Sie sind auf Seite 1von 12

Designation U40BS U40BL U40C

Mechanical failing load kN 40 40 40


Mechanical residual strength kN 32 32 32
Diameter of the insulating part mm 175 175 175
Spacing mm 100 110 146
Nominal creepage distance mm 185 185 185
Ball and socket coupling mm 11 11 16C
Puncture voltage in insulating medium kV 100 100 100
50 Hz withstand voltage (dry) kV 55 55 55
50 Hz withstand voltage (wet) kV 33 33 33
Dry lightning impulse withstand voltage
kV 70/70 70/70 70/70
1.2/50+/- one unit
Radio interference voltage at 0.5 MHz dB/kV 86/25 86/25 86/25
Weight kg 1,7 1,7 2,0
Designation U70BS U70BL
Mechanical failing load kN 70 70
Mechanical residual strength kN 56 56
Diameter of the insulating part mm 255 255
Spacing mm 127 146
Nominal creepage distance mm 303 303
Ball and socket coupling mm 16 16
Puncture voltage in insulating medium kV 130 130
50 Hz withstand voltage (dry) kV 70 70
50 Hz withstand voltage (wet) kV 40 40
Dry lightning impulse withstand voltage kV 100/100 100/100
1.2/50+/- one unit
dB 60 60
kV 20 20
Radio interference voltage at 0.5 MHz
dB 86 86
kV 25 25
Weight kg 3,4 3,4
Designation U120BS U120BL
Mechanical failing load kN 120 120
Mechanical residual strength kN 96 96
Diameter of the insulating part mm 255 255
Spacing mm 146 170
Nominal creepage distance mm 320 320
Ball and socket coupling mm 16 16
Puncture voltage in insulating medium kV 130 130
50 Hz withstand voltage (dry) kV 70 75
50 Hz withstand voltage (wet) kV 40 40
Dry lightning impulse withstand voltage kV 100/100 100/100
1.2/50+/- one unit
dB 60 60
kV 20 20
Radio interference voltage at 0.5 MHz
dB 86 86
kV 30 30
Weight kg 3,9 3,9
Designation U160BS U160BL
Mechanical failing load kN 160 160
Mechanical residual strength kN 128 128
Diameter of the insulating part mm 280 280
Spacing mm 146 170
Nominal creepage distance mm 370 370
Ball and socket coupling mm 20 20
Puncture voltage in insulating medium kV 130 130
50 Hz withstand voltage (dry) kV 75 75
50 Hz withstand voltage (wet) kV 45 45
Dry lightning impulse withstand voltage kV 110/110 110/110
1.2/50+/- one unit
dB 60 60
kV 20 20
Radio interference voltage at 0.5 MHz
dB 86 86
kV 35 35
Weight kg 6,2 6,2
Low Frequency Mechanical
Impuls
Withstand Puncture Breaking
Leakage Withstand Weight
Type Voltage kV Voltage Load
Distance Voltage (kg)
kV Minimum
kV
daN
dry wet
Ps-12 230 60 45 100 120 1.000 1,84
Ps-17,5 265 70 53 120 130 1.000 2,52
Ps-24 360 80 65 140 150 1.200 3,65
Ps-28 420 90 75 160 150 1.200 5,5
Ps-36 540 100 86 180 160 1.300 7,5
Ps-38 630 110 100 200 180 1.300 10,8
Low Mechanical
Impuls
Frequency Breaking
Leakage Withstand Weight
Type Withstand Load
Distance Voltage (kg)
Voltage kV Minimum
kV
dry wet daN
LSP12L 250 NA 28 75 1250 5,8
LSP17.5L 350 NA 38 95 1250 6,4
LSP 24L 530 NA 50 125 800 8
LSP 24N 400 NA 50 125 1250 9,8
LSP 24L 530 NA 50 125 1250 10,5
LSP 38L 720 NA 70 170 800 11,5
LSP 38N 580 NA 70 170 1250 12
LSP 38L 720 NA 70 170 1250 13
LSP 52L 1140 NA 95 250 1250 20
Number
r1 & r2
Type of H (mm) h (mm) D (mm) d (mm)
(mm)
sheds

LSP12L 3 190 156 150 0 25


LSP17.5L 4 222 188 150 100 25
LSP 24L 5 305 268 150 100 25
LSP 24N 5 305 270 160 116 25
LSP 24L 5 305 270 170 116 25
LSP 38L 6 370 333 160 100 25
LSP 38N 6 370 335 170 116 25
LSP 38L 6 370 335 180 116 25
LSP 52L 10 510 475 200 130 25
Designation J 70 K J 70KP J 100 DP
Insulators part diameter mm 255 255 280
Spacing mm 127 127 170
Standard coupling size mm 16 A 16 A 16 A
Total leakage distance mm 290 292 300
Protected leakage distance mm 190 187 200
Split-pin R 16 A R 16 A R 16 A
Impuls Voltage 1,2/50µs
- 100 % Impuls Flashover Voltage - Positive kV 115 125 135
- 50% Impuls Flashover Voltage - Positive kV 105 117 130
- 0 % - Impuls Withstand Voltage - Positive kV 100 110 120
- 100 % Impuls Flashover Voltage - Negative kV 120 130 145
-50 % Impuls Flashover Voltage - Negative kV 115 122 136
-0 % Impuls Withstand Voltage - Negative kV 105 115 127
Low Frequency Flashover Voltage Dry kV 65 75 75
Low Withstand Flashover Voltage Dry kV 60 70 70
Low Frequency Flashover Voltage Wet kV 43 45 50
Low Withstand Flashover Voltage Wet kV 40 38 45
Low Frequency Puncture Voltage in Oil kV 120 110 110
Capacity pF 52 52 56
Radio influence level at 10 kV dB 18 16 15
Radio influence level at 14 kV dB 49 34 37
Radio influence level at 18 kV dB 53 54 52
Radio influence level at 22 kV dB 60 64 61
Test at 1000 kHz
Routine test Mechanical Load kN 28 28 40
Mehanical Breaking Load kN NA 70 100
Elektromehanical Breaking Load kN 70 70 100
Weight per insulator string unit kg 3,9 5,55 6,1
LP LP LP LP
Type of insulators š 75/28 š 75/18 š 75/22 š 60/5 š 60/7 š 75/14 š 85/22
60/5 60/7 75/14 85/22
Core insulators
mm 60 60 75 85 75 75 75 85 85 85 85
diameter
Number of sheds 5 7 14 22 30 18 22 14 18 22 24
Total length mm 380 490 860 1.270 1.260 1.240 1.270 935 1.275 1.270 1.330
Spacing between
mm 46 46 46 46 70 57 47,6 48 57 46 44,5
sheds
Overall sheds
mm 120 120 150 160 180 170 195 210 180 205 220
diameter
Distance between
mm 260 340 690 1.060 1.075 1.060 1.090 720 1.060 1.060 1.120
caps
Leakage distance mm 500 700 1.500 2.300 3.300 2.200 3.300 2.250 2.200 3.350 4.000
Medium breking
daN 5.500 6.700 12.000 15.000 10.000 10.000 10.000 14.000 14.000 14.000 14.000
extention Load
Routine test
daN 3.800 4.700 8.400 10.500 7.000 7.000 7.000 12.200 12.200 12.200 12.200
extention Load
Impuls withstand
kV 150 200 405 625 550 550 550 405 550 550 550
voltage
Low Frequency
withstand voltage, kV 70 90 185 285 230 230 230 185 230 230 230
wet
Weight, cca kg 7 8 20 26 42 28 38 36 39 50 52
Standard coupling
mm 11 16 16 20 16 16 16 20 20 20 20
size