HVAC WORKS - SPAZE PLAZO, GURGAON

Date:- 24.12.2011

PUMP HEAD CALCULATION FOR SECONDARY CHILLED WATER PUMP

Secondary Chilled Water Pump(zone-2)

1 Total Piping Length Meter FT


a. Pipe Φ 200 mm = 15 49
b. Pipe Φ 150 mm = 43 141
c. Pipe Φ 125 mm = 75 246
d. Pipe Φ 80 mm = 28 92
e. Pipe Φ 50 mm = 43 141
f. Pipe Φ 25 mm = 35 115
g. Equivalent Length Pipe Φ 200 mm , 20% for Fitting = 3 10
h. Equivalent Length Pipe Φ 150 mm , 20% for Fitting = 8.6 28
i. Equivalent Length Pipe Φ 125 mm , 20% for Fitting = 15 49
j. Equivalent Length Pipe Φ 80 mm , 20% for Fitting = 5.6 18
k. Equivalent Length Pipe Φ 50 mm , 20% for Fitting = 8.6 28
l. Equivalent Length Pipe Φ 25 mm , 20% for Fitting = 7 23

2 Total Valve
For Pump
a. Equivalent Length For 1 Nos. Φ 150 mm Butterfly Valve = 7
b. Equivalent Length For 1 Nos. Φ 80 mm Butterfly Valve = 4
c. Equivalent Length For 1 Nos. Φ 50 mm Butterfly Valve = 2
d. Equivalent Length For 1 No. Φ 150 mm Y - Strainer = 110

3 Total Equivalent Length Including bends and fittings


a. Total Equivalent Length Pipe Φ 200 mm = 59
b. Total Equivalent Length Pipe Φ 150 mm = 169
c. Total Equivalent Length Pipe Φ 125 mm = 295
d. Total Equivalent Length Pipe Φ 80 mm = 110
e. Total Equivalent Length Pipe Φ 50 mm = 169
f. Total Equivalent Length Pipe Φ 25 mm = 138

4* Pressure Drop Across


a. Pipe Φ 200 mm , Valves & Fittings = 0.94
b. Pipe Φ 150 mm , Valves & Fittings = 5.42
c. Pipe Φ 125 mm , Valves & Fittings = 11.81
d. Pipe Φ 80 mm , Valves & Fittings = 2.87
e. Pipe Φ 50 mm , Valves & Fittings = 8.46
f. Pipe Φ 25 mm , Valves & Fittings = 8.95
38.45
5 Pressure Drop Across AHU's Coil = 18.00

6 Pressure Drop Across Control Valve = 18.00

7 Total Pressure Drop For Secondary Chilled Water Pump = 74.45

8 Considering 7.5 % overall Safety = 5.58

9 Overall Head = 24 80.03

Selected Head = 24 80.00

* For 2952 GPM Φ 350 mm pipe, ΔP = 1


* For 2550 GPM Φ 300 mm pipe, ΔP = 1.1
* For 1500 GPM Φ 250 mm pipe, ΔP = 1.1
* For 1000 GPM Φ 200 mm pipe, ΔP = 1.6
* For 700 GPM Φ 150 mm pipe, ΔP = 3.2
* For 480 GPM Φ 125 mm pipe, ΔP = 4
* For 300 GPM Φ 100 mm pipe, ΔP = 5
* For 150 GPM Φ 80 mm pipe, ΔP = 2.6
* For 80 GPM Φ 65 mm pipe, ΔP = 1.5
* For 50 GPM Φ 50 mm pipe, ΔP = 5
* For 16 GPM Φ 32 mm pipe, ΔP = 1.8
* For 10 GPM Φ 25 mm pipe, ΔP = 6.5

Conclusion : - The pump selected for 80 Ft. (24 Mtr.) as per BOQ is correct.
HVAC WORKS - SPAZE PLAZO, GURGAON

Date:- 24.12.2011

PUMP HEAD CALCULATION FOR SECONDARY CHILLED WATER PUMP

Secondary Chilled Water Pump(zone-1)

1 Total Piping Length Meter FT


a. Pipe Φ 250 mm = 152 499
b. Pipe Φ 200 mm = 62 203
c. Pipe Φ 150 mm = 37 121
d. Pipe Φ 125 mm = 12 39
e. Pipe Φ 100 mm = 12 39
f. Pipe Φ 80 mm = 12 39
g. Pipe Φ 50 mm = 20 66
h. Pipe Φ 32 mm = 14 46
i. Pipe Φ 25 mm = 14 46
j. Equivalent Length Pipe Φ 250 mm , 20% for Fitting = 30.4 100
k. Equivalent Length Pipe Φ 200 mm , 20% for Fitting = 12.4 41
l. Equivalent Length Pipe Φ 150 mm , 20% for Fitting = 7.4 24
m Equivalent Length Pipe Φ 125 mm , 20% for Fitting = 2.4 8
n Equivalent Length Pipe Φ 100 mm , 20% for Fitting = 2.4 8
o Equivalent Length Pipe Φ 80 mm , 20% for Fitting = 2.4 8
p Equivalent Length Pipe Φ 50 mm , 20% for Fitting = 4 13
q Equivalent Length Pipe Φ 32 mm , 20% for Fitting = 2.8 9
r Equivalent Length Pipe Φ 25 mm , 20% for Fitting = 2.8 9

2 Total Valve
For Pump
a Equivalent Length For 1 Nos. Φ 200 mm Butterfly Valve = 9
b Equivalent Length For 1 Nos. Φ 250 mm Butterfly Valve = 12
c. Equivalent Length For 1 No. Φ 200 mm Y - Strainer = 150
d For AHU's
e Equivalent Length For 1 Nos. Φ 50 mm Butterfly Valve = 2.3

3 Total Equivalent Length Including bends and fittings


a. Total Equivalent Length Pipe Φ 250 mm = 598
b. Total Equivalent Length Pipe Φ 200 mm = 244
c. Total Equivalent Length Pipe Φ 150 mm = 146
d. Total Equivalent Length Pipe Φ 125 mm = 47
e. Total Equivalent Length Pipe Φ 100 mm = 47
f. Total Equivalent Length Pipe Φ 80 mm = 47
g. Total Equivalent Length Pipe Φ 50 mm = 79
h. Total Equivalent Length Pipe Φ 32 mm = 55
i. Total Equivalent Length Pipe Φ 25 mm = 55
4* Pressure Drop Across
a. Pipe Φ 250 mm , Valves & Fittings = 6.58
b. Pipe Φ 200 mm , Valves & Fittings = 3.90
c. Pipe Φ 150 mm , Valves & Fittings = 4.66
d. Pipe Φ 125 mm , Valves & Fittings = 1.89
e. Pipe Φ 100 mm , Valves & Fittings = 2.36
f. Pipe Φ 80 mm , Valves & Fittings = 1.23
g. Pipe Φ 50 mm , Valves & Fittings = 3.94
h. Pipe Φ 32 mm , Valves & Fittings = 0.99
i. Pipe Φ 25 mm , Valves & Fittings = 3.58
29.13

5 Pressure Drop Across AHU's Coil 18.00

6 Pressure Drop Across Control Valve 18.00

8 Total Pressure Drop For Secondary Chilled Water Pump = 65.13

9 Considering 7.5 % overall Safety = 4.89

10 Overall Head = 21 70.02

Selected Head = 21 70.00

* For 2952 GPM Φ 350 mm pipe, ΔP = 1


* For 2550 GPM Φ 300 mm pipe, ΔP = 1.1
* For 1500 GPM Φ 250 mm pipe, ΔP = 1.1
* For 1000 GPM Φ 200 mm pipe, ΔP = 1.6
* For 700 GPM Φ 150 mm pipe, ΔP = 3.2
* For 480 GPM Φ 125 mm pipe, ΔP = 4
* For 300 GPM Φ 100 mm pipe, ΔP = 5
* For 150 GPM Φ 80 mm pipe, ΔP = 2.6
* For 80 GPM Φ 65 mm pipe, ΔP = 1.5
* For 50 GPM Φ 50 mm pipe, ΔP = 5
* For 16 GPM Φ 32 mm pipe, ΔP = 1.8
* For 10 GPM Φ 25 mm pipe, ΔP = 6.5

Conclusion : - The pump selected for 70 Ft. (21 Mtr.) as per BOQ is correct.
HVAC WORKS - SPAZE PLATINUM TOWER
Annexure - III
Date:- 13.01.2011

PUMP HEAD CALCULATION FOR CONDENSER WATER PUMP

Condenser Water Pump

1 Total Piping Length Meter FT


a. Pipe Φ 450 mm = 220 722
b. Pipe Φ 250 mm = 60 197
c. Equivalent Length Pipe Φ 450 mm , 20% for Fitting = 44 144
d. Equivalent Length Pipe Φ 250 mm , 30% for Fitting = 18 59

2 Total Valve
a. Equivalent Length For 6 Nos. Φ 250 mm Butterfly Valve = 72
b. Equivalent Length For 1 No. Φ 250 mm Check Valve = 100
c. Equivalent Length For 1 No. Φ 250 mm Y - Strainer = 190
d. Equivalent Length For 1 No. Φ 250 Balancing Valve = 280

3 Total Equivalent Length Including bends and fittings


a. Total Equivalent Length Pipe Φ 450 mm = 866
b. Total Equivalent Length Pipe Φ 250 mm = 898

4* Pressure Drop Across


a. Pipe Φ 350 mm , Valves & Fittings = 12.99
b. Pipe Φ 250 mm , Valves & Fittings = 22.45

Pressure drop across condensor 410 TR TRANE Make


5 Chiller = 29.52

Pressure Drop in Cooling Tower from sump to inlet


7 connection = 11.48

8 Total Pressure Drop For Condenser Water Pump = 76.43

9 Considering 7.5 % overall Safety = 5.73

10 Overall Head = 25 82.17

Selected Head = 27 88.56

* For 4920 GPM Φ 450 mm pipe, ΔP = 1.5


* For 1640 GPM Φ 250 mm pipe, ΔP = 2.5
Conclusion : - The pump selected for 88.56 Ft. (27 Mtr.) as per BOQ is correct.
HVAC WORKS - SPAZE PLATINUM TOWER
Annexure - I
Date:- 20.12.2011

PUMP HEAD CALCULATION FOR PRIMARY CHILLED WATER PUMP

Primary Chilled Water Pump

1 Total Piping Length Meter FT


a. Pipe Φ 350 mm = 30 98
b. Pipe Φ 200 mm = 15 49
c. Equivalent Length Pipe Φ 350 mm , 30% for Fitting = 9 30
d. Equivalent Length Pipe Φ 200 mm , 30% for Fitting = 4.5 15

2 Total Valve
a. Equivalent Length For 4 Nos. Φ 200 mm Butterfly Valve = 36
b. Equivalent Length For 1 No. Φ 200 mm Check Valve = 80
c. Equivalent Length For 1 No. Φ 200 mm Y - Strainer = 150
d. Equivalent Length For 1 No. Φ 200 Balancing Valve = 220

3 Total Equivalent Length Including bends and fittings


a. Total Equivalent Length Pipe Φ 350 mm = 128
b. Total Equivalent Length Pipe Φ 200 mm = 550

4* Pressure Drop Across


a. Pipe Φ 350 mm , Valves & Fittings = 1.28
b. Pipe Φ 250 mm , Valves & Fittings = 7.70

5 Pressure drop across Cooler 410 TR TRANE Make Chiller = 20.66

8 Total Pressure Drop For Primary Chilled Water Pump = 29.64

9 Considering 7.5 % overall Safety = 2.22

10 Overall Head = 10 31.86

Selected Head = 15 49.20

* For 2952 GPM Φ 350 mm pipe, ΔP = 1


* For 984 GPM Φ 200 mm pipe, ΔP = 1.4

Conclusion : - The pump selected for 49.20 Ft. (15 Mtr.) as per BOQ is correct.
HVAC WORKS - SPAZE PLAZO, GURGAON

Date:- 22.12.2011

PUMP HEAD CALCULATION FOR SECONDARY CHILLED WATER PUMP

Secondary Chilled Water Pump(zone-1)

1 Total Piping Length Meter FT


a. Pipe Φ 300 mm = 50 164
b. Pipe Φ 250 mm = 52 171
c. Pipe Φ 200 mm = 33 108
d. Pipe Φ 150 mm = 7 23
e. Pipe Φ 125 mm = 7 23
f. Pipe Φ 100 mm = 18 59
g. Pipe Φ 65 mm = 12 39
h. Equivalent Length Pipe Φ 300 mm , 20% for Fitting = 10.4 34
i. Equivalent Length Pipe Φ 250 mm , 20% for Fitting = 6.6 22
j. Equivalent Length Pipe Φ 200 mm , 20% for Fitting = 1.4 5
k. Equivalent Length Pipe Φ 150 mm , 20% for Fitting = 1.4 5
l. Equivalent Length Pipe Φ 125 mm , 20% for Fitting = 3.6 12
m Equivalent Length Pipe Φ 100 mm , 20% for Fitting = 2.4 8
n Equivalent Length Pipe Φ 65 mm , 20% for Fitting = 2.4 8

2 Total Valve
For Pump
a Equivalent Length For 1 Nos. Φ 250 mm Butterfly Valve = 12
b Equivalent Length For 1 No. Φ 200 mm Y - Strainer = 150
For AHU's
c Equivalent Length For 1 Nos. Φ 65 mm Butterfly Valve = 2.8

3 Total Equivalent Length Including bends and fittings


a. Total Equivalent Length Pipe Φ 300 mm = 205
b. Total Equivalent Length Pipe Φ 250 mm = 130
c. Total Equivalent Length Pipe Φ 200 mm = 28
d. Total Equivalent Length Pipe Φ 150 mm = 28
e. Total Equivalent Length Pipe Φ 125 mm = 71
f. Total Equivalent Length Pipe Φ 100 mm = 47
g. Total Equivalent Length Pipe Φ 65 mm = 47

4* Pressure Drop Across


a. Pipe Φ 300 mm , Valves & Fittings = 2.25
b. Pipe Φ 250 mm , Valves & Fittings = 1.43
c. Pipe Φ 200 mm , Valves & Fittings = 0.44
d. Pipe Φ 150 mm , Valves & Fittings = 0.83
e. Pipe Φ 125 mm , Valves & Fittings = 2.83
f. Pipe Φ 100 mm , Valves & Fittings = 2.36
g. Pipe Φ 65 mm , Valves & Fittings = 2.13
12.27

5 Pressure Drop Across AHU's Coil 18.00


6 Pressure Drop Across Control Valve 18.00

7 Total Pressure Drop For Secondary Chilled Water Pump = 48.27

8 Considering 7.5 % overall Safety = 3.62

9 Overall Head = 16 51.89

Selected Head = 21 70.00

* For 2952 GPM Φ 350 mm pipe, ΔP = 1


* For 2550 GPM Φ 300 mm pipe, ΔP = 1.1
* For 1500 GPM Φ 250 mm pipe, ΔP = 1.1
* For 1000 GPM Φ 200 mm pipe, ΔP = 1.6
* For 700 GPM Φ 150 mm pipe, ΔP = 3
* For 480 GPM Φ 125 mm pipe, ΔP = 4
* For 300 GPM Φ 100 mm pipe, ΔP = 5
* For 150 GPM Φ 80 mm pipe, ΔP = 2.6
* For 80 GPM Φ 65 mm pipe, ΔP = 1.5
* For 50 GPM Φ 50 mm pipe, ΔP = 5
* For 16 GPM Φ 32 mm pipe, ΔP = 1.8

Conclusion : - The pump selected for 70 Ft. (21 Mtr.) as per BOQ is correct.