New technology „Measuring SF6 Gas Quality“


„All in one“ measuring device with integrated gas return system

www.dilo-gmbh.com
Control of SF6 quality

Why are measurements necessary?

 SF6 gas quality must be controlled acc. to EC regulation 842/2006 on fluorinated


greenhouse gases and the provisions regarding the use of chemicals with
respect to climate protection.
 Before the circuit breaker is serviced, gas quality must be known.
 Measuring concentration of decomposition products reflects operational history of
the circuit breaker, e.g. electrical discharges.
 For decision on recycling, re-use or disposal of SF6 the quality must be
determined.

© February 2013 Introduction Page 2


Limit values acc. to IEC 60480

-36 °C
High voltage

-23 °C
Medium voltage

© February 2013 Introduction Page 3


Measuring SF6 quality on site

Measuring major parameters

 SF6 gas must always exhibit the proper quality.


 Humid or toxic and corrosive decomposition
products in the switchgear may severely impair
insulation strength of the gas.

Major quality criteria of SF6 gas in the circuit


breaker:
 Purity (percentage)
 Moisture
 Decomposition products

© February 2013 Introduction Page 4


SF6 Multi-Analyser with gas return
system

Up to six measurements in one operation:


 SF6 concentration (%)
 Moisture concentration
 SO2 concentration (ppmv)
 Options:
 HF concentration (ppmv) / four-in-one device
 HF, H2S and CO concentration (ppmv) /
six-in-one device

Gas return system:


 Collection and storage of the measuring gas in
an internal vessel
 After measurement, the stored measuring gas is
pumped back automatically into the gas
compartment.

© February 2013 Main features Page 5


SF6 Multi-Analyser with gas return
system

Main features:

 Indication of SF6 concentration in volume percentage

 Dew point indication in °C, °F, ppmv, ppmm, referred to


atmospheric or input pressure

 Indication of SO2, HF, H2S and CO concentration in ppmv

 Indication of input pressure in bar


(pa or pe), psi, kPa, MPa (max. input pressure pe = 9 bar)

 Gas return system

© February 2013 Main features Page 6


SF6 Multi-Analyser with gas return
system

Main features:

 Easy operation via 5.7“ colour touch screen


 Measuring results can be saved indicating
the name of measuring point, date and time
 Data storing of 100 measuring results which
can be transferred to a PC or USB stick
 Self-closing connecting couplings
 Automatic identification of residual lifetime of
the SO2 sensor
 Very easy handling by exchange of modules
for calibration
 Menu navigation in German, English, French,
Spanish, Italian, Czech, Portuguese, Czech, Dimensions of the device 3-038R-R:
Polish and Chinese language Width: 500 mm Depth: 625 mm
Height: 297 mm Weight: 33 kg

© February 2013 Main features Page 7


SF6 Multi-Analyser with gas return
system

Front view

USB connection 5.7“ colour touch


screen
Power supply
with fuse

Fan Hose connections


DN8 / DN20
Gas inlet

© February 2013 Functions Page 8


SF6 Multi-Analyser with gas return
system

Option Menu

When pressing the key the following page appears:

Select desired language

Select desired pressure unit

Select N2 or CF4 carrying gas

Select moisture unit

Set date and time

© February 2013 Functions Page 9


SF6 Multi-Analyser with gas return
system

Configuration Menu

When pressing the key the following page appears:

Serial number Software version

Automatic pumping
on/off

Manual start of back


pumping when automatic
mode has been deactivated

© February 2013 Functions Page 10


SF6 Multi-Analyser with gas return system

Service Menu / Configuration

When pressing the key, the following page appears:

Operating hours / Operating hours


since the last maintenance /
maintenance interval

Configuration menu

Status indication

© February 2013 Functions Page 11


SF6 Multi-Analyser with gas return system

Special functions

© February 2013 Functions Page 12


SF6 Multi-Analyser with gas return
system

Starting the measurement:


Connection to the gas compartment

© February 2013 Functions Page 13


SF6 Multi-Analyser with gas return system

Starting the measurement

Select hose length (6 m or 12 m) -


important for purging time of hose.

After completion of the necessary settings,


the measurement can be started by
pressing the “Start/Stop“ key.

After connection of the measuring device


to the gas compartment the current
pressure is indicated.

© February 2013 Functions Page 14


SF6 Multi-Analyser with gas return system

Rinsing hose

After pressing the start / stop key the following page appears:

Current process

Current measurement
progress in %

Switch to current values


during measurement

Gas compartment pressure

© February 2013 Functions Page 15


SF6 Multi-Analyser with gas return system

SO2 measurement (if installed)

After pressing the start/stop key the following page appears:

Ongoing process

Measuring progress in %

Switch to current values


during measurement

Gas compartment pressure

© February 2013 Functions Page 16


SF6 Multi-Analyser with gas return system

Measured values

When pressing the key during measurement, the page with the current measured
values appears:

After the end of the measuring


time it is automatically switched
over to the “Measuring results”
window.

© February 2013 Functions Page 17


SF6 Multi-Analyser with gas return system

SO2 limit value exceeded (if sensor installed)

Limit value can be set via


„configuration“ menue.
(Factory setting: CIGRE value 12 ppmv)

© February 2013 Functions Page 18


SF6 Multi-Analyser with gas return system

Measured values

When pressing the key during measurement, the page with the
current measured values appears:

After the end of the measuring time it


is automatically switched over to the
“Measuring results” window.

© February 2013 Functions Page 19


SF6 Multi-Analyser with gas return system

Pumping measuring gas back

 When the measurement is completed, the result page shows up automatically


 The ongoing process „Pumping measuring gas in compartment“ is activated

Return of measured
gas

© February 2013 Functions Page 20


SF6 Multi-Analyser with gas return system

Limit values

In case the values fall below or exceed the limit values entered on the
“Configuration“ window, the following message appears:

© February 2013 Functions Page 21


SF6 Multi-Analyser with gas return system

Storing measured values

When the measurement is


completed, the name for the
measurement can be entered by
pressing XYZ123

© February 2013 Functions Page 22


SF6 Multi-Analyser with gas return system

Enter name for measurement

Enter the name and press the „RET“ key

© February 2013 Functions Page 23


SF6 Multi-Analyser with gas return system

Storage of measurement

Double-click the key


for data storage

© February 2013 Functions Page 24


SF6 Multi-Analyser with gas return system

Stored measured values

When pressing the key the following page appears:

Measured values

Transfer all measured values


to a USB stick

Delete all measuring data or only


one on the display

© February 2013 Functions Page 25


SF6 Multi-Analyser with gas return system

Transfer of measured values

When pressing the key all values can be transferred to


USB stick.

After having completed the data transmission a message appears after about 2 seconds.

© February 2013 Functions Page 26


SF6 Multi-Analyser with gas return system

Storage of measuring values

When pressing the key the following page appears:

Measured values

Transfer all measured values


to a USB stick

Delete all measuring data or only one


on the display

© February 2013 Functions Page 27


SF6 Multi-Analyser – data transfer

Customer Server
SF6 Multi-Analyser UMTS Router
IP-Adress

Transfer of measuring results

© February 2013 Data transfer Page 28