Totally Enclosed where dust and grit are a maintenance problem a

totally enclosed unit is recommended. The unit is equipped with a


qasketed borosilicate glass drip cover, ceramic filter mounted in the
reflector. and an impact resistant full-gasketed glass door. Glass door
assemblV is equipped with safety cable.

Safety lO Lighting Systems - Two Tungsten Halogen Lighting


Systems are available for safety lighting in the event of momentary
power failures. The packages consist of a 250 watt tungsten halogen
lamp, a socket installed on a tube extending into the reflector down
from the power housing, control device, and all completely factory
wired- (Tungsten Halogen lamp operates off 120 volt tap on any
voltage ballast.) One 250 watt tungsten halogen lamp is standard.
lol System - Sylvania's exclusive low cost safety light system. ln- tot
stantly goes on with the resumption of power. providing 250 wattsof
Tungsten Halogen light (lO) until the l\4ercury/lvletalarc lamp re-
strikes.
IOD System -
Sylvania's electronic safety light system. lnstantly goes toD
on with resumption of power. Providing 250 watts of Tungsten
Halogen light {lQ) and operates until the Mercury/l\,4etalarc lamp is up
to approximately 50% of its normal brightness-

t,..-,
Hanger Hook - Hanger Hook and 2" nipple (%" IPS) included. HH
Hanger Hook with Cord - Hanger Hook and 2" nipple {%" IPS)
included. Factory wired cord set - 3 foot type SO,90'C wire, with HHC
locking twist-type cap. {SpeciJy voltage)

Hanger Loop - Hanger Loop and 2" nipple (7a" IPS) included. HL
Hanger Loop with Cord - Hanger Loop and 2" nipple (3/i' IPS)
included. Factory wired cord set 3 foot type SO,90'C wire, with HLC
locking twist-type cap. (Specify voltage)

Power Hook - Fixture cannot be removed or wiring compartment PHC


entered until plug is disconnected,

Fusing - The factory installed fuse holder and fuse are mounted in the
ballast housing or power hook. Fuses are accessible without removing F
cover plate.

103/46
Wire Guard used for the physical protection of the lamp. WG
Tennis Ball Wire Guard offers additional protection but has to be
removed for lamp servicinq,
TB

Glass Door Cover includes gasketed door assembly with latch and
safety cable. Lens is heat tempered impact resistant glass. GD

Ultra Low Blightness glass reflectors have interior surface of metal


protective shroud painted black for ultra low brightness. LB

INPUT VOLTAGE INPUT VOLTAGE


120 205 240 277 4AO '120 204 240 277 4aO

175 Watt Single Mercury - CWA 400 Watt Sinqle Metalarc


Operatinq Line Current* 1.8 1.10 .95 5
.8 .48 Operating Line Current* 4 2.3 2.O 1.1 1.0
lnput Power {Watts)t 2OO 2OO 2OO 200 200 lnput Power (Watts)l 455 455 455 455 455

175 Watt Sinqle Metalarc 400 Watt Dual l!4etalarc


Operatinq Line Current" 1-8 1.05 .9 .8 .45 Operating Line Current* 8.3 4.8 4.2 3.6 2.1
lnput Power (Watts)t 21O 210 210 210 210 lnput Power (Watts)t 910 910 910 910 910

250 Watt Single Mercury - CWA 400 Watt Sinqle Lumalux (H.P.S.)- REGULATED
Operating Line Current* 2-6 1.5 '1.3 1.1 .65 Operating Line Current* 4.2 2.4 2.1 1.8 1.05
lnput Power (Watts)t 285 285 285 245 245 lnput Power (Watts)l 480 480 480 480 480

250 Watt Sinqle Metalarc 1000 Watt Single lvlercury - CWA


Operating Line Current* 2.50 't.44 1.25 1.08.625 Operating Line Current* 9.8 5.6 4.9 4.2 2.4
lnput Power (Watts)t 292 292 292 292 292 lnputPower (Watts)t 1O15 1O75 1O15 1015 1015

400 Watt Single Metcury - CWA 1000 Watt Single Metalarc


Operating Line Current* 4. 2.3 2.O 1.1 1 Operating Line Current" 9.8 5.5 4.9 4.1 2.4
lnput Power (Watts)t 450 450 450 450 450 lnput Power (Watts)t 1085 1085 1085 1085 1085

400 Watt Dual Mercury


- CWA
I
Operating Line Current* 4.25 4. 3.4 2 *Starting current never exceeds operating current
lnput Power {Watts)t 880 BB0 BB0 BB0 880 tlncludes hallast loss

Outdoor Lighting and iligh lntensity lndoor Lighting