FIRE CODE PROVISION VIOLATION SECTION GRACE

VIOLATED PERIOD
10.2.15.1 REQUIREMENTS
A-2. Occupant Load
The occupant load of industrial Failure to comply 10.2.15.1 15 days
occupancies for which exits are to with required para A-2
be provided shall be one(1) person occupant load.
per nine and three tenths square
meters(9.3m2) gross floor area,
provided that in Special Purpose
Industrial Occupancy and for Open
Industrial Structures, the occupant
load shall be maximum number of
persons to occupy the area under
any probable conditions, and
further provided that in existing
industrial occupancies the Chief
,BFP or his duly authorized
representative may waive
requirements for additional exits if
the existing exits are adequate for
the maximum number of persons
actually employed .
10.2.15.2 EXIT DETAILS
A.General
Each required exit shall be in Failure to comply 10.2.15.2 15 days
accordance with the applicable with required exit Para A
Sections of Division 4 of this detail
Chapter, with access thereto and
ways of travel therefrom in
accordance with Section 10.2.5.2
of this IRR.
10.2.15.2 EXIT DETAILS
B. Types of Exit
Exits shall be restricted to the
following permissible types:
a. Doors
b. Stairs,or smokeproof
enclosures
c. Horizontal exits
d. Ramps
e. Slide Escapes
10.2.15.2 EXIT DETAILS
C. Minimum Corridor Width
The minimum width of any corridor Failure to comply 10.2.15.2 15 days
or passageway serving as a with the required para C
required exit or means of travel to minimum width
or from required exit shall be one of corridor or
hundred twelve centimeters passageway.
(112cm) in the clear.
10.2.15.2 EXIT DETAILS
D. Capacity of Exits
Capacity of means of egress shall Failure to comply 10.2.15.2 15 days
be determined in accordance with with the required para D
Section 10.2.5.2 of this IRR. capacity of
means of egress
10.2.15.2 EXIT DETAILS
E. Number of Exits
At least two(2) exits shall be Failure to comply 10.2.15.2 15 days
provided for every floor section, with the required Para E
including floors below the floor of number of exits
exit discharge used for industrial
purposes or uses incidental
thereto. At least one of which shall
be reached without traversing
another storey.
10.2.15.2 EXIT DETAILS
F. Travel Distance to Exits
Exit shall be as remote from other Failure to comply 10.2.15.2 15 days
as practicable, so arranged that it with the required Para F
will not be necessary to travel travel distance
more than thirty one meters (
31m) from any point to reach the
nearest exit for buildings not
protected by a complete automatic
fire suppression system, or forty
six meters ( 46 m) in a building
protected by an approved ,
supervised sprinkler system in
accordance with Section 10.2.6.5
of this IRR.
From every point there shall be at
least two (2) separate exits
accessible so arranged as to be
reached by different paths of travel
in different directions .
10.2.15.2 EXIT DETAILS
G. Discharge from Exits
A maximum of fifty percent ( 50%) Failure to comply 10.2.15.2 15 days
of the exits may discharge through with required Para G
areas on the floor of exit discharge from
discharge provided: exit
1. Such exits discharges to a
free and unobstructed way
to the exterior of the
building, which way is
readily visible and
identifiable from the point of
discharge from the exit.
2. The floor of discharge into
which the exit discharges is
provided with automatic fire
suppression system and
any other portion of the
level of discharge with
access to the discharge
area is provided with
automatic fire suppression
system protection or
separated from it in
accordance with
requirements for the
enclosure of exits. ( see
Section 10.2.6.2 of this IRR)
10.2.15.2 EXIT DETAILS
H. Signs , Lighting ,and Exit
Signages
1. Signs designating exits or Absence of exit 10.2.15.2 145
ways of travel thereto shall signs, lights and Para H days
be provided in accordance emergency lights
with Section 10.2.5.12 of
this IRR.
2. Exit lighting shall be
provided in accordance with
Section 10.2.5.11 of this
IRR.
3. Emergency lighting shall be
provided in accordance with
Section 10.2.5.11 of this
IRR.
10.2.15.3 PROTECTION
A. Protection of Vertical Opening
Every stairway, elevator shaft, Failure to 10.2.15.3 15 days
escalator opening and other provide safety para A
vertical opening shall be enclosed measure and
or protected in accordance with protection for
Section 10.2.6.2 of this IRR. vertical opening
10.2.15.3 PROTECTION
B.Interior Finish
Interior finish shall be Class A , Improper 10.2.15.3 15 days
Class B or Class C installation of para B
Interior finish
10.2.15.3 PROTECTION
C. Detection Alarm and
Communications Systems
An approved automatic fire Absence of fire 10.2.15.3 15 days
detection and alarm system shall detection alarm para C
be required on all industrial and
occupancies except for buildings communication
with less than 25 employees where system.
such building shall be equipped
with manual fire alarm system.

FIRE CODE PROVISION VIOLATION SECTION GRACE


VIOLATED PERIOD
10.2.15.3 PROTECTION
D. Extinguishing Requirement
1.Every high hazard occupancy shall Absence 10.2.15.3 15 days
have automatic fire suppression portable fire para D
system protection as may be extinguisher
appropriate to the particular hazard, and standpipe
including explosion venting for any
area subject to an explosion hazard,
designed to minimize danger to
occupants in case of fire or other
emergency before they have time to
utilize exits to escape.

2.Portable fire extinguishers shall be


installed in accordance with Section
10.2.6.7 of this IRR.

Submitted by:

F/T Rommel C Gomez Jr.


F/T Jacqueline M Fradela
FAICC CL 2018-01

Submitted to:

FCINSP JAN GARRY D LUNAS


FAICC CL 2018-01 Instructor