CT Primary Injection Ratio Testing Problem


Situation after CT Primary Injection:
New 230kv breaker
Testing CT’s, 4000/5, by high current injection
injecting 80 amps A phase to ground
the secondary leads are shorted in a junction box A-B-C-N / additionally a voltage is connected
to test instrument form test set
The secondary readings are A = 0.096 @ 176 degrees, B = 0.01 @ 0, C = 0.01 @ 0, N = 0.108 @
4
only one set of CT’s, 2 per phase read this all others tested where i.e. A=0@0, B=0.1@180,
C=0@0, N=0.1@0

When load was applied secondary current looked correct


Seems like I ‘ve seen this before, is there an answer for this?