Sie sind auf Seite 1von 8

Electric Power Systems Research 77 (2007) 851–858

Discriminating changes introduced in the model for the winding


of a transformer based on measurements
Subrat K. Sahoo ∗ , L. Satish
Department of H.V. Engineering, Indian Institute of Science, Bangalore 560012, India
Received 28 March 2006; received in revised form 14 June 2006; accepted 27 July 2006
Available online 30 August 2006

Abstract
A systematic procedure is evolved that enables identification of the type-of-changes introduced in the model winding of a transformer, based on a
comparison of measured neutral or line current and transfer-function with those corresponding to the reference case. Further, it was also possible to
ascertain, whether the pertinent circuit element viz. series capacitance, shunt capacitance and self-inductance has increased or decreased (compared
to initial value). The proposal was formulated based on analytical calculation and circuit simulation. Thereafter, the approach was experimentally
verified using two model windings, and the results were found to be encouraging. Thus, it demonstrates one possible way, how interpretation of
monitored data can lead to meaningful inferences.
© 2006 Elsevier B.V. All rights reserved.

Keywords: Diagnostic testing; Interpretation of monitored data; LVI testing; FRA/TF method

1. Introduction data has, as yet, not happened. It is desirable that every moni-
toring method is adequately supported by powerful diagnosis or
Power utilities perform condition monitoring on large power interpretation, so that its true potential can be harnessed.
transformers to assess its status. Many monitoring methods have In a practical scenario (e.g. when fault is implied), a diag-
evolved over the years and each one of them is intended to ascer- nostic method is expected to provide assistance to the operation
tain some specific aspect of dielectric, thermal and mechanical engineer regarding, the extent of fault, its location, and so on,
integrity of the transformer. Amongst these low voltage impulse such that timely action can be initiated. Instead of resorting to
(LVI) and frequency response analysis (FRA) or transfer func- expensive and time-consuming disassembly of the transformer,
tion (TF) method have been found to be useful in detecting it would be certainly advantageous to seek answers to these
winding deformations. Such deformities occur due to short- questions by interpretation of monitored data, as far as possi-
circuit forces and sometimes may be caused due to unskilled ble. Therefore, exploration of newer ways of interpretation is
handling during transportation [1]. Although, minor and incip- desirable.
ient deformations/damages are generally not immediately per- A survey of pertinent literature reveals that most publications
ceivable, they are in fact potential sites from where major faults on this topic can be classified into:
can develop subsequently.
The existing detection philosophy of these methods is based • Introduce a deformation (axial, radial, etc.) on an actual wind-
on a comparison of two subsequently gathered records, and if a ing and then examine ability of a method to detect the smallest
mismatch were to be observed, then a possible fault is implied. possible change [2–8].
It is generally observed that, beyond a visual comparison, moni- • Attempt to model or translate the winding deformation (i.e.
tored data does not seem to be post-processed to draw inferences. physical changes) into a corresponding change in the equiv-
Strictly speaking, diagnosis or interpretation of the monitored alent circuit, so that, measured and computed TF are similar
[4–6].

• Preliminary efforts attempting to link observed changes in TF,
Corresponding author. Tel.: +91 80 22933179; fax: +91 80 22932373.
E-mail addresses: subrat@hve.iisc.ernet.in, subrat.sahoo@gmail.com
to the nature and location of fault, was examined via simula-
(S.K. Sahoo), satish@hve.iisc.ernet.in (L. Satish). tion studies [9].

0378-7796/$ – see front matter © 2006 Elsevier B.V. All rights reserved.
doi:10.1016/j.epsr.2006.07.007
852 S.K. Sahoo, L. Satish / Electric Power Systems Research 77 (2007) 851–858

study evolves a logical procedure to predict the type of changes


introduced, entirely based on data from terminal measurements.
In this respect, it attempts to interpret monitored data and thereby
show how information regarding changes (of the model winding
in this case) could be extracted. The next step would be to exam-
ine possibilities of extending this method to actual windings.

3. Model employed for simulation and experiments


Fig. 1. Equivalent circuit of a uniform winding of a transformer.
The circuit representation in Fig. 1 comprising of series
Thus, it emerges that monitored data has not been subjected to capacitance (Cs ), shunt capacitance (Cg ), self-inductance (Ls ),
any rigorous interpretation or diagnosis. Generally, in practice, lumped resistance (r), and mutual inductances (Mi−j ) is known
an expert opinion is sought. Recognising this need, the present to adequately describe the lightning impulse behaviour of the
authors recently demonstrated [10], how TF of a two-winding transformer winding [11]. For a symmetrical circuit, all the self
transformer could be interpreted and meaningful information inductance (Ls1 , Ls2 , Ls3 , . . .) are taken as Ls , all the series capac-
about the origin of its natural frequencies extracted. Hence, it itance (Cs1 , Cs2 , Cs3 , . . .) are taken as Cs , and all the shunt capac-
just goes to show how interpretation of monitored data can yield itance (Cg2 , Cg3 , Cg4 , . . .) are taken to be Cg (except Cg1 and
useful information. When such is the prevalent situation, it is Cg11 , i.e. the first and last section shunt capacitance, which are
imperative that exploratory investigations are essential. This was taken as Cg /2). Additionally, in such a representation, the value
the main motivation. of any element can be varied, and hence, by changing Cs , both
continuous-disc and interleaved winding configurations could
2. Problem definition be represented. Further, this representation permits analytical
investigation (symbolic computation, MAPLE), computation of
Admittedly, a full-scale solution of the above problem on an time and frequency-domain responses using circuit simulation
actual transformer winding is far too complicated, and to the software (PSPICE), as well as construction of a model winding
best knowledge of the authors, has not been attempted earlier. for experimental verification. Two model windings (with 10 sec-
Further, many of the complex interactions that exist between tions each) were used in the experiments. The self and mutual
winding deformation and its influence on natural frequencies, inductance values shown in Table 1 were as a result of a mea-
type of change, effect on position of change, etc., are not yet surement on the model-winding done at a frequency of 1 kHz,
fully understood. This lack of knowledge is the main bottleneck using the 1657 L-C-R DigiBridge (GenRad, USA). These values
that prevents a direct solution from being addressed. Therefore, have been used during simulation studies, so that any mismatch
as a first step, a simplified version of the problem is initially between measured and calculated inductances in experiments
considered to untangle some of these intricate dependencies. and simulation are avoided.
So, considering a single uniform winding of the transformer
(as in Fig. 1) considerably reduces the complexity of the prob- 4. Underlying principle and solution approach
lem. With this modification, the focus of problem under inves-
tigation shifts from the transformer winding to the equivalent For evolving the logical procedure, it was essential to initially
circuit. This step should not be construed as an oversimplifica- study the nature of interrelation that exists between each circuit
tion of the task, since fault discrimination and location (based on element, line/neutral current and natural frequencies. To achieve
terminal measurements alone), even with respect to this circuit this, an analytical solution for the neutral current in s-domain
has not been fully understood and resolved. Therefore, starting (i.e. In (s)) was derived using nodal analysis [12]. Initially, a loss-
with the representation in Fig. 1 and using data arising from ter- less case with solidly grounded neutral was considered for the
minal measurements (i.e. LVI, FRA/TF method), the following sake of clarity. The general expression of the neutral current, for
becomes the problem statement: a step-input excitation, as a function of the circuit elements, for

1. Data from LVI and FRA method is available for the reference Table 1
(or initial) case. Self and mutual inductances (Ls , Mi−j , in ␮H/section)
2. A capacitance (shunt or series) and/or inductance is changed.
Model Ls Mi−j
3. Step 1 is repeated, and the two data sets are compared.
4. Based on observed deviations, is it possible to discriminate I 180 m1–2 = 110.75, m1–3 = 73.97,
m1–4 = 54.67, m1–5 = 42,
the type of circuit change introduced?
m1–6 = 33.15, m1–7 = 26.7,
m1–8 = 21.45, m1–9 = 17.6,
The proposed solution strategy was formulated using ana- m1–10 = 14.8
lytical computations and simulation studies. Then, these are II 65 m1–2 = 36, m1–3 = 25, m1–4 = 18,
experimentally verified on a model winding. Applicability of m1–5 = 14, m1–6 = 10, m1–7 = 8,
m1–8 = 6.3, m1–9 = 5, m1–10 = 4.25
the proposed method is verified for both disc and interleaved
types of windings, in simulation and experiments. Thus, this Other Mi−j values are determined from symmetry considerations.
S.K. Sahoo, L. Satish / Electric Power Systems Research 77 (2007) 851–858 853

Fig. 2. Percentage variation in components of line and neutral current. Capac- Fig. 3. Variation of inductive and oscillatory components of neutral current,
itive component as a function of: (A) series and (B) shunt capacitance and (C) following a change in: (A) series capacitance and (B) self inductance.
inductive component as a function of self-inductance.
These matters are graphically shown in Fig. 2. In subplot-A,
the percentage variation of the capacitive component for In (s),
an n-section network can be compactly written as: when series capacitance at section-1 is varied (either increased
or decreased) with respect to the reference case is shown. The
Csn 1
In (s) = + subplot-B of Fig. 2 illustrates a similar variation, when shunt
Poly1(Cs , Cg ) Poly2(Ls , Mi−j )s2 capacitance at section-2 is varied. From the two subplots, it is
Poly3(Cs , Cg , Ls , Mi−j , s) seen that changes in series and shunt capacitance influence the
+ (1) capacitive component of In (s) in the opposite way (i.e. an inverse
Poly4(Cs , Cg , Ls , Mi−j , s)
relationship exists). In other words, an increase in capacitive
where Poly1 is a polynomial function of Cs and Cg alone, Poly2 component of In (s), results due to either an increase in series
is a function of Ls and Mi−j alone, while, Poly3 and Poly4 are capacitance or a decrease in shunt capacitance, and vice versa for
functions of Cs , Cg , Ls , Mi−j and ‘s’. a decrease in capacitive component. So, this is another important
An examination of the above expression reveals that In (s) distinguishing feature for segregating series and shunt capacitive
contains three terms, viz., the first term (dependent on Cs and changes. Subplot-C represents the variation of inductive com-
Cg alone and independent of ‘s’) is the capacitive term, the sec- ponent with respect to change in self-inductance in the circuit
ond term (dependent on Ls and Mi−j alone and a function of 1/s2 ) at section-1. This has a decreasing trend with increase in induc-
is the inductive term, while the last term corresponds to the oscil- tance value.
latory components pertaining to the natural frequencies or poles The next important task was to translate these findings and
[12]. This separable or decoupled feature between the three com- inferences derived from analytical studies to those actually
ponents is an important aspect. The fact that the first two terms observable from LVI and FRA measurements. For this purpose,
are independent of each other is the most important feature, and consider the neutral current response in time-domain, due to
can be explicitly shown, by substituting n = 3, and taking ele- a standard lightning impulse. The capacitive component can be
ments in each section to be identical. Imposing this condition, recognized by observing the initial few microseconds of the neu-
Cs3 tral current. In some cases, a zoomed version may have to be
it turns out that the first two terms of In (s) are 4Cg Cs +3Cs2 +Cg2 considered. So, the logic arrived at from the analytical studies
and s2 (3L +2M1 +4M ) , respectively. Thus, from this it is clear can be extended here as well (examples will be discussed in next
s 1−3 1−2
that capacitive term is dependent on only the capacitances of section).
the circuit, while the inductive term is a function of self and Unlike the capacitive component of the neutral current that
mutual inductances alone. In other words, it indicates that a exists for only the first few microseconds, the inductive com-
change in either series or shunt capacitance (made at any posi- ponent manifests as a relatively slow build-up and exists for
tion) in the model will affect the capacitive term alone, keeping hundreds of microseconds, over which the oscillatory compo-
the inductive component unaffected. Similarly a change in self nents are superimposed. This aspect is not directly evident from
or mutual inductance anywhere in the circuit would result in a the expressions, since it is the response for an ideal step input.
corresponding change that is confined only to the inductive term. Instead of this, consider Fig. 3, which shows in time-domain,
Of course, in both these cases, the oscillatory component (i.e. variation of both inductive and oscillatory components of the
natural frequencies) would change. However, if there occurs a neutral current, when a capacitance or inductance was changed
simultaneous change in inductance and capacitance, then both (obtained from PSPICE for a standard lightning impulse exci-
these two components would undergo a change. tation). When a capacitance change is imposed on the circuit
854 S.K. Sahoo, L. Satish / Electric Power Systems Research 77 (2007) 851–858

Fig. 4. Flowchart-1 principle of the proposed method.

(increase or decrease), the peak value of the inductive component a decrease of the natural frequencies (resulting in left-shift of
does not change (capacitive and inductive changes are indepen- poles in TF plot) with respect to reference case. And similarly, a
dent of each other, as discussed earlier). However, the natural decrease would result in their right-shift. The evolved procedure
frequencies will obviously change, and this introduces a time- for distinguishing the various changes in the model winding are
shift to the oscillatory components, due to which the inductive summarised below and shown as a flowchart in Fig. 4.
component appears to have slightly changed, which is not the
case, and, if a mean-curve is drawn, then the average value of the
• Separability of the components of In (s) was possible.
inductive component will be found to remain unchanged. This
• Capacitive and Inductive components of In (s) are independent
aspect is observed in subplot-A, of Fig. 3. Next, variation of both
of each other.
inductive and oscillatory components of neutral current, when
• Cg and Cs change affect capacitive component of In (s) oppo-
inductance is changed, is shown in Fig. 3, subplot-B, where it is
sitely.
seen that mean-value of inductive component clearly undergoes
a significant change, in contrast to that seen in subplot-A. Thus,
changes imposed to both inductance and capacitance elements The procedure developed above was found to be successful,
of the circuit can be identified, based on the fact that the corre- only when one change was introduced at a time. However in
sponding changes they introduce on the neutral current are well practice, it is natural to expect simultaneous change in Ls and
separated in time. Cs or Cg . Hence, the investigation was continued further and
Once the occurrence of a capacitive change is identified, the another quantity measurable at the terminals, namely, the line
next task is to distinguish it, as either due to a change in Cs or current was examined for this purpose. An analytical expres-
Cg . To achieve this, information available in frequency domain, sion, similar to that of In (s), was derived corresponding to
i.e. in TF, can be employed for interpretation as follows. An the line current (IL (s)). These two expressions were identical,
increase in capacitance (either series or shunt) would result in except for the first term. The capacitive component of IL (s)

Fig. 5. Flowchart-2 principle of the proposed method.


S.K. Sahoo, L. Satish / Electric Power Systems Research 77 (2007) 851–858 855

1 6Cg Cs +9Cg Cs +Cg +2Cs


2 2 3 3
is: 2 4Cg Cs +3Cs +Cg
2 2 . A comparison of this term with the
capacitive term of In (s) reveals that this capacitive component
has a direct relation with respect to a variation in both Cg and Cs ,
in contrast to what was observed with In (s). That means, there
is an increase in capacitive component of IL (s) when either Cs
or Cg increases. This aspect is shown in subplot-A and -B of
Fig. 2 respectively. From this it emerges that a simple combi-
nation of these information about the inductive and capacitive
components of line and neutral current would help in discrim-
inating changes due to both Ls and Cs or Cg . This matter is
summarized in flowchart-2, Fig. 5. Thus, simultaneous changes
were also distinguishable.

5. Simulation studies

Applicability of proposed method was initially verified by Fig. 6. Comparison of computed (A) neutral current and (B) TF, corresponding
to increase and decrease in Cs , in section-1.
simulation studies on a 5-section circuit (as in Fig. 1), details of
which are given below.
was decreased. Thus, occurrence of either a decrease or increase
in Cs can be distinguished.
1. Total Cg was chosen as 3.0 nF and Cs was varied.
2. Ls and Mi−j (first four Mi−j values for a 5-section), corre-
5.2. Case-2: change in Cg
sponding to Model I (Table 1), were used.
3. A resistance (r) of 1.2  per section was used. The series capacitance chosen for this case study was
0.15 nF per section, so that the equivalent circuit represents a
Three cases studies are reported, namely Case-1, Case-2 and continuous-disc type of winding. The reference value of Cg was
Case-3 to discuss circuit changes (both increase and decrease) 0.6 nF/section. The shunt capacitance in section-2 was changed
in series capacitance in section-1, shunt capacitance in section-2 from the original value to 0.2 nF/section and later increased
and self-inductance in section-1, respectively. to 1.0 nF/section. Fig. 7, subplot-A shows the neutral current
response, depicting these changes. Similar to the previous case
5.1. Case-1: change in Cs study, the inductive component of In (t) does not show a percep-
tible change, when there is a change in Cg . The initial capacitive
It is generally accepted that fault detection in a transformer component is shown, within subplot-A, as an inset. Unlike in
with interleaved winding is difficult [3,12]. So, in this case the previous case study, increase in Cg results in a reduction of
study, an interleaved winding was considered by choosing the capacitive component, and the reverse is true for a decrease
Cs = 7.5 nF/section. The reference neutral current (In (t)) and in Cg , as illustrated in the flowchart (in Fig. 4). Fig. 7, subplot-B
TF (up to 400 kHz, with 1 kHz resolution) were computed and represents the corresponding TF. As expected, an increase in Cg
stored. These two quantities were computed again, and cor- results in left-shift of all the poles compared to reference TF, and
respond to both an increase (from 7.5 to 10 nF/section) and a decrease in Cg results in a right-shift. Hence the knowledge
decrease (from 7.5 to 5.0 nF/section) in Cs , in section-1. Subplot-
A, in Fig. 6 represents In (t) corresponding to reference case
superposed over those pertaining to increase and decrease in Cs .
No perceptible change was observed in the long-term behaviour
(i.e. inductive component) of In (t), between the reference case
and that due to change in Cs . So, it can be inferred that there is
no inductive change.
Next, a zoomed view of In (t) corresponding to the initial
1–2 ␮s is shown as an inset in subplot-A. Clearly a change was
observable in the initial capacitive component with respect to the
reference case, for both increase and decrease in Cs , thus indicat-
ing occurrence of a capacitive change. When Cs was increased,
it resulted in a higher value of capacitive component and vice
versa, as already discussed. Next, TF was computed and is shown
for reference case and those corresponding to an increase and
decrease in Cs . Subplot-B, in Fig. 6 shows these results. A left-
shift of all the natural frequencies occurs (compared to reference Fig. 7. Comparison of computed (A) neutral current and (B) TF, corresponding
TF) when Cs was increased, and a right-shift occurs when Cs to increase and decrease in Cg , in section-2.
856 S.K. Sahoo, L. Satish / Electric Power Systems Research 77 (2007) 851–858

6.1. Case 4: increase and decrease in Cs , at section-1

An interleaved winding was selected (Model–I) by choos-


ing Cg = 2.2 and Cs = 20 nF/section (corresponding to α = 3.3).
In this study, series capacitance was increased from 20 to
40 nF/section and then decreased to 10 nF/section. The impulse
voltage and In (t) were acquired (128 K points, sampled at 10 ns)
corresponding to the reference condition, increase in Cs , and
decrease in Cs respectively, and the TFs computed. Fig. 9,
subplot-A, shows the initial portion of In (t) (i.e. capacitive com-
ponent), zoomed up to 2.5 ␮s for the reference case together
with those corresponding to a change in Cs at section-1. A clear
increase and decrease in capacitive component is seen, corre-
sponding to an increase and decrease in Cs respectively, thus
indicating that capacitance has changed. In subplot-B, the TFs
are compared. A left-shift of the natural frequencies is observed
Fig. 8. Comparison of computed (A) neutral current and (B) TF, corresponding compared to the reference condition when Cs is increased, and
to increase and decrease in Ls , in section-1.
a right-shift occurs when Cs was decreased. The corresponding
simulation results are included in subplot-C and subplot-D, and
of the shift in TF (following the change in Cg ), along with the
indicate a reasonable degree of agreement.
increase or decrease in capacitive component (from the neutral
current response) together, gives the information of change in
6.2. Case 5: increase and decrease in Cg , at section-2
Cg , which is already elaborated in Section 4.
The circuit configuration same as in Case 4 was adopted
5.3. Case-3: change in Ls
here. Cg , in section-2 was increased from 2.2 to 6.9 nF and
In this study, effect of a change in Ls was simulated.
Although increase in Ls is rare, for sake of completeness, both
an increase and decrease was considered. An interleaved wind-
ing was chosen with Cs = 7.5 nF/section. Ls in section-1 was
increased from 180 to 250 ␮H/section and decreased from 180
to 100 ␮H/section. The inductive and oscillatory part of In (t)
shows a change, as can be seen in Fig. 8, subplot-A. Whereas the
capacitive component (not shown in figure), and being indepen-
dent of changes in inductance, has remained unaltered, thereby
indicating a change in inductance. A significant change in the
inductive component in the time interval between 20 and 90 ␮s
(the observed time interval depends on the value of inductance
involved) has been observed. An increase in Ls would reduce
long-term magnitude of In (t) and a decrease would result in an
increase in its magnitude. The corresponding TF are shown in
subplot-B. Shifts in the natural frequencies were exactly as pre-
dicted.

6. Experimental results

The proposed method was verified by experiments on two


model windings (Fig. 1). Two models (with 10-sections each)
were used, whose details are given in Table 1. For brevity, only a
few sample results are presented. A low voltage recurrent surge
generator (Haefely RSG 482) was used to acquire neutral current
response (as a voltage across 47 ) due to a standard lightning
impulse excitation (peak value of 30 V). Data was acquired using
a 10-bit, 200 MSa/s digitizer (RTD 710A), and TF was computed
via FFT, instead of manually sweeping the frequency. For each
case study discussed, simulation results (corresponding to time Fig. 9. Comparison of measured (A) neutral current, (B) TF, corresponding to
and frequency ranges of interest) are also presented to enable a an increase and decrease in Cs , in section-1, and the corresponding simulation
comparison. results (C) neutral current and (D) TF.
S.K. Sahoo, L. Satish / Electric Power Systems Research 77 (2007) 851–858 857

Fig. 11. Comparison of measured (A) neutral current (B) TF, corresponding to a
Fig. 10. Comparison of measured (A) neutral current (B) TF, corresponding to decrease in Ls , in section-1, and the corresponding simulation results (C) neutral
an increase and decrease in Cg , in section-2, and the corresponding simulation current and (D) TF.
results (C) neutral current and (D) TF.
considered due to operational difficulties. In this study, Model-2
thereafter decreased to 560 pF. Fig. 10, subplot-A shows the was chosen with Cg = 1020, Cs = 350 pF/section (corresponding
capacitive component for the reference case and those corre- to α = 17). A clear difference (Fig. 11, subplot-A) was observable
sponding to the changes incorporated in Cg . An increase in in the oscillatory part of the In (t) i.e. an increase when compared
capacitive component is observed for a decrease in Cg and vice to the reference value. Subplot-B shows a comparison of TF. The
versa. A comparison of the respective TFs is given in subplot-B. reduced inductance causes an increase in the natural frequencies,
A left-shift of natural frequencies occurs following an increase as expected. These aspects are clearly seen in Section 6, and are
in Cg and a right-shift of natural frequencies is observed when in good agreement with the simulation results, shown in subplot-
Cg is decreased. The simulation results pertinent to this case are C and subplot-D.
shown in subplot-C and subplot-D.
It may be noted here that due to quasi-static approxima- 6.4. Case-7: change in Ls and Cg /Cs
tions employed for determining the circuit elements of such
lumped parameter equivalent circuits (used to represent trans- It is easily visualized that representation of winding deforma-
former behaviour), these models, cannot exactly replicate the tion would naturally necessitate incorporating multiple changes
frequency-dependent behaviour of its elements and hence there into the circuit in Fig. 1. In order to consider this, simultaneous
will occur a slight mismatch between the measured and simu- change in inductance and capacitance elements were imposed.
lated TF plots. However this mismatch gradually increases at By considering the IL (t) and In(t), it was possible to segregate
higher frequencies, and at lower frequencies, it is of the order of the L and C changes. Model-1 was chosen for the above purpose
a few kHz, as is observed in Figs. 9 and 10. This should not be with an α value of 2.36.
construed as an error, but is a limitation of the representation.
6.4.1. Decrease in Ls at section-4 and increase in Cs at
6.3. Case 6: decrease in Ls , at section-1 section-1
The series capacitance in first section was increased from
A reduction in self-inductance, at section-1, was achieved by 10 to 30 nF and the series inductance was reduced from 180 to
short-circuiting one section. Increase in self-inductance was not 65 ␮H in the fourth section. An increase in capacitive component
858 S.K. Sahoo, L. Satish / Electric Power Systems Research 77 (2007) 851–858

winding representations. Experimental results were found to be


in good agreement with those predicted by simulation and ana-
lytical studies. Therefore, it is demonstrated how interpretation
of monitored data (LVI and TF data) can be used to extract infor-
mation about changes inside the winding. In final summary, the
objective of interpreting LVI and TF data has been partially
achieved.

References

[1] K. Feser, J. Christian, C. Neumann, U. Sundermann, T. Liebfried, A. Kach-


ler, M. Loppacher, The transfer function method for detection of winding
displacements on power transformer after transport, short circuit or 30 years
of service, CIGRE 12/33-04, Session 2000.
[2] W. Lech, L. Tyminski, Detecting transformer winding damage—the low
Fig. 12. Comparison of capacitive component of line and neutral currents when voltage impulse method, Electr. Rev. 179 (21) (1966) 768–772.
combined L and C changes are incorporated. (A) Line current and (B) neutral [3] B.I. Gururaj, B.N. Jayaram, Use of recurrent surge generator for detecting
current. (Note: Ls in section-4, Cs is section-1 and Cg in section-2 was varied.) displacement and deformations in transformer winding, IE(I) J. -EL 54
(1974) 99–102.
[4] E. Rahimpour, J. Christian, K. Feser, H. Mohesini, Transfer function
is observed both for IL (t) and In (t) for an increase in Cs along method to diagnose axial displacement and radial deformation of trans-
with an increase in inductive and oscillatory component, as seen former windings, IEEE Trans. PWRD 18 (2) (2003) 493–505.
in the inset of Fig. 12, subplot-A and subplot-B, respectively. [5] M. Florkowski, J. Furgal, Detection of transformer winding deformations
based on the transfer function measurements and simulations, J 2003 Meas.
Sci. Techl.-14 (2003) 1986–1992.
6.4.2. Decrease in Ls at section-4 and decrease in Cg at [6] M. Wang, A.J. Vandermaar, K.D. Srivastava, Improved detection of power
section-2 transformer winding movement by extending the FRA high frequency
In another case study, the Cg was reduced in the second sec- range, IEEE Trans. PWRD 20 (3) (2005) 1930–1938.
tion from 560 to 100 pF, while the same change (as in Case-7) [7] J.A.S.B. Jayasinghe, Z.D. Wang, P.N. Jarman, A.W. Darwin, Investiga-
in inductance was made at fourth section. A decrease in the tion on sensitivity of fra technique in diagnosis of transformer wind-
ing deformations, in: Proceedings of the Conference Record of IEEE
capacitive component of IL (t), is observed (Fig. 12, subplot-A) International Symposium On EI, Indianapolis, USA, 2004, pp. 496–
for decrease in Cg but an increase in capacitive component is 499.
observed for In (t) (Fig. 12, subplot-B). However the inductive [8] S.A. Ryder, Diagnosing transformer faults using frequency response anal-
and oscillatory component continues to increase both in line and ysis, IEEE EI Magn. 19 (2) (2003) 16–22.
neutral current (seen in the inset of subplot-A and -B of Fig. 12) [9] T. Leibfried, EinfluB von windungsschlussen auf die ubertragungsfunktion
von transformator wicklungen am beispiel homogener spulen, Electr. Eng.
against the reference case. (1997) 99–108.
In summary an increase in capacitive component of both [10] L. Satish, S.K. Sahoo, An effort to understand what factors affect the trans-
IL (t) and In (t) can be a result of an increase in “Cs ”, whereas fer function of a two-winding transformer, IEEE Trans. Power Deliv. 20
an increase in capacitive component of In (t) but a decrease in (2) (2005) 1430–1440.
capacitive component of IL (t) is a result of decrease in “Cg ”. The [11] P.A. Abetti, F.J. Maginniss, Natural frequency of coils and wind-
ings determined by equivalent circuit, AIEE Trans. 74 (1953) 495–
change in inductive component happens for both the currents 504.
in a similar way, which has an inverse relation with change in [12] L. Satish, A. Jain, Structure of transfer function of transformers with special
“Ls ”. The procedure follows in accordance with the Flowchart- reference to interleaved windings, IEEE Trans. Power Deliv. 17 (3) (2002)
2 of Fig. 5. Thus, using the proposed approach, simultaneous 754–760.
changes in Ls and Cs /Cg could also be identified. For brevity Subrat K. Sahoo (S 04) was born in 1979. He received the B.E. degree (Hons.) in
more examples are not included. electrical engineering from the Indira Gandhi Institute of Technology, Sarang,
India, which is affiliated with Utkal University, Orissa, India, in 2001. He
7. Conclusions completed (in August 2003) his M.Sc. (Engg.) from the Department of High
Voltage Engineering, Indian Institute of Science (I.I.Sc.), Bangalore, India. He
is currently registered for the Ph.D. degree in the Department of High Voltage
In a model winding, if a deviation is observed when a pair of Engineering. His research interests include diagnostics and condition monitoring
subsequently acquired neutral/line current and TF data are com- of transformers.
pared, then it is possible to figure out, which one of the three L. Satish (SM 02) was born in 1964. He received the Ph.D. degree from the
circuit elements of the equivalent circuit, namely, series capac- Indian Institute of Science (I.I.Sc.), Bangalore, India, in 1993. Since 2001, he has
itance, shunt capacitance or self-inductance is responsible for been an Associate Professor with the Department of High Voltage Engineering,
the observed change. Further, it can also be inferred whether the I.I.Sc. He was a Postdoctoral Fellow with ETH, Zurich, Switzerland, from 1993
pertinent circuit element has increased or decreased, from its ini- to 1995. He was a Visiting Researcher with H.V. Institute, Helsinki University
of Technology, Helsinki, Finland, during the summer of 1998. His research
tial value. The proposed approach requires data corresponding interests include application of signal processing to high voltage impulse testing,
to terminal measurements, and does not impose any necessity dynamic and static testing of ADCs, diagnostics and condition monitoring of
for newer measurements. Applicability of the method was ver- transformers, PD measurements and pattern recognition. Dr. Satish is a member
ified (to a limited extent) for both disc and interleaved type of of CIGRE D1-33 in CIGRE WG D1-33.

Das könnte Ihnen auch gefallen