Sie sind auf Seite 1von 5

Filename: RunTest.

test Manufacturer:
Date/Time: 08/09/17 16:51:13 Model: CT0.6
Company: NPS S/N:
Station: PTN DDT Operator:
Circuit: Frequency: 50 Hz
Comments: Knee Type: IEC 10/50

Test Tap IEEE30 V/I IEEE45 V/I IEC 10/50 V/I NP-Ratio M-Ratio % Error Phase Angle Winding Resistance
1 X1-X5 8.00 / 0.0804 6.80 / 0.0656 8.40 / 0.0870 200/5.0 39.761 0.5975 179.94 [Out Ø]

EZCT-2000 Software Version: 2.3


www.vanguard-instruments.com Page 1
Test # 1 : X1-X5
IEEE 30 IEEE 45 IEC 10/50 NP-RATIO: 200/5.0 Ex V[Volts]: 5.200V
Vkp[Volts]: 8.00 Vkp[Volts]: 6.80 Vkp[Volts]: 8.40 M-RATIO: 39.761 Ex I[Amps]: 0.053
Ikp[Amps]: 0.0804 Ikp[Amps]: 0.0656 Ikp[Amps]: 0.0870 % ERROR: 0.5975 Phase Angle: 179.94 [Out Ø]
Winding Resistance:
Test Notes:

Graph Point Current (Amps) Voltage Z (Ohm) Graph Point Current (Amps) Voltage Z (Ohm)
1 0.0010 0.1000 100.00 11 0.1000 8.8000 88.00
2 0.0020 0.1000 50.00 12 0.2000 9.6000 48.00
3 0.0040 0.2000 50.00 13 0.4000 10.0000 25.00
4 0.0050 0.3000 60.00 14 0.5000 10.1000 20.20
5 0.0080 0.5000 62.50 15 0.8000 10.3000 12.88
6 0.0100 0.6000 60.00 16 1.0000 10.4000 10.40
7 0.0200 1.4000 70.00 17 2.0000 10.5000 5.25
8 0.0400 3.6000 90.00 18 4.0000 10.5000 2.63
9 0.0500 4.8000 96.00 19 5.0000 10.4000 2.08
10 0.0800 8.0000 100.00

EZCT-2000 Software Version: 2.3


www.vanguard-instruments.com Page 2
Test # 1 : X1-X5
Data Point Current (Amps) Voltage Z (Ohm) Data Point Current (Amps) Voltage Z (Ohm)
1 0.0158 0.96 60.76 14 0.2074 9.64 46.48
2 0.0162 1.04 64.20 15 0.2638 9.80 37.15
3 0.0228 1.60 70.18 16 0.3142 9.88 31.44
4 0.0268 2.04 76.12 17 0.3726 9.96 26.73
5 0.0308 2.44 79.22 18 0.4774 10.08 21.11
6 0.0378 3.28 86.77 19 0.5344 10.12 18.94
7 0.0460 4.32 93.91 20 0.7484 10.28 13.74
8 0.0570 5.80 101.75 21 1.0124 10.40 10.27
9 0.0696 7.28 104.60 22 1.2084 10.44 8.64
10 0.0872 8.44 96.79 23 1.6454 10.52 6.39
11 0.1052 8.92 84.79 24 3.1024 10.56 3.40
12 0.1288 9.24 71.74 25 5.0460 10.44 2.07
13 0.1658 9.52 57.42

EZCT-2000 Software Version: 2.3


www.vanguard-instruments.com Page 3
Pass / Fail Report

Test Tap IEEE 30 NP-Ratio M-Ratio % Error Phase Angle


1 X1-X5 200/5.0 39.761 0.5975 179.94 [F]

CT Type: C100
CT Location: Circuit Breaker
Turns Ratio Deviation: Metering 1%
Knee-Point Voltage Deviation: 20%

EZCT-2000 Software Version: 2.3


www.vanguard-instruments.com Page 4
Filename: RunTest.test Manufacturer:
Date/Time: 08/09/17 16:51:13 Model: CT0.6
Company: NPS S/N:
Station: PTN DDT Operator:
Circuit: Frequency: 50 Hz
Comments: Knee Type: IEC 10/50

Test Plan

Tap Nameplate Ratio Ratio Excitation Winding Excitation Excitation Note


Test Test Res. Test Voltage Current
X1-X5 200/5.0 X X 250.0000 5.0000

Burden Test [ ]
Insulation Test [ ]

EZCT-2000 Software Version: 2.3


www.vanguard-instruments.com Page 5