Beruflich Dokumente
Kultur Dokumente
Company Profile Products Application Catalog Global Network Trade Show Schedule
Home Products Information Switches & Breakers Air Circuit Breakers Auxiliary devices
Motor
Air Circuit Breakers : Auxiliary devices
Inverter
AC Servo
Characteristics
Ratings
Operating characteristics of
trip relay / OCR-III
3:Closing Coil(CC)
The coil only operates when the power is supplied continuously over 100ms
External dimensions(Draw-
Power should be supplied separately from the moer charging power. out type)
Electric pumping prevent circuit is built in it.
Type selection
Rated voltage(V) Operational voltage (V) Inrush current peak value(A) Steady current(A) Closing time(sec)
Air Circuit Breakers
AC/DC 110 94-121 2 1 [AKH,AKS,AKN Series]
50/60Hz 220 187-242 3 1.3
Magnetic Starters & Contactors
125 106-138 2.3 1 0.08 Under
http://www.hitachi-ies.co.jp/english/products/switches/acb/A_devices.htm 1/3
5/21/2018 Air Circuit Breakers : Auxiliary devices : Hitachi Industrial Equipment Systems
Blower
4:Shunt coil(SHT)
Marking System
To open the breaker by remote control
Use an auxiliary contact(INO) to prevent coil burnig Products Overview
When the control power is 'OFF' at the ACB is 'ON' state, the ACB remains 'ON'
Rated voltage(V) Operational voltage (V) Inrush current peak value(A) Steady current(A) Closing time(sec)
AC/DC 110 77-121 2 1
50/60Hz 220 154-242 3 1.3
125 88-138 2.3 1 0.04 Under
DC 24 21-26V 30 3.5
48 41-53V 30 7
Note
* The extent of operation voltage is 70-110% of the rated voltage.
To Page Top
OCR alarm contact is fundamentally installed in only ACB with trip relay.
When the ACB is tripped by the OCR operation, electrical signal flows through the OCR alarm contact for
remote supervisory(INO).
Contact type
http://www.hitachi-ies.co.jp/english/products/switches/acb/A_devices.htm 2/3
5/21/2018 Air Circuit Breakers : Auxiliary devices : Hitachi Industrial Equipment Systems
Contact capacity
TYPE Capacity
AC 250V 5A
Ratings
DC 30V 5A
Rated current 5A
AC 380V
Maximum contact voltage
DC 125V
Maximum contact current 5A
Minimum applicable load DC 5V 10mA
Product Inquiry
To Page Top
Terms of Use Privacy Policy Revision History © Hitachi Industrial Equipment Systems Co.,Ltd. 2002-2018. All rights reserved.