TB1:7-8) 48 1
CI4:GTB (TB3:1-2) 49 1
CI5:NRecl (TB3:3-4) 50 1
CI6:TargR (TB3:5-6) 51 1
CI7 (TB3:7-8) 52 1
Ground Overcurrent alarm 53 1
Phase Overcurrent alarm 54 1
Negative Sequence Overcurrent 55 1
alarm
Hot Line tag input from Idea 56 1
Workbench
Hot Line tag input from 57 1
Communications Workbench
Hot Line tag input from Front 58 1
Panel toggle switch
CCI:Control Circuit Interrupted 59 1
INPUT SUBSYSTEM
Default
Event
Description Index Class Deadband
Number of phase A operations 00 1 10000
Number of phase B operations 01 1 10000
Number of phase C operations 02 1 10000
Number of ground operations 03 1 10000
Number of SEF operations 04 1 10000
Number of trip phase operations 05 1 10000
INPUT SUBSYSTEM
Binary Output 00 12 01 CROB Self Resetting 0xff Off Yes * Close Mechanism
Binary Output 01 12 01 CROB Self Resetting 0xff Off Yes * Trip Mechanism
Binary Output 02 12 01 CROB Latched 0xff Off Yes Block Reclosing
Binary Output 03 12 01 CROB Latched 0xff Off Yes Block Ground Trip
Binary Output 04 12 01 CROB Latched 0xff Off Yes Block SEF
Binary Output 05 12 01 CROB Latched 0xff Off Yes Block Cold Load PU
Binary Output 06 12 01 CROB Latched 0xff Off Yes Block Fast Trips
Binary Output 07 12 01 CROB Self Resetting 0xff Off Yes * Profile:Normal
Binary Output 08 12 01 CROB Self Resetting 0xff Off Yes * Profile:Alt1
Binary Output 09 12 01 CROB Self Resetting 0xff Off Yes * Profile:Alt2
Binary Output 10 12 01 CROB Self Resetting 0xff Off Yes * Profile:Alt3
Binary Output 11 12 01 CROB Self Resetting 0xff Off Yes * Reset targets
Binary Output 12 12 01 CROB Self Resetting 0xff Off Yes * Reset demands
Binary Output 13 12 01 CROB Self Resetting 0xff Off Yes * Reset alarms
Binary Output 14 12 01 CROB Self Resetting 0xff Off Yes *, ** Test Battery
Binary Output 15 12 01 CROB Self Resetting 0xff Off No *, *** HLT Set
Binary Output 16 12 01 CROB Self Resetting 0xff Off Yes *, *** HLT Reset
Binary Output 17 12 01 CROB Latched 0xff Off Yes Enable Reclose retry
Binary Output 18 12 01 CROB Self Resetting 0xff Off Yes Combined Trip/Close
Binary Output 19 12 01 CROB Latched 0xff Off Yes Sync-Check Enable
Binary Output 20 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 21 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 22 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 23 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 24 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 25 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 26 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 27 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 28 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 29 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 30 12 01 CROB Latched 0xff Off Yes User Defined
Binary Output 31 12 01 CROB Latched 0xff Off Yes User Defined
* Momentary/Self Resetting,
always read FALSE
22 (Page 6 of 7) CROB
F6 DNP 3.0 Device Profile data dictionary
* Momentary/Self Resetting,
always read FALSE
23 (Page 7 of 7) CROB
Kyle® Form 6 Microprocessor-Based Recloser Control Serial Communications Protocol DNP3
KDL
9/04