Sie sind auf Seite 1von 17

Science of the Total Environment 637–638 (2018) 1081–1097

Contents lists available at ScienceDirect

Science of the Total Environment

journal homepage: www.elsevier.com/locate/scitotenv

Investigation of sub-slab pressure field extension in specified granular fill


materials incorporating a sump-based soil depressurisation system for
radon mitigation
Le Chi Hung a,b,c, Jamie Goggins b,c,⁎, Marta Fuente a,b,c, Mark Foley a
a
School of Physics, National University of Ireland Galway, Ireland
b
Civil Engineering, College of Engineering & Informatics, National University of Ireland Galway, Ireland
c
Centre for Marine and Renewable Energy (MaREI), Ryan Institute, National University of Ireland Galway, Galway, Ireland

H I G H L I G H T S G R A P H I C A L A B S T R A C T

• The subslab pressure field extension


(SPFE) was examined by CFD simula-
tions.
• The SPFE is critical for a soil
depressurisation (SD) system.
• CFD simulations were validated to be
suitable for design of the SD systems.
• Air permeabilities of soil and granular
fill material strongly affect on the SPFE.
• The SPFE varies with wall cracks, slab
airtightness and thickness of fill
material.

a r t i c l e i n f o a b s t r a c t

Article history: Design of bearing layers (granular fill material layers) is important for a house with a soil depressurisation (SD)
Received 9 March 2018 system for indoor radon mitigation. These layers should not only satisfy the bearing capacity and serviceability
Received in revised form 29 April 2018 criteria but should also provide a sufficient degree of the air permeability for the system. Previous studies have
Accepted 30 April 2018
shown that a critical parameter for a SD system is the sub-slab pressure field extension in the bearing layers,
Available online 14 May 2018
but this issue has not been systematically investigated. A series of two-dimensional computational fluid dynamic
Editor: D. Barcelo simulations that investigate the behaviour of the sub-slab pressure field extension developed in a SD system is
presented in this paper. The SD system considered in this paper consists of a granular fill material layer and a
Keywords: radon sump. The granular fill materials are ‘T1 Struc’ and ‘T2 Perm’, which are standard materials for building
Radon in the Republic of Ireland. Different conditions, which might be encountered in a practical situation, were exam-
Granular fill materials ined. The results show that the air permeability and thickness of the granular fill materials are the two key factors
Building construction which affect the sub slab pressure field extension (SPFE) significantly. Furthermore, the air permeability of native
Soil depressurisation system soil is found to be a fundamental factor for the SPFE so that it should be well understood when designing a SD
CFD simulations
system. Therefore, these factors should be considered sufficiently in each practical situation. Finally, a significant
improvement of the pressure field extension can be achieved by ensuring air tightness of the SD system.
© 2018 Elsevier B.V. All rights reserved.

1. Introduction

⁎ Corresponding author at: Civil Engineering, College of Engineering & Informatics,


Radon (222Rn) is a product of the decay chain of uranium (238U)
National University of Ireland Galway, Ireland. present in soils and rocks. It is a colourless, odourless, tasteless gas
E-mail address: jamie.goggins@nuigalway.ie (J. Goggins). which has been identified as a human carcinogen by the World Health

https://doi.org/10.1016/j.scitotenv.2018.04.401
0048-9697/© 2018 Elsevier B.V. All rights reserved.
1082 L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097

pressure [i.e., the suction pressure developed in the granular fill (per-
meable) layer beneath the concrete slab], thus reversing the entry
path of radon from soil into the building, as well as extracting gas
trapped in the granular fill layer (Gadgil et al., 1991; BRE, 1998;
Andersen, 2001; Jiránek and Svoboda, 2007; Abdelouhab et al., 2010;
Vazquez et al., 2011; Jiránek, 2014). From this assumption, it is inferred
that the subslab pressure field extension (SPFE) is the most critical issue
that affects the effectiveness of a SD system.
Previous studies have suggested that various parameters would in-
fluence the effectiveness of a SD system significantly. These parameters

pipe
Wall crack
Ground surface are the air permeability (kah) of granular fill material, the air permeabil-
Radon sump ity of native soil (kas), effective particle size (def) of the granular fill ma-
Sand layer terial, width of wall crack (wcrack), radon sump size, airtightness of the
Concrete slab Fan box
slab, moisture content and atmospheric conditions (Gadgil et al.,
1991; Turk et al., 1991; Bonnefous et al., 1992; Gadgil et al., 1994; BRE,
1998; Andersen, 2001; Johner and Surbeck, 2001; Jiránek and
Granular fill material Svoboda, 2007; Jelle, 2012; Baeza et al., 2018). In addition to the degree
Footing of permeability of granular fill materials required for effective perfor-
Native soil mance of SD systems, these materials act as bearing layers for buildings
are thus required to have adequate bearing capacity, as well as meet
certain serviceability criteria (NSAI, 2016a). This work investigates the
effects of the above parameters on the SPFE of the SD systems. Two di-
mensional (2D) computational fluid dynamic (CFD) simulations are
adapted. Various parameters, such as kah, kas, def, wcrack, sump width
Fig. 1. A schematic diagram of a house with a SD system.
(wsump), sump depth (dsump), thickness of the granular fill layers (t),
and airtightness of the slab, are considered.
Organisation (WHO), the International Agency for Research on Cancer
(IARC) and the U.S. Environmental Protection Agency (EPA) (ICRP, 2. Computational fluid dynamic simulations
2010; Pacheco-Torgal, 2012; Yarmoshenko et al., 2016). Previous stud-
ies have proven that the outdoor radon concentration globally is be- CFD simulations could be a useful tool in the design of a SD system. It
tween 5 Bq/m3–15 Bq/m3 which does not pose a health risk (Gunning allows engineers and researchers to understand the working mecha-
et al., 2014; WHO, 2017). However, a high indoor radon concentration, nism of the system, thus enabling them to design without conducting
i.e. over 200 Bq/m3, will significantly impact the indoor air quality and is trial experimental tests. The commercial CFD package Ansys FLUENT
a cause of lung cancer through the decay of radon's short−lived daugh- version 15.0 (Ansys, 2013) was used in this study. The SD systems
ter products resulting pulmonary cell DNA damage (Pacheco-Torgal, were adopted following the configuration defined in the Irish standard
2012; Lopez-Abente et al., 2018). I.S.888:2016 (NSAI, 2016a) for radon mitigation. An urban family
To minimise the indoor radon concentration, various techniques house of 64 m2 (8 m × 8 m) was simulated. Typical numerical mesh of
might be considered for buildings. These techniques include the active the house is shown in Fig. 2. The SD system includes a 15 cm thick con-
and passive soil depressurisation (SD), sealing of the slab, membranes, crete slab, a 50 mm thick sand layer above granular fill layers. Details of
ventilation of unoccupied spaces, and ventilation of occupied spaces. granular materials will be discussed in the next section.
However, the active and passive SD techniques have proven to be the All simulations were performed under transient analysis obeying the
most effective techniques for indoor radon prevention and mitigation Reynolds−Averaged Navier−Stokes (RANS) realizable k–ω turbulence
(Gadgil et al., 1991; Bonnefous et al., 1992; Gadgil et al., 1994; Rydock model. However, all results were obtained once steady state conditions
and Skaret, 2002; WHO, 2009; Abdelouhab et al., 2010). were reached. The k–ω turbulence model was adopted because it pro-
A SD system can be built by a granular fill material layer with the use vides more accuracy in comparison with the other models, e.g. Laminar,
of various suction components such as sumps, wells or perforated pipes k–ε, and Reynolds Stress models (Ansys, 2014). The quadrilateral ele-
(Jiránek, 2014). However, the SD system that was the subject of this ment type was applied for meshing. Numerical mesh was generated
study consists mainly of a granular fill material layer and a radon by applying a maximum size of 5 mm. However, in the crack area
sump (Fig. 1). The principle of the SD system is to decrease the subslab where its domain size is changed with the change of wcrack, the mesh

Wall crack position


BH
Ground surface Concrete slab
Concrete slab
Observation line 1 Granular material layer Sand layer

Observation line 2 Sump


Granular
Native soil material layer
(a) (b)
Fig. 2. (a) Typical numerical domain geometry of a SD system. (b) A typical mesh with 5 mm mesh size (extracted at the sump area).
L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097 1083

Table 1 were conducted to determine the optimal values for BV and BH and
Boundary conditions for the CFD simulations. the numerical mesh so that they do not affect the final results. The opti-
Boundary Type Momentum mal BV and BH values were found to be 2 and 3.5 times the total thick-
Sump Outlet Prelative = −100 Pa
ness t, i.e. t = 0.9 m, of the granular fill layer.
Wall crack (wcrack N 0) Inlet (or opening) Prelative = 0 Pa
Imperfectly sealed slab Inlet (or opening) Prelative = 0 Pa
Ground surface Inlet (or opening) Prelative = 0 Pa 3. Parametric study and material properties
Wall crack (wcrack = 0) Wall No slip wall
Perfectly sealed slab Wall No slip wall
Bottom of the domain Wall No slip wall Three types of granular fill materials to form the permeable layer of
Left side of the domain Wall No slip wall the SD systems are investigated. They are the ‘T1 Struc’, the ‘T2 Perm’
Note: Prelative is the pressure relative to the reference pressure at 102300 Pa (1.01 atm).
and the ‘Hybrid’ materials, as defined in the Irish standard
I.S.888:2016 (NSAI, 2016a), as shown in Fig. 3. The ‘Hybrid’ material is
made by layering the ‘T1 Struc’ and the ‘T2 Perm’ materials. The thick-
size is remotely divided to be smaller than 5 mm. For example, a crack ness t of the granular fill layers is varied in this study and will be de-
has wcrack = 7.5 mm, the mesh size in this crack area is divided at scribed in the next sections. The Irish standard I.S. 888:2016 (NSAI,
3.75 mm. If a crack has a width of 1 mm then the mesh size on this 2016a) states that maximum thickness of a permeable layer in a SD sys-
crack area is defined as 1 mm. This procedure is applied identically for tem is 0.9 m. The footing dimensions were simulated at 0.5 m width and
all simulations conducted in this study. To ensure a numerical con- 0.9 m depth from the ground surface.
verged solution, the residual convergence criterion for velocity was set The wall crack and airtightness of the concrete slab of a house affect
to be 10−4, and the scaled energy residual was 10−6 in all simulations the effectiveness of its SD system significantly. A wall crack might de-
(Ansys, 2014). velop along the joint of a wall and a slab. In this study, the width of
By applying symmetric conditions, only half of the entire system was the wall crack (wcrack) was assumed to vary at 0 mm, 0.5 mm, 1 mm,
simulated (Fig. 2). The bottom and the left side of the system were fixed 1.5 mm, 2 mm, 3 mm, 5 mm, 7.5 mm, 10 mm, and 20 mm. The airtight-
with the wall boundary conditions, i.e. no air flow is allowed. The open- ness could be defined as the perfectly and imperfectly sealed labs. A per-
ing boundary condition is applied at the ground surface. This boundary fect seal could exist in a newly built house with good quality
condition is also applied for the wall crack and the imperfectly sealed construction details between the concrete slab and wall. For example,
slab. Suction pressure, Psump, was applied at the side and the bottom a perfect seal could be formed by using proper radon membranes
of the sump. All boundary conditions applied in CFD simulations are under the slab with good construction practice. This perfect seal could
summarised in Table 1. BV and BH indicated in Fig. 2 are the distances prevent soil gas from entering the house through the slab. However, a
to the vertical and horizontal boundaries measured from the bottom perfectly sealed slab might not last for the full life-time of the building.
and the side of the footing, respectively. Preliminary CFD simulations For example, cracks might develop on the surface of an old slab, and

(a) (b)
Fig. 3. Photos of (a) ‘T1 Struc’ and (b) ‘T2 Perm’ granular fill materials. ‘T1 Struc’ and ‘T2 Perm’ are formed by the crushed stone. ‘T1 Struc’ is standardised with grade varied from 0–32 mm.
‘T2 Perm’ is standardised with grade of 4/40 mm according to NSAI (2016b).

124 mm

Fig. 4. Example of two common sump types in used for SD systems in Ireland.
1084 L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097

Fig. 5. Particle size distribution test results of Irish ‘T1 Struc’ and ‘T2 Perm’ granular fill materials. Lower and upper bounds for ‘T1 Struc’ and ‘T2 Perm’ materials are standardised in NSAI
(2016b) [adopted from Hung et al., 2018].

radon membranes can deteriorate with time, thus allowing soil gas to with dsump = 0.124 m, as indicated in Fig. 4 (b). For simplicity in the nu-
pass through. In this case, an imperfectly sealed slab is expected. merical simulations, a square sump with a wsump value of 0.27 m that
Fig. 4 shows typical radon sumps which have been widely used in has an equivalent sump area and dsump = 0.124 mm was utilised, unless
the Republic of Ireland for the SD systems. These sumps have either per- stated otherwise. The pressure Psump was set at −100 Pa for all cases.
forated sides [sump type 1, shown in Fig. 4 (a)] or are completely open The sub-slab pressures (P) were normalised by this Psump, thus the
at the bottom [sump type 2, shown in Fig. 4 (b)]. Based on the manufac- final results do not affect by Psump. This assumption was also confirmed
turer specifications, each sump has a cross−sectional area of 0.072 m2 by performing initial simulations at different Psump to make sure this

Fig. 6. Compaction test results for ‘T1 Struc’ and ‘T2 Perm’ granular fill materials [adopted from Hung et al. (2018)].

5m

2.4 m
0.5 m
Se
ct
io
n
#
1

2m 0.77 m
Section # 2 Sump #2
5m
Sump #1
drilled hole
1m 1m

(a) Test hole locations (b) Photo of the house (c) Electric fan on pipe
Fig. 7. Test configuration and photos of the Pilot house in Spain (not to scale).
L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097 1085

Fig. 8. Comparison between experimental measurements and CFD simulations.

assumption is correct. Psump was applied simultaneously at the bottom following equations to represent the pressure loss:
and the side of the sump, unless stated otherwise.
We have previously reported that the kah, porosity (nh), and def are ΔP μ  V C  G  V
three key parameters of granular material required for the design of a ¼ þ ð1Þ
L kah 2
SD system (Hung et al., 2018). Ergun (1952) found that the pressure
loss of fluid flow through a column a granular material is mainly
governed by the kinetic and viscous energy losses, which are dirrectly 1 ð1−nh Þ2
¼ 150  2
ð2Þ
related to these three parameters. Ergun (1952) suggested the kah n3  d h ef

Fig. 9. Effect of a crack on the SPFE with the ‘T2 Perm’ granular fill material layer at observation lines OL1 (at the sump level) and OL2 (at the footing level) for two thicknesses of ‘T2 Perm’
granular fill material (i.e. tT2Perm = 0.2 m and 0.9 m) with a perfectly sealed slab.
1086 L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097

3:5  ð1−nh Þ for 1% ≤ mnc ≤ 4.5%,where mnc is the compaction moisture content of the
C¼ ð3Þ
n3h  def ‘T1 Struc’ material. The mnc values for ‘T1 Struc’ was varied at 1%, 1.5%,
2%, 2.5%, 3%, 3.5%, 4% and 4.5%. mnc of the ‘T2 Perm’ was not considered
where ΔP is the pressure drop, L is the flow length, μ is the dynamic vis- in this study as the trend of its compaction degree is unclear, as shown
cosity of air, G is the mass flow rate, V is the air flow velocity, C is the in- in Fig. 6 (b).
ertial loss coefficient and is a parameter required for the CFD
simulations in this study. nhðT1StrucÞ ¼ 0:23 ð5aÞ
The properties of the ‘T1 Struc’ and ‘T2 Perm’ materials used in this
when mnc ≤ 2%
study were adopted from experimental tests (Hung et al., 2018). Test re-
sults for the particle size distributions and compaction tests of these ma-
nhðT1StrucÞ ¼ 0:28−0:03mnc ð5bÞ
terials are shown in Figs. 5 and 6, respectively. From the test results, the
‘T1 Struc’ and ‘T2 Perm’ materials could be classified as the well-graded when 2% b mnc ≤ 6%
and poorly graded granular materials, respectively. Previous studies
have shown that the permeable layer of a SD system should be formed def ðT1StrucÞ ¼ 1:56 e−0:83mnc ð6Þ
by a poorly graded granular material (US-EPA, 1993; BRE, 1998). There-
fore, it would be expected that the ‘T1 Struc’ fill layer would induce a when 1% ≤ mnc ≤ 4:5%
poor SPFE in a SD system in comparison with that formed by the ‘T2
Perm’ material. The kah(T2Perm) and nh(T2Perm) values of the ‘T2 Perm’ material were
According to NSAI (2016b), the ‘T1 Struc’ granular fill material has a fixed at 22.5 × 10−9 m2 and 0.37 respectively for all simulations,
wide range of particle size between 0 and 32 mm (formed by crushed whereas its def(T2Perm) value was taken as the d50 value on its grading
stone) or 0–40 mm (formed by gravel) and is classified as a well- curve [Fig. 5 (b)]. The air permeability of soil kas was set to be kas =
compacted material. The ‘T2 Perm’ has a grade of 4 mm–40 mm, and 10−4 × kah(T2Perm) for all simulations, unless stated otherwise. The po-
is relatively difficult to compact in comparison with the ‘T1 Struc’ mate- rosity of soil was fixed at 0.3. The air used in CFD simulations has a den-
rial. The ‘T1 Struc’ and ‘T2 Perm’ materials reported in the work of Hung sity of 1.225 kg/m3 with a viscosity of 1.7894 × 10−5 kg/(m·s).
et al. (2018) were formed by crushed stone. The following equations Abbas et al. (1999) found that the air permeability of 28 − day aged
were applied to determine the input parameters for the ‘T1 Struc’ mate- concrete could vary from 0.2 × 10−16 m2 to 0.8 × 10−16 m2. Diallo et al.
rial as follows: (2015) reported a measurement of the air permeability of the concrete
slab from the MARIA house in France. They found that the effective air
kahðT1StrucÞ ¼ 20  10−9 e−1:25mnc ð4Þ permeability of the concrete slab was 1.69 × 10−10 m2. Therefore, the

a) wcrack = 0.5 mm

b) wcrack = 20 mm

Fig. 10. Example of the SPFE contours for tT2Perm = 0.2 m with a perfectly sealed slab.
L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097 1087

air permeability of the concrete slab was set at 0.5 × 10−16 m2 and 1.69 shown in Fig. 8(a). Each measurement was conducted at least three
× 10−10 m2 for perfectly and imperfectly sealed slabs, respectively. times (approx. 1 h/measurement). As shown in Fig. 8(a), the SPFEs are
homogenous with the pressure varied in between 19.5 Pa to 20.5 Pa.
This finding suggests that the slab of the pilot house was well treated
4. Validation of the CFD simulation
to minimise crack developed on the slab with a sufficient permeable
layer built under the slab.
The reliability and suitability of the CFD simulations should be con-
To validate the CFD simulations with the measurement of the Span-
firmed. Therefore, the accuracy of the CFD simulations in this study
ish Pilot house, 2D CFD simulations were conducted. Boundary condi-
were validated by comparing the CFD results with experimental test re-
tions and configurations were defined as discussed above. The kas of
sults from a Pilot house in Spain (Vazquez et al., 2011) and from the test
soil was set at 10−12 m2 (Vazquez, 2017). Comparisons between the
results from the MARIA house reported by Abdelouhab et al. (2010) and
CFD simulation results and those of the measurement are presented in
Abdelouhab (2011).
Fig. 8 (a). It is found that the CFD simulations agree with the test data
with an average error of ±2%.
4.1. Case I: Spanish pilot house measurements

SPFE measurements were conducted in the Pilot house in Spain 4.2. Case II: French MARIA house
(Vazquez et al., 2011). The SD system of the house consists of a 1 m
× 1 m sump, with 15 cm of granular fill material and 10 cm of the con- Abdelouhab et al. (2010) and Abdelouhab (2011) reported experi-
crete slab. The sump was placed at the centre of the house. The area of mental measurements for the SPFE in the MARIA house in France. The
the slab is 25 m2, as shown in Fig. 7 (a). The kah value of 9 × 10−8 m2 house had a floor area of 81 m2 with a 40-cm thick gravel layer. Diallo
of the granular fill material was obtained in the laboratory. To generate et al. (2015) reported that this gravel had a kah value of 10−7 m2 and
sump pressure, a 30-Watt electric fan was connected to the pipe that the soil beneath the house had a kas value of 2.61 × 10−13 m2. All bound-
goes from the sump centre as shown in Fig. 7 (c). A highly accurate pres- ary conditions for CFD simulations were defined following Abdelouhab
sure sensor with accuracy of ±0.25% (Honeywell TruStability™, Golden et al. (2010) and Abdelouhab (2011). Comparison between CFD simula-
Valley, MN, USA) was used to measure the SPFE. tion results and the test results is shown in Fig. 8(b). An average error of
Measurements were performed at seven different holes drilled ±5.6% was found between the CFD simulations and the measurements.
through the concrete slab at various distances from the sump centre Based on the above comparisons, it can be concluded that the CFD
[sections #1 and #2 in Fig. 7 (a)]. Interval distance between each hole simulations are reliable. Therefore, the CFD simulations could be prop-
is 0.5 m. The maximum fan speed was activated, and an average sump erly used to analyse the pressure field extension behaviour of a SD
pressure of approximately −20.5 Pa was recorded, and SPFEs are system.

Fig. 11. Effect of a crack on the SPFE with the ‘T2 Perm’ granular fill material layer (imperfectly sealed slab) at observation lines OL1 (at the sump level) and OL2 (at the footing level) for two
thicknesses of ‘T2 Perm’ granular fill material (i.e. tT2Perm = 0.2 m and 0.9 m) with an imperfectly sealed slab.
1088 L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097

5. Numerical results and discussions distance of 4 m from the sump centre, P/Psump = 1 for wcrack = 0 mm
and P/Psump = 0.6 for wcrack = 1.0 mm, as shown in Fig. 9 (a). For
All SPFE results presented in this work were monitored at the obser- tT2Perm = 0.9 m, this differential rate is smaller, as shown in Fig. 9
vation lines OL1 (at the sump level) and OL2 (at the footing level). These (c, d). The reduction of the SPFE occurs because the air flow resis-
observation lines have been defined in Fig. 2. tance decreases through the wall crack when the crack becomes
wider, i.e. a larger amount of air enters the granular fill layer, thus re-
5.1. Effects of a wall crack on the SPFE ducing the pressure from the crack side to the sump side, as shown in
Fig. 10. Figs. 11 and 12 show the SPFE for the case of a imperfectly
This section presents the effect of a wall crack on the SPFE of the SD sealed slab. A similar explanation can be applied as discussed
systems. The results presented in this section were investigated at dif- above. The pressures for the imperfectly sealed slab are smaller
ferent wcrack values, as mentioned previously. The ‘T2 Perm’ and the ‘Hy- than that of the perfectly sealed slab, as expected. In addition, as
brid’ granular materials to form the permeable fill layers of the SD can be seen from these figures, the SD system with tT2Perm = 0.9 m
systems were considered. The thickness of these fill layers were set induces higher SPFEs in comparison with those for tT2Perm = 0.2 m.
in accordance with the standard I.S. 888: 2016 (NSAI, 2016a). For This finding suggests that the thicker the ‘T2 Perm’ layer, the better
the ‘T2 Perm’ fill layer, the thickness t was set at two different values, the SPFE. This observation will be examined further in Section 5.4.
i.e. tT2Perm = 0.2 m and 0.9 m, whereas that for the ‘Hybrid’ fill layer
the thickness of each sub-layer are t T2Perm = 0.2 m and t T1Struc =
0.7 m for the ‘T2 Perm’ and the ‘T1 Struc’, respectively. The effects 5.1.2. SD system with ‘Hybrid’ granular material
of varying tT2Perm and tT1Struc will be further discussed in Section 5.4. Fig. 13 shows the SPFEs for the SD systems with the ‘Hybrid’ granular
Both perfectly and imperfectly sealed slabs were simulated. fill layers (tT2Perm = 0.2 m and tT1Struc = 0.7 m) with perfectly and im-
perfectly sealed slabs. The properties of the ‘T1 Struc’ were obtained
5.1.1. SD system with ‘T2 Perm’ material fill layers using Eqs. (4)–(6). The compaction moisture content mnc was consid-
Fig. 9 presents the SPFEs of the SD systems using the ‘T2 Perm’ gran- ered at 4%. The same boundary conditions applied in Section 5.1.1 are
ular fill material with thicknesses of tT2Perm = 0.2 m [Fig. 9 (a, b)] and also applied here. As shown in Fig. 13, similar findings were observed
0.9 m [Fig. 9 (c, d)] for the case of a perfectly sealed slab. For tT2Perm = for the ‘Hybrid’ material in comparison with that for the case of
0.2 m, the SPFEs decrease dramatically when wcrack varied from tT2Perm = 0.2 m presented in Section 5.1.1. This similarity could be
0.5 mm to 1.5 mm, and the differential rate of the normalised pressure a result of a low permeability degree of the ‘T1 Struc’ material, as it
(P/Psump) reduces at wcrack N 1.5 mm. For example, at the horizontal does not provide a good SPFE at its low kah value at mnc = 4%.

a) wcrack = 0.5 mm

b) wcrack = 20 mm

Fig. 12. Example of the SPFE contours for the ‘T2 Perm’ granular fill material layer (tT2Perm = 0.2 m) with an imperfectly sealed slab.
L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097 1089

Fig. 13. Effect of a crack on the SPFE with the ‘Hybrid’ granular fill material layers (i.e. 0.2 m ‘T2-Perm’ over 0.7 m ‘T1-Struc’) at observation lines OL1 (at the sump level) and OL2 (at the
footing level) for a perfectly sealed slab [(a), (b)] and an imperfectly sealed slab [(c), (d)].

5.2. Effects of mnc of the ‘T1 Struc’ material on the SPFE will allow designers to define accurately the type of foundation that
should be used to support the house. In addition, if a SD system is
The effects of mnc of the ‘T1 Struc’ on the SPFEs were investigated for required for the house, the kas value is a key parameter. Practically,
the SD systems with the ‘Hybrid’ granular fill layers and the ‘T1 Struc’ kas is expected to affect the effectiveness of a SD system. For example,
granular fill layer alone. The mnc was varied at 1%, 1.5%, 2%, 2.5%, 3%, a significant pressure loss in the system would occur if the native soil
3.5%, 4% and 4.5%, and the wcrack value was fixed at 1.5 mm for all sim- had a relatively high k as , as a significant airflow might enter the
ulations. For the SD system with the Hybrid granular fill layer, tT2Perm system from the ground surface outside the house causing pressure
and tT1Struc were set at 0.2 m and 0.7 m, respectively. For the ‘T1 Struc’ loss.
layer alone, the tT1Struc was fixed at 0.9 m. Both perfectly and imperfectly In this section, the effects of the kas values were investigated. Only a
sealed slabs were considered. Simulation results for the Hybrid fill layer perfectly sealed ground bearing slab was considered to minimise the ef-
are shown in Fig. 14. The pressures decrease slightly with the increase in fects of the pressure loss through the slab. The SD systems with the ‘Hy-
the mnc for both perfectly and imperfectly sealed slabs, as the pressure is brid’ and ‘T2 Perm’ granular fill material layers were examined. For the
trapped inside the ‘T2 Perm’ sub-layer fill layer due to low kah(T1Struc) ‘Hybrid’ case, tT1Struc and tT2Perm were fixed at 0.7 m and 0.2 m, respec-
and kas. This phenomenon is in contrast with that for the ‘T1 Struc’ fill tively. The mnc value of the ‘T1 Struc’ was set at 4%, as it is expected to
layer, as shown in Fig. 15. The SPFEs decrease significantly when mnc in- be in practice. Five kas values were assigned for the soil with the ratio
crease. For example, at the distance of 4 m from the sump centre, a nor- of kah(T2Perm)/kas which were varied at 1, 10, 102, 103 and 104. The wall
malised pressure of 0.62 was obtained when mnc = 1% [high kah(T1Struc)], crack was specified as wcrack = 1.5 mm.
whereas that was 0.1 when mnc = 4.5 [low kah(T1Struc)]. The SPFEs for different kas values are shown in Fig. 17. For the SD
Therefore, in order to have a high SPFE, the mnc value should be low system with the ‘T2 Perm’ granular fill layer, the pressures are similar
enough, e.g. mnc ≤ 3% with relatively good airtightness of the slab. An ex- at kah(T2Perm)/kas ≥ 102 at the same horizontal distance along the two ob-
ample of the pressure contours for mnc = 4% with the imperfectly sealed servations lines (i.e. at the sump and foundation levels). However, a sig-
slab is shown in Fig. 16. As can be seen, the SPFEs decrease rapidly from nificant reduction is observed at kah(T2Perm)/kas b 102 for all cases. For
the sump centre. From these findings, it is suggested that the ‘T1 Struc’ example, at the horizontal distance of 4 m from the sump centre,
material is not an optimal option to form a permeable layer for a SD sys- when kah(T2Perm)/kas = 102, the ratio P/Psump is found to be 0.75 and
tem. It is also evident that an imperfectly sealed slab will result in a sig- this ratio reduced to 0.65 and 0.34 at kah(T2Perm)/kas = 10 and 1, respec-
nificant reduction of the SPFE. tively. This significant reduction in the SPFE can be explained by a signif-
icant amount of airflow entering the granular fill layer from the ground
5.3. Effects of the kas value on the SPFE surface outside the house when kas is high, thus reducing the air resis-
tance of the system [Fig. 18(b)].
An important factor for the design of the foundation for a house is However, an insignificant reduction of pressure is obtained in the
to characterise the properties of the native soil. This characterisation fill layer with the ‘Hybrid’ fill layers at the sump level (OL1) [Fig. 17
1090 L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097

Fig. 14. Effect of the mnc values of the ‘T1 Struc’ granular fill material on the SPFE with the ‘Hybrid’ granular fill layers at observation lines OL1 (at the sump level) and OL2 (at the footing
level) for a perfectly sealed slab [(a), (b)] and an imperfectly sealed slab [(c), (d)].

(c)], and a significant pressure loss is found at the foundation level thickness of ‘T2 Perm’ layer (tT2Perm) induces better pressure field ex-
(OL2) [Fig. 17 (d)] at k ah(T2Perm)/k as ≤ 102. These findings are sup- tension when the granular fill layer is formed by the ‘T2 Perm’ mate-
ported by monitoring the air flow paths, as shown in Fig. 18. For rial, as discussed previously. Hence, it is expected that the same
the ‘T2 Perm’ fill layer with kah(T2Perm)/kas = 104, the air flow paths principle could be applied for the ‘Hybrid’ granular fill layer.
occur predominantly in the granular fill layer, whereas those occur According to the Irish standard I.S. 888: 2016 (NSAI, 2016a), the
predominantly in both fill layer and granular soil when kah(T2Perm)/ tT2Perm value might vary from 0.2 m to 0.9 m. The selection of the tT2Perm
kas = 1. For the ‘Hybrid’ fill layers with kah(T2Perm) /kas = 1, the air will depend on an actual situation of the native soil and requirement of
flow paths occur in both the soil and fill layers, and a significant pres- the SD system. In this section, the thickness tT2Perm was varied at 0 m,
sure loss is observed in the soil whilst good SPFEs maintained in the 0.2 m, 0.4 m, 0.6 m and 0.9 m, while maintaining the total thickness of
fill layer. the ‘Hybrid’ granular layer (tT2Perm + tT1Struc) at 0.9 m. Both perfectly
Thus, it is inferred that the ‘T1 Struc’ could work as a barrier layer to and imperfectly sealed slabs are examined. The wcrack value was set at
minimise pressure loss in the granular fill layer of a system due to a high 1.5 mm for all cases.
kas. Therefore, the ‘Hybrid’ granular fill material might be preferred, and The simulation results are shown in Fig. 19. The best PSFE is ob-
the ‘T1 Struc’ sub-layer should be well compacted at high compaction tained for t T2Perm = 0.9 m, whereas t T1Struc = 0.9 m induces the
degree (e.g., mnc ≥ 4%) below the ‘T2 Perm’ sub-layer, especially if the worst, as the ‘T2 Perm’ material has much higher kah in comparison
native soil has a high permeability degree in comparison with that of with that of the ‘T1 Struc’ material. In addition, as tT2Perm becomes
the ‘T2 Perm’ material. larger, this will allow the SPFE gradient to develop deeper and
wider in the fill layer. It also can be seen that the SPFE increases sig-
5.4. Effects of the variation of tT2Perm and tT1Struc nificantly when the tT2Perm increases from 0.2 m to 0.4 m for all cases.
From the results presented in Fig. 19, it is suggested that the optimal
As discussed in Section 5.3, the ‘Hybrid’ granular fill layers might thickness of the ‘T2 Perm’ might be considered in between 0.2 m to
be preferred in some cases, for example when kas is high or when a 0.6 m depending on the actual design condition, for example founda-
soil improvement is required because of soft soil. Moreover, a greater tion soil condition and air tightness of the house. In addition, these
L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097 1091

Fig. 15. Effect of the mnc values of the ‘T1 Struc’ granular fill material on the SPFE with the ‘T1 Struc’ granular fill material layer at observation lines OL1 (at the sump level) and OL2 (at the
footing level) for a perfectly sealed slab [(a), (b)] and an imperfectly sealed slab [(c), (d)].

Fig. 16. Example of the SPFE contours for tT1Struc = 0.9 m (mnc = 4%) with an imperfectly sealed slab.
1092 L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097

Fig. 17. Effect of the air permeability of soil on the SPFE at observation lines OL1 (at the sump level) and OL2 (at the footing level) for a perfectly sealed slab over ‘T2 Perm’ granular fill
material [(a), (b)] and the ‘Hybrid’ granular fill material layers [(c), (d)].

results re-confirm that the ‘T1Struc’ is not an optimal option to be a 0.75 m and 1 m, whilst maintaining dsump = 0.124 m. Similarly, to inves-
permeable layer for a SD system. tigate the effect of the sump depth, the dsump are varied at 0.124 m,
0.2 m, 0.4 m, 0.6 m whilst keeping wsump = 0.27 m. All values of
5.5. Effect of sump type and sump size wsump and dsump are indicated in the figure. The pressures were found
to be slightly increased with the increase in the wsump and dsump. This
The suitability of sump types has not been well documented. Fur- finding suggests that at a specific sump pressure, the sump size does
thermore, the sump size might also affect the PSFE. Previous studies not affect the pressure field extension significantly.
designed their sumps at different sizes. For example, Abdelouhab
(2011) designed a sump by a concrete block approximately 0.5 m × 5.6. Effect of footing shape and dimension
0.5 m × 0.5 m with circular holes made on each side of the block,
whereas Vazquez et al. (2011) built a relatively large sump with a di- In practical design, different shapes of strip footings can be used.
mension of 1 m × 1 m × 0.5 m formed by conventional perforated Therefore, they might affect the SPFE of a SD system. The footing can
bricks. In Ireland, the plastic sumps with the octangular shape be either partially embedded with the top of the footing on the ground
(Fig. 3) (effective area of 72,000 mm2 and height of 124 mm) have surface [Figs. 2 and 22(a)] or fully embedded (Fig. 22b). This section dis-
been widely used. Therefore, the effect of sump size should also be cusses the effects of footing shape and dimension on the SPFE for four
examined. different cases with partially and fully embedded footings. Case 1 - par-
Fig. 20 presents the effects of the sump type on the PSFE. The ‘Hybrid’ tially embedded footing: The footing has the embedment depth of 0.9 m
granular fill layer with tT2Perm = 0.2 m and tT1Struc = 0.7 m was consid- and footing width of 0.5 m, which are the same as that analysed in the
ered, as this could be the worst case for the PSFE to be monitored if there previous sections. Case 2 - partially embedded footing: The footing has
is any improvement from the sump type. wcrack was 1.5 mm with both the embedment depth of 0.4 m and footing width of 0.5 m. Case 3-
perfectly and imperfectly sealed slabs were investigated. As shown in fully embedded footing: The footing width and embedment depth are
the figure, the PSFEs are practically identical for both sump types. It set at 0.65 m and 0.4 m, respectively. Case 4-fully embedded footing:
means that both sump types in the Irish market are suitable for use in The footing width and embedment depth are set at 0.4 m and 0.4 m,
the SD systems. respectively.
Fig. 21 shows the effect of sump sizes on the SPFE. The wsump and The footing thickness was fixed at 200 mm for Cases 3 and 4 (ECLG,
dsump were investigated separately. To investigate the effect of the 2012). The granular fill layer is formed with the ‘T2 Perm’ at tT2Perm =
sump width, the wsump values are varied at 0.14 m, 0.27 m, 0.5 m, 0.4 m. A perfectly sealed slab and a wcrack = 1.5 mm are considered
L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097 1093

Air flow path

a) kah(T2Perm)/kas =104, T2 Perm fill

Air flow path

b) kah(T2Perm)/kas =1, T2 Perm fill layer

Air flow path

c) kah(T2Perm)/kas =1, Hybrid fill layer


Fig. 18. Example of the air flow paths developed in the granular fill layers with different air permeability.

for all cases. Pressure contours obtained from Case 2 and 3 are presented The air extract ability of a permeable granular fill layer is greatly in-
in Fig. 22, and SPFE obtained at OL1 and OL2 are shown in Fig. 23. As fluenced by its kah, nh and def values, whereas the airtightness of the sub-
shown in the figures, the SPFE are similar within the slab area for all slab strongly depends on development of crack and air permeability of
cases. For these specific cases, the shape and dimension of a strip footing the native soil. Bonnefous et al. (1992) experimentally proved that by
have an insignificant influence on the effectiveness of a SD system. carefully sealing crack along the wall of a house, the SPFE in the perme-
able layer could increase significantly. Similar observation was reported
6. Discussion in the works of Jiránek and Svoboda (2007), and Jiránek (2014). They
showed that high SPFEs were obtained for houses with good air-
The results presented in this paper address the effect of different tightness of the sub-slab. In addition, Jiránek and Svoboda (2007) also
factors on the SPFE of a SD system. The impact level of each factor found that the ratio of kah/kas is an important factor with higher kah/kas
would depend on an actual practical situation. Previous studies ratios induce higher SPFEs.
have confirmed that the main entry mechanism of Radon gas into In buildings, the bearing layer beneath the foundation and floor
buildings is convection which is related to the pressure difference should be designed appropriately. This should include a good com-
between the indoor air and soil/granular fill layers beneath the paction process and should have a sufficient thickness to ensure
floor slab (Collignan, 2018). In addition, the design of a SD system the bearing capacity and serviceability criteria as well as to have
should focus mainly on decreasing the pressure in the permeable good degree of permeability of granular fill material layers beneath
granular fill layers beneath the floor slab of a buildings (Jiránek, the floor and foundation. Therefore, thickness of the granular layer is
2014). Therefore, the air extract ability of the permeable layer and also an important factor that should be addressed before any further ac-
airtightness of the slab would be two key issues. tion is taken.
1094 L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097

Fig. 19. Variation the SPFE at various tT2Perm and tT2Struc at observation lines OL1 (at the sump level) and OL2 (at the footing level) for a perfectly sealed slab [(a), (b)] and an imperfectly
sealed slab [(c), (d)].

This study investigated the SPFE in specified granular fill materials perforated pipes instead of a radon sump (Jiránek and Svoboda, 2007;
incorporating a sump-based SD system only. Previous research has Jiránek, 2014). Therefore, further investigation is required to assess
shown that the SPFE in a SD system could be generated using drainage the performance of perforated pipe-based SD systems.

Fig. 20. Effect of sump types on the SPFE at observation lines (a) OL1 (at the sump level) and (b) OL2 (at the footing level) for a perfectly sealed slab and an imperfectly sealed slab.
L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097 1095

Fig. 21. Effect of sump sizes on the SPFE with the ‘T2 Perm’ granular fill material layer (tT2Perm = 0.9 m) at observation lines OL1 (at the sump level) and OL2 (at the footing level).

7. Conclusion The results presented in this study apply to the conditions consid-
ered only, i.e., based on the design parameters for the ‘T1 Struc’ and
A series of transient CFD simulations have been conducted to inves- ‘T2 Perm’ granular materials in the Republic of Ireland. However, the re-
tigate the behaviour of the pressure field extension of SD systems for sults might be adopted to analyse the SPFE of SD systems formed with
radon mitigations. The results showed that the wall crack and airtight- different permeable granular materials. For a proper design, it is sug-
ness of the concrete slab of the house affected the PSFE significantly. gested that a suitable kah/kas ratio should vary in between 102 and 104,
Good SPFEs were observed if the granular fill layers were formed by and the air permeability of the permeable layer should fall in the mag-
the ‘T2 Perm’ material. nitude of 10−8 to 10−9 m2.
The ‘T1 Struc’ fill layer induces poor SPFEs. This suggests that the ‘T1 Finally, the results reported in this study were obtained from 2D CFD
Struc’ material is not an optimal option to be the permeable layer of the simulations, which did not consider a number of complexities; for ex-
SD system. The compaction moisture content (mnc) of the ‘T1 Struc’ ma- ample the effects of slab shape, wall corner, sump shape, limited area
terial do not affect the SPFEs of the ‘Hybrid’ granular fill layer that con- of the house, and limited granular material types.
tains ‘T2 Perm’ on top of ‘T1 Struc’, and its ‘T1 Struc’ sub-layer might
work as a barrier layer to prevent pressure loss of the system. Acknowledgments
The thickness of the ‘T2 Perm’ layer (tT2Perm) plays an important
role to the SPFE. The presures increase with the increase of the This study is a part of the OPTI-SDS project, which is funded by the
tT2Perm. In addition, the soil with a high air permeability (kas) will in- Irish Environmental Protection Agency through Grant No. 2015–HW–
duce a poor SPFE for a SD system. For this case, a design approach MS5. The authors wish to acknowledge the DJEI/DES/SFI/HEA Irish Cen-
might be considerd by using the ‘Hybrid’ granular fill layers with a tre for High-End Computing (ICHEC) for the provision of computational
‘T1 Struc’ material having a high compaction moisture content, e.g. facilities and support required for the CFD simulations. The authors
mnc ≥ 4%, to improve the SPFE. would like to thank the University of Cantabria research group in Spain
At a specified pump suction pressure (Psump), the sump type and for their support during measurements in the Pilot house, and the CSTB
sump size do not affect significantly the SPFE of the SD system. How- research group for their experimental test data. The second author would
ever, selection of sump types might be based on the practice experience, like to acknowledge the support of Science Foundation Ireland through
as well as each individual design condition. the Career Development Award programme (Grant No. 13/CDA/2200).
1096 L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097

(a)

(b)

Fig. 22. Pressure contour development for two strip footings with different shape and dimension. (a) Case 2: Partially embedded footing with footing width = 0.5 m and embedment depth =
0.4 m. Footing for Case 1 has the same shape and width but the embedment depth = 0.9 m. (b) Case 3: Fully embedded footing with footing width = 0.65 m and embedment depth = 0.4 m.
Footing for Case 4 has the same shape and embedment depth but width = 0.4 m. The pressure contours for Cases 1 and 4 show a similar trend thus are not presented here.

Fig. 23. Pressure development for strip footings with different shape and dimension.

References Andersen, C.E., 2001. Numerical modelling of radon-222 entry into houses: an outline of
techniques and results. Sci. Total Environ. 272, 33–42.
Abbas, A., Carcasses, M., Ollivier, J.P., 1999. Gas permeability of concrete in relation to its Ansys Inc, 2013. Ansys User's Manual. Ansys Inc, Canonsburg, Pennsylvania, United States.
degree of saturation. Mater. Struct. 32, 3–8. Ansys Inc, 2014. Introduction to Ansys Fluent. Ansys Inc, Canonsburg, Pennsylvania,
Abdelouhab, M., 2011. Contribution à l'étude du transfert des polluants gazeux entre le United States.
sol et les environnements intérieurs des bâtiments. Université de La Rochelle, Baeza, A., García-Paniagua, J., Guillen, J., Montalban, B., 2018. Influence of architectural
France, Autre (214 pages). style on indoor radon concentration in a radon prone area: a case study. Sci. Total En-
Abdelouhab, M., Collignan, B., Allard, F., 2010. Experimental study on passive soil depres- viron. 610–611, 258–266.
surization system to prevent soil gaseous pollutants into the building. Build. Environ. Bonnefous, Y.Y., Gadgil, A.J., Fisk, W.J., Prill, R.J., Nematollahi, A., 1992. Field study and numer-
45, 2400–2406. ical simulation of sub − lab ventilation systems. Environ. Sci. Technol. 26, 1752–1759.
L.C. Hung et al. / Science of the Total Environment 637–638 (2018) 1081–1097 1097

BRE, 1998. Modeling and measurement of soil gas flow. BRE Report. IHS BRE Press, UK depressurization, tested in prototype housing built in a high radon area in Spain.
(274 pages). J. Environ. Radioact. 102, 378–385.
Collignan, B., 2018. Radon management in buildings: applied research results on building WHO, 2009. Handbook on Indoor Radon. WHO Press, World Health Organisation, Geneva,
characterization and protection. IAEA Webinar 25 April 2018. Switzerland (94 pages).
Diallo, M.O., Collignan, B., Allard, F., 2015. Air flow models for sub-slab depressurization WHO, 2017. http://www.who.int/mediacentre/factsheets/fs291/en/, Accessed date: 4
systems design. Build. Environ. 87, 327–341. September 2017.
ECLG, 2012. Building Regulations. Government Publication, Postal Trade Section, Yarmoshenko, I., Vashilyev, A., Malinovsky, G., Bossew, P., Zunic, Z.S., Onischenko, A.,
Claremorris, Mayo, Ireland. Zhukovsky, M., 2016. Variance of indoor radon concentration: major influencing fac-
Ergun, S., 1952. Fluid flow through packed columns. Chem. Eng. Process. 48 (2), 89–94. tors. Sci. Total Environ. 541, 155–160.
Gadgil, A.J., Bonnefous, Y.C., Fisk, W.J., Prill, R.J., Nematollahi, A., 1991. Influence of sub-
slab aggregate permeability on SSV performance. Lawrence Berkeley Laboratory, Re-
Glossary
port: LBL−31160.
2D: two dimensional
Gadgil, A.J., Bonnefous, Y.C., Fisk, W.J., 1994. Relative effectiveness of sub-slab pressuriza-
ΔP: pressure difference
tion and depressurization systems for indoor radon mitigation: studies with an ex-
C: inertial loss coefficient [1/m]
perimentally verified numerical model. Indoor Air 4, 265–275.
CFD: Computational Fluid Dynamics
Gunning, G.A., Pollard, D., Finch, E.C., 2014. An outdoor radon survey and minimizing the
d50: particle size of the granular fill material at 50% passing [mm]
uncertainties in low-level measurements using CR−39 detectors. J. Radiol. Prot. 34
def: effective particle size of the granular fill material [m]
(2), 457–467.
def(T1Struc): effective particle size of the ‘T1 Struc’ granular fill material [m]
Hung, L.C., Goggins, J., Fuente, M., Foley, M., 2018. Characterisation of specified granular
def(T2Perm): effective particle size of the “T2 Perm” granular fill material [m]
fill materials for radon mitigation by soil depressurisation systems. Constr. Build.
dsump: sump depth [m]
Mater. https://doi.org/10.1016/j.conbuildmat.2018.04.210.
G: mass flow rate [kg/m2·s]
ICRP, 2010. Lung cancer risk from radon and progeny and statement on radon. ICRP pub-
k: turbulent kinetic energy [m2/s2]
lication 115. Ann. ICRP 40 (1) (64 pages).
kah: air permeability of the granular fill material [m2]
Jelle, B.P., 2012. Development of a model for radon concentration in indoor air. Sci. Total
kah(T1Struc): air permeability of the ‘T1 Struc’ granular fill material [m2]
Environ. 416, 33–350.
kah(T2Perm): air permeability of the “T2 Perm’ granular fill material [m2]
Jiránek, M., 2014. Sub-slab depressurisation systems used in the Czech Republic and ver-
kas: air permeability of soil [m2]
ification of their efficiency. Radiat. Prot. Dosim. 162 (1–2), 63–67.
L: flow length [m]
Jiránek, M., Svoboda, Z., 2007. Numerical modelling as a tool for optimisation of sub-slab
mnc: compaction moisture content [%]
depressurisation system design. Build. Environ. 42 (5), 1994–2003.
mnc(opt): optimum compaction moisture content [%]
Johner, H.U., Surbeck, H., 2001. Soil gas measurement below foundation depth improve
mnc(95%): 95% optimum compaction moisture content [%]
indoor radon prediction. Sci. Total Environ. 272, 337–341.
nh: porosity
Lopez-Abente, G., Nunez, O., Fernandez-Navarro, P., Barros-Dios, J.M., Martín-Méndez, I.,
nh(T1Struc): porosity of the ‘T1 Struc’ granular fill material
Bel-Lan, A., Locutura, J., Quindos, L., Sainz, C., Ruano-Ravina, A., 2018. Residential
nh(T2Perm): porosity of the ‘T2 Perm’ granular fill material
radon and cancer mortality in Galicia, Spain. Sci. Total Environ. 610-611, 1125–1132.
nh(T1Struc): porosity of the ‘T1 Struc’ granular fill material
NSAI, 2016a. Code of Practice for the Procurement and Use of Unbound Granular Fill
nh(T2Perm): porosity of the ‘T2 Perm’ granular fill material
Hardcore Material for Use Under Concrete Floors. I.S. 888: 2016, NSAI, 1 Swift Square,
OL1: observation line #1 in CFD simulation
Northwood, Santry, Dublin 9, Ireland.
OL2: observation line #2 in CFD simulation
NSAI, 2016b. S.R. 21: 2014+A1:2016. Guidance On the Use of I.S. EN 13242: 2002 +A1:
P: suction pressure developed in a SD system obtained from CFD simulations [Pa]
2007- Aggregates for Unbound and Hydraulically Bound Materials for Use in Civil En-
P(point): pressure developed in the granular fill layer measured at a drilled hole on the con-
gineering Work and Road Construction, NSAI, 1 Swift Square, Northwood, Santry,
crete floor [Pa]
Dublin 9, Ireland.
Psump: suction pressure at the sump [Pa]
Pacheco-Torgal, F., 2012. Indoor radon: an overview on a perennial problem. Build. Envi-
SPFE: sub-slab pressure field extension
ron. 58, 270–277.
t: thickness of the granular fill material [m]
Rydock, J.P., Skaret, E., 2002. A case study of sub-slab depressurization for a building lo-
t(T1Struc): thickness of the ‘T1 Struc’ granular fill material [m]
cated over VOC-contaminated ground. Build. Environ. 37 (12), 1343–1347.
t(T2Perm): thickness of the ‘T2 Perm’ granular fill material [m]
Turk, B.H., Pill, R.J., Fisk, W.J., Grimsrud, D.T., Sextro, R.G., 1991. Effectiveness of radon con-
wsump: sump width [m]
trol techniques in fifteen homes. J. Air Waste Manage. Assoc. 41, 723–734.
wcrack: width of wall crack [mm]
US-EPA, 1993. Radon mitigation standards. EPA 402-R-93-078. United States Environ-
V: flow velocity [m/s]
mental Protection Agency.
γdry (95%): 95% maximum dry unit weight [kN/m3]
Vazquez, B.F., 2017. The Spanish experience: approaches, optimisation, and singularities
γdry: dry unit weight [kN/m3]
concerning to energy saving. International IAEA Workshop ‘Radon for Building Pro-
μ: dynamic viscosity [Pa·s]
fessionals’. Ciudad Rodrigo, Salamanca, Spain, 13–17 November.
ε: turbulent dissipation rate [m2/s3]
Vazquez, B.F., Adan, M.O., Poncela, L.S.Q., Fernandez, C.S., Merino, I.F., 2011. Experimental
ω: specific dissipation rate [1/s]
study of the effectiveness of four radon mitigation solutions, based on underground

Das könnte Ihnen auch gefallen