Sie sind auf Seite 1von 1

Section 12—Power-Zone™ Metal-Enclosed Busway

General

Power-Zone Metal-Enclosed Busway—Minimum Dimensions and Other Specifications (continued)

Dimensionsq
Voltage
Ampere
and F G H I J
Rating
Material
IN mm IN mm IN mm IN mm IN mm
1200 48.00 1219 22.00 559 18.25 464 28.00 711 17.00 432
1600 48.00 1219 22.00 559 18.25 464 28.00 711 17.00 432
2000 48.00 1219 22.00 559 19.25 489 30.00 762 17.00 432

Copper 2500 48.00 1219 22.00 559 21.25 540 34.00 864 17.00 432
600 3200 60.00 1524 25.00 635 24.25 616 34.00 864 20.00 508
4000 60.00 1524 25.00 635 24.25 616 34.00 864 20.00 508
5000 60.00 1524 30.00 762 28.75 730 34.00 864 25.00 635
6000 60.00 1524 30.00 762 33.75 857 44.00 1118 25.00 635
1200 48.00 1219 22.00 559 18.25 464 28.00 711 17.00 432

Aluminum 1600 48.00 1219 22.00 559 19.25 489 30.00 762 17.00 432
600 2000 48.00 1219 22.00 559 21.25 540 34.00 864 17.00 432
2500 60.00 1524 25.00 635 24.25 616 34.00 864 20.00 508
1200 60.00 1524 25.00 559 24.25 616 34.00 864 20.00 508
1600 60.00 1524 25.00 559 24.25 616 34.00 864 20.00 508
2000 60.00 1524 27.00 686 25.75 654 34.00 864 22.00 589
Copper 2500 60.00 1524 30.00 762 28.75 730 34.00 864 25.00 635
5000 and
15000 3200 60.00 1524 30.00 762 28.75 730 34.00 864 25.00 635
4000 60.00 1524 30.00 762 28.75 730 34.00 864 25.00 635
5000 60.00 1524 33.00 838 36.75 933 44.00 1118 28.00 711
6000 60.00 1524 33.00 838 36.75 933 44.00 1118 28.00 711
1200 60.00 1524 25.00 559 24.25 616 34.00 864 20.00 508
Aluminum 1800 60.00 1524 27.00 686 25.75 654 34.00 864 22.00 589
5000 and
15000 2000 60.00 1524 30.00 762 28.75 730 34.00 864 25.00 635
2500 60.00 1524 27.00 686 25.75 654 34.00 864 22.00 589
600 84.00 2134 37.00 940 45.88 1165 48.00 1219 33.00 838
1200 84.00 2134 37.00 940 45.88 1165 48.00 1219 33.00 838

Copper 1800 84.00 2134 37.00 940 45.88 1165 48.00 1219 33.00 838
38000 2000 84.00 2134 37.00 940 45.88 1165 48.00 1219 33.00 838
2500 84.00 2134 37.00 940 45.88 1165 48.00 1219 33.00 838
3200 84.00 2134 37.00 940 45.88 1165 48.00 1219 33.00 838
600 24.00 610 51.00 1295 37.00 940 24.00 610 23.00 584

Aluminum 1200 24.00 610 51.00 1295 37.00 940 24.00 610 23.00 584
38000 1800 24.00 610 51.00 1295 37.00 940 24.00 610 23.00 584
2000 24.00 610 51.00 1295 37.00 940 24.00 610 23.00 584
NOTES:
1. Performance values are calculated using a maximum conductor temperature rise of 149 °F (65 °C) and the full rated continuous current in a 68 °F (20 °C) ambient.
2. All data is based upon standard 3-phase totally enclosed non-ventilated aluminum enclosures.
3. The table information is based on standard Power-Zone bus construction. Other bus bar sizes and arrangements are available to meet the purchaser’s required
electrical characteristics and space considerations. Use of steel housing could require a derating of the busway. Consult the factory for more information.

146
06/2012 © 1986–2012 Schneider Electric