Beruflich Dokumente
Kultur Dokumente
2015
Product Guide and Price List Americas
Effective April 1, 2015
Thank you for 40 years!
The cover of the 2015 Product Guide and Price List
features our brand new Belimo Americas Headquarters, a Green
building for production, customizing, and warehousing. The
200,000 sq. ft. building also includes a valve engineering center,
valve testing laboratory, and office space. Belimo University
provides training classes for Belimo solutions and an Experience
Tour that demonstrates our actuators and valves in action.
Over four decades, Belimo has become the world leader in the
design and production of HVAC valve and actuator technology.
Through collaboration with our customers we have been able to
innovate the industry.
You have the opportunity within this guide to browse through
our extensive line of products and software solutions for 2015.
You will also meet individuals of the Belimo team as they
highlight our energy-saving technologies.
I am showcasing three of our state-of-the-art products. In my
right hand is the new Belimo ZoneTight™, the best zone valve in
the industry. The ZoneTight range is based on our CCV ball valve
technology. Nigel Gallimore, product manager, explains more on
the next page.
In my left hand I am holding the ZIP Economizer™, programmed
with all relevant climate zone and energy code data, allowing
users to maximize savings at their location by simply selecting
their ZIP code. In front is the award-winning Belimo Energy Valve™
- a pressure independent control valve that measures energy,
controls power, and manages Delta T.
DAMPER ACTUATORS
SPRING RETURN DAMPER ACTUATORS
EF Series (270 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 12
AF Series (180 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 12
NF Series (90 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 12
AF Series with NEMA 4 Housing (180 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 12
NF Series with NEMA 4 Housing (90 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 12
LF Series (35 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4 14
TF Series (22 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4 14
Jackshaft for Spring Return Series Damper Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 19
ELECTRONIC FAIL-SAFE DAMPER ACTUATORS
GK Series (360 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 24
NKQ Series (54 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 24
AHK Series (101 lbf) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 24
GK Series with NEMA 4 Housing (360 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 24
FIRE AND SMOKE DAMPER ACTUATORS
FSAF*A Series (180 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 32
FSAFB Series (180 in-lbs) and FSAF Series (133 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 32
FSNF Series(70 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 32
FSLF Series (30 in-lbs) . . . . . . . . . . . . . . . . .
FSTF Series (18 in-lbs) . . . . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
3-2
3-2
32
32 Fire and Smoke
NON-SPRING RETURN DAMPER ACTUATORS
GM Series (360 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 38
Actuators –
AM Series (180 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 38 Technology that
NM Series (90 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 38
LM Series (45 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 38 Saves Lives
CM Series (18 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 38
NEMA 4/4X Series Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 38
Quick Running Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4 40
AH Linear Series (101 lbf) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 42
LH Linear Series (34 lbf) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 42
LU Rotary Series (27 in-lbs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 42
Jackshaft for Non-Spring Return Series Damper Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10 46
DAMPER ACTUATOR ACCESSORIES
MFT Damper Actuator Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 49
Mechanical Damper Actuator Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2 50
Electronic Damper Actuator Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10 58
ENERGY VALVE
Energy Valve Product Range Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5 66
Operation/Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6 67
2-way (½” to 2”) with Non-Spring Return and Electronic Fail-Safe Actuators . . . . . . . . . . . . . . . . 6-9 70
2-way (2½” to 6”) with Non-Spring Return and Electronic Fail-Safe Actuators . . . . . . . . . . . . . . . . 6-10 71
All information subject to change. Visit www.belimo.us for the latest version.
Table of Contents (cont.) Book
Page
PDF
Page
Flexibility Stainless Steel Trim (½” to 2”) 2-way with Non-Spring Return and Electronic Fail-Safe Actuators .
Bronze or Stainless Steel Trim (½” to 2”) 2-way/3-way with Spring Return Actuators . . . . . . .
.
.
.
.
.
.
.
.
.17-9
17-11
226
228
Bronze Trim (2½” to 6”) 2-way/3-way, Pressure Compensated ANSI 125 Flanged . . . . . . . . . . . . . 17-14 231
Stainless Steel Trim (2½” to 6”) 2-way/3-way, Pressure Compensated ANSI 125 Flanged . . . . . . . . . 17-17 234
Bronze Trim (2½” to 6”) 2-way/3-way, ANSI 250 Flanged . . . . . . . . . . . . . . . . . . . . . . . . . 17-23 240
Stainless Steel Trim (2½” to 6”) 2-way/3-way, ANSI 250 Flanged . . . . . . . . . . . . . . . . . . . . . 17-26 243
Globe Valve Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-29 246
All information subject to change. Visit www.belimo.us for the latest version.
Table of Contents (cont.) Book
Page
PDF
Page
All information subject to change. Visit www.belimo.us for the latest version.
DAMPER ACTUATORS
ONE
DAMPER ACTUATORS
AND ACCESSORIES
Intelligence Down to the Last Detail
• Extensive range of rotary and linear actuators
to meet the environmental and performance
demands of HVAC applications.
• Multi-Function Technology allows you to
adapt an actuator to your specific system for
replacement or changes in your system.
• Minimum torque guaranteed over the entire
specific operating range and design life, no
loss in performance due to temperature or
supply voltage.
ZIP Economiz er
Fast Route to Reliable Energy Sav ings
• Efficient Free Cooling
Now Available
ZIP Packs – a single part number that provides everything you need to retrofit your economizer.
www.ZIPeconomizer.com
1
SPRING RETURN
DAMPER ACTUATORS
Maximum Performance with Low
Power Consumption
• Comprehensive torque offering 22 in-lbs to
270 in-lbs over a vast selection of actuators
for a wide range of applications.
• True mechanical spring return, providing
reliable fail-safe.
• MFT is available in all spring return actuators,
giving the user the flexibility to customize and
adapt a single actuator to various controllers
and applications.
EF X 24 -MFT -S N4
Ordering Example
5
1 Choose the actuator.* EFX 24 -MFT -S N4 NEMA 4 option
(if available)
3 4 -S = Built-in
Designate Designate Auxiliary
control switch Switch
24 = 24 VAC/DC
MFT (2-10 VDC Default)
*All functions and options are not available with all versions
SPRING RETURN
Effic
ciency Through Training
The Belimo University team is passionate about
providing training programs to the Heating,
Ventilation, and Air Conditioning industry. Explore our
comprehensive portfolio of learning products and
services designed to maximize your results. From
foundation knowledge development to best practices,
Belimo University offers flexible, value based solutions.
www.BelimoUniversity.com
BELIMO
UNIVERSITY
Actuator Specifications
EF AF NF
Series† Series† Series
270 in-lbs [30 Nm] 180 in-lbs [20 Nm] 90 in-lbs [10 Nm]
Approx. 66 sq.ft. Approx. 45 sq.ft. Approx. 22 sq.ft.
Angle of rotation 95°, adjustable with mechanical Angle of rotation 95°, adjustable with mechanical Angle of rotation 95°, adjustable with mechanical
end stops end stops end stops
MFT electronically variable 0-100% MFT electronically variable 0-100% MFT electronically variable 0-100%
Fits shaft diameter ½” to 1.05” (clamp centers on ¾” Fits shaft diameter ½” to 1.05” (clamp centers on ½”, Fits shaft diameter ½” to 1.05” (clamp centers on ½”,
and 1.05”) ¾”, and 1.05”) ¾”, and 1.05”)
Position indication visual indicator Position indication visual indicator Position indication visual indicator
Manual override 5 mm hex crank (3/16” allen), Manual override 5 mm hex crank (3/16” allen), Manual override 5 mm hex crank (3/16” allen),
supplied supplied supplied
Direction of rotation external switch with -SR and MFT Direction of rotation external switch with -SR and MFT Direction of rotation external switch with -SR and MFT
Spring return CW/CCW mounting (reversible) Spring return CW/CCW mounting (reversible) Spring return CW/CCW mounting (reversible)
Dimensions 11.32” x 5.43” x 4.74” Dimensions 9.69” x 3.86” x 3.42” Dimensions 9.69” x 3.86” x 3.42”
[287.5 x 138 x 120.5 mm] [246.1 x 98 x 86.9 mm] [246.1 x 98 x 86.9 mm]
N4, N4H models: 13.54” x 5.43” x 4.74” Electrical connection 3 ft., 18 GA appliance cable, ½” Electrical connection 3 ft., 18 GA appliance cable, ½”
[344 x 138 x 120.5 mm] conduit fitting (default) conduit fitting (default)
Electrical connection 3 ft., 18 GA appliance cable, ½” Overload protection electronic throughout rotation Overload protection electronic throughout rotation
conduit fitting (default)
Ambient temperature -22°F to +122°F [-30°C to +50°C] Ambient temperature -22°F to +122°F [-30°C to +50°C]
Overload protection electronic throughout rotation
Auxiliary switch(es) (-S) models: 2 SPDT, 3A (0.5A Auxiliary switch(es) (-S) models: 2 SPDT, 3A (0.5A
Ambient temperature -22°F to +122°F [-30°C to +50°C] inductive) @ 250V, one switch fixed inductive) @ 250V, one switch fixed
N4H models: -40°F to +122°F at 10°, one adjustable 10° to 90° at 10°, one adjustable 10° to 90°
[-40°C to +50°C]
Housing NEMA 2/IP54, UL enclosure Type 2 Housing NEMA 2/IP54, UL enclosure Type 2
Auxiliary switch(es) (-S) NEMA 2 models: 2 SPDT, 3A
(0.5A inductive) @ 250V, one switch Agency listings cULus according to UL 60730-1A/- Agency listings cULus according to UL 60730-1A/-
fixed at 10°, one adjustable 10° 2-14, UL 2043*, CAN/CSA E60730- 2-14, UL 2043*, CAN/CSA E60730-
to 85° 1:02, CE according to 2004/108/EC 1:02, CE according to 2004/108/EC
and 2006/95/EC and 2006/95/EC
Housing NEMA 2/IP54, UL enclosure Type 2
N4, N4H models: NEMA 4/IP66,
Enclosure Type 4
Agency listings cULus according to UL 60730-1A/-
2-14, UL 2043*, CAN/CSA E60730-
1:02, CE according to 2004/108/EC
and 2006/95/EC
1-2
EF, AF, NF, Power Power Running Control
Control Input
Position Auxiliary List
Damper Actuator
0-10 V Phasecut
Floating Point
On/Off
On/Off
EFB24 ● 16 9.5 (4.5) 75 <20♦ ● $866
EFB24 N4 ● 16 9.5 (4.5) 75 <20♦ ● $1,023
EFB24-S ● 16 9.5 (4.5) 75 <20♦ ● ● $1,036
EFB120 ● ● 21 9.5 (4.5) 75 <20♦ ● $969
Approx. 45 sq. ft. AFB24-S N4H ● 7.5/25 5/25(3) <75 20♦ ● ● $2,148
AFBUP N4H ● 8.5*/25 7/25 (3) <75 20♦ ● $2,112
AFBUP-S N4H ● 8.5*/25 7/25 (3) <75 20♦ ● ● $2,206
AFB24-SR N4H ● 8.5/25 5.5/25 (3) 95 <20♦ ● ● $2,175
AFB24-SR-S N4H ● 8.5/25 5.5/25 (3) 95 <20♦ ● ● ● $2,269
AFB24-MFT N4H ● 10/25 7.5/25 (3) 70…220 (150) <20♦ ● ● ● ● ● ● ● $2,237
AFB24-MFT-S N4H ● 10/25 7.5/25 (3) 70…220 (150) <20♦ ● ● ● ● ● ● ● ● $2,331
AFB24-MFT95 N4H ● 10/25 7.5/25 (3) 70…220 (150) <20♦ ● ● ● $2,262
NFB24 ● 8.5 6 (2.5) <75 <20♦ ● $405
NFB24-S ● 8.5 6 (2.5) <75 20♦ ● ● $499
NFBUP ● 6.5** 6 (2.5) <75 20♦ ● $458
NFBUP-S ● 6.5** 6 (2.5) <75 20♦ ● ● $552
NFB24-SR ● 6 3.5 (2.5) 95 <20♦ ● ● $540
NFB24-SR-S ● 6 3.5 (2.5) 95 <20♦ ● ● ● $634
NFB24-MFT ● 9 6.5 (3) 40…220 (150) <20♦ ● ● ● ● ● ● ● $601
NFB24-MFT-S ● 9 6.5 (3) 40…220 (150) <20♦ ● ● ● ● ● ● ● ● $695
NFB Series
NFB24 N4H ● 8.5/25 6/25 (2.5) <75 <20♦ ● $1,964
90 in-lbs
[10 Nm] NFB24-S N4H ● 8.5/25 6/25 (2.5) <75 20♦ ● ● $2,058
Approx. 22 sq. ft. NFBUP N4H ● 6.5***/25 6/25 (2.5) <75 20♦ ● $2,017
NFBUP-S N4H ● 6.5***/25 6/25 (2.5) <75 20♦ ● ● $2,111
NFB24-SR N4H ● 6/25 3.5/25 (2.5) 95 <20♦ ● ● $2,099
NFB24-SR-S N4H ● 6/25 3.5/25 (2.5) 95 <20♦ ● ● ● $2,193
NFB24-MFT N4H ● 9/25 6.5/25 (3) 40…220 (150) <20♦ ● ● ● ● ● ● ● $2,160
NFB24-MFT-S N4H ● 9/25 6.5/25 (3) 40…220 (150) <20♦ ● ● ● ● ● ● ● ● $2,254
♦ <60 seconds @ -22°F [-30°C].
* 8.5 VA for 120 VAC; 7 VA for 24 VAC, 18 VA for 240 VAC.
** 6.5 VA for 120 VAC; 6 VA for 24 VAC; 9.5 VA for 240 VAC.
NEMA 4 Heater: add “H” to the end of select “N4”, for example
p NFB24-MFT N4H. All AF/NF NEMA 4 models are configured ffor a CCW spring return rotation.
1-3
SPRING RETURN
LF, TF Series
Direct Coupled, Spring Return Damper Actuators
Actuator Specifications
LF TF
Series Series
35 in-lbs [4 Nm] 22 in-lbs [2.5 Nm]
Approx. 8.5 sq. ft. Approx. 5.5 sq. ft.
Angle of rotation 95°, adjustable with mechanical 95°, adjustable with mechanical
end stops end stops
MFT electronically variable 0-100% MFT electronically variable 0-100%
Fits shaft diameter 3/ ”-½” standard (centers on ½”);
8 Fits shaft diameter ¼”- ½” (centers on ½”)
½”-¾” with K6-1 clamp accessory Position indication visual indicator
Position indication visual indicator
Direction of CW/CCW external switch
Direction of CW/CCW external switch rotation (proportional models)
rotation (proportional models) Spring return CW/CCW mounting
Spring return CW/CCW mounting reversible
reversible Dimensions 6.28” x 3.0” x 3.30”
Dimensions 7.67” x 3.86” x 3.23” [159.5 x 76.2 x 83.72 mm]
[195 x 98 x 82 mm] Electrical connection 3 ft., 18 GA plenum cable
Electrical connection 3 ft., 18 GA plenum cable (modulating), 3 ft., 18 GA appliance
(modulating), 3 ft., 18 GA appliance cable (on/off, -S types), ½” conduit
cable (on/off, MFT, -S types), ½” fitting
conduit fitting Overload protection electronic throughout rotation
Overload protection electronic throughout rotation
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Ambient temperature -22°F to +122°F [-30°C to +50°C]
Auxiliary switch(es) (-S) models: 1 SPDT, 3 A (0.5 A
Auxiliary switch(es) (-S) models: 1 SPDT, 3A (0.5 A inductive) @ 250V adjustable 0°
inductive) @ 250V adjustable 0° to 95°
to 95° Housing NEMA 2 (IP42), UL enclosure Type
Housing NEMA 2 (IP54) any orientation 2, any orientation
Agency listings cULus according to UL 873, UL Agency listings cULus according to UL60730-
2043* and CAN/CSA C22.2 No. 1A/-2-14, UL 2043*, CAN/CSA
24-93 E60730-1:02, CE according to
2004/108/EC and 2006/95/EC
1-4
LF, TF Power Power Running Control
Control Input
Position Auxiliary List
Spring Return Supply Consumption Time(s) Input MFT Feedback Switches Price
Damper Actuator
Floating Point
Floating Point
On/Off
On/Off
LF24 US ● 7 5 (2.5) <40 to 75 <25♦ ● $339
LF24-S US ● 7 5 (2.5) <40 to 75 <25♦ ● ● $398
LF120 US ● 7.5 5.5 (3.5) <40 to 75 <25♦ ● $375
LF120-S US ● 7.5 5.5 (3.5) <40 to 75 <25♦ ● ● $434
LF230 US ● 7 5 (3) <40 to 75 <25♦ ● $465
LF230-S US ● 7 5 (3) <40 to 75 <25♦ ● ● $524
LF24-SR US ● 5 2.5 (1) 150 <25♦ ● ● $465
LF24-SR-S US ● 5 2.5 (1) 150 <25♦ ● ● ● $524
LF Series
LF24-SR-E US ● 5 2.5 (1) 150 <25♦ ● ● $501
35 in-lbs [4 Nm]
LF24-3 US ● 5 2.5 (1) 150 <25♦ ● $413
Approx. 8.5 sq. ft.
LF24-3-S US ● 5 2.5 (1) 150 <25♦ ● ● $472
LF24-ECON-R03 US ● 5 2.5 (1) 95 <25♦ ● ● $526
LF24-MFT US ● 5 2.5 (1) 75…300 (150) <25♦ ● ● ● ● ● ● ● $526
LF24-MFT-S US ● 5 2.5 (1) 75…300 (150) <25♦ ● ● ● ● ● ● ● ● $585
LF24-MFT-20 US ● 6 3.5 (1.5) 150 <25♦ ● ● ● ● ● ● ● $585
LF24-MFT-S-20 US ● 6 3.5 (1.5) 150 <25♦ ● ● ● ● ● ● ● ● $644
LFC24-3-R US ● 5 2.5 (1) 90 <25♦ ● $465
LFC24-3-S US ● 5 2.5 (1) 90 <25♦ ● ● $524
TFB24 ● 5 2 (1.3) <75 <25♦ ● $281
TFB24-S ● 5 2 (1.3) <75 <25♦ ● ● $340
TFLB24 ● 5 2 (1.3) <75 <75 ● $281
TFB120 ● ● 5 2.5 (1.3) <75 <25♦ ● $327
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
1-5
SPRING RETURN
Custom Options
1 ACTUATOR TYPE
2 MECHANICAL INTERFACE
2 TYPE Size Actuator Series List Price
No Clamp - AFX, NFX, TFX No Charge
Standard Universal Clamp 1/2” - 1.05” EFX, AFX, NFX No Charge
1 Standard Clamp 1/4” - 1/2” TFX No Charge
Crank Arm - AFX, NFX $2
1-6
Custom Power Power Running Control Control Input Position Auxiliary List Cable
Supply Consumption Time(s) Input MFT Feedback Switches Price Options
Spring Return
®
Floating Point
On/Off
On/Off
EFX24 ● 16 9.5 (4.5) 75 <20♦ ● $866 ●
EFX24-S ● 16 9.5 (4.5) 75 <20♦ ● ● $1,036 ●
EFX120 ● ● 21 9.5 (4.5) 75 <20♦ ● $969 ●
EFX120-S ● ● 21 9.5 (4.5) 75 <20♦ ● ● $1,139 ●
EFX24-SR ● 14 8 (4.5) 95 <20♦ ● ● $1,081 ●
EFX24-SR-S ● 14 8 (4.5) 95 <20♦ ● ● ● $1,251 ●
EFX24-MFT ● 16 9.5 (4.5) 60…150 (150) <20♦ ● ● ● ● ● ● ● $1,190 ●
EFX24-MFT-S ● 16 9.5 (4.5) 60…150 (150) <20♦ ● ● ● ● ● ● ● ● $1,360 ●
EFX24-S N4 ● 16 9.5 (4.5) 75 <20♦ ● ● $1,193
EFX Series
EFCX24-S N4 ● 16 9.5 (4.5) 75 <10♦♦ ● ● $1,275
270 in-lbs [30 Nm]
Approx. 66 sq. ft. EFX24-S N4H ● 16/21 9.5/21 (4.5) 75 <20♦ ● ● $1,315
EFX120-S N4 ● ● 21 9.5 (4.5) 75 <20♦ ● ● $1,296
EFCX120-S N4 ● ● 21 9.5 (4.5) 75 <10♦♦ ● ● $1,378
EFX120-S N4H ● ● 21/22 9.5/22 (4.5) 75 <20♦ ● ● $1,418
EFX120-SR N4 ● ● 21 9(5.5) 95 <20♦ ● ● $1,341
EFX120-SR-S N4 ● ● 21 9(5.5) 95 <20♦ ● ● ● $1,511
EFX24-SR-S N4 ● 14 8 (4.5) 95 <20♦ ● ● ● $1,408
EFX24-SR-S N4H ● 14/21 8/21 (4.5) 95 <20♦ ● ● ● $1,530
EFX24-MFT-S N4 ● 16 9.5 (4.5) 60…150 (150) <20♦ ● ● ● ● ● ● ● ● $1,517
EFX24-MFT-S N4H ● 16/21 9.5/21 (4.5) 60…150 (150) <20♦ ● ● ● ● ● ● ● ● $1,639
AFX24 ● 7.5 5 (2.5) <75 20♦ ● $495 ●
AFX24-S ● 7.5 5 (2.5) <75 20♦ ● ● $589 ●
AFXUP ● 8.5* 7 (3.5) <75 20♦ ● $553 ●
AFXUP-S ● 8.5* 7 (3.5) <75 20♦ ● ● $647 ●
AFX24-SR ● 8.5 5.5 (3) 95 <20♦ ● ● $616 ●
AFX24-SR-S ● 8.5 5.5 (3) 95 <20♦ ● ● ● $710 ●
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
1-7
Custom Power Power Running Control
Control Input
Position Auxiliary List Cable
Damper Actuator
Floating Point
Floating Point
On/Off
On/Off
TFX24 ● 5 2 (1.3) <75 <25♦ ● $281 ●
TFX24-S ● 5 2 (1.3) <75 <25♦ ● ● $340 ●
TFX120 ● ● 5 2.5 (1.3) <75 <25♦ ● $327 ●
TFX120-S ● ● 5 2 (1.3) <75 <25♦ ● ● $386 ●
1-8
SPRING RETURN
Jackshaft Linkage for Spring Return Damper Actuators
ZG-JSLA
Running List Price
Power Auxiliary List Price*
BASIC PRODUCTS Control Input Feedback
Supply
Time(s) VA Rating
Switch
(Linkage
(Actuator +
[Default] Only)
Linkage)
Jackshaft (only) ZG-JSL $261
CUSTOMIZE PRODUCTS‡‡ REORDER #
ZG-JSLA + AFX24 JSL+AF200 2A1 003 On/Off - 24 VAC/DC <75 seconds 7.5 - $706
ZG-JSLA + AFX24-S JSL+AF220 2A1 003 On/Off - 24 VAC/DC <75 seconds 7.5 Built-in $800
ZG-JSLA + AFXUP JSL+AF000 2A1 003 On/Off - 24-240 VAC <75 seconds 8.5 - $764
ZG-JSLA + AFXUP-S JSL+AF020 2A1 003 On/Off - 24-240 VAC <75 seconds 8.5 Built-in $858
ZG-JSLA + AFX24-SR JSL+AF400 2A1 H01 2-10 VDC 2-10 VDC 24 VAC/DC 95 seconds 8.5 - $827
ZG-JSLA + AFX24-SR-S JSL+AF420 2A1 H01 2-10 VDC 2-10 VDC 24 VAC/DC 95 seconds 8.5 Built-in $921
Variable with MFT
Variable
ZG-JSLA + AFX24-MFT JSL+AF600 2A1 A01 (VDC, PWM, Floating 24 VAC/DC 150 seconds 10 - $889
VDC
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Point, On/Off))
Variable with MFT
Variable
ZG-JSLA + AFX24-MFT-S JSL+AF620 2A1 A01 (VDC, PWM, Floating 24 VAC/DC 150 seconds 10 Built-in $983
VDC
Point, On/Off))
Variable
ZG-JSLA + AFX24-MFT95 JSL+AFE10 2C1 R01 0-135 Ω 24 VAC/DC 150 seconds 10 - $914
VDC
ZG-JSLA + NFX24 JSL+NF200 2A1 003 On/Off - 24 VAC/DC <75 seconds 8.5 - $616
ZG-JSLA + NFX24-S JSL+NF220 2A1 003 On/Off - 24 VAC/DC <75 seconds 8.5 Built-in $710
ZG-JSLA + NFXUP JSL+NF000 2A1 003 On/Off - 24-240 VAC <75 seconds 6.5 - $669
ZG-JSLA + NFXUP-S JSL+NF020 2A1 003 On/Off - 24-240 VAC <75 seconds 6.5 Built-in $763
ZG-JSLA + NFX24-SR JSL+NF400 2A1 H01 2-10 VDC 2-10 VDC 24 VAC/DC 95 seconds 6 - $751
ZG-JSLA + NFX24-SR-S JSL+NF420 2A1 H01 2-10 VDC 2-10 VDC 24 VAC/DC 95 seconds 6 Built-in $845
Variable with MFT
Variable
ZG-JSLA + NFX24-MFT JSL+NF600 2A1 A01 (VDC, PWM, Floating 24 VAC/DC 150 seconds 9 - $812
VDC
Point, On/Off))
Variable with MFT
Variable
ZG-JSLA + NFX24-MFT-S JSL+NF620 2A1 A01 (VDC, PWM, Floating 24 VAC/DC 150 seconds 9 Built-in $906
VDC
Point, On/Off))
<40 to 75
ZG-JSLA + LF24 US JSL+LF24 US On/Off - 24 VAC/DC 7 - $550
seconds
<40 to 75
ZG-JSLA + LF24-S US JSL+LF24-S US On/Off - 24 VAC/DC 7 Built-in $609
seconds
<40 to 75
ZG-JSLA + LF120 US JSL+LF120 US On/Off - 24 VAC/DC 7.5 - $586
seconds
ZG-JSLA + LF24-SR US JSL+LF24-SR US 2-10 VDC 2-10 VDC 24 VAC/DC 150 seconds 5 - $676
ZG-JSLA + LF24-3 US JSL+LF24-3 US Floatingg Point - 24 VAC/DC 150 seconds 5 - $624
Variable with MFT
Variable
ZG-JSLA + LF24-MFT US JSL+LS100 0A1 A01 (VDC, PWM, Floating 24 VAC/DC 150 seconds 5 - $737
VDC
Point, On/Off))
*At the factory, there is a $50 savings on the ZG-JSL if assembled with the actuator.
Example: ZG-JSL ($261) + NFX24-MFT-S ($695) = Total List Price ($956) - Factory Installed Savings ($50)
Total List Price of Assembled at Factory ZG-JSLA + NFX24-MFT-S is $906
‡‡ For other actuator models, please contact factory or visit us at www.belimo.us for possible combinations.
1-9
Sizing and Selection Made Simple.
SelectPro is a quick and user-friendly means for accurately selecting valves, actuators,
and replacement solutions. New enhancements include:
• Updated User Interface – Toggle screen, vertical scrolling, and the ability to clear
valve and actuator selection sections separately
• Manual Selection – Enter model numbers and skip the selection process
2
ELECTRONIC FAIL-SAFE
DAMPER ACTUATORS
Reliability and Safety Performance
• Patented change management system
ensures reliable fail-safe and selectable fail
position between 0-100%.
• High torque, linear and quick running
offering to handle challenging applications.
• Minimum torque guaranteed over entire
specified operating range, no loss in
performance due to temperature or
supply voltage.
GK B 24 -SR
NEMA 4 option on select models.
*GK...24-3 is 24 VAC only.
Ordering Example
3
Designate
control
24 = 24 VAC/DC
2-10 VDC
*All functions and packaging are not available with all versions.
ELECTRONIC FAIL-SAFE
ASStand Alone Handheld Tool
for F
Field Programming
The ZT
TH directly connects to Belimo’s Multi-Function
Techno
ology (MFT) series actuator offering you the ability
to quic
ckly change the parameters of the actuator, such as
contro
ol input, control feedback, runtime, and minimum and
maxim
mum values without needing to connect to a personal
computer or having another person at the front end.
Actuator Specifications
GKB NKQB
Series GK NEMA 4 Series
ELECTRONIC FAIL-SAFE
Angle of rotation 95°, adjustable with mechanical Angle of rotation 95°, adjustable with mechanical 95°, adjustable with mechanical
end stops end stops end stops
MFT electronically variable 0-100% MFT electronically variable 0-100% MFT electronically variable 0-100%
Fits shaft diameter ½” to 1.05” (center on ¾” shaft with Fits shaft diameter ½” to 1.05” (clamp centers on ¾” Fits shaft diameter ½” to 1.05” (center on ½” and ¾”
insert and on 1” without insert) and 1.05”) shaft with insert and on 1” without
Position indication reflective visual indicator (snap on) Shaft length minimum 1” insert)
Manual override external push button maximum 2¼” Position indication reflective visual indicator (snap on)
Dimensions 12.5” x 6.25” x 7.25” Manual override external push button
Direction of external switch
[318 x 159 x 184 mm]
rotation Direction of external switch
Electrical connection terminal strip (-T) rotation
Dimensions 8.3” x 4.5” x 3.4”
[211 x 114 x 86 mm] Ambient temperature -22°F to +122°F [-30°C to +50°C] Dimensions 7.25” x 3.9” x 3”
Fail-safe setting N4H Models: -40°F to +122°F [184 x 99 x 76 mm]
-3, -SR 0°-95° at 10° intervals [-40°C to +50°C] Fail-safe setting
MFT 0-100% at 10% intervals Overload protection electronic throughout rotation -1, -SR 0°-95° at 10° intervals
Electrical connection 3 ft., 18 GA plenum rated cable, ½” Auxiliary switch(es) add-on: 1 or 2 SPDT, 3A (0.5A MFT 0-100% at 10% intervals
conduit fitting inductive) @ 250V adjustable 5° Electrical connection 3 ft., 18 GA plenum rated cable, ½”
Overload protection electronic throughout rotation to 85° conduit fitting
Ambient temperature -22°F to +122°F [-30°C to +50°C] Housing NEMA 4, IP66, UL enclosure Type 4 Ambient temperature -22°F to +122°F [-30°C to +50°C]
Auxiliary switch(es) add on: 1 or 2 SPDT, 3A (0.5A Agency listings cULus according to UL 60730- Overload protection electronic throughout rotation
inductive) @ 250V adjustable 5° 1A/-2-14, CAN/CSA E60730-1:02, Auxiliary switch(es) add on: 1 or 2 SPDT, 3A (0.5A
to 85° CE according to 2004/108/EC and inductive) @ 250V adjustable 5°
2006/95/EC to 85°
Housing NEMA 2/IP54, UL enclosure Type 2
Agency listings cULus according to UL 60730-1A/- Housing NEMA 2/IP54, UL enclosure Type 2
2-14, UL 2043, CAN/CSA E60730- Agency listings cULus according to UL 60730-1A/-
1:02, CE according to 2004/108/EC 2-14, UL 2043, CAN/CSA E60730-
and 2006/95/EC 1:02, CE according to 2004/108/EC
and 2006/95/EC
AHK
2-2
GKB, NKQB Power Power Running Control Position
List Price
Add-On
Supply Consumption Time Input Feedback Accessory
Electronic Fail-Safe
Damper Actuator
Fail-Safe
On/Off
GKB24-3 ● 21 12 (3) 150 35 ● ● $1,135 ● ●
GKB Series
360 in-lbs [40 Nm] GKB24-3-T N4H ● 21/21 12/21 (3) 150 35 ● ● $2,052 ● ●
Approx. 90 sq. ft.
GKB24-SR-T N4H ● 21/21 12/21 (3) 150 35 ● ● $2,332 ● ●
54 in-lbs [6 Nm]
Approx. 12 sq. ft. NKQB24-SR ● 22 11 (3) 4 4 ● ● $822 ● ●
*Piggy back mounting on a single shaft for -MFT wired Master-Slave, 720 in-lbs maximum load, and 1” minimum diameter shaft.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
2-3
Custom Options
2
1 ACTUATOR TYPE
ELECTRONIC FAIL-SAFE
2 CLAMP
TYPE Size Actuator Series List Price
Standard Universal Clamp 3/4” to 1.05” GKX, NKQX No Charge
1
Reversible NKQX $16
None - AHKX No Charge
3 CABLES
4
CABLE
Size Actuator Series Cable Code List Price
(with conduit fitting)
3
24V Plenum Rated 3 ft. GKX, NKQX, AHKX C1 No Charge
10 ft. GKX, NKQX, AHKX C3 $28
16 ft. GKX, NKQX, AHKX C5 $48
4
PROGRAM
Running Program
GKB... Control Input Feedback Actuator Series List Price
Time Code
B = Basic stocked product -1
• Standard 150 second run time. 4 seconds On/Off - NKQX T0H No Charge
• Standard ¾” to 1.05” clamp.
• Standard 3’ plenum cable with -3 On/Off,
150 seconds - GKX F1D No Charge
Floating Point
conduit connector.
Typical Lead Time: 1 day On/Off,
90 seconds - GKX F1E No Charge
Floating Point
-SR 4 seconds 2-10 VDC 2-10 VDC NKQX T0L No Charge
GKX...
150 seconds 2-10 VDC 2-10 VDC GKX AE2 No Charge
X = Customizable product
• Choice of 10’ or 16’ cable with 90 seconds 2-10 VDC 2-10 VDC GKX AE0 No Charge
conduit connector. -MFT 4 seconds 2-10 VDC 2-10 VDC NKQX T02 No Charge
• Factory programming for run time,
control signal and feedback. 7 seconds 2-10 VDC 2-10 VDC NKQX T03 No Charge
Typical Lead Time: 3 days or less 10 seconds 2-10 VDC 2-10 VDC NKQX T04 No Charge
2 No Charge 150 seconds On/Off 2-10 VDC GKX, AHKX J02 No Charge
150 seconds PWM (0.02-5 sec) 2-10 VDC GKX, AHKX W02 No Charge
1 $1,562
Multi-Function Technology offers a wide variety of programmable control inputs and feedback signals. Parameters can be
$1,590 Final Price set for voltage control (VDC), time proportional control (PWM), floating point, on/off and feedback signal. Parameters can be
changed on-site to optimize/enable application. You can also set, modify or read position, running time, mechanical working
range, address, status, and diagnostics.
For additional MFT programming codes, refer to MFT technical documentation or visit www.belimo.us.
2-4
Custom Power Power Running Control
Control Input
Position List Cable Add-On
Electronic Fail-Safe Supply Consumption Time(s) Input MFT Feedback Price Options Accessory
Damper Actuator
Span 2 to 10 VDC
Floating Point
Floating Point
Fail-Safe
On/Off
On/Off
90, 150
GKX24-3 ● 21 12 (3) 35 ● ● $1,135 ● ● ●
(150)
90, 150
GKX24-SR ● 21 12 (3) 35 ● ● $1,415 ● ● ●
( )
(150)
90, 150
GKX24-MFT* ● 21 12 (3) 35 ● ● ● ● ● ● ● $1,562 ● ● ●
GKX Series (150)
360 in-lbs [40 Nm] 90, 150
Approx. 90 sq. ft. GKX24-3-T N4 ● 21 12 (3) 35 ● ● $1,682 ● ●
(150)
90, 150
GKX24-SR-T N4 ● 21 12 (3) 35 ● ● $1,962 ● ●
(150)
90, 150
GKX24-MFT-T N4* ● 21 12 (3) 35 ● ● ● ● ● ● ● $2,109 ● ●
(150)
AHKX Series
90, 150
101 lbf [450 N Force] AHKX24-MFT-100 ● 22 11 (3) 35 ● ● ● ● ● ● ● $1,466 ●
(150)
Approx. 4” stroke
*Piggy back mounting on a single shaft for -MFT wired Master-Slave, 720 in-lbs maximum load, and 1” minimum diameter shaft.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
2-5
Sizing and Selection Made Simple.
SelectPro is a quick and user-friendly means for accurately selecting valves, actuators,
and replacement solutions. New enhancements include:
• Updated User Interface – Toggle screen, vertical scrolling, and the ability to clear
valve and actuator selection sections separately
• Manual Selection – Enter model numbers and skip the selection process
3
FIRE AND SMOKE
DAMPER ACTUATORS
Technology that Saves Lives
• Lowest power consumption life safety
actuators available in the market.
• ISO 9001 Certified Quality Control and a
5-year warranty assure reliable operation
with exceptional customer support.
• Extensive product range offers 18 in-lbs
to 180 in-lbs from 250°F and 350°F
specifications.
FS L F 120 -S US
Fire and Torque Rating Actuator Type Power Supply Generation Control -S = Built-in
Smoke A = 133/180 in-lbs F = Spring Return 24 = 24 VAC Blank = Original Blank = On/Off Auxiliary
Switches
N = 70 in-lbs 120 = 120 VAC A = New Generation -SR = 2-10 VDC
L = 30 in-lbs 230 = 230 VAC -BAL = 3-position
T = 18 in-lbs
Ordering Example
3
Designate
control
&
DAMPER ACTUA
ATTORS
Codes require all life safety systems be inspected, maintained, and in working order.
Belimo Fire and Smoke Series Actuators are equal to or better replacements for existing old motors.
PROBLEM SOLUTION
Actuator Specifications
Direction of rotation CW/CCW mounting Direction of rotation reversible with built-in switch Direction of rotation CW/CCW mounting
Dimensions 10.2” x 3.86” x 3.23” Dimensions 9.69” x 3.86” x 3.42” Dimensions 10.59” x 3.86” x 3.25”
[259 x 98 x 82 mm] [246.1 x 98 x 86.9 mm] [269 x 98 x 82.7 mm]
Electrical connection 3 ft., 18 GA, ½” conduit fitting Electrical connection 3 ft., 18 GA, ½” conduit fitting Electrical connection 3 ft., 18 GA, ½” conduit fitting
Overload protection electronic throughout rotation Overload protection electronic throughout rotation Overload protection electronic throughout rotation
Auxiliary switch(es) 2 SPST 7A (2.5A inductive) @ Auxiliary switch(es) 2 SPDT, 7A (2.5A inductive) @ Auxiliary switch(es) 2 SPST or 2 SPDT, 7A (2.5A
120/250V 125/250V inductive) @ 120/250V
Housing NEMA 1 Housing NEMA 2/IP54, enclosure Type 2 Housing NEMA 1
Agency listings cULus listed according to UL6730- Agency listings cULus listed acc. to UL60730- Agency listings cULus listed according to UL873
1A/-2-14, CAN/CSA E60730-1 1A/-2-14, CAN/CSA E60730, CE and CAN/CSA C22.2 No. 24-93.
andCSA22.2 No. 24-93. Listed to acc. to 2004/108/EC & 2006/95/EC. Listed to UL2043
UL2043 Listed to UL2043.
**For UL555S, torque is the same for ½ hour at 350°F. ***For UL555S, torque is the same for ½ hour at 250°F. ***For UL555S, torque is the same for ½ hour at 250°F.
**For UL555S, torque is the same for ½ hour at 350°F. **For UL555S, torque is the same for ½ hour at 350°F. ***For UL555S, torque is the same for ½ hour at 250°F.
Specific models and sizes vary with each damper manufacturer. Visit www.belimo.us/firesmoke for latest listings.
Accessories
located on page 5-11
3-2
FSAF*A, FSAFB, FSAF,
Power Power Running Control Auxiliary
FSNF, FSLF, FSTF Supply Consumption Time(s) Input Switches
List Price
Spring Return
Motor Drive
VA Rating
120 VAC
230 VAC
2 SPDT
2 SPST
On/Off
FSAF24A ● 32 <30 <20 ● $618
FSAF24A-S ● 32 <30 <20 ● ● $718
FSAF*A Series FSAF120A ● 35.5 <30 <20 ● $680
180 in-lbs [20 Nm]
Approx. 18 sq. ft. @ 350°F FSAF120A-S ● 35.5 <30 <20 ● ● $782
FSAF230A ● 34 <30 <20 ● $804
FSAF230A-S ● 34 <30 <20 ● ● $905
FSAFB Series FSAFB24-SR ● 9 <75 <20 2-10 VDC $773
180 in-lbs [20 Nm]
Approx. 18 sq. ft. @ 250°F FSAFB24-SR-S ● 9 <75 <20 2-10 VDC ● $872
● ● ●
FSNF Series FSNF120 US ● 23 ‡
<15 <15 ● $550
70 in-lbs [8 Nm]
Approx. 12 sq. ft. @ 350°F FSNF120-S US ● 23‡ <15 <15 ● ● $652
FSNF230 US ● 23‡ <15 <15 ● $660
FSNF230-S US ● 23 ‡
<15 <15 ● ● $762
FSLF24 US ● 15♦ <15 <15 ● $387
FSLF24-S US ● 15 ♦
<15 <15 ● ● $461
FSLF Series FSLF120 US ● 18♦ <15 <15 ● $426
30 in-lbs [3.5 Nm]
Approx. 4 sq. ft. @ 350°F FSLF120-S US ● 18 ♦
<15 <15 ● ● $501
FSLF230 US ● 17♦ <15 <15 ● $506
FSLF230-S US ● 17 ♦
<15 <15 ● ● $579
FSTF24 US ● 5 <75 <25 ● $280
FSTF24-S US ● 5 <75 <25 ● ● $350
FSTF Series♦♦ FSTF120 US ● 3.5 <75 <25 ● $310
18 in-lbs [2 Nm]
Approx. 1.5 sq. ft. @ 250°F FSTF120-S US ● 3.5 <75 <25 ● ● $380
FSTF230 US ● 5 <75 <25 ● $385
FSTF230-S US ● 5 <75 <25 ● ● $455
‡
FSNF VA Rating Note:
Individual Fusing or Breakers are not required by Belimo. The FSNF draws higher peak current when driving against any type of stop. This requires the value of fuse or breaker
to be increased to avoid nuisance opening or tripping. A 2.5 amp slow blow fuse should be used for 24 VAC. A 0.5 amp slow blow fuse should be used for 120 VAC. A 0.25 amp
slow blow fuse should be used for 230 VAC.
♦
FSLF VA Rating Note:
Individual Fusing or Breakers are not required by Belimo. The FSLF draws higher peak current when driving against any type of stop. This requires the value of fuse or breaker to
be increased to avoid nuisance opening or tripping. A 1 amp sloww blow fuse should be used for 24 VAC. A 0.25 amp slow blow fuse
u should be used for 120 VAC. A 0.125 amp
slow blow fuse should be used for 230 VAC.
♦♦
Not recommended for retrofit or replacement.
3-3
New Tools from Belimo to Make Your Life Easier
From sizing and selecting to estimating savings, Belimo offers the following tools
to help make your job easier:
• Retrofit App allows you to quickly and easily find HVAC replacement
solutions for valves and actuators.
• Energy Valve Savings Estimator is a Microsoft Excel based tool that profiles
constant speed chilled water plant performance.
LM C B 24 -3 -T
Ordering Example
3 -T = Terminal
Designate Block
control
24 = 24 VAC/DC
*All functions and packaging are not available with all versions.
NON-SPRING RETURN
Sizing and Selection Made Simple.
SelectPro is a quick and user-friendly means for accurately selecting valves, actuators,
and replacement solutions. New enhancements include:
• Updated User Interface – Toggle screen, vertical scrolling, and the ability to clear
valve and actuator selection sections separately
• Manual Selection – Enter model numbers and skip the selection process
GMB, AMB, NMB, LMB, CMB Series
Direct Coupled, Non-Spring Return Damper Actuators
Actuator Specifications
Angle of rotation 95°, adjustable with mechanical Angle of rotation 95°, adjustable with mechanical Angle of rotation 95°, adjustable with mechanical
end stops end stops end stops
MFT electronically variable 0-100% MFT electronically variable 0-100% MFT electronically variable 0-100%
Fits shaft diameter ½” to 1.05” (centers on ¾” shaft Fits shaft diameter ½” to 1.05” (centers on ½” and ¾” Fits shaft diameter ½” to 1.05” (centers on ½” and ¾”
with insert and on 1” without insert) shafts with insert and 1.05” without shafts with insert and 1.05” without
Position indication reflective visual indicator (snap-on) insert) inserts)
Manual override external push-button Position indication reflective visual indicator (snap-on) Position indication reflective visual indicator (snap-on)
Direction of external switch Manual override external push-button Manual override external push-button
rotation Direction of external switch Direction of external switch
Dimensions 9.02” x 4.55” x 2.87” rotation rotation
[229.2 x 115.6 x 72.9 mm] Dimensions 7.47” x 3.46” x 2.49” Dimensions 6.88” x 3.15” x 2.42”
Electrical connection 3 ft., 18 GA plenum cable, ½” [189.8 x 88 x 64 mm] [174.8 x 80 x 61.4 mm]
conduit fitting Electrical connection 3 ft., 18 GA plenum cable, ½” Electrical connection 3 ft., 18 GA plenum cable,
Overload protection electronic throughout rotation conduit fitting ½” conduit fitting
Auxiliary switch(es) add-on: 1 or 2 SPDT, 3A (0.5A Overload protection electronic throughout rotation Overload protection electronic throughout rotation
inductive) @ 250V adjustable 5° Auxiliary switch(es) (-S) models: 1 SPDT, 3A (0.5A Auxiliary switch(es) add-on: 1 or 2 SPDT, 3A (0.5A
to 85° inductive) @ 250V adjustable 5° to inductive) @ 250V adjustable 5°
NON-SPRING RETURN
Housing NEMA 2/IP54, enclosure Type 2 85°, add-on: 1 or 2 SPDT, 3A (0.5 A to 85°
inductive) @ 250V one switch Housing NEMA 2/IP54, enclosure Type 2
Agency listings cULus according to UL 60730-1A/-
adjustable 5° to 85°
2-14, UL2043, CAN/CSA E60730- Agency listings cULus according to UL 60730-1A/-
1:02, CE according to 2004/108/EC Housing NEMA 2/IP54 (NEMA 1/IP20 for -T 2-14, UL2043, CAN/CSA E60730-
and 2006/95/EC models), enclosure Type 2 1:02, CE according to 2004/108/EC
Agency listings cULus according to UL 60730-1A/- and 2006/95/EC
2-14, UL 2043, CAN/CSA E60730-
1:02, CE according to 2004/108/EC
and 2006/95/EC
Angle of rotation 95°, adjustable with mechanical Angle of rotation limitless without end stops, 315° 95°, adjustable with mechanical
end stops with one end stop, 287.5° with two end stops
MFT electronically variable 0-100% stops MFT electronically variable 0-100%
Fits shaft diameter ¼” to 5/8” (self-centers on 5/8” shaft) L = counter clockwise rotation, Fits shaft diameter NM, AM- ½” to ¾”
R = clockwise rotation GM- ½” to 1.05”
Position indication reflective visual indicator (snap-on)
Fits shaft diameter ¼” to ½” (self-centers on 3/8” shaft) Manual override external push-button
Manual override external push-button
Position indication reflective visual indicator (snap-on) (NM and AM only)
Direction of external switch with magnet Direction of external switch
rotation rotation (NM and AM only)
Manual override engages with magnet.
Dimensions 6.57” x 2.6” x 2.34” magnet built-in to position indicator Dimensions NM, AM- 10.66” x 5.28” x 4.88”
[167 x 66 x 59.4 mm] [271 x 134 x 124 mm]
Dimensions 6.22” x 2.2” x 1.10”
Electrical connection 3 ft., 18 GA plenum rated cable, ½” [158 x 56 x 28 mm] GM- 12.5” x 6.25” x 7.25”
conduit fitting terminal strip (-T) [318 x 159 x 184 mm]
Electrical connection 3 ft., 18 GA plenum rated cable
models Electrical connection terminal strip (-T)
terminal strip (-T) models
Overload protection electronic throughout rotation
Overload protection electronic throughout rotation Overload protection electronic throughout rotation
Auxiliary switch(es) (-S) Models: 1 SPDT, 3A (0.5A
Auxiliary switch N/A Auxiliary switch(es) add-on: 1 or 2 SPDT, 3A (0.5A
inductive) @ 250V adjustable 5°
Housing NEMA 2/IP54 (NEMA 1/IP20 for -T inductive) @ 250V adjustable 5°
to 85°
models), enclosure Type 2 to 85°
add-on: 1 or 2 SPDT, 3A (0.5A
inductive) @ 250V one switch Agency listings cULus according to UL 60730-1A/- Housing NEMA 4/4X, IP66/IP67
adjustable 5° to 85° 2-14, UL 2043, CAN/CSA E60730- Agency listings cULus according to UL 60730-
Housing NEMA 2/IP54 (NEMA 1/IP20 for -T 1:02, CE according to 2004/108/EC 1A/-2-14, CAN/CSA E60730-1:02,
models), enclosure Type 2 and 2006/95/EC CE according to 2004/108/EC and
Agency listings cULus according to UL 60730-1A/- 2006/95/EC
2-14, UL2043, CAN/CSA E60730- Control shaft length NM, AM- minimum ¾”
1:02, CE according to 2004/108/EC maximum 2¼”
and 2006/95/EC GM- minimum 1”
maximum 3”
4-2
GMB, AMB, NMB, Power Power Running Control
Control Input
Position List Bulk
NEMA
4/4X
Add-On
LMB, CMB
Supply Consumption Time Input MFT ®
Feedback Price Pack
List Price
Accessory
Non-Spring Return
10 kΩ Resistive Feedback
5 kΩ Resistive Feedback
100 VAC to 240 VAC
Potentiometer
Floating Point
Floating Point
Motor Drive
S1A or S2A
VA Rating
On/Off
On/Off
GMB24-3 ● 6 4.0 (2.0) 150 ● ● $493 $1,120 ● ●
GMB Series
360 in-lbs [40 Nm] GMB24-SR ● 6.5 4.5 (2.0) 150 ● ● $658 $1,285 ● ●
Approx. 90 sq.ft.
GMB24-MFT† A ● 7 4.0 (1.5) 150 ● ● ● ● ● $730 ● ●
† Dual mounting on a single shaft is possible for 720 in-lb (-MFT wired Master-Slave). Please call Belimo customer service for details.
Shipped default. 150 seconds running time, 2-10 VDC control input and feedback. Field programmable with MFT tools.
B Drop-in replacement of LM24-M VAV actuator.
1
Heater option for NEMA 4/NEMA 4X has a list price adder of $370.
* ZZ-PICM
PICM position indicator and Z-ARCM
Z ARCM anti-rotation
anti rotation bracket ssold separately.
4-3
AMQB, NMQB, LMQB Series
Direct Coupled, Quick Running Non-Spring Return Damper Actuators
Actuator Specifications
Angle of rotation 95°, adjustable with mechanical Angle of rotation 95°, adjustable with mechanical Angle of rotation 95°, adjustable with mechanical
end stops end stops end stops
MFT electronically variable 0-100% MFT electronically variable 0-100% MFT electronically variable 0-100%
Fits shaft diameter ½” to 1.05” (centers on ¾” shafts Fits shaft diameter ½” to 1.05” (centers on ½” and ¾” Fits shaft diameter ½” to 1.05” (centers on ½” and ¾”
with insert and 1.05” without insert) shafts with insert and 1.05” without shafts with insert and 1.05” without
Position indication reflective visual indicator (snap-on) insert) insert)
Manual override external push-button Position indication reflective visual indicator (snap-on) Position indication reflective visual indicator (snap-on)
Direction of external switch Manual override external push-button Manual override external push-button
rotation Direction of external switch Direction of external switch
Dimensions 9.02” x 4.55” x 2.87” rotation rotation
[229.2 x 115.6 x 72.9 mm] Dimensions 7.47” x 3.46” x 2.49” Dimensions 6.88” x 3.15” x 2.42”
Electrical connection 3 ft., 18 GA plenum cable, ½” [189.8 x 88 x 64 mm] [174.8 x 80 x 61.4 mm]
conduit fitting Electrical connection 3 ft., 18 GA plenum cable, ½” Electrical connection 3 ft., 18 GA plenum cable, ½”
Overload protection electronic throughout rotation conduit fitting conduit fitting
Auxiliary switch(es) add-on: 1 or 2 SPDT, 3A (0.5A Overload protection electronic throughout rotation Overload protection electronic throughout rotation
inductive) @ 250V adjustable 5° Auxiliary switch(es) add-on: 1 or 2 SPDT, 3A (0.5A Auxiliary switch(es) add-on: 1 or 2 SPDT, 3A (0.5A
to 85° inductive) @ 250V adjustable 5° inductive) @ 250V adjustable 5°
NON-SPRING RETURN
4-4
AMQB, NMQB, LMQB Power Power Running Control
Control Input
Position
List Price
Add-On
Quick Running
Supply Consumption Time Input MFT ®
Feedback Accessory
Non-Spring Return
10 kΩ Resistive Feedback
5 kΩ Resistive Feedback
100 VAC to 240 VAC
Potentiometer
Floating Point
Floating Point
Motor Drive
S1A or S2A
VA Rating
On/Off
On/Off
AMQB Series AMQB24-1 ● 23 15 (1.5) 7 ● $577 ● ●
140 in-lbs [16 Nm]
Approx. 16 sq.ft. AMQB24-MFT A ● 23 15 (1.5) 7 ● ● ● $613 ● ●
Shipped default. 2-10 VDC control input and feedback. Field programmable with MFT tools.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
4-5
AHB, AHQB, LHB, LHQB, LUB Series
Direct Coupled, Non-Spring Return Damper Actuators
Actuator Specifications
LHQB
Series LUB
22 lbf
Series
[100 N Force] 27 in-lbs [3 Nm]
4” stroke
4-6
AHB, AHQB, LHB, Power Power Running Control
Control Input
Position
List Price
LHQB, LUB
Supply Consumption Time Input MFT ®
Feedback
Non-Spring Return
10 kΩ Resistive Feedback
5 kΩ Resistive Feedback
100 VAC to 240 VAC
Floating Point
Motor Drive
VA Rating
On/Off
On/Off
AHB24-3-100 ● 4.5 2.0 (0.5) 150* ● ● $408
4-7
Custom Options
1 ACTUATOR TYPE
2 CLAMP
2 TYPE Size Actuator Series List Price
Standard Universal Clamp 5/8” LMX No Charge
3/8” LMX No Charge
1/2” LMX No Charge
1 3/4” LMX No Charge
1/2” to 1.05” GMX, AMX, NMX No Charge
1/2” to 3/4” Reversible AMX, NMX $16
4
8 mm to 12 mm LUX No Charge
8 mm to 12 mm with end stop LUX No Charge
3 Formfit 8 mm X 8 mm LUX No Charge
Formfit 10 mm X 10 mm LUX No Charge
Formfit 12 mm X 12 mm LUX No Charge
3 CABLES
CABLE (with conduit fitting) Size Actuator Series Cable Code List Price
GMB...
24V Plenum Rated 3 ft. All Non-Spring Return C1 No Charge
B = Basic stocked product
• Standard 150 second run time. 10 ft. All Non-Spring Return C3 $28
• Standard ¾” to 1.05” clamp. 16 ft. All Non-Spring Return C5 $48
NON-SPRING RETURN
GMX... 4 PROGRAM
X = Customizable product Running Time Control Input Feedback Actuator Series Program Code List Price
• Choice of 10’ or 16’ cable with -3 On/Off, GMX, AMX, NMX, LMX, AHX,
conduit connector. 150 seconds - 000 No Charge
Floating Point LHX, LUX
• Option of 3’ right angle cables for tight
On/Off,
spaces (-3 version only). 95 seconds - AMX, NMX, LMX, LHX 002 No Charge
Floating Point
• Factory programming for run time,
On/Off,
control signal and feedback. 45 seconds - LMX 004 No Charge
Floating Point
4 No Charge 150 seconds 8-20 VDC 2-10 VDC AHX, LHX AAL No Charge
100 seconds 0.5-10 VDC 0.5-10 VDC AMX, NMX, LMX A28 No Charge
3 $28
95 seconds 0.5-10 VDC 0.5-10 VDC NMX ACA No Charge
2 No Charge 150 seconds 6-9 VDC 2-10 VDC LUX A56 No Charge
For additional MFT programming codes, refer to MFT technical documentation or visit www.belimo.us.
4-8
Custom Power Power Running Control
Control Input
Position Custom NEMA 4/4X Add-on
List Price
Non-Spring Supply Consumption Time Input MFT ®
Feedback Options List Price Accessory
Return Damper
Potentiometer
Floating Point
Floating Point
S1A or S2A
VA Rating
On/Off
On/Off
GMX24-3 ● 6 4.0 (2.0) 150 ● ● ● $493 $1,120 ● ●
GMX Series GMX24-SR ● 6.5 4.5 (2.0) 150 ● ● ● $658 $1,285 ● ●
360 in-lbs [40 Nm] GMX24-PC ● 7 4.0 (1.5) 150 ● ● ● $793 ● ●
Approx. 90 sq.ft. GMX120-3 ● 7 4.0 (2.0) 150 ● ● ● $539 ● ●
GMX24-MFT† ● 7 4.0 (1.5) 75-300 (150) ● ● ● ● ● ● ● ● $730 $1,383 ● ●
AMX24-3 ● 5.5 2.5 (0.5) 95 ● ● ● $348 $634 ● ●
AMX24-3-T ● 5.5 2.5 (0.5) 95 ● ● ● $324 ● ●
AMX24-SR ● 5 2.5 (0.4) 95 ● ● ● $507 $793 ● ●
AMX24-SR-T ● 5 2.5 (0.4) 95 ● ● ● $483 ● ●
AMX Series AMX24-PC ● 5.5 3.5 (1.3) 90 ● ● ● $574 ● ●
180 in-lbs [20 Nm]
Approx. 45 sq.ft.
AMX120-3 ● 7 3.0 (0.6) 95 ● ● ● $434 ● ●
AMX120-SR ● 7.5 4.0 (1.0) 95 ● ● ● $596 ● ●
AMX24-MFT ● 6 3.5 (1.3) 90-300 (150) ● ● ● ● ● ● ● ● $549 $835 ● ●
AMCX24-MFT ● 6 3.5 (1.3) 35-120 (35) ● ● ● ● ● ● ● ● $660 ● ●
AMX24-MFT95 ● 6 3.5 (1.3) 75-150 (150) ● ● ● ● $574 ● ●
AMQ Series
AMQX24-MFT ● 26 15 (1.5) 7-15 (7) ● ● ● ● ● $613 ● ●
140 in-lbs [16 Nm]
NMX24-3 ● 4 2.0 (0.2) 95 ● ● ● $248 $534 ● ●
NMX24-3-T ● 4 2.0 (0.2) 95 ● ● ● $222 ● ●
NMX24-SR ● 5 2.5 (0.4) 95 ● ● ● $348 $634 ● ●
NMX Series NMX24-SR-T ● 5 2.5 (0.4) 95 ● ● ● $323 ● ●
90 in-lbs [10 Nm] NMX120-3 ● 5.5 2.5 (0.6) 150 ● ● ● $288 ● ●
Approx. 22 sq.ft. NMX120-SR ● 6.5 3.5 (1.0) 150 ● ● ● $408 ● ●
NMX24-MFT ● 6 3.5 (1.3) 45-150 (150) ● ● ● ● ● ● ● ● $441 $753 ● ●
NMX24-MFT95 ● 6 3.5 (1.3) 45-150 (150) ● ● ● ● $512 ● ●
NMCX24-MFT ● 5 3.0 (0.6) 20-75 (20) ● ● ● ● $512 ● ●
NMQ Series
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Actuator Specifications
ZG-JSLA
Running List Price
Power Auxiliary List Price*
BASIC PRODUCT Control Input Feedback Time(s) VA Rating (Linkage
Supply Switch (Actuator +
[Default] Only)
Linkage)
Jackshaft (only) ZG-JSL $261
CUSTOMIZE PRODUCTS REORDER #
ZG-JSLA + AMX24-3 JSL+AM000 7C1 002 On/Off, Floatingg Point Add-on 24 VAC/DC 95 seconds 5.5 Add-on $559
ZG-JSLA + AMX24-SR JSL+AM030 7C1 002 2-10 VDC (4-20 mA*) 2-10 VDC 24 VAC/DC 95 seconds 5.5 Add-on $718
ZG-JSLA + AMX24-MFT JSL+AM100 7C1 A01 Various Various 24 VAC/DC 95 seconds 6 Add-on $760
ZG-JSLA + NMX24-3 JSL+NM000 7C1 002 On/Off, Floatingg Point Add-on 24 VAC/DC 95 seconds 4 Add-on $459
ZG-JSLA + NMX24-SR JSL+NM030 7C1 002 2-10 VDC ((4-20 mA*)) 2-10 VDC 24 VAC/DC 95 seconds 5 Add-on $559
4-10
5
DAMPER ACTUATOR
ACCESSORIES
Enhance Performance
and Add Value
• Universal mounting brackets are designed
for applications where the actuator cannot
be mounted directly to the shaft.
• Jackshaft linkage (JSL) or crank arm adaptor
kits allow for easy retrofit applications.
• ZTH handheld device enables programming
of any ePIV, Energy Valve, or MFT actuators.
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB List
PROGRAMMING TOOLS LF SY
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX Price
MFT-P
Belimo MFT configuration
software (V3.X). ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● $166
Includes: PC-Tool software
(hardware not included)
INTERFACES, CABLES
ZK1-GEN
Cable for use with ZTH-GEN,
ZTH US, or ZIP-USB-MP US ● ● ● ● ● ● ● ● ● ● $107
to connect to actuator via
diagnostic/programming socket.
ZK2-GEN
Cable for use with ZTH-GEN,
ZTH US, or ZIP-USB-MP US
● ● ● ● ● ● ● ● ● ● ● ● ● ● $49
to connect to actuators not
equipped with diagnostic/
programming socket.
ZK4-GEN
Cable for use with ZTH US to
Available for all MFT Actuators $107
connect to UK24... gateways and
VRP-M.
ZK6-GEN
Cable for use with ZTH-GEN,
ZTH US, or ZIP-USB-MP US ● $51
to connect to SY actuator via
RJII port.
UK24LON
LON gateway that can connect Available for all MFT Actuators $903
up to 8 MFT actuators.
DAMPER ACCESSORIES
UK24BAC
BACnet gateway that can Available for all MFT Actuators $903
connect up to 8 MFT actuators.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
UK24MOD
Modbus gateway that can Available for all MFT Actuators $903
connect up to 8 MFT actuators.
ZTH US
Handheld programming tool
Available for all MFT Actuators $701
with ZK1-GEN, ZK2-GEN, and
ZK6-GEN.
5-1
Mechanical Damper Actuator Accessories
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB List
CLAMPS LF
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX Price
K9-2
● $48
Standard EFB clamp (½” to 1.05”)
K7-2
Standard AFB/NFB clamp ● ● $29
(½” to 1.05”)
K6 US
● $21
Standard LF clamp (3/8” to ½”)
K6-1
● $18
Jackshaft clamp (½” to ¾”)
K8 US
● $18
Standard TF clamp (¼” to ½”)
K-GM20
● ● $35
Reversible clamp (½” to 1.05”)
K-AM25
● ● ● $23
Standard clamp (½” to 1.05”)
K-SA
● ● $29
Reversible clamp (½” to ¾”)
K-NA
● $29
Reversible clamp (½” to ¾”)
DAMPER ACCESSORIES
K-LM20
● $16
Clamp (¾”)
K-LM12
● $16
Clamp (½”)
K-LM10
● $16
Clamp (3/8”)
K-LU
● $31
Spindle clamp (5/16” to ½”)
5-2
Mechanical Damper Actuator Accessories
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB
POSITION INDICATORS / ROTATION LIMITERS LF List Price
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX
IND-EFB
● $17
Position indicator
IND-AFB
● ● $12
Position indicator
IND-LF
● $12
Position indicator
IND-TF
● $12
Position indicator
ZDB-LF
● $12
Angle of rotation limiter for LF
ZDB-TF
● $12
Angle of rotation limiter for TF
ZDB-LU
● $15
Angle of rotation limiter for LU
MOUNTING BRACKETS
DAMPER ACCESSORIES
ZG-100
Right angle ● ● ● ● ● ● ● ● $86
(17” H x 111/8” W x 6” base)
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
ZG-101
Right angle ● ● ● ● ● ● ● $86
(13” H x 11” W x 77/16” base)
ZG-102
Multiple actuator mounting ● ● ● $84
bracket
ZG-103
Right angle ● ● ● ● ● $63
(7½” H x 11” W x 2¾” base)
ZG-104
Right angle ● ● ● ● ● $63
(135/8” H x 7½” W x 4” base)
* Positions crank arm in same relative position as crank arm on electric foot mount-type linkage actuators.
5-3
Mechanical Damper Actuator Accessories
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB
MOUNTING BRACKETS LF List Price
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX
ZG-112*
Right angle ● $35
(4½” H x 5½” W x 2½” base)
ZG-113*
Right angle ● $35
(4½” H x 5½” W x 2½” base)
ZG-118*
Channel ● ● $58
(5 7/8” H x 5½” W x 219/32” base)
ZG-120
● ● ● ● ● ● ● ● $84
Jackshaft mounting bracket
Z-AF
AF/NF to AFB, AFX/NFB, NFX ● ● $21
retrofit mounting bracket
Z-SF
● ● $388
20 piece Z-AF kit
Z-GMA
GM to GMB, GMX retrofit
● ● $18
mounting bracket (supplied with
DAMPER ACCESSORIES
Z-NMA
NM to NMB, NMX retrofit
● ● $18
mounting bracket (supplied with
non-spring return actuators)
* Positions crank arm in same relative position as crank arm on electric foot mount-type linkage actuators.
5-4
Mechanical Damper Actuator Accessories
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB List
CRANK ARM ADAPTOR KITS LF
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX Price
● $44
Crank arm
● ● $29
Crank arm for shafts to ¾”
KH-LF
● $27
Crank arm for shafts to ½”
KH-LFV
V-bolt kit for direct coupling ● $12
with KH-LF
KH-TF US
● $31
Crank arm with 5/16” slot
KH-TF-1 US
● $31
Crank arm with ¼” slot
AH-GMA
● ● $37
GMB, GMX crank arm
AH-25
NKQ, NMB, NMX and AMB, AMX ● ● ● $31
crank arm
ZG-EFB
● $107
DAMPER ACCESSORIES
Crank arm adaptor kit
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
ZG-AFB
● ● $89
Crank arm adaptor kit
ZG-AFB118
● ● $86
Crank arm adaptor kit
ZG-LF112
Crank arm adaptor kit ● $56
(includes ZG-112 & KH-LF)
ZG-LF2
Crank arm adaptor kit ● $65
(includes mounting hardware)
ZG-LFC114
Trane Voyager retrofit kit ● $105
(includes retrofit bracket)
5-5
Mechanical Damper Actuator Accessories
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB List
CRANK ARM ADAPTOR KITS LF
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX Price
ZG-ECON1
Honeywell economizer retrofit kit
● $94
(includes 20477-00001 retrofit
bracket)
ZG-ECON2
Honeywell economizer retrofit
● $75
kit (logic module bracket not
included)
20477-00001
● $56
Honeywell logic module bracket
ZG-TF112
Crank arm adaptor kit ● $58
(includes ZG-113 and KH-TF-1)
ZG-TF2
Crank arm adaptor kit ● $49
(includes mounting hardware)
ZG-GMA
● ● $94
Crank arm adaptor kit
DAMPER ACCESSORIES
ZG-NMA
● ● ● $63
Crank arm adaptor kit
ZG-JSL
Jackshaft linkage
● ● ● ● ● ● ● ● ● $261
Note: LF requires K6-1 clamp
Note: EFB, EFX requires ZG-121
ZG-121
Support plate for ● $57
ZG-JSL with EF actuator
5-6
Mechanical Damper Actuator Accessories
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB
BALL JOINTS, DAMPER CLIPS, PUSH RODS LF List Price
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX
KH6**
Universal crank arm for KG6 ball
joint. Slot width ¼” [6.2 mm]. For
● ● ● ● ● $21
damper shafts: 3/8” to 11/16” diameter
[10 to 18 mm] or 3/8” to 9/16” sq.
[10 to 14 mm].
KH8**
Universal crank arm for KG8 or
KG10A ball joint. Slot width 21/64”
● ● ● ● ● ● ● $21
[8.2 mm]. For damper shafts: 3/8”
to 11/16” diameter [10 to 18 mm] or
3/ ” to 9/ ” sq. [10 to 14 mm].
8 16
KH10
Universal crank arm.
Slot width 21/64” [8.2 mm]. ● ● ● ● ● $49
For damper shafts 9/16” to 1”
diameter [14 to 25 mm].
KH12
Universal crank arm.
Slot width 21/64” [8.2 mm]. ● ● ● ● ● ● ● $28
For damper shafts ¾” to 1”
diameter [20 to 25 mm].
KG6
Ball joint (5/16” diameter rod) ● ● ● ● ● ● $18
zinc plated
KG8
Ball joint (5/16” diameter rod, 90°) ● ● ● ● ● ● ● ● ● ● $23
galvanized steel
DAMPER ACCESSORIES
KG10A
Ball joint for KH8 (3/8” diameter rod) ● ● ● ● ● ● ● ● ● ● ● $25
zinc plated
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
SH8
Push rod for KG6 & KG8 ball joints ● ● ● ● ● ● ● ● ● ● $27
(36”, 5/16” diameter)
SH10
Push rod for KG10 ball joints ● ● ● ● ● ● ● ● ● $35
(36”, 3/8” diameter)
ZG-DC1
Damper clip for damper blade, ● ● ● ● ● ● ● ● ● ● $41
3½” width
ZG-DC2
Damper clip for damper blade, ● ● ● ● ● ● ● ● ● ● $45
6” width
**Universal crank arms are not designed to be directly attached to an actuator’s universal clamp. They also cannot be modified for the same installation. Universal crank arms are to be
mounted to a control shaft only. Crank arm adaptor kits can be found on the respective actuator pages.
5-7
Mechanical Damper Actuator Accessories
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB List
HOUSINGS LF
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX Price
ZS-T
Terminal cover for NEMA 2 ● ● ● $23
(-T models)
ZS-100
Weather shield - galvaneal ● ● ● ● ● ● ● ● ● ● ● $155
(13” L x 8” W x 6” D)
ZS-101
● ● ● ● ● ● ● ● ● ● ● $35
Base plate for ZS-100
ZS-150
Weather shield - polycarbonate
● ● ● ● ● ● ● ● ● ● ● $175
with foam seal
(16” L x 8 3/8” W x 4” D)
ZS-260
● ● ● ● ● ● $2,589
Explosion proof housing
ZG-109
● ● ● ● ● ● $123
Right angle bracket for ZS-260
DAMPER ACCESSORIES
ZG-110
● ● ● ● ● ● $147
Stand-off bracket for ZS-260
ZS-300-5
NEMA 4X, 316L stainless steel ● ● ● ● ● ● $2,584
enclosure
ZS-300-C1
½” Shaft adaptor (standard with ● ● ● ● ● ● $325
ZS-300)
ZS-300-C2
● ● ● ● ● ● $326
¾” Shaft adaptor
ZS-300-C3
● ● ● ● ● ● $473
1” Shaft adaptor
5-8
Mechanical Damper Actuator Accessories
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB List
SHAFT ADAPTORS LF CM
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX Price
AV6-20
6.7” Shaft extension fits ¼” to ● ● ● ● $51
¾” diameter shafts
AV8-25*
9.8” Shaft extension fits 5/16” to ● ● ● ● ● ● ● ● $60
1” diameter shafts
ZG-JSA-1
● ● ● ● ● ● ● $201
1” Jackshaft adaptor [11”]
ZG-JSA-2
● ● ● ● ● ● ● $441
15/16” Jackshaft adaptor [12”]
ZG-JSA-3
● ● ● ● ● ● ● ● $370
1.05” Jackshaft adaptor [12”]
ZG-NMSA-1
Shaft extension for ½” diameter ● ● $56
shafts [3.8”]
ZG-LMSA
Shaft extension for ½” diameter ● $63
shafts [3”]
ZG-LMSA-1
Shaft extension for 3/8” ● ● $63
diameter shafts [4”]
ZG-LMSA-½”-5
Shaft extension for ½” diameter ● ● $70
shafts [5”]
MISCELLANEOUS
EF-P
● ● ● $10
Anti-rotation bracket
AF-P
● ● $10
Anti-rotation bracket
DAMPER ACCESSORIES
LF-P
● $10
Anti-rotation bracket
TF-P
● ● ● ● ● $8
Anti-rotation bracket
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Z-DS1
Rotary support for lateral force ● ● $37
compensation
Z-KSA
5/ ” Shaft clevis
● $47
16
Z-KSC
3/ ”- 16 Shaft clevis
● $47
8
ZG-119
● ● $54
Bracket for linear actuators
Tool-06 No
● ● ● ● ● ● ● ●
8 mm and 10 mm wrench Charge
Tool-07 No
● ● ●
13 mm wrench Charge
Z-ARCM
● $6
Anti-rotation bracket
Z-PICM
● $8
Position indicator
5-9
Electronic Damper Actuator Accessories
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB List
AUXILIARY SWITCHES & POTENTIOMETERS LF
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX Price
S1A
Auxiliary switch, 1x SPDT, 3A
● ● ● ● ● ● $88
resistive (0.5A inductive) @ 250
VAC
S2A
Auxiliary switch, 2x SPDT, 3A
● ● ● ● ● ● $131
resistive (0.5A inductive) @ 250
VAC
P475
Shaft mount, non-Mercury
● ● ● ● ● ● ● ● ● ● ● ● $171
auxiliary switch for 1/2” diameter
shafts
P475-1
Shaft mount, non-Mercury
● ● ● ● ● ● ● ● ● ● ● ● $182
auxiliary switch for 1” diameter
shafts.
P140A GR
● ● ● ● ● ● $144
Feedback potentiometer 140 Ω
P500A GR
● ● ● ● ● ● $144
Feedback potentiometer 500 Ω
P1000A GR
● ● ● ● ● ● $144
Feedback potentiometer 1000 Ω
P2800A GR
● ● ● ● ● ● $144
Feedback potentiometer 2800 Ω
P5000A GR
● ● ● ● ● ● $144
Feedback potentiometer 5000 Ω
P10000A GR
● ● ● ● ● ● $144
Feedback potentiometer 10000 Ω
DAMPER ACCESSORIES
Z-SPA*
Adaptor for auxiliary switches and ● ● $17
potentiometers
ZG-SGF
● ● ● ● ● ● ● ● ● ● ● ● ● ● $25
Mounting plate for SGF
IRM-100
Input rescaling module ● ● ● ● ● ● ● ● ● ● ● ● ● ● $219
(proportional models)
PTA-250
Pulse width modulation interface ● ● ● ● ● ● ● ● ● ● ● ● ● ● $278
(proportional models)
ADS-100
Analog to digital switch ● ● ● ● ● ● ● ● ● ● ● ● ● ● $234
(proportional models)
5-10
Electronic Damper Actuator Accessories
EFB AFB NFB TFB GKB NKQB GMB AMB NMB LMB AHB LHB LUB List
CONTROL & POSITIONING LF
EFX AFX NFX TFX GKX NKQX GMX AMX NMX LMX AHX LHX LUX Price
ZG-R01
4 to 20 mA adaptor, 500 Ω, ¼” W ● ● ● ● ● ● ● ● ● ● ● ● ● ● $21
resistor with 6” pigtail wires
ZG-R02
● ● ● ● ● ● ● ● ● ● ● ● ● ● $31
50% voltage divider
ZG-R03
Resistor kit for -MFT95 actuators ● ● ● ● ● $21
in a 0 to 135 Ω control application
MISCELLANEOUS
PS-100
● ● ● ● ● ● ● ● ● ● ● ● ● ● $1,416
Actuator power supply simulator
MFT-XFMR
Replacement transformer for ● ● ● ● ● ● ● ● ● ● ● ● ● ● $78
PS-100
NSV24 US
● ● ● ● ● ● ● $817
Battery back-up module
NSV-BAT
12V 1.2AH battery (2 required for ● ● ● ● ● ● ● $124
NSV24 US)
ZG-X40
● ● ● ● ● ● ● ● ● ● ● ● ● ● $93
120 to 24 VAC, 40 VA transformer
DAMPER ACCESSORIES
TF-CC US
● ● ● ● ● ● ● ● ● ● ● ● ● $15
Conduit connector
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
43442-00001
No
Cable gland ● ● ● ● ● ●
Charge
(for NEMA 4 models)
11097-00001
No
Gasket for cable gland ● ● ● ● ● ●
Charge
(for NEMA 4 models)
ZG-CBLS
Electrical junction box for LF ● $93
actuators
List
FIRE AND SMOKE ACCESSORIES FSAF FSNF FSLF FSTF
Price
BAE165 US
● ● ● ● $208
165°F Electric thermal sensor. SPST, NC
S2A-F US
Auxiliary switch, 2x SPDT, 3A resistive ● ● ● $308
(0.5A inductive) @ 250 VAC
5-11
PRESSURE INDEPENDENT VALVES
PRESSURE INDEPENDENT
VALVES (ENERGY VALVES,
PICCV & EPIV)
Energy Efficient Valves
• No manual balancing valve required.
• Automatic Dynamic Balancing optimizes
system performance at all times.
• Improves Delta T reducing pumping and
chiller costs.
Energy Valve Valve Size Flow Rate Actuator Type Power Supply
NPT 2-way 050 = ½” 1.65 - 713 GPM Non-Spring Return 24 = 24 VAC/DC EV = ½” to 6”
Flanged 2-way 075 = ¾” Refer to valve pages for LRB (default)
100 = 1” a full list LRX (customized)
125 = 1¼” NRB (default)
150 = 1½” NRX (customized)
200 = 2” ARB (default)
250 = 2½” ARX (customized)
300 = 3” GRB (default)
400 = 4” GRX (customized)
500 = 5” Electronic Fail-Safe
600 = 6” AKRB (default)
S = Stainless Steel AKRX (customized)
Ball and Stem
GKRB (default)
GKRX (customized)
DEFAULT SETTINGS
Installation Control and
Maximum Flow Delta T Manager Delta T Setpoint Actuator Setup
Position Feedback Signal
Maximum flow of Return Off 10°F [5.6°C] Non-Spring Return- Control Signal (Y)
the valve Normally Closed (NC) DC 2 to 10V
Electronic Fail-Safe- Feedback Signal (U)
Normally Closed (NC) / DC 2 to 10V
Fail Closed (FC)
2” 2”
Flow Code ½” GPM ¾” GPM 1” GPM 1¼” GPM 1½” GPM 2½” GPM 3” GPM 4” GPM 5” GPM 6” GPM
(76.1 GPM) (100 GPM)
30 1.65 3.1 5.5 8.6 11.9 22.8 30 38 54 95 149 214
37 2 3.8 6.7 10.5 14.7 28.2 37 47 67 117 183 264
45 2.5 4.6 8.2 12.8 17.8 34.2 45 57 81 143 223 321
55 3 5.7 10 15.7 21.8 41.9 55 70 99 174 272 392
63 3.5 6.5 11.5 18 24.9 47.9 63 80 113 200 312 449
65 3.6 6.7 11.8 18.5 25.7 49.5 65 83 117 206 322 463
68 3.7 7 12.4 19.4 26.9 51.7 68 86 122 216 337 485
71 3.9 7.3 12.9 20.2 28.1 54 71 90 128 225 351 506
72 4 7.4 13.1 20.5 28.5 54.8 72 91 130 228 356 513
75 4.1 7.7 13.7 21.4 29.7 57.1 75 95 135 238 371 535
76 4.2 7.8 13.8 21.7 30.1 57.8 76 97 137 241 376 542
78 4.3 8 14.2 22.2 30.9 59.4 78 99 140 247 386 556
80 4.4 8.2 14.6 22.8 31.7 60.9 80 102 144 254 396 570
82 4.5 8.4 14.9 23.4 32.5 62.4 82 104 148 260 406 585
83 4.6 8.5 15.1 23.7 32.9 63.2 83 105 149 263 411 592
85 4.7 8.8 15.5 24.2 33.7 64.7 85 108 153 269 421 606
87 4.8 9 15.8 24.8 34.5 66.2 87 110 157 276 431 620
89 4.9 9.2 16.2 25.4 35.2 67.7 89 113 160 282 441 635
91 5 9.4 16.6 25.9 36 69.3 91 116 164 288 450 649
93 5.1 9.6 16.9 26.5 36.8 70.8 93 118 167 295 460 663
95 5.2 9.8 17.3 27.1 37.6 72.3 95 121 171 301 470 677
97 5.3 10 17.7 27.6 38.4 73.8 97 123 175 307 480 692
00 5.5 10.3 18.2 28.5 39.6 76.1 100 127 180 317 495 713
2. SELECT CODE FOR INSTALLATION POSITION 3. SELECT CODE FOR DELTA T MANAGER STATUS
Where the Energy Valve is installed in a system either on the supply or return. The Delta T Manager provides a fixed delta T setpoint.
Delta T Scaling varies the setpoint.
Code Description
Code Description
A Supply
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
0 OFF
Z Return
1 ON Delta T Manager
2 ON Delta T Scaling
ENERGY VALVE
Code Description Code Description Code Description Code Description
07 07°F / 3.9°C 21 21°F / 11.7°C 35 35°F / 19.4°C 49 49°F / 27.2°C
6-3
Energy Valve Set Up Options
Programmed Ordering Example Continued
5. SELECT CODE FOR ACTUATOR SETUP 6. SELECT CODE FOR CONTROL AND FEEDBACK SIGNAL
EV250S-127+ARX24-EV(97,
97 Z,1,13,
Z 1 13 2,
2 2)
2
6-4
Control Valve Product Range
Energy Valve Product Range
Valve Nominal
Type Suitable Actuators
Size
DN Non-Spring Electronic
GPM Range Inches 2-way
[mm] Return Fail-Safe
LRB(X)24-EV
Equal Percentage
3.1 - 10.3* ¾ 20 EV075S-103 EV Characteristic
NRB(X)24-EV
NPT
AKRB(X)24-EV
Controls Power: with its Power Control logic, providing linear
heat transfer regardless of temperature and pressure variations.
22.8 - 76.1* 2 50 EV200S-761 Manages Delta T: by solving Low Delta T Syndrome. In addi-
tion, it reduces pumping costs while increasing chiller/boiler
efficiency by optimizing coil efficiency.
30-100* 2 50 EV200S-1000
Actuator Specifications
Control type proportional
ARB(X)24-EV
SET-UP
2-WAY VALVE
LRX Series NC* Valve: Normally NO* Valve: Normally
NON-SPRING RETURN NRX Series Closed- valve will open as Open - valve will close as
ACTUATOR ARX Series voltage increases. voltage increases.
STAYS IN LAST POSITION GRX Series
AKRX Series NO/FO Valve: Normally NO/FC Valve: Normally NC/FO Valve: Normally NC/FC Valve: Normally
GKRX Series Open-valve will close Open -valve will close Closed - valve will open Closed - valve will open
as voltage increases. as voltage increases. as voltage increases. as voltage increases.
Actuator switch on CCW. Actuator switch on CCW. Actuator switch on CW. Actuator switch on CW.
ELECTRONIC FAIL-SAFE Spring Action: Will fail Spring Action: Will fail Spring Action: Will fail Spring Action: Will
open upon power loss. closed upon power loss. open upon power loss. fail closed upon power
loss.
*Feedback signal is always NC Valve is set up at the factory based on customer needs, see ordering example on page 6-3.
FUNCTIONALITY
The Energy Valve offers different operating modes which can be selected using the Web View or ZTH US.
change in pressure and modulates T1 setpoint, the flow will be reduced by the Delta
the actuator to maintain the flow T Manager logic to achieve the dT setpoint,
setpoint based on the DDC control regardless of the control signal Y.
Y Signal controls the flow. signal. Y Signal controls the flow as long as the 6T
is above the dT setpoint.
If the measured coil power is below coil power is below setpoint, flow will be
setpoint, flow will be increased. If increased. If the measured coil power is
T1 T1
the measured coil power is above above setpoint, flow will be decreased as long
setpoint, flow will be decreased as as the defined V’max is not exceeded. If the
long as the defined V’max is not Y Signal controls the thermal power
measured T is lower than the dT setpoint,
Y Signal controls the coil thermal power
setpoint (BTU/hr or kW). exceeded. setpoint as long as the 6T is above the dT flow will be reduced by the Delta T Manager
setpoint. logic and will override the thermal power
control setpoint.
6-6
Energy Valves
Operation/Installation
INSTALLATION
Inlet Length
The Energy Valve requires a section of straight pipe on the valve inlet to guarantee sensor accuracy. This section
should be at least 5 pipe diameters long with respect to the size of the valve.
PIPING
The Energy Valve is recommended to be installed on the return side of the coil. This diagram illustrates a typical application. Consult engineering specification and
drawings for particular circumstances.
ENERGY VALVE
6-7
Energy Valves
Operation/Installation
ORIENTATION
Energy Valve shall be installed with flow in the direction of the arrow on the valve body.
The valve assembly can be installed in a vertical or horizontal arrangement, as long as the actuator is positioned to avoid condensation from
dripping onto the actuator or flow sensor.
6-8
Energy Valves with Non-Spring Return and Electronic Fail-Safe Actuators
2-way Valves with Stainless Steel Ball and Stem, Threaded NPT
Valve Specifications
chilled or hot water, up to 60%
Service glycol max (open loop/steam not
allowed)
Flow Characteristic equal percentage/linear
End Fitting NPT female ends
Body forged brass, nickel plated
Sensor Housing forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
O-ring EPDM
Media Temp. Range
14°F to 250°F [-10°C to +120°C]
1.65 to 76.1 GPM
Media Temp. Range
39°F to 250°F [4°C to 120°C]
EV200S-1000
Diff. Pressure Range 5 to 50 psid or 1 to 50 psid with
1.65 to 76.1 GPM flow reductions*
Diff. Pressure Range 8 to 50 psid or 1 to 50 psid with
EV200S-1000 flow reductions*
Leakage 0%
Inlet Length to Meet
Specified Measurement 5X nominal pipe size (NPS)
Accuracy
ultrasonic with glycol and
Flow Sensor Technology
temperature compensation
Power Supply for the
sensor is powered by the actuator
Flow Sensor
Remote Temperature standard: 2.75 ft. [0.8m],
Sensor Length 9.8 ft. [3m]
ENERGY VALVE
Electronic Fail-Safe actuator: AKRX24-EV
* See flow reduction chart on page 6-8.
6-9
Energy Valves with Non-Spring Return and Electronic Fail-Safe Actuators
2-way Valves with Stainless Steel Ball and Stem, Flanged Ends
Valve Specifications
chilled or hot water, up to 60%
Service glycol max (open loop/steam not
allowed)
Flow Characteristic equal percentage/linear
pattern to mate with ANSI 125
End Fitting
flange
Body cast iron - GG25
Sensor Housing ductile iron - GGG50
Ball stainless steel
Stem stainless steel
Seat PTFE
Media Temperature Range
14°F to 250°F [-10°C to +120°C]
(Water)
Conductivity min. 20uS/cm
5 to 50 psid or 1 to 50 psid with
Differential Pressure Range
flow reductions*
Leakage 0%
Inlet Length to Meet
Specified Measurement 5X nominal pipe size (NPS)
Accuracy
Power Supply for the
sensor is powered by the actuator
Flow Sensor
standard: 32.8 ft. [10m]
Remote Temperature
optional: 4.9 ft. [1.5m], 9.8 ft. [3m],
Sensor Length
16.4 ft. [5m]
6-10
Valve Accessories
Energy Valve
ZTH US
Handheld interface module that allows • • • • • • $701
field programming
WEATHER SHIELDS
ZS-EPIV-EV-20-NF
Sizes ½” [DN15] to 1” [DN25] • $500
non-spring return (cover only)
ZS-EPIV-EV-50-SCNF
Sizes ½” [DN15] to 2” [DN50],
non-spring return (cover only) • • • • $459
Sizes 1” [DN25] to 2” [DN50],
electronic fail-safe (cover only)
ZS-EPIV-EV-80
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
ENERGY VALVE
Auxiliary switch - 1x SPDT, 3A • • • • • • $88
(0.5A inductive) @ 250 VAC
S2A
Auxiliary switch - 2x SPDT, 3A • • • • • • $131
(0.5A inductive) @ 250 VAC
ENERGY VALVE ACCESSORIES
EV050S-055
½” Energy unit- Includes flow sensor,
• • $1,022
control valve, 2 temperature sensors and 2
fittings for temperature sensors
EV075S-103
¾” Energy unit- Includes flow sensor,
• • $1,110
control valve, 2 temperature sensors and 2
fittings for temperature sensors
EV100S-182
1” Energy unit- Includes flow sensor,
• • $1,377
control valve, 2 temperature sensors and 2
fittings for temperature sensors
EV125S-285
1¼” Energy unit- Includes flow sensor,
• • $1,400
control valve, 2 temperature sensors and 2
fittings for temperature sensors
6-11
Valve Accessories
Energy Valve
M2450-EV-100
• • $823
2” Energy Valve fl ow sensor, 30 to 100 GPM
EV FS-60
• • • • $1,632
2½” - 6” Energy Valve flow sensor
ZF15-50
• • $29
Temperature sensor- threaded pipe body ½”
ZF15-75
• • $36
Temperature sensor- threaded pipe body ¾”
ZF15-100
• • $43
Temperature sensor- threaded pipe body 1”
6-12
7
PRESSURE INDEPENDENT
CONTROL VALVES (EPIV & PICCV)
Compact Performance Solution
• No manual balancing valve required.
• Automatic Dynamic Balancing optimizes
system performance at all times.
• Characterized control ball valve technology
provides self-cleaning, reliability, high close-
off and zero leakage.
Ordering Example
D01
Non-Spring Models Tagging:
NO = Normally Open D00 0.5 to 10 VDC
Valves may be
NC = Normally Closed D01 2 to 10 VDC tagged per customer
specification. ($10.00
Electronic Fail-Safe Models charge per tag)
NO/FO = Normally Open/Fail Open
NO/FC = Normally Open/Fail Closed Example:
AHU-1
NC/FO = Normally Closed/Fail Open FCU-2
NC/FC = Normally Closed/Fail Closed
Part number for tagging:
Refers to valve ports from inlet to outlet, 99981-00101
per flow arrow.
LRX24-EP
6 - 10.3* ¾ 20 P2075S
Equal Percentage
11.1 - 18.2* 1 25 P2100S
Characteristic
AKRX24-EP
NPT
NRX24-EP
The Electronic Presure Independent Control Valve (ePIV)
is a two-way valve which is unaffected by pressure
variations in a system.
26.1 - 39.6* 1½ 40 P2150S
Product Features
Provides constant flow regardless of pressure variations
32.7 - 76.1* 2 50 P2200S in the system. Simplified valve sizing and selection, no Cv
ARX24-EP
calculations required.
Actuator Specifications
80-100** 2 50 P2200S Control type proportional
Manual override LR, NR, AR, GR, AKR, GKR
Electrical connection 3 ft. [1 m] cable with
80 - 127* 2½ 65 P6250S AKRX24-PI
ARX24-PI
½” conduit fitting
2-WAY VALVE
STAYS IN LAST POSITION
AKRX...Series NO/FO Valve: Normally NO/FC Valve: Normally NC/FO Valve: Normally NC/FC Valve: Normally
Open-valve will close as Open-valve will close as Closed-valve will open as Closed-valve will open
ELECTRONIC FAIL-SAFE
GKRX...Series
voltage increases. voltage increases. voltage increases. as voltage increases.
Fail Action: Will fail open Fail Action: Will fail Fail Action: Will fail open Fail Action: Will fail
upon power loss. closed upon power loss. upon power loss. closed upon power
loss.
NOTE: Feedback signal is always direct acting (2V close, 10V open). Feedback signal can be set to true flow or valve position. The default is true flow. Changing this setting requires the use of
the PC-Tool software.
INSTALLATION
Inlet Length
The ePIV requires a section of straight pipe on the valve inlet to guarantee sensor accuracy. This section should be at least 5 pipe diameters long
with respect to the size of the valve.
DN15-DN50
7-4
Electronic Pressure Independent Control Valves
P2/P6 Series
PIPING
The ePIV is recommended to be installed on the return side of the coil. This diagram is for typical applications only. Consult engineering specification and
drawings for particular circumstances. Refer to ePIV technical documentation for flow verification and commissioning procedures.
Belimo recommends installing one strainer per system. If the system has multiple branches, it is recommended to install one strainer per branch.
Electronic Pressure Independent Valves can be piped in a parallel orientation to achieve increased flow rates.
To achieve flows larger than nominal flow, it is recommended to connect two valves in parallel leading to a common manifold. To correctly operate these
valves, Multi-Function Technology (MFT) will be employed to utilize one common control signal. It is recommended to use the same signal in parallel (2-10
VDC); the two actuators are wired from the same control signal and the two valves control the flow in an identical pattern. The resulting flow will be double
an individual valve. This arrangement is preferable to a split signal since it offers a more stable and accurate flow and feedback signal is easier to interpret.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
ePIV
7-5
Electronic Pressure Independent Control Valves
P2/P6 Series
ORIENTATION
ePIVs shall be installed with flow in the direction of the arrow on the valve body.
The valve assembly can be installed in a vertical or horizontal arrangement, as long as the actuator is positioned to avoid condensation
from dripping onto the actuator or flow sensor.
7-6
P2 Series Electronic Pressure Independent Valves
with Non-Spring Return Actuators
2-way Valves with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60% glycol
Service
max (open loop/steam not allowed)
Flow Characteristic equal percentage/linear
End Fitting NPT female ends Models with V'nom values: P2050S-055, P2075S-103, P2100S-182, P2125S-285.
*See flow reduction table on page 7-6
Body forged brass, nickel plated
Sensor Housing forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
O-ring EPDM
Media Temperature Range
14°F to 250°F [-10°C to +120°C]
(Water)
5 to 50 psid or 1 to 50 psid with
Differential Pressure Range
flow reductions*
Leakage 0%
Inlet Length to Meet Specified
5X nominal pipe size (NPS)
Measurement Accuracy
ultrasonic with glycol and
Flow Sensor Technology
temperature compensation
7-7
P2 Series Electronic Pressure Independent Valves
with Non-Spring Return Actuators
2-way Valves with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60% glycol
Service
max (open loop/steam not allowed)
Flow Characteristic equal percentage/linear
End Fitting NPT female ends
Body forged brass, nickel plated
Sensor Housing forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
O-ring EPDM
Media Temp. Range
14°F to 250°F [-10°C to +120°C]
1.65 to 76.1 GPM
Media Temp. Range
39°F to 250°F [4°C to +120°C]
80 to 100 GPM
Diff. Pressure Range 5 to 50 psid or 1 to 50 psid with
1.65 to 76.1 GPM flow reductions*
Diff. Pressure Range 8 to 50 psid or 1 to 50 psid with
80 to 100 GPM flow reductions*
Leakage 0%
Inlet Length to Meet
Specified Measurement 5X nominal pipe size (NPS)
Accuracy
ultrasonic with glycol and
Flow Sensor Technology
temperature compensation
7-8
P6 Series Electronic Pressure Independent Valves
with Non-Spring Return Actuators
2-way Valves with Stainless Steel Ball and Stem, Flanged Ends
Valve Specifications
chilled or hot water, up to 60% glycol
Service
max (open loop/steam not allowed)
Flow Characteristic equal percentage/linear
pattern to mate with ANSI 125
End Fitting
flange
Body cast iron - GG25
Sensor Housing ductile iron - GGG50
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
O-ring Viton
Media Temperature Range
14°F to 250°F [-10°C to +120°C]
(Water)
5 to 50 psid or 1 to 50 psid with
Differential Pressure Range
flow reductions*
Leakage 0%
Inlet Length to Meet
Specified Measurement 5X nominal pipe size (NPS)
Accuracy
Flow Sensor Technology electromagnetic
Power Supply for the Flow
sensor is powered by the actuator
Sensor
ePIV
7-9
P6 Series Electronic Pressure Independent Valves
with Non-Spring Return Actuators
2-way Valves with Stainless Steel Ball and Stem, Flanged Ends
Valve Specifications
chilled or hot water, up to 60% glycol
Service
max (open loop/steam not allowed)
Flow Characteristic equal percentage/linear
pattern to mate with ANSI 125
End Fitting
flange
Body cast iron - GG25
Sensor Housing ductile iron - GGG50
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
O-ring Viton
Media Temperature Range
14°F to 250°F [-10°C to +120°C]
(Water)
Conductivity min. 20uS/cm
5 to 50 psid or 1 to 50 psid with
Differential Pressure Range
flow reductions*
Leakage 0%
Inlet Length to Meet
Specified Measurement 5X nominal pipe size (NPS)
Accuracy
Flow Sensor Technology electromagnetic
Power Supply for the Flow
sensor is powered by the actuator
Sensor
7-10
P2 Series Electronic Pressure Independent Valves
with Electronic Fail-Safe Actuators
2-way Valves with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60% glycol
Service
max (open loop/steam not allowed)
Flow characteristic equal percentage/linear
End Fitting NPT female ends Models with V'nom values: P2050S-055, P2075S-103, P2100S-182, P2125S-285.
*See flow reduction table on page 7-6
Body forged brass, nickel plated
Sensor Housing forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
O-ring EPDM
Media Temperature Range
14°F to 250°F [-10°C to +120°C]
(Water)
5 to 50 psid or 1 to 50 psid with
Differential Pressure Range
flow reductions*
Leakage 0%
Inlet Length to Meet Specified
5X nominal pipe size (NPS)
Measurement Accuracy
ultrasonic with glycol and
Flow Sensor Technology
temperature compensation
ACTUATOR PART # AKRX24-EP
Proportional/MFT
Manual Override •
Running Time (Motor) 90 seconds
Noise Level (Motor) max. 45 dB (A)
Electrical Connection 3 ft, 18 GA plenum cable with ½” conduit connector
2-Way
Body Close-Off
Size
Model # GPM Pressure Pressure
[mm]
Rating [psi] [psi]
P2050S-165 1.65 200 $895
P2050S-020 2 200 $895
P2050S-025 2.5 200 $895
P2050S-030 3 200 $895
0.5”
P2050S-035 3.5 200 $895
[15]
P2050S-040 4 200 $895
P2050S-045 4.5 200 $895
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
7-11
P2 Series Electronic Pressure Independent Valves
with Electronic Fail-Safe Actuators
2-way Valves with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60% glycol
Service
max (open loop/steam not allowed)
Flow Characteristic equal percentage/linear
End Fitting NPT female ends
Body forged brass, nickel plated
Sensor Housing forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
O-ring EPDM
Media Temp. Range
14°F to 250°F [-10°C to +120°C]
1.65 to 76.1 GPM
Media Temp. Range
39°F to 250°F [4°C to +120°C]
80 to 100 GPM
Diff. Pressure Range 5 to 50 psid or 1 to 50 psid with
1.65 to 76.1 GPM flow reductions*
Diff. Pressure Range 8 to 50 psid or 1 to 50 psid with
80 to 100 GPM flow reductions*
Leakage 0%
Inlet Length to Meet
Specified Measurement 5X nominal pipe size (NPS)
Accuracy
ultrasonic with glycol and
Flow Sensor Technology
temperature compensation
7-12
P6 Series Electronic Pressure Independent Valves
with Electronic Fail-Safe Actuators
2-way Valves with Stainless Steel Ball and Stem, Flanged Ends
Valve Specifications
chilled or hot water, up to 60% glycol
Service
max (open loop/steam not allowed)
Flow Characteristic equal percentage/linear
pattern to mate with ANSI 125
End Fitting
flange
Body cast iron - GG25
Sensor Housing ductile iron - GGG50
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
O-ring Viton
Media Temperature Range
14°F to 250°F [-10°C to +120°C]
(Water)
5 to 50 psid or 1 to 50 psid with
Differential Pressure Range
flow reductions*
Leakage 0%
Inlet Length to Meet
Specified Measurement 5X nominal pipe size (NPS)
Accuracy
Flow Sensor Technology electromagnetic
Power Supply for the Flow
sensor is powered by the actuator
Sensor
ePIV
7-13
P6 Series Electronic Pressure Independent Valves
with Electronic Fail-Safe Actuators
2-way Valves with Stainless Steel Ball and Stem, Flanged Ends
Valve Specifications
chilled or hot water, up to 60% glycol
Service
max (open loop/steam not allowed)
Flow Characteristic equal percentage/linear
pattern to mate with ANSI 125
End Fitting
flange
Body cast iron - GG25
Sensor Housing ductile iron - GGG50
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
O-ring Viton
Media Temperature Range
14°F to 250°F [-10°C to +120°C]
(Water)
5 to 50 psid or 1 to 50 psid with
Differential Pressure Range
flow reductions*
Leakage 0%
Inlet Length to Meet
Specified Measurement 5X nominal pipe size (NPS)
Accuracy
Flow Sensor Technology electromagnetic
Power Supply for the Flow
sensor is powered by the actuator
Sensor
7-14
Valve Accessories
ePIV
ZTH US
Handheld interface module that allows • • • • • • $701
field programming
SENSORS
M2415-EP
• • $504
½” flow sensor
M2420-EP
• • $533
¾” flow sensor
M2425-EP
• • $565
1” flow sensor
M2432-EP
• • $602
1¼” flow sensor
M2440-EP
• • $639
1½” flow sensor
M2450-EP
• • $700
2” flow sensor, 76.1 GPM
ePIV
M2450-EP-100
• • $700
2” flow sensor, 80 to 100 GPM
EPIVFS-60
• • • • $1,576
2½”-6” flow sensor
7-15
Pressure Independent Characterized Control Valves (½” and ¾”) Nomenclature
P 2 050 B 005 +LRX 24 -MFT
Porting Valve Body Body Type Flow Rate Actuator Type Power Control
P= Pressure 2 = Two Way Size B = Nickel Plated 005 = .50 GPM Non-Spring Return Supply -3 = Floating Point
Independent 050 = ½” 010 = 1 GPM LRB 24 = 24 VAC/
Characterized -MFT = Multi-
075 = ¾” 015 = 1.5 GPM LRX DC
Control Valve Function
020 = 2 GPM 120 = 120 VAC
KR Technology
025 = 2.5 GPM
030 = 3 GPM Spring Return -SA = Proportional
035 = 3.5 GPM TF 2-10 VDC
040 = 4 GPM LF
045 = 4.5 GPM
050 = 5 GPM
055 = 5.5 GPM
060 = 6 GPM
065 = 6.5 GPM
070 = 7 GPM
075 = 7.5 GPM
080 = 8 GPM
085 = 8.5 GPM
090 = 9 GPM
095 = 9.5 GPM
100 = 10 GPM
Ordering Example
Ordering Example
3 ½ 15 P2050B030 (-P)
3.5 ½ 15 P2050B035 (-P)
4 ½ 15 P2050B040 (-P)
4.5 ½ 15 P2050B045 (-P) PICCV
TFRX24-MFT
5 ½ 15 P2050B050 (-P)
5.5 ½ 15 P2050B055 (-P)
LF24-MFT US
Forged Body
LRX24-MFT
7 ¾ 20 P2075B070 (-P) Mode of Operation
LRX120-3
LRB24-3
1” to 2” Tefzel®
ARX24-MFT
Cast Body
KRB24-3
0...(1.6-3.0) ½ 15 P2050B025
LRB24-SA
0...(3.0-5.6) ½ 15 P2050B055
0...(5.7-10) ¾ 20 P2075B100
0...(11-16) 1 25 PICCV-25-016 PICCV
0...(17-21) 1 25 PICCV-25-021
Characteristic
0...(1.6-3.0) ½ 15 P2050B025-P Once field set the valve will provide constant flow regardless of
0...(3.0-5.6) ½ 15 P2050B055-P LRB24-SA pressure variations in the system at set degrees of ball opening.
0...(5.7-10) ¾ 20 P2075B100-P Maximizes chiller, preventing energizing additional chillers due to
low ΔT. Simplified valve sizing and selection, no Cv calculations
0...(11-16) 1 25 PICCV-25-016-P required.
0...(17-21) 1 25 PICCV-25-021-P
(-P) ΔP verification across valve using PT ports.
(-F) Flow verification using ΔP across flow orifice.
Flow verification using ΔP across orifice (-F)
Valve is supplied at maximum flow in the full open position only.
Valve Nominal Size Type Suitable Actuators Field adjustment is necessary to achieve lower flow.
GPM Range Inches DN [mm] 2-way NPT Non-Spring Return
Actuator Specifications
0...(0.5-1.5) ½ 15 P2050B010-F Control type on/off, floating point, proportional
KRB24-3
0...(11-16) 1 25 PICCV-25-016-F
0...(17-21) 1 25 PICCV-25-021-F Valve Specifications
Service chilled or hot water, 60% glycol max
Flow characteristic equal percentage
Controllable flow range 75°
Sizes ½”, ¾”, 1”
End fitting NPT female ends
Materials
Body brass, nickel plated
Ball chrome plated brass
Stem nickel plated brass
Seats
½” and ¾” Teflon PTFE
®
1” PTFE / ETFE
Seat o-rings Viton
®
Characterizing disc
½” and ¾” brass
1” Tefzel®
Stem o-rings EPDM (lubricated)
Diaphragm
½” and ¾” Nomex reinforced silicone
1” polyester reinforced silicone
Regulator components stainless steel/brass/Nitrile
Spring stainless steel
Media temp. range 0°F to 212°F [-18°C to +100°C]
KR valve assembly 0°F to 176°F [-18°C to +80°C]
Body pressure rating 600 psi
Close-off pressure 200 psi
Differential pressure 5 to 50 psi
(ΔP) range
Leakage ANSI Class IV (0.01% of rated valve
capacity at 50 psi differential)
Tefzel® and Teflon® are registered trademarks of DuPont™
7-19
Pressure Independent Characterized Control Valves
P2 Series Pressure Independent Characterized Control Valves
2-WAY VALVE
LRB24-3, KRB24-3 NC: Normally Closed- NO: Normally Open-
Floating type actuators Factory default with the LRB Only- Change
directional switch in the directional switch from
1 positon. Power to pin default ”1” position to the
2 will drive valve CW. ”0” postion.
Power to pin 3 will drive
NON-SPRING RETURN
Stays in Last Position
valve CCW.
LF24-MFT US NC/FO Valve: Normally NC/FC Valve: Normally NO/FC Valve: Normally NO/FO Valve: Normally
AFRX24-MFT Closed-valve will open Closed-valve will open Open-valve will close Open-valve will close
MFT type actuators† as voltage increases. as voltage increases. as voltage increases. as voltage increases.
Actuator switch on CW. Actuator switch on CW. Actuator switch on CCW. Actuator switch on CCW.
Spring Action: Will fail Spring Action: Will fail Spring Action: Will fail Spring Action: Will fail
SPRING RETURN
Note Fail Position
open upon power loss. closed upon power loss. closed upon power loss. open upon power loss.
TFRX24-MFT NC/FO Valve: Normally NC/FC Valve: Normally NO/FC Valve: Normally NO/FO Valve: Normally
Closed-valve will open as Closed-valve will open as Open-valve will close as Open-valve will close as
voltage increases. voltage increases. voltage increases. voltage increases.
Switch on Switch on Switch on Switch on
† The design flow rate of PICCVs with MFT actuators are dependent on their Minimum and Maximum Percentages of rotation.
Actuators must be re-programmed for different Minimum and Maximum Settings if actuator set-ups must be changed.
Please refer to PICCV online technical documentation and MFT Adjustment Tables for re-programming the settings.
PICCV
7-20
Pressure Independent Characterized Control Valves
Operation and Installation
FLOW PATTERN
PICCV consists of a differential pressure regulator in series
with a control valve. Regulator Control Valve
Section Section
Water exits valve
The control valve is throttled to match the flow command of
– pressure is P3
the control signal. The differential pressure regulator holds (low).
the pressure drop across the ball of the valve. As system
pressures change, the differential pressure regulator moves in
response to keep the flow stable.
Pressure P1 at the inlet of the PICCV is high and pressure P1- Upstream pressure P2
P3 at the outlet is low. The differential pressure between entering valve. P1 P3
P1 and P3 must be between 5-50 PSI to achieve pressure
independent flow. When differential pressure increases the
regulator opening is reduced. When differential pressure
decreases the regulator opening is increased. This allows for P3
the constant pressure differential across the ball of the valve.
P3
P3 is downstream of the ball as well
as below diaphgram. P1 is upstream.
INSTALLATION
PICCVs should be installed with flow in the direction of the arrow
on the valve body. If installed backwards, there could be damage
to either the diaphragm or the regulator.
The valve assembly can be installed in a vertical or horizontal
arrangement, as long as the actuator is positioned to avoid
condensation from dripping on the actuator.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
PIPING
PICCVs are recommended to be installed on the return side of the coil. This diagram is for typical applications only. Consult engineering specification and drawings
for particular circumstances. PT ports are recommended if not supplied on either side of the valve and the supply side of the heat transfer device to allow for
pressure/flow measurement/calculation. Refer to PICCV technical documentation for flow verification and commissioning procedures.
BELIMO PICCV (TYP.)
FLOW
P/T PORT FLOW STRAINER FLOW SHUT–OFF
(Optional) VALVE
PICCV
DRAIN
7-21
TYPICAL PARALLEL PIPING IN RELATION
Field Set P2 Series Pressure Independent Characterized Control Valves
with Floating Point, Proportional, Non-Spring Return Actuators
2-way Valves with Chrome Plated Brass Ball and Nickel Plated Brass Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75° Valve is supplied at maximum flow in the full open position only.
End Fitting NPT female ends Field adjustment is necessary to achieve lower flow.
Body forged brass, nickel plated
Ball chrome plated brass
Stem nickel plated brass
Seat Teflon® PTFE
Material (seat o-rings) EPDM (lubricated)
Characterized Disc brass
O-ring EPDM (lubricated)
Diaphragm Nomex reinforced silicone
Regulator Components stainless steel / brass / Nitrile
Spring stainless steel
Media Temp. Range LR 0°F to 212°F [-18°C to +100°C]
Media Temp. Range KR 0°F to 176°F [-18°C to +80°C]
Differential Pressure Range 5 to 50 psid
Leakage ANSI Class IV
ACTUATOR PART # KRB24-3 KRB24-3 with PT Port LRB24-SA LRB24-SA with PT Port
Control On/Off, Floating Point On/Off, Floating Point Proportional Proportional
Manual Override • • • •
75 seconds 75 seconds 95 seconds 95 seconds
Running Time (Motor) (varies in the flow setting) (varies in the flow setting) (varies in the flow setting) (varies in the flow setting)
Noise Level (Motor) <35 dB (A) <35 dB (A) <35 dB (A) <35 dB (A)
3 ft cable, 3 ft cable, 3ft cable, 3ft cable,
Electrical Connection no conduit fitting no conduit fitting ½” conduit fitting ½” conduit fitting
2-Way
Body Close-Off
GPM Liter/ Size
Model # Pressure Pressure
Range Sec [mm]
Rating [psi] [psi]
P2050B010(-P) 0...(0.5-1.5) 0.06 200 $391 $464 $577 $649
0.5”
P2050B025(-P) 0...(1.6-3.0) 0.16 200 $391 $464 $577 $649
[15]
P2050B055(-P) 0...(3.0-5.6) 0.35 200 $391 $464 $577 $649
0.75” 600
P2075B100(-P) 0...(5.7-10) 0.63 200 $412 $489 $577 $678
[20]
PICCV-25-016(-P) 0...(11-16) 1.01 1” 200 $721 $885
PICCV-25-021(-P) 0...(17-21) 1.2 [25] 200 $721 $885
7-22
P2 Series Pressure Independent Characterized Control Valves
with Floating Point and MFT, Non-Spring Return Actuators
2-way Valve with Chrome Plated Brass Ball and Nickel Plated Brass Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass, nickel plated
Ball chrome plated brass
Stem nickel plated brass
Seat Teflon® PTFE
Material (seat o-rings) EPDM (lubricated)
Characterized Disc brass
O-ring EPDM (lubricated)
Diaphragm Nomex reinforced silicone
Regulator Components stainless steel / brass / Nitrile
Spring stainless steel
Media Temp. Range 0°F to 212°F [-18°C to +100°C]
Differential Pressure Range 5 to 50 psid
ANSI Class IV (0.01% of rated
Leakage
valve capacity at 50 psi differential)
ACTUATOR PART # LRB24-3 LRB24-3 with PT Port LRX24-MFT LRX24-MFT with PT Port
Control On/Off, Floating Point On/Off, Floating Point Proportional/MFT Proportional/MFT
Manual Override • • • •
95 seconds 95 seconds
Running Time (Motor) 100 seconds 100 seconds
(varies in the flow setting) (varies in the flow setting)
Noise Level (Motor) <35 dB(A) <35 dB(A) <35 dB(A) <35 dB(A)
3 ft 18 GA plenum cable with 3 ft 18 GA plenum cable with 3 ft 18 GA plenum cable with 3 ft 18 GA plenum cable with
Electrical Connection
½” conduit connector ½” conduit connector ½” conduit connector ½” conduit connector
2-Way
Body Close-Off
Liter/ Size
Model # GPM Pressure Pressure
sec [mm]
Rating [psi] [psi]
0.5 0.03 200 $506 $578 $693 $765
P2050B010(-P) 1 0.06 200 $506 $578 $693 $765
P2050B015(-P) 1.5 0.09 200 $506 $578 $693 $765
P2050B020(-P) 2 0.13 200 $506 $578 $693 $765
P2050B025(-P) 2.5 0.16 200 $506 $578 $693 $765
0.5"
P2050B030(-P) 3 0.19 200 $506 $578 $693 $765
[15]
P2050B035(-P) 3.5 0.22 200 $506 $578 $693 $765
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
7-23
P2 Series Pressure Independent Characterized Control Valves
with MFT, Non-Spring Return Actuators
2-way Valve with Chrome Plated Brass Ball and Nickel Plated Brass Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic equal percentage
1½” body has two discs with different flow capabilities (26 GPM to 30 GPM) (31 GPM to 33 GPM).
Controllable Flow Range 75° 2” has a small and a large body. The larger body has two discs with different flow capabilities.
End Fitting NPT female ends Small: (33 GPM to 40 GPM), Large: (44 GPM to 80 GPM) (90 GPM to 100 GPM).
Body forged brass, nickel plated
Ball chrome plated brass
Stem nickel plated brass
Seat Teflon® PTFE
Material (seat O-rings) EPDM (lubricated)
Characterized Disc TEFZEL® or stainless steel
O-ring EPDM (lubricated)
Diaphragm Polyester reinforced Silicone
Regulator Components stainless steel / brass / Nitrile
Spring stainless steel
Media Temperature Range 0°F to 250°F [-18°C to +120°C]
Differential Pressure Range 5 to 50 psid
ANSI Class IV (0.01% of rated
Leakage
valve capacity at 50 psi differential)
7-24
P2 Series Pressure Independent Characterized Control Valves
with MFT, Non-Spring Return Actuators
2-way Valve with Chrome Plated Brass Ball and Nickel Plated Brass Stem, NPT Female Ends
MULTI-FUNCTION TECHNOLOGY
Description P-CODE Control Input Running Time Built-in Feedback List Price
P-10019 A19 2-10 VDC 100 seconds 2-10 VDC No Charge
P-10028 A28 0-10 VDC 100 seconds 0-10 VDC No Charge
g
P-10118 AAJ 2-6 VDC 100 seconds 2-10 VDC No Charge
g
P-10119 AAK 6-10 VDC 100 seconds 2-10 VDC No Charge
g
P-10137 AD5 2-5 VDC 100 seconds 2-10 VDC No Charge
g
P-20031 W31 0.02-5.00 seconds PWM 100 seconds 2-10 VDC No Charge
g
P-20032 W32 0.10-25.5 seconds PWM 100 seconds 2-10 VDC No Charge
g
P-20034 W34 0.59-2.93 seconds PWM 100 seconds 2-10 VDC No Charge
g
P-30003 F03 Floatingg Point 100 seconds 2-10 VDC No Charge
g
P-10019 †
A19 On/Off 100 seconds 2-10 VDC No Charge
g
Example: ARX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.
Note: Most popular configurations available at no additional cost. All other configurations carry a $34.00 list price.
† Wire for On/Off. Refer to PICCV technical documentation for wiring diagram.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
PICCV
7-25
P2 Series Pressure Independent Characterized Control Valves
with MFT, Spring Return Actuators
2-way Valve with Chrome Plated Brass Ball and Nickel Plated Brass Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass, nickel plated
Ball chrome plated brass
Stem nickel plated brass
Seat Teflon® PTFE
Material (seat o-rings) EPDM (lubricated)
Characterized Disc brass
O-ring EPDM (lubricated)
Diaphragm Nomex reinforced silicone
Regulator Components stainless steel / brass / Nitrile
Spring stainless steel
Media Temperature Range 0°F to 250°F [-18°C to +120°C]
Differential Pressure Range 5 to 50 psid
ANSI Class IV (0.01% of rated
Leakage
valve capacity at 50 psi differential)
ACTUATOR PART # TFRX24-MFT TFRX24-MFT with PT Port LF24-MFT US LF24-MFT US with PT Port
3 ft, 18 GA plenum cable with 3 ft, 18 GA plenum cable with 3 ft, 18 GA plenum cable with 3 ft, 18 GA plenum cable with
Electrical Connection
½” conduit connector ½” conduit connector ½” conduit connector ½” conduit connector
2-Way
Liter/ Size Body Close-Off
Model # GPM Pressure Pressure
sec [mm] Rating [psi] [psi]
P2050B005(-P) 0.5 0.03 200 $803 $876 $853 $925
P2050B010(-P) 1 0.06 200 $803 $876 $853 $925
P2050B015(-P) 1.5 0.09 200 $803 $876 $853 $925
P2050B020(-P) 2 0.13 200 $803 $876 $853 $925
7-26
P2 Series Pressure Independent Characterized Control Valves
with MFT, Spring Return Actuators
2-way Valve with Chrome Plated Brass Ball and Nickel Plated Brass Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass, nickel plated
Ball chrome plated brass
Stem nickel plated brass
Seat Teflon® PTFE
Material (seat o-rings) EPDM (lubricated)
Characterized Disc brass
O-ring EPDM (lubricated)
Diaphragm Nomex reinforced silicone
Regulator Components stainless steel / brass / Nitrile
Spring stainless steel
Media Temperature Range 0°F to 250°F [-18°C to +120°C]
Differential Pressure Range 5 to 50 psid
ANSI Class IV (0.01% of rated
Leakage
valve capacity at 50 psi differential)
PICCV
7-27
P2 Series Pressure Independent Characterized Control Valves
with MFT, Spring Return Actuators
2-way Valve with Chrome Plated Brass Ball and Nickel Plated Brass Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass, nickel plated
Ball chrome plated brass
Stem nickel plated brass
Seat Teflon® PTFE
Material (seat o-rings) EPDM (lubricated)
Characterized Disc TEFZEL® or stainless steel
O-ring EPDM (lubricated)
Diaphragm Polyester reinforced Silicone
Regulator Components stainless steel / brass / Nitrile
Spring stainless steel
Media Temperature Range 0°F to 250°F [-18°C to 120°C]
Differential Pressure Range 5 to 50 psid
ANSI Class IV (0.01% of rated
Leakage
valve capacity at 50 psi differential)
7-28
Customize Products
MFT Programming Codes
MULTI-FUNCTION TECHNOLOGY
Description P-CODE Control Input Running Time Built-in Feedback List Price
P-10019 A19 2-10 VDC 100 seconds 2-10 VDC No Charge
g
P-10028 A28 0-10 VDC 100 seconds 0-10 VDC No Charge
g
P-10118 AAJ 2-6 VDC 100 seconds 2-10 VDC No Charge
g
P-10119 AAK 6-10 VDC 100 seconds 2-10 VDC No Charge
g
P-10137 AD5 2-5 VDC 100 seconds 2-10 VDC No Charge
g
P-20031 W31 0.02-5.00 seconds PWM 100 seconds 2-10 VDC No Charge
g
P-20032 W32 0.10-25.5 seconds PWM 100 seconds 2-10 VDC No Charge
g
P-20034 W34 0.59-2.93 seconds PWM 100 seconds 2-10 VDC No Charge
g
P-30003 F03 Floatingg Point 100 seconds 2-10 VDC No Charge
g
P-10019† A19 On/Off 100 seconds 2-10 VDC No Charge
g
Example: AFRX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.
Note: Most popular configurations available at no additional cost. All other configurations carry a $34.00 list price.
† Wire for On/Off. Refer to PICCV technical documentation for wiring diagram.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
PICCV
7-29
LR Series Non-Spring Return Actuators
Custom, Direct Coupled, 45 in-lbs Minimum Torque
Actuator Specifications
Torque 45 in-lbs [5 Nm]
Angle of rotation max. 90°, adjustable
with mechanical stop
electronically variable
Fits shaft diameter N/A
Position indication reflective visual Indicator
(snap-on)
Manual override external push-button
Direction of reversible with switch
rotation
Dimensions 6.18” x 2.6” x 2.34”
[157 x 66 x 59.4 mm]
Electrical connection 18 GA plenum rated cable,
½” conduit fitting
Overload protection electronic throughout
rotation
Housing NEMA 2/IP54
Agency listings cULus acc. to UL 60730-
1A/-2-14, CAN/CSA E60730- MFT= 2-10 VDC Default, or Set, Modify, Read:
1:02, CSA C22.2 No. 24-93, All LR
• Control (PWM, VDC range, Floating Point) Actuators
CE acc. to 2006/95/EC and • Feedback (0-10 VDC, 0-5 VDC, 2-10 VDC, Variable)
89/336/EEC have BDCM
• Motion (run time)
Variable with MFT
CUSTOMIZE PRODUCTS
Power Running Cable
Model Control Input Feedback VA Rating Re-order Number List Price
Supply Time(s) Length
LRX24-3 On/Off, Floating Point Add-on 24 VAC/DC 95 2 10 ft. LR000 RC3 000 $248
LRX24-3 On/Off, Floating Point Add-on 24 VAC/DC 95 2 16 ft. LR000 RC5 000 $270
LRX24-3-S On/Off, Floating Point Built-in 24 VAC/DC 95 2 10 ft. LR020 RA3 000 $340
LRX24-3-S On/Off, Floating Point Built-in 24 VAC/DC 95 2 16 ft. LR020 RA5 000 $363
LRX120-3 On/Off, Floating Point Add-on 100-230 VAC 95 4 10 ft. LR060 RA3 000 $297
LRX120-3 On/Off, Floating Point Add-on 100-230 VAC 95 4 16 ft. LR060 RA5 000 $319
LRX24-MFT Various Various 24 VAC/VDC Various 5 3 ft. LR100 RC1 XXX** $413
** See page 7-25 for P-Codes available.
7-30
AR Series Non-Spring Return Actuators
Custom, Direct Coupled, 180 in-lbs Minimum Torque
Actuator Specifications
Torque 180 in-lbs [20 Nm]
Angle of rotation max 90°, adjustable with
mechanical stop
electronically variable
Position indication handle
Manual override external push-button
Direction of reversible with switch
rotation
Dimensions 7.47” x 3.45” x 2.52”
[189.8 x 88 x 64 mm]
Electrical connection 18 GA plenum rated cable,
½” conduit connector
Overload protection electronic throughout
rotation
Auxiliary switch(es) (-S) models: 1 SPDT, 3A
(0.5A inductive) @ 250V
adjustable 5° to 85°
Housing NEMA 2/IP54
Agency listings cULus acc. to UL 60730-
1A/-2-14, CAN/CSA E60730- MFT= 2-10 VDC Default, or Set, Modify, Read: All AR
1:02, CSA C22.2 No. 24-93,
• Control (PWM, VDC range, Floating Point) Actuators
CE acc. to 2006/95/EC and • Feedback (0-10 VDC, 0-5 VDC, 2-10 VDC, Variable) have BDCM
89/336/EEC • Motion (run time)
Variable with MFT
CUSTOMIZE PRODUCTS
Power Running Cable
Model Control Input Feedback VA Rating Re-order Number List Price
Supply Time(s) Length
ARX24-MFT Various Various 24 VAC/VDC Various 6 3 ft. AR100 0C1 XXX** $550
ARX24-MFT Various Various 24 VAC/VDC Various 6 10 ft. AR100 0C3 XXX** $582
ARX24-MFT Various Various 24 VAC/VDC Various 6 16 ft. AR100 0C5 XXX** $606
** See page 7-25 for P-Codes available.
The P-Code programs the actuator for the desired Control Input, Feedback and Running Time.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
PICCV
7-31
Valve Accessories
PICCV
ZS-CCV-90*
• • $224
CCV/PICCV weather shield kit LF/AF
ZS-CCV-100*
• • $224
CCV/PICCV weather shield kit LR/AR
ZS-CCV-110*
• $224
CCV/PICCV weather shield kit AFR
EXTENSION BRACKET
CCV-EXT-KIT
• • • • • $201
CCV/PICCV valve neck extension kit
AUXILIARY SWITCHES & POTENTIOMETERS
S1A
Auxiliary switch - 1x SPDT, 3A • • $88
(0.5A inductive) @ 250 VAC
S2A
Auxiliary switch - 2x SPDT, 3A • • $131
(0.5A inductive) @ 250 VAC
P140A GR
• • $144
Feedback potentiometer 140 Ω
P500A GR
• • $144
Feedback potentiometer 500 Ω
P1000A GR
• • $144
Feedback potentiometer 1000 Ω
P2800A GR
• • $144
Feedback potentiometer 2800 Ω
P5000A GR
• • $144
Feedback potentiometer 5000 Ω
P10000A GR
• • $144
ZTH US
Handheld interface module that allows • • • • • $701
field programming
NOTE: For TF actuators, no weather shield available at this time. Please call 800-543-9038 for assistance.
* Designed to NEMA 4 specifications.
PICCV
7-32
ZONETIGHT VALVES
BELIMO ZONETIGHT™
ZONE VALVES
(QCV, PIQCV, 6-WAY)
Efficient in Every Way
• Compact size.
• Low power consumption.
• Zero leakage.
From sizing and selecting to estimating savings, Belimo offers the following tools
to help make your job easier:
• Retrofit App allows you to quickly and easily find HVAC replacement
solutions for valves and actuators.
• Energy Valve Savings Estimator is a Microsoft Excel based tool that profiles
constant speed chilled water plant performance.
Ordering Example
Non-
2-way 3-way
Cv Inches DN [mm] Spring Fail-Safe
NPT NPT
Return
5.9* ½ 15 Z2050Q-J
9.8* ¾ 20 Z2075Q-K
CQK Series
CQ Series
1 ½ 15 Z3050Q-E
2.7 ½ 15 Z3050Q-H
4.6 ¾ 20 Z3075Q-J
QCV
*Maximum flow. Adjustable 0 to max value.
Mode of Operation
The ZoneTight Zone Valve (QCV) is operated by a rotary actuator.
The actuators are controlled by a standard voltage for on/off control,
a proportional signal, or 3-point control system which move the ball
of the valve to the position dictated by the control system.
Product Features
The equal percentage characteristic of the flow is ensured by
the design of the ball. This characteristic provides linear heating
or cooling output from the coil improving energy efficiency and
comfort.
Actuator Specifications
Control type
-3 on/off, floating point
-SR proportional, 2-10 VDC (configurable)
Manual override use actuator to turn valve stem
Electrical connection 3 ft. [1 m] cable with ½” conduit fitting
screw terminals
Power consumption
CQ.. 0.3 W running, 0.2 W holding
CQK.. 2.5 W running, 0.5 W holding
CQ..UP 1.0 W running, 0.7 W holding
Power supply 24V (110-230 VAC, UP series)
Transformer sizing
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
CQ.. 0.6 VA
CQK.. 5 VA
CQ..UP 2 VA
Valve Specifications
Service chilled or hot water, 60% glycol
Flow characteristic equal percentage (2-way)
linear (3-way)
Controllable flow range 75° (2-way), 90° (3-way)
Sizes ½”, ¾”
End fitting NPT female ends
Materials
Body forged brass
Ball chrome plated brass
Stem brass
Seats Teflon® PTFE
O-rings EPDM (lubricated)
Media temp. range 36°F to 212°F [2°C to 100°C]
Media temp. limit 250°F [120°C]
Maximum allowable
operating temperature 212°F [100°C]
Body pressure rating 230 psi
Close-off pressure 75 psi
Maximum differential
pressure (ΔP) 40 psi
Leakage 0%
Teflon® is a registered trademark of DuPont™
8-3
ZoneTight Zone Valves (QCV)
QCV
CQBUP-3 Power to brown wire (pin 2 for -T versions) will drive valve Power to brown wire (pin
CW. Power to blue wire (pin 3 for -T versions) will drive 2 for -T versions) will drive
valve CCW. valve CW. Power to blue
wire (pin 3 for -T versions)
NON-SPRING RETURN
CQB24-3 Power to red wire (pin 2 for -T versions) will drive valve CW. Power to red wire (pin 2 for
Power to white wire (pin 3 for -T versions) will drive valve -T versions) will drive valve
CCW. CW. Power to white wire
(pin 3 for -T versions) will
drive valve CCW.
8-4
ZoneTight Zone Valves (QCV)
Flow Pattern and Piping Diagrams
QCV
FLOW PATTERN
Port A Port B
Port AB
PIPING DIAGRAMS
3-way Switching Valve Piping Diagram 3-way Diverting Valve Piping Diagram
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
8-5
ZoneTight Zone Valves (QCV) with Non-Spring Return Actuators
2-way and 3-way Valves with NPT Female Ends
QCV
Valve Specifications
Service chilled , hot water, 60% glycol
equal percentage (2-way)
Flow Characteristic
linear (3-way)
75° (2-way)
Controllable Flow Range
90° (3-way)
End Fitting NPT female ends
Body forged brass
Ball chrome plated brass
Stem brass
Seat Teflon® PTFE
Media Temperature Limit 250°F [120°C]*
Max Differential Pressure
40 psi
(Water)
Maximum Allowable
212°F [100°C]*
Operating Temperature
Leakage 0%
2-Way
Body
Close-Off
Size Pressure
Model # Cv Pressure
[mm] Rating
[psi]
[psi]
Z2050Q-J 5.9 0.5" [15] $174 $237 $237 $187
230 75
Z2075Q-K 9.8 0.75" [20] $194 $257 $257 $207
3-Way
Z3050Q-E 1 $194 $207
0.5" [15]
Z3050Q-H 2.7 230 75 $194 $207
Z3075Q-J 4.6 0.75" [20] $214 $227
8-6
ZoneTight Zone Valves (QCV) with Fail-Safe Actuators
2-way and 3-way Valves with NPT Female Ends
QCV
Valve Specifications
Service chilled , hot water, 60% glycol
equal percentage (2-way)
Flow Characteristic
linear (3-way)
75° (2-way)
Controllable Flow Range
90° (3-way)
End Fitting NPT female ends
Body forged brass
Ball chrome plated brass
Stem brass
Seat Teflon® PTFE
Media Temperature Limit 250°F [120°C]*
Max Differential Pressure
40 psi
(Water)
Maximum Allowable
212°F [100°C]*
Operating Temperature
Leakage 0%
ON/OFF
ACTUATOR PART # CQKB24-LL CQKB24-RR CQKB24-S-LL CQKB24-S-RR
PROPORTIONAL
ACTUATOR PART # CQKB24-SR-LL CQKB24-SR-LR CQKB24-SR-RL CQKB24-SR-RR
Control Proportional, 2-10 VDC Proportional, 2-10 VDC Proportional, 2-10 VDC Proportional, 2-10 VDC
Power Supply 24V 24V 24V 24V
Set-Up NO/FO NO/FC NC/FO NC/FC
Running Time (Motor) 75 seconds 75 seconds 75 seconds 75 seconds
Running Time (Fail-Safe) 60 seconds 60 seconds 60 seconds 60 seconds
Noise Level (Motor) <35 dB (A) <35 dB (A) <35 dB (A) <35 dB (A)
3 ft, 18 GA plenum cable with ½” 3 ft, 18 GA plenum cable with ½” 3 ft, 18 GA plenum cable with ½” 3 ft, 18 GA plenum cable with ½”
Electrical Connection
conduit connector conduit connector conduit connector conduit connector
2-Way
Body
Close-Off
Size Pressure
Model # Cv Pressure
[mm] Rating
[psi]
[psi]
Z2050Q-J 5.9 0.5" [15] $256 $256 $256 $256
230 75
Z2075Q-K 9.8 0.75" [20] $276 $276 $276 $276
* If temperature exceeds 212°F [100°C] operating range due to a boiler control failure the valve will safely contain the hot water but manufacturers product warranty becomes invalid.
8-7
Valve Accessories
ZoneTight Zone Valve (QCV)
QCV
VALVES
ACCESSORIES Z2 (2-WAY) Z3 (3-WAY) List Price
ZCQB-FL
• $52
Flow setter
ZCQ-E
QCV/PIQCV valve stem extension
• • $22
Designed for chilled water service up to 104°F
[40°C] media temperature
FLOW ORIFICE
FO15010
• $76
½” Flow orifice for 1.0 GPM
FO15025
• $76
½” Flow orifice for 2.5 GPM
FO15055
• $76
½” Flow orifice for 5.5 GPM
FO20100
• $81
¾” Flow orifice for 10.0 GPM
8-8
9
BELIMO ZONETIGHT™
PRESSURE INDEPENDENT
ZONE VALVES (PIQCV)
Balancing and Control Valve
in One Compact Unit
• Smallest pressure independent characterized
ball valve in the market.
• Low power consumption up to 95% less
than conventional zone valves.
• Adjustable flow to meet the design.
Ordering Example
2-way Non-
2-way
GPM Inches DN [mm] NPT Spring Fail-Safe
NPT
with PT ports Return
0.9* ½ 15 Z2050QPT-B
CQK Series
CQ Series
1.9* ½ 15 Z2050QPT-D
4* ½ 15 Z2050QPT-F
*Maximum flow. Adjustable 0 to max value.
PIQCV
Mode of Operation
The ZoneTight Pressure Independent Zone Valve (PIQCV) is a
two-way valve which combines the functionality of a control valve
and a pressure regulating valve, creating one precise product which
is unaffected by pressure variations in a system.
Product Features
Constant flow regardless of pressure variations in the system at set
degrees of ball opening. Maximizes chiller ΔT, preventing energizing
additional chillers due to low ΔT. Simplified valve sizing and
selection, no Cv calculations required.
Actuator Specifications
Control type
-3 on/off, floating point
-SR proportional, 2-10 VDC (configurable)
Manual override use actuator to turn valve stem
Electrical connection 3 ft. [1 m] cable with ½” conduit fitting
screw terminals
Power consumption
CQ.. 0.3 W running, 0.2 W holding
CQK.. 2.5 W running, 0.5 W holding
CQ..UP 1.0 W running, 0.7 W holding
Power supply 24V (110-230 VAC, UP series)
Transformer sizing
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
CQ.. 0.6 VA
CQK.. 5 VA
CQ..UP 2 VA
Valve Specifications
Service chilled or hot water, 60% glycol
Flow characteristic equal percentage
Controllable flow range 75°
Sizes ½”
End fitting NPT female ends
Materials
Body forged brass
Ball stainless steel
Stem stainless steel
Seats Teflon© PTFE
O-rings PTFE
Spring stainless steel
Media temp. range 36°F to 212°F [2°C to 100°C]
Media temp. limit 250°F [120°C]
Maximum allowable
operating temperature 212°F [100°C]
PT ports optional
Body pressure rating 360 psi
Close-off pressure 100 psi
Differential pressure 5 to 50 psi
(ΔP) range
Leakage 0%
9-3
ZoneTight Pressure Independent Zone Valves (PIQCV)
2-WAY VALVE
PIQCV
CQBUP-3 Power to brown wire (pin 2 for -T versions) will drive valve CW. Power to blue wire (pin 3 for -T versions) will
NON-SPRING RETURN
CQB24-3 Power to red wire (pin 2 for -T versions) will drive valve CW. Power to white wire (pin 3 for -T versions) will
drive valve CCW.
CQB24-SR NC: Normally closed A to AB, valve will open as NO: Normally open A to AB, valve will close as voltage
voltage increases increases
NO/FO: Normally open A to AB, valve will drive closed. NC/FC: Normally closed A to AB, valve will drive open.
CQKB24-S Fail-Safe Action: Actuator will fail open A to AB upon Fail-Safe Action: Actuator will fail closed A to AB upon
FAIL-SAFE
CQKB24-SR NC/FO: Normally closed A to AB, valve will open as voltage NC/FC: Normally closed A to AB, valve will open as voltage
increases. Actuator switch on CW. increases. Actuator switch on CW.
Fail-Safe Action: Will fail open upon power loss. Fail-Safe Action: Will fail closed upon power loss.
9-4
ZoneTight Pressure Independent Zone Valves (PIQCV)
Operation and Installation
FLOW PATTERN
ZoneTight Pressure Independent Zone Valve (PIQCV)
consists of a differential pressure regulator in series
with a control valve.
The control valve is throttled to match the flow command of
the control signal. The differential pressure regulator holds
PIQCV
the pressure drop across the ball of the valve. As system
pressures change, the differential pressure regulator moves in
response to keep the flow stable.
INSTALLATION
ZoneTight Pressure Independent Zone Valves (PIQCV) should
360°
be installed with flow in the direction of the arrow on the valve
body. If installed backwards, there could be damage to either the
diaphragm or the regulator.
The valve assembly can be installed in a vertical or horizontal
arrangement, as long as the actuator is positioned to avoid
condensation from dripping on the actuator.
90°
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
PIPING
ZoneTight Pressure Independent Zone Valves (PIQCV) are recommended to be installed on the return side of the coil. This diagram is for typical applications
only. Consult engineering specification and drawings for particular circumstances. PT ports are recommended if not supplied on either side of the valve and the
supply side of the heat transfer device to allow for pressure/flow measurement/calculation. Refer to ZoneTight Pressure Independent Zone Valve (PIQCV) technical
documentation for flow verification and commissioning procedures.
BELIMO PIQCV (TYP.)
FLOW
P/T PORT FLOW STRAINER FLOW SHUT–OFF
(Optional) VALVE
DRAIN
9-5
TYPICAL PARALLEL PIPING IN RELATION
ZoneTight Pressure Independent Zone Valves (PIQCV)
with Non-Spring Return Actuators
2-way Valves with NPT Female Ends
Valve Specifications
chilled, hot water, up to 60% glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass
Ball stainless steel
Stem stainless steel
PIQCV
2-Way
Body
Close-Off
Size Pressure
Model # GPM Pressure
[mm] Rating
[psi]
[psi]
Z2050QPT-B 0.9 100 $350 $413 $413 $363
Z2050QPT-D 1.9 0.5" [15] 360 100 $350 $413 $413 $363
Z2050QPT-F 4 100 $370 $433 $433 $383
9-6
ZoneTight Pressure Independent Zone Valves (PIQCV) with Fail-Safe Actuators
2-way Valves with NPT Female Ends
Valve Specifications
chilled, hot water, up to 60% glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass
Ball stainless steel
Stem stainless steel
PIQCV
Seat Teflon® PTFE
Characterization incorporated into the ball
Media Temperature Limit 250°F [120°C]*
Differential Pressure Range 5 to 50 psi
Maximum Allowable
212°F [100°C]*
Operating Temperature
Leakage 0%
ON/OFF
ACTUATOR PART # CQKB24-LL CQKB24-RR CQKB24-S-LL CQKB24-S-RR
PROPORTIONAL
ACTUATOR PART # CQKB24-SR-LL CQKB24-SR-LR CQKB24-SR-RL CQKB24-SR-RR
Control Proportional, 2-10 VDC Proportional, 2-10 VDC Proportional, 2-10 VDC Proportional, 2-10 VDC
Power Supply 24V 24V 24V 24V
Set-Up NO/FO NO/FC NC/FO NC/FC
Running Time (Motor) 75 seconds 75 seconds 75 seconds 75 seconds
Running Time (Fail-Safe) 60 seconds 60 seconds 60 seconds 60 seconds
Noise Level (Motor) <35 dB (A) <35 dB (A) <35 dB (A) <35 dB (A)
3 ft, 18 GA plenum cable with ½” 3 ft, 18 GA plenum cable with ½” 3 ft, 18 GA plenum cable with ½” 3 ft, 18 GA plenum cable with ½”
Electrical Connection
conduit connector conduit connector conduit connector conduit connector
2-Way
Body
Close-Off
Size Pressure
Model # GPM Pressure
[mm] Rating
[psi]
[psi]
Z2050QPT-B 0.9 100 $432 $432 $432 $432
Z2050QPT-D 1.9 0.5" [15] 360 100 $432 $432 $432 $432
Z2050QPT-F 4 100 $452 $452 $452 $452
* If temperature exceeds 212°F [100°C] operating range due to a boiler control failure the valve will safely contain the hot water but manufacturers product warranty becomes invalid.
9-7
Valve Accessories
ZoneTight Pressure Independent Zone Valves (PIQCV)
VALVES
ACCESSORIES Z2 (2-WAY) Z3 (3-WAY) List Price
ZCQB-FL
• $52
Flow setter
PIQCV
ZCQ-E
QCV/PIQCV valve stem extension
• • $22
Designed for chilled water service up to 104°F
[40°C] media temperature
FLOW ORIFICE
FO15010
• $76
½” Flow orifice for 1.0 GPM
FO15025
• $76
½” Flow orifice for 2.5 GPM
FO15055
• $76
½” Flow orifice for 5.5 GPM
9-8
10
6-WAY CHARACTERIZED
CONTROL VALVES
Easy Way to Control both Heating
and Cooling Using One Valve
• True close-off to isolate both heating and
cooling loops.
• Replaces four 2-way valves drastically
simplifying installation.
• Only one actuator to integrate and wire.
Ordering Example
Example:
Sequence 1
Sequence 2
10-1
6-Way Characterized Control Valves with Non-Spring Return Actuators
6-way Valves with Chrome Plated Ball and Nickel Plated Stem, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
Flow Characteristic linear
End Fitting NPT female ends
Body nickel plated brass
Ball chrome plated brass
Stem nickel plated brass
Seat Teflon® PTFE
O-ring EPDM
Characterized Disc chrome plated steel
Media Temperature Range
43°F to 180°F [6°C to 82°C]
(Water)
Max Differential Pressure
15 psi for typical applications
(Water)
6-WAY VALVES
Leakage 0%
10-2
CHARACTERIZED CONTROL
VALVES (CCV & HTCCV)
Control and Reliability
• Ball valve design offers self-cleaning
and zero leakage.
• Rated for media temperatures up to 250°F.
• Updated User Interface – Toggle screen, vertical scrolling, and the ability to clear
valve and actuator selection sections separately
• Manual Selection – Enter model numbers and skip the selection process
11
CHARACTERIZED CONTROL
VALVES (CCV)
True Advancement in
Control Valves
• Ball valve design offers self-cleaning and
zero leakage.
• Rated for water temperatures up to 250°F.
• Maintenance free – no repacking required
after being in service for an extended period
of time.
B2 09 LRX 24 -MFT
Valve Valve Size Trim Material Actuator Type Power Supply Control -S = Built-in
07-80 = ½” to 3” B = Chrome Plated Non-Spring Return 24 = 24 VAC/DC Blank = On/Off, Floating Auxiliary
B2 = 2-way
Brass Ball, TR 120 = 120 VAC* Point Switch
B3 = 3-way
Nickel Plated LRB 230 = 230 VAC -3 = Floating Point -T = Terminal
Stem LRX Strip
UP = 24 to 240 VAC -SR = 2-10 VDC
Blank = Stainless LRQX -MFT = Multi-Function N4 = NEMA
Steel Ball NRB Technology 4/4X
and Stem NRX -MFT95 = 0-135 Ω N4H = NEMA
NRQX 4/4X
ARB with
ARX Heater
ARQX
Spring Return
TFR
TFRX
LF
AFR
AFRX
Electronic Fail-Safe
GKR
*LR and AR include 120-240 VAC
Ordering Example
Non-Spring Models
P-10001 (A01) Tagging:
NO = Normally Open Valves may be
P-100xx (Axx) Control voltage applications
NC = Normally Closed tagged per customer
P-200xx (Wxx) Pulse width modulation specification. ($10.00
Spring Return Models applications charge per tag)
NO/FO = Normally Open/Fail Open P-300xx (Fxx) Floating Point applications
NO/FC = Normally Open/Fail Closed P-400xx (Jxx) On/Off applications Example:
X-XXXXX Create custom MFT AHU-1
NC/FO = Normally Closed/Fail Open FCU-2
configuration code
NC/FC = Normally Closed/Fail Closed
X-XXXXX Create custom MFT
Part number for
See settings configuration in the field
tagging: 99981-00101
Refers to valve ports A to AB. with MFT-actuator PC-Tool software
Valve Valve Size Trim Material Cv Actuator Type Power Supply Control
B6 = 2-way 250 = 2½” to 6” S = Stainless 070 = 70 Cv Non-Spring Return 24 = 24 VAC/DC Blank = On/Off, Floating
Flanged Steel Ball and 110 = 110 Cv AR 120 = 120 VAC* Point
Stem 186 = 186 Cv GR 230 = 230 VAC -3 = Floating Point
290 = 290 Cv Spring Return UP = 24 to 240 VAC -SR = 2-10 VDC
AFR -MFT = Multi-Function
400 = 400 Cv
Electronic Fail-Safe Technology
GKR -MFT95 = 0-135 Ω
Ordering Example
Non-Spring Models
P-10001 (A01) Tagging:
NO = Normally Open Valves may be
P-100xx (Axx) Control voltage applications
NC = Normally Closed tagged per customer
P-200xx (Wxx) Pulse width modulation specification. ($10.00
Spring Return Models applications charge per tag)
NO/FO = Normally Open/Fail Open P-300xx (Fxx) Floating Point applications
NO/FC = Normally Open/Fail Closed P-400xx (Jxx) On/Off applications Example:
X-XXXXX Create custom MFT AHU-1
NC/FO = Normally Closed/Fail Open FCU-2
configuration code
NC/FC = Normally Closed/Fail Closed
X-XXXXX Create custom MFT
Part number for
See settings configuration in the field
tagging: 99981-00101
Refers to valve ports A to AB. with MFT-actuator PC-Tool software
11-1
Control Valve Product Range
Characterized Control Valve Product Range
½ 15 B207(B) B307(B)
0.46 ½ 15 B208(B) B308(B)
0.8 ½ 15 B209(B) B309(B)
1.2 ½ 15 B210(B) B310(B)
1.9 ½ 15 B211(B) B311(B) CCV
3 ½ 15 B212(B) B312(B) Equal Percentage
TFR Series
TR Series
Characteristic
4.7 ½ 15 B213(B) B313(B)
7.4 ½ 15 B214(B) Mode of Operation
The Characterized Control Valve is operated by a rotary actua-
10 ½ 15 B215(B) B315(B)
tor. The actuators are controlled by a standard voltage for on/
16 ½ 15 B216(B)* B316(B)* off control, a proportional signal, or 3-point control system
which move the ball of the valve to the position dictated by the
NR Series
LR Series
LF Series
4.7 ¾ 20 B217(B) B317(B) control system.
7.4 ¾ 20 B218(B) B318(B) Product Features
The equal-percentage characteristic of the flow is ensured by
10 ¾ 20 B219(B) the integral characterizing disc. This characteristic provides
linear heating or cooling output from the coil improving
14 ¾ 20 B220(B)*
energy efficiency and comfort.
14 ¾ 20 B320(B)
Actuator Specifications
24 ¾ 20 B221(B)* B321(B)* Control type on/off, floating point, 2-10 VDC,
multi-function technology (MFT)
7.4 1 25 B222 B322 Manual override TR, LR, AR, NR, AFR series
10 1 25 B223 B323 Electrical connection 3 ft. [1 m] cable with ½”
conduit fitting or covered screw
19 1 25 B224 terminal strip
30 1 25 B225* B325* Valve Specifications
10 1¼ 32 B229 Service chilled or hot water, up to
60% glycol
19 1¼ 32 B230* Flow characteristic A-port equal percentage
AFR Series
AR Series
AR Series
Non-
2-way Spring
Cv Inches DN [mm] Spring NEMA 4X
NPT Return
Return
60 2½ 65 B261
75 2½ 65 B262
110 2½ 65 B263
AFR Series
AR Series
AR Series
150 2½ 65 B264 CCV
210 2½ 65 B265*
Equal Percentage
70 3 80 B277 Characteristic
130 3 80 B278
Mode of Operation
170 3 80 B280* The Characterized Control Valve is operated by a rotary
* Models without characterizing disc actuator. The actuators are controlled by a standard voltage
for on/off control, a proportional signal, or 3-point control
system which move the ball of the valve to the position
dictated by the control system.
Product Features
The equal-percentage characteristic of the flow is ensured
by the integral characterizing disc. This characteristic
provides linear heating or cooling output from the coil
improving energy efficiency and comfort.
Actuator Specifications
Control type on/off, floating point, 2-10 VDC,
multi-function technology (MFT)
Manual override AR and AFR series
Electrical connection 3 ft. [1 m] cable with ½”
conduit fitting or covered screw
terminal strip
Valve Specifications
Service chilled or hot water, up to
60% glycol
Flow characteristic A-port equal percentage
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
11-3
Control Valve Product Range
Characterized Control Valve Product Range
70 2½ 65 B6250S-070
AFR
AFR
110 2½ 65 B6250S-110 AR
AR
110 3 80 B6300S-110
186 4 100 B6400S-186
CCV
GKR
GKR
GR
GR
290 5 125 B6500S-290
400 6 150 B6600S-400 Equal Percentage
Characteristic
Mode of Operation
The Characterized Control Valve is operated by a rotary
actuator. The actuators are controlled by a standard voltage for
on/off control, a proportional signal, or 3-point control system
which move the ball of the valve to the position dictated by the
control system.
Product Features
The equal-percentage characteristic of the flow is ensured by
the integral characterizing disc. This characteristic provides
linear heating or cooling output from the coil improving energy
efficiency and comfort.
Actuator Specifications
Control type on/off, floating point, 2-10 VDC,
multi-function technology (MFT)
Manual override AR, GR, AFR and GKR series
Electrical connection 3 ft. [1 m] cable with ½”
conduit fitting or covered screw
terminal strip
Valve Specifications
Service chilled or hot water, up to
60% glycol max.
Flow characteristic A-port equal percentage
11-4
Characterized Control Valves
CCV
NOTE: Please use the corrected Cv values for the valves listed in the chart when installing them in pipes larger than the line size of the valve.
All CCVs not listed do not require piping reduction factors.
11-5
Characterized Control Valves
LRB24-3(-T), ARB24-3(-T) Power to pin 2 will drive Power to pin 2 will drive
valve CW. Power to pin 3 valve CW. Power to pin 3
will drive valve CCW. The will drive valve CCW. The
above will fuction when above will fuction when
the directional switch is in the directional switch is in
the ”1” position to reverse, the ”1” position to reverse,
select the ”0” position. select the ”0” position.
TR24-SR(-T), LRB24-SR, NC: Normally closed A NO: Normally open A to AB, NC: Normally closed A NO: Normally open A to AB,
LRB(X)24-MFT, to AB, valve will open as valve will close as voltage to AB, valve will open as valve will close as voltage
ARB24-SR, ARB(X)24-MFT voltage increases increases voltage increases increases
TFRB24, LF24 US, NO/FO: Normally open A to NC/FC: Normally closed A NO/FO: Normally open A to NC/FC: Normally closed A
AFRB24 AB, valve will drive closed. to AB, valve will drive open. AB, valve will drive closed. to AB, valve will drive open.
Spring Action: Actuator Spring Action: Actuator will Spring Action: Actuator Spring Action: Actuator will
SPRING RETURN
Note Fail Position
will fail open A to AB upon fail closed A to AB upon will fail open A to AB upon fail closed A to AB upon
CCV
TFRB24-3, TFRB24-SR, NC/FO: Normally closed A NC/FC: Normally closed A NO/FC: Normally open A NO/FO: Normally open A
TFRX24-MFT, to AB, valve will open as to AB, valve will open as to AB, valve will close as to AB, valve will close as
LF24-3 US, LF24-SR US, voltage increases. Actuator voltage increases. Actuator voltage increases. Actuator voltage increases. Actuator
LF24-MFT US, switch on CW. switch on CW. switch on CCW. switch on CCW.
AFRB24-SR, AFRX24-MFT Spring Action: Will fail open Spring Action: Will fail Spring Action: Will fail Spring Action: Will fail open
upon power loss. closed upon power loss. closed upon power loss. upon power loss.
will drive valve CCW. The will drive valve CCW. The
above will fuction when the above will fuction when the
directional switch is in the directional switch is in the
”Y2” position to reverse, ”Y2” position to reverse,
select the ”Y1” position. select the ”Y1” position.
GKRX24-MFT-5-14† NC: Normally closed A to NO: Normally open A to NC: Normally closed A to NO: Normally open A to
AB, will open as voltage AB, will close as voltage AB, will open as voltage AB, will close as voltage
increases when directional increases when directional increases when directional increases when directional
switch is in the ”Y2” switch is in the ”Y1” switch is in the ”Y2” switch is in the ”Y2”
position. position. position. position.
† The GK series Electronic Fail-Safe actuator will drive to a predetermined postion using the FO/FC dial on the actuator upon loss of power.
11-6
Characterized Control Valves
FLOW PATTERNS
2-way Characterized Control Valves™ (Belimo B2 Series)
Flow direction
Two-way valves
should be installed
with the disc
upstream.
A AB 100% A AB 0%
INCORRECT PIPING
CCV
WARNING! Do Not Pipe in this manner!
Note Valve Porting!
The A-port must be piped to the coil, not the B-port!
Flow is not possible from A to B. If AB-port is not piped as
the common port, the valve must be re-piped. It is good
practice to install a balancing valve in the bypass line. These
valves are intended for closed loop systems. Do not install
in an open loop system or in an application that is open to
atmospheric pressure.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
2-way valves should be installed with the disc upstream. If installed with disc downstream, flow curve will be deeper. If installed ”backwards” it is NOT necessary to
remove and change. No damage or control problems will occur.
3-WAY VALVES MUST BE PIPED CORRECTLY. They can be mixing or diverting. Mixing is the preferred piping arrangement.
The BELIMO Characterized Control Valve is a CONTROL valve, not a manual valve adapted for actuation. The control port is the A-port. It is similar to the globe valve in that
the middle port is the B or bypass port. The common port AB is on the main opposite the A-port. These diagrams are for typical applications only. Consult engineering
specification and drawings for particular circumstances.
REDUCED B-PORT FLOW
Note: The B-port flow of the 3-way CCV is lower than that of the A-port. In most applications this is beneficial since the reduced flow compensates for the inexistent
pressure drop across the coil in the bypass mode. Therefore, proper sizing is important to avoid flow noise in particular when the system is designed with constant
speed pumps. Please refer to our valve sizing and selection guidelines.
The flow velocity in the pipe upstream and downstream of the valve should be considered as well. The typical HVAC design maximum flow is 4 to 8 ft./s to avoid
noise issues.
Also, the pipe reduction factor must be considered. Pipe reducers decrease the Cv value of a valve and consequently increase the pressure drop across the valve
creating a situation that could lead to noise or a lower than designed flow.
11-7
B2/B3 Series Characterized Control Valves with Non-Spring Return Actuators
2-way and 3-way Valves with Chrome Plated Brass Ball and Brass Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic (B2) A-port equal percentage
A- port equal percentage; B-port Visit www.belimo.uss to see additional non-spring return
Flow Characteristic (B3)
modified linear for constant flow actuator options including 120V and -S models.
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass, nickel plated
Ball chrome plated brass
Stem nickel plated brass
Seat Teflon® PTFE
Characterized Disc TEFZEL®
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB, <2.0% for B to AB
A-port: as stated in chart
Cv Flow Rating
B-port: 70% of A to AB Cv
Noise Level (Motor) <35 dB (A) <35 dB (A) <35 dB (A) <35 dB (A) <35 dB (A) <35 dB (A)
3 ft, 18 GA plenum 3 ft, 18 GA plenum 3 ft, 18 GA plenum
screw terminal (for screw terminal (for 3 ft, 18 GA
Electrical Connection cable with ½” conduit cable with ½” conduit cable with ½” conduit
26 to 14 GA wire) 26 to 14 GA wire) plenum cable
connector connector connector
2-Way
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B207B 0.3 200 $188 $201 $282 $295 $259 $387
B208B 0.46 200 $188 $201 $282 $295 $259 $387
B209B 0.8 200 $188 $201 $282 $295 $259 $387
B210B 1.2 200 $191 $203 $284 $297 $261 $389
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-8
B2/B3 Series Characterized Control Valves with Spring Return Actuators
2-way and 3-way Valves with Chrome Plated Brass Ball and Brass Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic (B2) A-port equal percentage
A- port equal percentage; B-port Visit www.belimo.uss to see additional spring return
Flow Characteristic (B3)
modified linear for constant flow
actuator options including 120V and -S models.
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass, nickel plated
Ball chrome plated brass
Stem nickel plated brass
Seat Teflon® PTFE
Characterized Disc TEFZEL®
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB, <2.0% for B to AB
A-port: as stated in chart
Cv Flow Rating
B-port: 70% of A to AB Cv
CCV
Noise Level (Motor) <40 dB (A) <35 dB (A) <35 dB (A) <50 dB (A) <30 dB (A) <30 dB (A)
Noise Level (Fail-Safe) <40 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A)
3 ft, 18 GA appliance 3 ft, 18 GA plenum 3 ft, 18 GA plenum 3 ft, 18 GA appliance 3 ft, 18 GA plenum 3 ft, 18 GA plenum
Electrical Connection cable, ½” conduit cable with ½” conduit cable with ½” conduit cable, ½” conduit cable with ½” conduit cable with ½” conduit
connector connector connector connector connector connector
2-Way
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B207B 0.3 200 $366 $418 $448 $417 $529 $546
B208B 0.46 200 $366 $418 $448 $417 $529 $546
B209B 0.8 200 $366 $418 $448 $417 $529 $546
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-9
B2 Series Characterized Control Valves with Non-Spring Return Actuators
2-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75° Visit www.belimo.uss for additional non-spring return
End Fitting NPT female ends actuator options including 120V and -S models.
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL®
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-10
B2 Series Characterized Control Valves with Non-Spring Return Actuators
2-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75° Visit www.belimo.uss for additional non-spring return
End Fitting NPT female ends actuator options including 120V and -S models.
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL® or stainless steel
O-ring EPDM (lubricated)
Media Temp. Range
0°F to 250°F [-18°C to +120°C]
1.25” - 2”
Media Temp. Range
0°F to 212°F [-18°C to 100°C]
2.5” - 3”
Max Differential Pressure
50 psi
1.25” - 2”
Max Differential Pressure
30 psi
2.5” - 3”
Leakage 0% for A to AB
CCV
Electrical Connection
connector connector connector
2-Way
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B231 25 1.25” 200 $457 $604 $657
B232 37 [32] 200 $466 $609 $672
B238 19 200 $466 $617 $672
1.5”
B239 29 200 $466 $619 $676
[40]
B240 37 200 $468 $622 $678
B248 29 200 $604 $749 $800
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-11
B3 Series Characterized Control Valves with Non-Spring Return Actuators
3-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
A-port equal percentage, B-port
Flow Characteristic
modified linear for constant flow Visit www.belimo.uss for additional non-spring return
Controllable Flow Range 75° actuator options including 120V and -S models.
End Fitting NPT female ends
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL®
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB, <2.0% for B to AB
Cv Flow Rating B-port: 70% of A to AB Cv
Noise Level (Motor) <35 dB (A) <35 dB (A) <35 dB (A) <35 dB (A) <35 dB (A) <35 dB (A) <35 dB (A)
3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA
screw terminal screw terminal
plenum cable 3 ft, 18 GA plenum cable plenum cable plenum cable
Electrical Connection (for 26 to 14 GA (for 26 to 14 GA
with ½” conduit plenum cable with ½” conduit with ½” conduit with ½” conduit
wire) wire)
connector connector connector connector
3-Way Mixing/Diverting
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B307 0.3 200 $276 $288 $398 $410 $340 $462 $587
B308 0.46 200 $276 $288 $398 $410 $340 $462 $587
B309 0.8 200 $276 $288 $398 $410 $340 $462 $587
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-12
B3 Series Characterized Control Valves with Non-Spring Return Actuators
3-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
A-port equal percentage, B-port
Flow Characteristic
modified linear for constant flow Visit www.belimo.uss for additional non-spring return
Controllable Flow Range 75° actuator options including 120V and -S models.
End Fitting NPT female ends
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc stainless steel
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB, <2.0% for B to AB
Cv Flow Rating B-port: 70% of A to AB Cv
CCV
3 ft, 18 GA plenum cable with ½” conduit 3 ft, 18 GA plenum cable with ½” conduit 3 ft, 18 GA plenum cable with ½” conduit
Electrical Connection
connector connector connector
3-Way Mixing/Diverting
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
10 200 $533 $624 $737
1.25”
B330 19 200 $539 $629 $747
[32]
B331 25 200 $678 $824 $879
B338 19 200 $687 $839 $905
B339 29 1.5” 200 $691 $844 $908
B340 37 [40] 200 $693 $848 $912
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-13
B2 Series Characterized Control Valves with Spring Return Actuators
2-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75° Visit www.belimo.uss for additional spring return
End Fitting NPT female ends actuator options including 120V and -S models.
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL®
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB
ACTUATOR PART # TFRB24 TFRB24-3 TFRB24-SR TFRX24-MFT LF24 US LF24-3 US LF24-SR US LF24-MFT US
Proportional/ Proportional/
On/Off Floating Point Proportional On/Off Floating Point Proportional
MFT MFT
150 seconds 150 seconds
(default), (default),
Running Time (Motor) <75 seconds 90 seconds 95 seconds 75 seconds 150 seconds 150 seconds
variable (75 to variable (75 to
300 seconds) 300 seconds)
Running Time (Fail-Safe) < 75 seconds <25 seconds <25 seconds <25 seconds <25 seconds <25 seconds <25 seconds <25 seconds
CCV
Noise Level (Motor) <40 dB (A) <35 dB (A) <35 dB (A) <35 dB (A) <50 dB (A) <30 dB (A) <30 dB (A) <30 dB (A)
Noise Level (Fail-Safe) <40 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A)
3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA
appliance plenum plenum plenum appliance plenum plenum appliance
Electrical Connection cable, ½” cable with cable with cable with cable, ½” cable with cable with cable, ½”
conduit ½” conduit ½” conduit ½” conduit conduit ½” conduit ½” conduit conduit
connector connector connector connector connector connector connector connector
2-Way
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B207 0.3 200 $379 $432 $464 $546 $437 $548 $566 $654
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-14
B2 Series Characterized Control Valves with Spring Return Actuators
2-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75° Visit www.belimo.uss for additional spring return
End Fitting NPT female ends actuator options including 120V and -S models.
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL® or stainless steel
O-ring EPDM (lubricated)
Media Temp. Range
0°F to 250°F [-18°C to +120°C]
1.25” - 2”
Media Temp. Range
0°F to 212°F [-18°C to 100°C]
2.5” - 3”
Max Differential Pressure
50 psi
1.25” - 2”
Max Differential Pressure
30 psi
2.5” - 3”
Leakage 0% for A to AB
CCV
Noise Level (Fail-Safe) <62 dB (A) <62 dB (A) <62 dB (A)
3 ft, 18 GA appliance cable, ½” conduit 3 ft, 18 GA appliance cable, ½” conduit 3 ft, 18 GA plenum cable with ½” conduit
Electrical Connection
connector connector connector
2-Way
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B231 25 1.25” 200 $624 $774 $887
B232 37 [32] 200 $626 $777 $889
B238 19 200 $630 $783 $894
1.5”
B239 29 200 $632 $788 $896
[40]
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-15
B3 Series Characterized Control Valves with Spring Return Actuators
3-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
A-port equal percentage, B-port
Flow Characteristic
modified linear for constant flow Visit www.belimo.uss for additional spring return
Controllable Flow Range 75° actuator options including 120V and -S models.
End Fitting NPT female ends
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL® or stainless steel
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB, <2.0% for B to AB
A-port: as stated in chart
Cv Flow Rating
B-port: 70% of A to AB Cv
ACTUATOR PART # TFRB24 TFRB24-3 TFRB24-SR TFRX24-MFT LF24 US LF24-3 US LF24-SR US LF24-MFT US
Proportional/ Proportional/
On/Off Floating Point Proportional On/Off Floating Point Proportional
MFT MFT
150 seconds 150 seconds
(default), (default),
Running Time (Motor) <75 seconds 90 seconds 95 seconds 75 seconds 150 seconds 150 seconds
variable (75 to variable (75 to
300 seconds) 300 seconds)
CCV
Running Time (Fail-Safe) < 75 seconds <25 seconds <25 seconds <25 seconds <25 seconds <25 seconds <25 seconds <25 seconds
Noise Level (Motor) <40 dB (A) <35 dB (A) <35 dB (A) <35 dB (A) <50 dB (A) <30 dB (A) <30 dB (A) <30 dB (A)
Noise Level (Fail-Safe) <40 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A)
3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA
appliance plenum plenum plenum appliance plenum plenum appliance
Electrical Connection cable, ½” cable with cable with cable with cable, ½” cable with cable with cable, ½”
conduit ½” conduit ½” conduit ½” conduit conduit ½” conduit ½” conduit conduit
connector connector connector connector connector connector connector connector
3-Way Mixing/Diverting
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-16
B3 Series Characterized Control Valves with Spring Return Actuators
3-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
A-port equal percentage, B-port
Flow Characteristic
modified linear for constant flow Visit www.belimo.uss for additional spring return
Controllable Flow Range 75° actuator options including 120V and -S models.
End Fitting NPT female ends
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc stainless steel
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB, <2.0% for B to AB
A-port: as stated in chart
Cv Flow Rating
B-port: 70% of A to AB Cv
CCV
Noise Level (Motor) <45 dB (A) <40 dB (A) <40 dB (A)
Noise Level (Fail-Safe) <62 dB (A) <62 dB (A) <62 dB (A)
3 ft, 18 GA appliance cable, ½” conduit 3 ft, 18 GA appliance cable, ½” conduit 3 ft, 18 GA plenum cable with ½” conduit
Electrical Connection
connector connector connector
3-Way Mixing/Diverting
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B329 10 200 $711 $851 $885
1.25”
B330 19 200 $717 $855 $889
[32]
B331 25 200 $867 $1,027 $1,100
B338 19 200 $881 $1,042 $1,103
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-17
B6 Series Characterized Control Valves with Non-Spring Return Actuators
2-way Valve with Stainless Steel Ball and Stem, Flanged Ends
Valve Specifications
chilled , hot water, up to 60%
glycol
Flow Characteristic equal percentage
Visit www.belimo.uss for additional non-spring return
Controllable Flow Range 75°
pattern to mate with ANSI 125 actuator options including 120V and -S models.
End Fitting
flange
Body cast iron - GG25
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc stainless steel
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB
11-18
B6 Series Characterized Control Valves with Spring Return
and Electronic Fail-Safe Actuators
2-way Valve with Stainless Steel Ball and Stem, Flanged Ends
Valve Specifications
chilled , hot water, up to 60%
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
pattern to mate with ANSI 125
End Fitting
flange
Body cast iron - GG25
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc stainless steel
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB
CCV
Noise Level (Fail-Safe) <62 dB (A) <62 dB (A)
3 ft, 18 GA appliance cable, ½” 3 ft, 18 GA plenum cable with ½” 3 ft, 18 GA plenum cable with ½” 3 ft, 18 GA plenum cable with ½”
Electrical Connection
conduit connector conduit connector conduit connector conduit connector
2-Way
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B6250S-070 70 2.5” 100 $1,840 $2,071
B6250S-110 110 [65] 100 $1,924 $2,146
B6300S-110 110 3” [80] ANSI 125, 100 $2,077 $2,364
Standard
B6400S-186 186 4” [100] 100 $2,574 $2,760
Class B
B6500S-290 290 5” [125] 100 $3,667 $3,804
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
AFRX24 MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed. Note: Most popular configurations available at no
additional cost. All other configurations carry a $34.00 list price.
11-19
B2 Series Characterized Control Valves with NEMA 4X Non-Spring Return Actuators
2-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow characteristic equal percentage
Controllable Flow Range 75° Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225,
B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325, B280.
End Fitting NPT female ends For corrected Cvs with piping reduction factor refer to page 11-5.
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL® or stainless steel
O-ring EPDM (lubricated)
Media Temp. Range 0.5” - 2” 0°F to 250°F [-18°C to +120°C]
Media Temp. Range 2.5” - 3” 0°F to 212°F [-18°C to 100°C]
Max Differential Pressure
50 psi
0.5” - 2”
Max Differential Pressure
30 psi
2.5” - 3”
Leakage 0% for A to AB
ACTUATOR PART # NRX24-3-T N4 NRX24-SR-T N4 NRX24-MFT-T N4 ARX24-3-T N4 ARX24-SR-T N4 ARX24-MFT-T N4
Control On/Off, Floating Point Proportional Proportional/MFT On/Off, Floating Point Proportional Proportional/MFT
Manual Override • • • • • •
150 seconds 150 seconds
Running Time (Motor) 90 seconds 90 seconds (default), variable 90 seconds 90 seconds (default), variable
(45 to 150 seconds) (90 to 300 seconds)
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
Electrical Connection terminal block terminal block terminal block terminal block terminal block terminal block
CCV
2-Way
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B207 0.3 200 $584 $693 $814
B208 0.46 200 $584 $693 $814
B209 0.8 200 $584 $693 $814
B210 1.2 200 $587 $695 $819
B211 1.9 0.5” 200 $587 $695 $819
B212 3 [15] 200 $587 $695 $819
B213 4.7 200 $591 $701 $824
B214 7.4 200 $597 $708 $830
B215 10 200 $602 $713 $834
11-20
B3 Series Characterized Control Valves with NEMA 4X Non-Spring Return Actuators
3-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
A-port equal percentage, B-port
Flow Characteristic
modified linear for constant flow
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL® or stainless steel
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB, <2.0% for B to AB
Cv Flow Rating B-port: 70% of A to AB Cv
CCV
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
Electrical Connection terminal block terminal block terminal block terminal block terminal block terminal block
3-Way Mixing/Diverting
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B307 0.3 200 $631 $756 $891
B308 0.46 200 $631 $756 $891
B309 0.8 200 $631 $756 $891
B310 1.2 200 $633 $758 $894
0.5”
B311 1.9 200 $633 $758 $894
[15]
B312 3 200 $635 $760 $896
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
ACTUATOR PART # NRX24-3-T N4H NRX24-SR-T N4H NRX24-MFT-T N4H ARX24-3-T N4H ARX24-SR-T N4H ARX24-MFT-T N4H
Add to List Price for heater +$370 +$370 +$370 +$370 +$370 +$370
11-21
B2, B3 Series Characterized Control Valves with NEMA 4 Spring Return Actuators
2-way and 3-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
A-port equal percentage, B-port
Flow Characteristic
modified linear for constant flow
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL® or stainless steel
O-ring EPDM (lubricated)
Media Temp. Range
0°F to 250°F [-18°C to +120°C]
1.25” - 2”
Media Temp. Range
0°F to 212°F [-18°C to 100°C]
2.5” - 3”
Max Differential Pressure
50 psi
1.25” - 2”
Max Differential Pressure
30 psi
2.5” - 3”
Leakage 0% for A to AB, <2.0% for B to AB
A-port: as stated in chart
Cv Flow Rating
B-port: 70% of A to AB Cv
Electrical Connection 3 ft, 18 GA appliance cable, ½” conduit connector 3 ft, 18 GA plenum cable with ½” conduit connector
2-Way
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B231 25 1.25” 200 $1,205 $1,383
B232 37 [32] 200 $1,208 $1,387
B238 19 200 $1,212 $1,391
1.5”
B239 29 200 $1,214 $1,393
[40]
B240 37 200 $1,217 $1,395
B248 29 200 $1,461 $1,471
B249 46 200 $1,471 $1,650
11-22
B6 Series Characterized Control Valves with NEMA 4 Non-Spring Return Actuators
2-way Valve with Stainless Steel Ball and Stem, Flanged Ends
Valve Specifications
chilled , hot water, up to 60%
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
pattern to mate with ANSI 125
End Fitting
flange
Body cast iron - GG25
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc stainless steel
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB
CCV
2-Way
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi] [psi]
B6250S-070 70 100 $2,437 $2,637
2.5” [65]
B6250S-110 110 100 $2,599 $2,861
B6300S-110 110 3” [80] ANSI 125, 100 $2,604 $3,032
Standard
B6400S-186 186 4” [100] 100 $2,907 $3,573
Class B
B6500S-290 290 5” [125] 100 $3,915 $4,230
B6600S-400 400 6” [150] 100 $4,324 $5,100
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
ACTUATOR PART # ARX24-3-T N4H ARX24-MFT-T N4H GRX24-3-T N4H GRX24-MFT-T N4H
Add to List Price for heater +$370 +$370 +$370 +$370
11-23
B6 Series Characterized Control Valves
with NEMA 4 Spring Return and Electronic Fail-Safe Actuators
2-way Valve with Stainless Steel Ball and Stem, Flanged Ends
Valve Specifications
chilled , hot water, up to 60%
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
pattern to mate with ANSI 125
End Fitting
flange
Body cast iron - GG25
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc stainless steel
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB
ACTUATOR PART # AFRX24 N4H AFRX24-MFT N4H GKRX24-3 N4H GKRX24-MFT N4H
Add to List Price for heater +$1,053 +$1,053 +$370 +$370
11-24
B2 Series Characterized Control Valves
with Quick Running Non-Spring Return Actuators
2-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
glycol
Flow Characteristic equal percentage
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL® or stainless steel
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB
CCV
2-Way
Close-Off
Size Body Pressure
Model # Cv Pressure
[mm] Rating [psi]
[psi]
B207 0.3 200 $674
B208 0.46 200 $674
B209 0.8 200 $674
B210 1.2 200 $678
B211 1.9 0.5” 200 $678
B212 3 [15] 200 $683
B213 4.7 200 $693
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-25
B3 Series Characterized Control Valves
with Quick Running Non-Spring Return Actuators
3-way Valve with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
A-port equal percentage, B-port
Flow Characteristic
modified linear for constant flow
Controllable Flow Range 75°
End Fitting NPT female ends
Body forged brass, nickel plated
Ball stainless steel
Stem stainless steel
Seat Teflon® PTFE
Characterized Disc TEFZEL® or stainless steel
O-ring EPDM (lubricated)
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage 0% for A to AB, <2.0% for B to AB
Cv Flow Rating B-port: 70% of A to AB Cv
3-Way Mixing/Diverting
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi] [psi]
B307 0.3 200 $754
B308 0.46 200 $754
B309 0.8 200 $754
B310 1.2 200 $756
0.5”
B311 1.9 200 $756
[15]
B312 3 200 $758
B313 4.7 200 $767
B315 10 200 $769
600
Models without characterizing discs: B216, B216B, B220, B220B, B221, B221B, B225, B230, B232, B240, B250, B254, B265, B280, B316, B316B, B321, B321B, B325.
For corrected Cvs with piping reduction factor refer to page 11-5.
11-26
AR Series Non-Spring Return Actuators
Custom, Direct Coupled, Non-Spring Return Actuator, 180 in-lbs Minimum Torque
Actuator Specifications
Torque 180 in-lbs [20 Nm]
Ambient Temperature -22°F to +122°F
[-30°C to +50°C]
Angle of Rotation max 90°, adjustable with
mechanical stop electronically
variable
Position Indication handle
Manual Override external push-button
Direction of Rotation reversible with switch
Dimensions 7.47” x 3.45” x 2.52”
[189.8 x 88 x 64 mm]
Electrical Connection 18 GA plenum rated cable, ½”
conduit connector
Overload Protection electronic throughout rotation
Auxiliary Switch(es) (-S) models: 1 SPDT, 3A (0.5A
inductive) @ 250V adjustable
5° to 85°
Housing NEMA 2/IP54
Agency Listings cULus acc. to UL 60730-1A/-
2-14, CAN/CSA E60730-1:02, MFT= 2-10 VDC Default, or Set, Modify, Read: All AR
CSA C22.2 No. 24-93, CE acc. • Control (PWM, VDC range, Floating Point) Actuators
to 2006/95/EC and 89/336/EEC • Feedback (0-10 VDC, 0-5 VDC, 2-10 VDC, Variable) have BDCM
• Motion (run time)
Variable with MFT
CCV
ARX24-3 On/Off, Floatingg Point Add on 24 VAC/VDC 95 5.5 10 ft. AR000 0C3 000 $404
ARX24-3 On/Off, Floatingg Point Add on 24 VAC/VDC 95 5.5 16 ft. AR000 0C5 000 $425
ARX24-3-S On/Off, Floatingg Point Built-in 24 VAC/VDC 95 5.5 10 ft. AR020 0A3 000 $507
ARX24-3-S On/Off, Floatingg Point Built-in 24 VAC/VDC 95 5.5 16 ft. AR020 0A5 000 $529
ARX24-3-T On/Off, Floatingg Point Add on 24 VAC/VDC 95 5.5 N/A ART00 0T2 000 $357
ARX120-3 On/Off, Floatingg Point Add on 100-230 VAC/VDC 95 7 10 ft. AR060 0A3 000 $458
ARX120-3 On/Off, Floatingg Point Add on 100-230 VAC/VDC 95 7 16.ft. AR060 0A5 000 $480
ARX24-SR 2-10 VDC (4-20mA*)
( ) 2-10 VDC 24 VAC/VDC 95 5 10 ft. AR030 0C3 000 $555
ARX24-SR 2-10 VDC (4-20mA*)
( ) 2-10 VDC 24 VAC/VDC 95 5 16 ft. AR030 0C5 000 $578
ARX24-SR-T 2-10 VDC (4-20mA*)
( ) 2-10 VDC 24 VAC/VDC 95 5 N/A ARTW0 0T2 000 $512
ARX120-SR 2-10 VDC (4-20mA*)
( ) 2-10 VDC 100-230 VAC/VDC 95 7.5 10 ft. AR450 0A3 000 $617
ARX120-SR 2-10 VDC (4-20mA*)
( ) 2-10 VDC 100-230 VAC/VDC 95 7.5 16 ft. AR4500A5 000 $640
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
MFT VERSIONS
ARX24-MFT Various Various 24 VAC/VDC Various 6 3 ft. AR100 0C1 XXX** $550
ARX24-MFT Various Various 24 VAC/VDC Various 6 10 ft. AR100 0C3 XXX** $582
ARX24-MFT Various Various 24 VAC/VDC Various 6 16 ft. AR100 0C5 XXX** $606
ARX24-MFT95 0 to 135 Ω Various 24 VAC/VDC 150 6 3 ft. AR0L0 0C3 R01 $564
*With 500 Ω resistor
** See page 11-29 for P-Codes available.
The P-Code programs the actuator for the desired Control Input, Feedback and Running Time.
11-27
LR Series Non-Spring Return Actuators
Custom, Direct Coupled Non-Spring Return Actuator, 45 in-lbs Minimum Torque
Actuator Specifications
Torque 45 in-lbs [5 Nm]
Ambient Temperature -22°F to +122°F
[-30°C to +50°C]
Angle of Rotation max. 90°, adjustable with
mechanical stop
electronically variable
Position Indication handle
Manual Override external push-button
Direction of Rotation reversible with switch
Dimensions 6.18” x 2.6” x 2.34”
[157 x 66 x 59.4 mm]
Electrical Connection 18 GA plenum rated cable, ½”
conduit fitting terminal strip
(-T) models
Overload Protection electronic throughout rotation
Auxiliary Switch LRX24-3-S - 1SPDT, 3A
(0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 100°
Housing NEMA 2/IP54
Agency Listings cULus acc. to UL 60730-1A/-
2-14, CAN/CSA E60730-1:02,
CSA C22.2 No. 24-93, CE acc.
to 2006/95/EC and 89/336/EEC
Variable with MFT MFT= 2-10 VDC Default, or Set, Modify, Read: All actuators
• Control (PWM, VDC range, Floating Point) have BDCM
• Feedback (0-10 VDC, 0-5 VDC, 2-10 VDC, Variable)
• Motion (run time)
CCV
Running
VA Cable Re-order List
Model Control Input Feedback Power Supply Time(s)
Rating Length Number Price ‡
[Default]
On/Off, Floating Point Add on 24 VAC/DC 90 seconds 2 10 ft. LR000 RC3 000 $248
LRX24-3 On/Off, Floating Point Add on 24 VAC/DC 90 seconds 2 16 ft. LR000 RC5 000 $270
LRX24-3-S On/Off, Floating Point Add on 24 VAC/DC 90 seconds 2 10 ft. LR020 RA3 000 $340
LRX24-3-S On/Off, Floating Point Add on 24 VAC/DC 90 seconds 2 16 ft. LR020 RA5 000 $363
LRX24-3-T On/Off, Floating Point Add on 24 VAC/DC 90 seconds 2 N/A LRT00 RT2 000 $200
LRX120-3 On/Off, Floating Point Add on 100-230 VAC 90 seconds 4 10 ft. LR060 RA3 000 $297
LRX120-3 On/Off, Floating Point Add on 100-230 VAC 90 seconds 4 16 ft. LR060 RA5 000 $319
LRX24-SR 2-10 VDC (4-20mA*) 2-10 VDC 24 VAC/DC 90 seconds 4.5 10 ft. LR030RC3 000 $370
MFT VERSIONS
LRX24-MFT Various Various 24 VAC/VDC Various 5 3 ft. LR100 RC1 XXX** $413
LRX24-MFT Various Various 24 VAC/VDC Various 5 10 ft. LR100 RC3 XXX** $444
LRX24-MFT Various Various 24 VAC/VDC Various 5 16 ft. LR100 RC5 XXX** $467
LRX24-MFT95 0 to 135 Ω 2-10 VDC 24 VAC/VDC 150 seconds 5 3 ft. LR0L0 RC1 R01 $477
‡ Prices do not reflect additional programming code surcharge.
*With 500 Ω resistor
** See page 11-29 for P-Codes available.
The P-Code programs the actuator for the desired Control Input, Feedback and Running Time.
11-28
Customize Products
Default and MFT Programming Codes
CONTROL
CONFIGURATION
ACTUATOR TYPE P-CODE CONTROL INPUT FEEDBACK POSITION RUNNING TIME List Price ‡
DESCRIPTION
N/A 0 2-10 VDC (for -3) 2-10 VDC (for -3) 150 seconds No Charge
-3 and SR
N/A 2 2-10 VDC (for -SR) 2-10 VDC (for -SR) 90 seconds No Charge
P-10001 A01 2-10 VDC 2-10 VDC 150 seconds No Charge*
MFT and PC
P-10002 A02 0.5-10 VDC 0-10 VDC 150 seconds No Charge
P-10003 A03 2-10 VDC 0-5.0 VDC 150 seconds No Charge
P-10004 A04 4-7 VDC 2-10 VDC 150 seconds $34
P-10005 A05 6-9 VDC 2-10 VDC 150 seconds $34
P-10006 A06 10.5 -13.5 VDC 2-10 VDC 150 seconds $34
P-10007 A07 0.5-5 VDC 2-10 VDC 150 seconds $34
P-10009 A09 5-10 VDC 2-10 VDC 150 seconds $34
P-10010 A10 5-10 VDC 0-10 VDC 150 seconds $34
P-10013 A13 0.5-10 VDC 2-10 VDC 150 seconds $34
P-10015 A15 2-5 VDC 2-10 VDC 150 seconds $34
P-10016 A16 2-6 VDC 2-10 VDC 150 seconds $34
P-10017 A17 6-10 VDC 2-10 VDC 150 seconds $34
P-10018 A18 14-17 VDC 2-10 VDC 150 seconds $34
P-10020 A20 9-12 VDC 2-10 VDC 150 seconds $34
P-10028 A28 0.5-10 VDC 0.5-10 VDC 100 seconds No Charge
P-10031 A31 0.5- 4 VDC 2-10 VDC 150 seconds $34
P-10063 A63 0.5-4.5 VDC 0.5- 4.5 VDC 150 seconds No Charge
P-10032 A32 2-10 VDC 2-10 VDC 100 seconds No Charge
P-10064 A64 5.5-10 VDC 5.5-10.0 VDC 150 seconds No Charge
N/A AAT 2-10 VDC 2-10 VDC 20 seconds No Charge
P-20001 W01 0.59-2.93 seconds 2-10 VDC 150 seconds $34
P-20002 W02 0.02 to 5.00 seconds 2-10 VDC 150 seconds No Charge
CCV
P-20003 W03 0.10 to 25.50 seconds 2-10 VDC 150 seconds No Charge
P-20004 W04 0.10 to 25.60 seconds 2-10 VDC 150 seconds $34
P-20005 W05 0.10 to 5.20 seconds 0-5.0 VDC 150 seconds $34
P-30001 F01 Floating Point 2-10 VDC 150 seconds No Charge
P-30002 F02 Floating Point 0-10 VDC 150 seconds $34
P-40002 J02 On/Off 2-10 VDC 150 seconds No Charge
N/A S01 (for -PC only) Phasecut 2-10 VDC 150 seconds No Charge
P-16001 R01 (for -MFT95 only) 0 to 135 Ω 2-10 VDC 150 seconds No Charge
NOTE: More P-codes are available, consult factory.
‡ Add to list price on previous page.
*P-10001 is the default configuration for MFT.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
11-29
Valve Accessories
CCV
ZS-CCV-90*
• • $224
CCV/PICCV weather shield kit LF/AF
ZS-CCV-100*
• • $224
CCV/PICCV weather shield kit LR/AR
ZS-CCV-110*
• $224
CCV/PICCV weather shield kit AFR
EXTENSION BRACKET
CCV-EXT-KIT
CCV/PICCV valve neck extension kit for • • • • • $201
M5 screw
CCV-EXT-M4
• • • • • $201
Linkage extension kit
AUXILIARY SWITCHES & POTENTIOMETERS
S1A
Auxiliary switch - 1x SPDT, 3A • • $88
(0.5A inductive) @ 250 VAC
S2A
CCV
11-30
12
HIGH TEMPERATURE
CHARACTERIZED CONTROL
VALVES (HTCCV)
Perfect Solution for Low
Pressure Steam
• Elongated, characterizing disc reduces
turbulent flow and improves efficiency
of the system.
• Maintenance free – no repacking required
after being in service for an extended
period of time.
• Ball valve design offers self-cleaning
and zero leakage.
Valve Valve Size High Cv Actuator Type Power Supply Control -S = Built-in
Temperature 1.86 24 = 24 VAC/DC Blank = On/Off Auxiliary
B2 = 2-way 15-25 = ½” to 1” Non-Spring Return
Refer to Switch
TR 120 = 120 VAC* -3 = On/Off, Floating
Table on Point
Page 12-1 LR
-SR = 2-10 VDC
Spring Return
TFR -MFT = Multi-Function
Technology
LF
Ordering Example
TFR Series
TR Series
1.16 ½ 15 B215HT116 HTCCV
T
1.86 ½ 15 B215HT186
Equal Percentage
2.90 ½ 15 B215HT290 Characteristic
4.55 ½ 15 B215HT455*
1.86 ¾ 20 B220HT186 Mode of Operation
The control valve is operated by an electronic actuator
LR Series
2.90 ¾ 20 B220HT290 that responds to a standard voltage for on/off control, by
4.64 ¾ 20 B220HT464 a proportional VDC/4…20 mA, or 3-point control system.
The actuator will then move the ball of the valve to the
7.31 ¾ 20 B220HT731 position dictated by the contol signal and change the flow.
9.28 ¾ 20 B220HT928
LF Series
Product Features
Equal-percentage characteristic of the flow. B215HT455
13.20 ¾ 20 B220HT1320
model has modified equal percentage characteristic.
4.64 1 25 B225HT464
7.31 1 25 B225HT731 Actuator Specifications
Control type on/off, floating point, 2-10 VDC
11.60 1 25 B225HT1160 multi-function technology (MFT)
18.56 1 25 B225HT1856 Manual override only LR, TR series
Electrical connection 3 ft. [1 m] cable with ½”conduit
28.00 1 25 B225HT2800 fitting (except TR)
* modified equal percentage.
Valve Specifications
Service hot water, up to 60% glycol,
steam
Flow characteristic A-port equal percentage
Q11000- 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
12-1
High Temperature Characterized Control Valves
2-WAY VALVE
TR24-SR US NC: Closed A to AB, will open as voltage increases. NO: Open A to AB, will close as voltage increases
(Can be chosen with switch inside terminal
block of actuator).
LRB24-3, Power to pin 2 will drive valve CW. Power to pin 3 will NO: Open A to AB, will close
LRB24-SR, drive valve CCW. The above will function when the as voltage increases or power applied.
LRX24-MFT directional switch is in the ”1” position, to reverse select (Can be chosen with CW/CCW switch ).
the ”0” position.
TFRB24 NO/FO Valve: Open A to AB will drive closed. NC/FC Valve: Closed A to AB will drive open.
LF24 US Spring Action: Will spring open A to AB Spring Action: Will spring closed A to AB
upon power loss. upon power loss.
SPRING RETURN
Note Fail Position
TFRB (-3), -MFT, -SR NC/FO Valve: Closed A to AB will drive open. NC/FC or NO/FC Valve: Closed A to AB or Open A to AB
LF (-3), -MFT, -SR Spring Action: Will spring open A to AB (Can be chosen with CW/CCW switch).
Floating or Proportional upon power loss. Spring Action: Will spring closed A to AB upon power loss.
type actuators
NO/FO Valve: Open A to AB
Spring Action: Will spring open A to AB upon power loss.
(NO action can be chosen with CW/CCW switch).
HTCCV
12-2
High Temperature Characterized Control Valves
General Information/Typical Installation
FLOW PATTERN
Upstream A
Downstream AB
Valve should be installed with the disc downstream unlike the CCV.
PIPING DIAGRAMS
HTCCV
Q11000- 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Assembly can be mounted horizontally or vertically for water applications. For steam
applications when the valve is mounted horizontally, it must be 90° off center of the
pipe. Do not install with actuator below pipe.
12-3
High Temperature Characterized Control Valves with Non-Spring Return Actuators
2-way Valves with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
Service hot water, up to 60% glycol, steam
Flow Characteristic A-port equal percentage
Controllable Flow Range 75°
End Fitting NPT female ends
Body brass (DZR) P-CuZn35Pb2
Ball stainless steel
Stem stainless steel
Seat ETFE
Packing Viton
Characterized Disc ETFE
O-ring EPDM (lubricated)
Media Temperature Range
250°F [120°C]
(Steam)
Media Temperature Range
60°F to 266°F [16°C to 130°C]
(Water)
Max Differential Pressure 60 psi partially open ball,
(Water) 116 psi full open (#B215HT455)
Max Inlet Pressure
15 psi
(Steam)
Leakage bubble tight 0%
Models with modified equal percentage characteristic: B215HT455. Maximum media temperature for TR24-3 US and TR24-SR US is 212°F [100°C].
12-4
High Temperature Characterized Control Valves with Spring Return Actuators
2-way Valves with Stainless Steel Ball and Stem, NPT Female Ends
Valve Specifications
Service hot water, up to 60% glycol, steam
Flow Characteristic A-port equal percentage
Controllable Flow Range 75°
End Fitting NPT female ends
Body brass (DZR) P-CuZn35Pb2
Ball stainless steel
Stem stainless steel
Seat ETFE
Packing Viton
Characterized Disc ETFE
O-ring EPDM (lubricated)
Media Temperature Range
250°F [120°C]
(Steam)
Media Temperature Range
60°F to 266°F [16°C to 130°C]
(Water)
Max Differential Pressure 60 psi partially open ball,
(Water) 116 psi full open (#B215HT455)
Max Inlet Pressure
15 psi
(Steam)
Leakage bubble tight 0%
ACTUATOR PART # TFRB24 TFRB24-3 TFRB24-SR TFRX24-MFT LF24 US LF24-3 US LF24-SR US LF24-MFT US
Proportional/ On/Off, Floating Proportional/
Control On/Off Floating Point Proportional On/Off Proportional
MFT Point MFT
150 seconds 150 seconds
(default), vari- (default), vari-
Running Time (Motor) <75 seconds 90 seconds 95 seconds 75 seconds 150 seconds 150 seconds
able (75 to 300 able (75 to 300
seconds) seconds)
Running Time (Fail-Safe) < 75 seconds <25 seconds <25 seconds <25 seconds <25 seconds <25 seconds <25 seconds <25 seconds
Noise Level (Motor) <50 dB (A) <35 dB (A) <35 dB (A) <30 dB (A) <50 dB (A) <30 dB (A) <30 dB (A) <30 dB (A)
Noise Level (Fail-Safe) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A)
3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA
appliance cable, plenum cable plenum cable plenum cable appliance cable, plenum cable plenum cable appliance cable
Electrical Connection
½” conduit with ½” conduit with ½” conduit with ½” conduit ½” conduit with ½” conduit with ½” conduit with ½” conduit
connector connector connector connector connector connector connector connector
2-Way
Body Close-Off
HTCCV
Size
Model # Cv Pressure Pressure
[mm]
Q11000- 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models with modified equal percentage characteristic: B215HT455. Maximum media temperature for TR24-3 US and TR24-SR US is 212°F [100°C].
12-5
Valve Accessories
HTCCV
NON-SPRING RETURN
AUXILIARY SWITCHES & POTENTIOMETERS LR List Price
S1A
Auxiliary switch - 1x SPDT, 3A • $88
(0.5A inductive) @ 250 VAC
S2A
Auxiliary switch - 1x SPDT, 3A • $131
(0.5A inductive) @ 250 VAC
P140A GR
• $144
Feedback potentiometer 140 Ω
P500A GR
• $144
Feedback potentiometer 500 Ω
P1000A GR
• $144
Feedback potentiometer 1000 Ω
P2800A GR
• $144
Feedback potentiometer 2800 Ω
P5000A GR
• $144
Feedback potentiometer 5000 Ω
P10000A GR
• $144
Feedback potentiometer 10000 Ω
HTCCV
12-6
BALL VALVES & ZONE VALVES
ROTARY VALVES
ROTARY VALVES
BALL AND ZONE VALVES
Easy Field Assembly and
Installation; Saving Time and Costs
• Fitted with rotary actuators, providing
easy field assembly and installation.
• A range of fluid temperature ratings suited
for chilled, hot water and steam service.
• Wide range of sizes and Cv’s for various
applications.
Ordering Example
Non-Spring Models
P-10001 (A01) Tagging:
NO = Normally Open Valves may be tagged per
P-100xx (Axx) Control voltage applications customer specification.
NC = Normally Closed
P-200xx (Wxx) Pulse width modulation ($10.00 per tag)
Spring Return Models applications
NO/FO = Normally Open/Fail Open P-300xx (Fxx) Floating point applications Example:
NO/FC = Normally Open/Fail Closed AHU-1
P-400xx (Jxx) On/off applications
FCU-2
X-XXXXX Create custom MFT
NC/FO = Normally Closed/Fail Open
configuration code Part number for tagging:
NC/FC = Normally Closed/Fail Closed
X-XXXXX Create custom MFT 99981-00101
Refers to valve ports A to AB. configuration in the field
with MFT actuator PC-Tool software
LM Series
LF Series
2 ½ 15 B2050VS-02*
4 ½ 15 B2050VS-04*
15 ½ 15 B2050VS-15*
30 ¾ 20 B219VS
Series
NM Series
NF
51 ¾ 20 B220VS
Mode of Operation
43 1 25 B224VS
The control valve is operated by an electronic actuator that
68 1 25 B225VS responds to a standard voltage for on/off control, by a
Series
AM
SY Series
proportional VDC/4…20 mA, or 3-point control system. The
AF Series
48 1¼ 32 B232VS actuator will then move the ball of the valve to the position
dictated by the contol signal thus changing the flow.
84 1½ 40 B239VS
GM Series
30 ¾ 20 B219VSS
NF
Actuator Specifications
Control type on/off, floating point,
AM
43 1 25 B224VSS
AF Series
108 2 50 B249VSS
Electrical connection 3 ft. [1 m] cable with
½” conduit fitting (excluding SY)
6.4 ½ 15 B315L**
LFR Series
LR Series
Valve Specifications
12.8 ¾ 20 B320L**
Service chilled or hot water,
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Sizes ½” to 2”
57 1½ 40 B340L** End fitting SAE NPT
Series
AR
Materials
87 2 50 B350L** Body bronze (B2..VS)
stainless steel (B2..VSS)
* For single temperature applications only nickel plated brass (B3..L)
** Not for steam applications Ball stainless steel, bronze
(B2050VSS-15)
NOTE: Industrial ball valves (B2..VS, B2..VSS) have serviceable components. Proper maintenance of these chrome plated brass (B3..L)
parts will ensure a longer in-service life for the valves. The seats of these valves will require replacement at Stem stainless steel, bronze
an interval consistent with number of full cycles the valve has be operated, or as field condition dictates. (B2050VSS-15)
nickel plated brass (B3..L)
Seats
2-way RPTFE
3-way Teflon PTFE
Packing
2-way NPT RPTFE
O-rings NPT EPDM (B3..L)
Media temp range
B2..VS -22°F to +280°F [-30°C to +138°C]
B2..VSS -22°F to +298°F [-30°C to +148°C]
B3...L 0°F to 250°F [-18°C to +120°C]
Body pressure rating
3-way 600 psi DN 15-25 (B3..L ½”-1”)
400 psi DN 32-50 (B3..L 1¼” - 2”)
Maximum inlet pressure
Steam 35 psi B2..VS
50 psi B2..VSS
Water 50 psi B3..L
Leakage ANSI Class VI (B2..VS)
watertight (B3..L)
13-1
B2...VS/VSS and B3 L Series Ball Valves
General Information/Typical Installation
FLOW PATTERN
Open CCW
A AB B to A B to AB
Flow Direction Closed CW Open CW Open CCW
PIPING DIAGRAMS
PIPING/MOUNTING ORIENTATION
VS, VSS BALL VALVES
Assembly can be mounted horizontally or vertically for water applications. For steam applications the valve can be mounted vertically but if mounted horizontally the
valve must be 90° off center of the pipe. Do not install with actuator below pipe.
13-2
Piping Reduction Chart
VS/VSS, B3...L Series Ball Valves
LINE SIZE
¾” 1” 1¼” 1½” 2” 2½” 3” 4”
VALVE SIZE Cv TYPE MODEL #
Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv
½” 1 2W NPT B2050VS-01 1.0 1.0 - - - - - -
½” 2 2W NPT B2050VS-02 2.0 1.9 - - - - - -
½” 4 2W NPT B2050VS-04 3.8 3.6 - - - - - -
½” 15 2W NPT B2050VS-15 8.9 7.2 - - - - - -
¾” 30 2W NPT B219VS/VSS 30.0 21.6 17.4 15.6 - - - -
¾” 51 2W NPT B220VS 51.0 26.5 19.9 17.3 - - - -
1” 43 2W NPT B224VS/VSS - 43.0 36.1 30.5 25.8 - - -
1” 68 2W NPT B225VS - 68.0 48.3 36.7 29.2 - - -
1½” 177 2W NPT B240VS - - - 177.0 102.7 77.9 67.3 -
2” 108 2W NPT B249VS/VSS - - - - 108.0 100.4 91.8 83.2
½” 6.4 3W NPT B315L 5.5 5.0 4.8 - - - - -
¾” 12.8 3W NPT B320L 12.8 11.8 11.0 10.5 - - - -
1” 11 3W NPT B325L - 11.0 10.9 10.7 10.4 - - -
1¼” 34 3W NPT B332L - - 34.0 32.8 29.9 28.2 - -
1½” 57 3W NPT B340L - - - 57.0 51.9 47.4 44.9 -
2” 87 3W NPT B350L - - - - 87.0 82.8 77.9 72.3
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
13-3
B2…VS Series Ball Valves with Non-Spring Return Actuators
2-way Valve, Bronze Body, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic modified equal percentage
90° rotation, valve open CW, valve
Controllable Flow Range
closed CCW
End Fitting SAE NPT (female connections)
Body B584-C84400 bronze
Ball 316 stainless steel
Seat reinforced PTFE w/ Durafill
Stem 316 stainless steel
Bearing reinforced PTFE
Stem Packing reinforced PTFE
Body Seal PTFE
Retainer B16 brass
Gland B16 brass
Jam Nut stainless steel
Media Temperature Range -22°F to +280°F
(Water) [-30°C to +138°C]
Maximum Velocity 15 FPS
Leakage ANSI Class VI
13-4
B2…VS Series Ball Valves with Non-Spring Return Actuators
2-way Valve, Bronze Body, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic modified equal percentage
90° rotation, valve open CW, valve
Controllable Flow Range
closed CCW
End Fitting SAE NPT (female connections)
Body B584-C84400 bronze
Ball 316 stainless steel
Seat reinforced PTFE w/ Durafill
Stem 316 stainless steel
Bearing reinforced PTFE
Stem Packing reinforced PTFE
Body Seal PTFE
Retainer B16 brass
Gland B16 brass
Jam Nut stainless steel
Media Temperature Range
-22°F to +280°F [-30°C to +138°C]
(Water)
Maximum Velocity 15 FPS
Leakage ANSI Class VI
13-5
B2…VS Series Ball Valves with Spring Return Actuators
2-way Valve, Bronze Body, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic modified equal percentage
90° rotation, valve open CW, valve
Controllable Flow Range
closed CCW
Visit www.belimo.uss for additional Spring Return options.
End Fitting SAE NPT (female connections)
Body B584-C84400 bronze
Ball 316 stainless steel
Seat reinforced PTFE w/ Durafill
Stem 316 stainless steel
Bearing reinforced PTFE
Stem Packing reinforced PTFE
Body Seal PTFE
Retainer B16 brass
Gland B16 brass
Jam Nut stainless steel
Media Temperature Range
-22°F to +280°F [-30°C to +138°C]
(Water)
Maximum Velocity 15 FPS
Leakage ANSI Class VI
0.75” [20]
B220VS 51 400 $951 $1,213
13-6
B2…VS Series Ball Valves with Spring Return Actuators
2-way Valve, Bronze Body, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic modified equal percentage
90° rotation, valve open CW,
Controllable Flow Range
valve closed CCW Visit www.belimo.uss for additional Spring Return options.
End Fitting NPT female ends
Body B584-C84400 bronze
Ball 316 stainless steel
Seat reinforced PTFE w/ Durafill
Stem 316 stainless steel
Bearing reinforced PTFE
Stem Packing reinforced PTFE
Body Seal PTFE
Retainer B16 brass
Gland B16 brass
Jam Nut stainless steel
Media Temperature Range -22°F to +280°F
(Water) [-30°C to +138°C]
Maximum Velocity 15 FPS
Leakage ANSI Class VI
Noise Level (Motor) <50 dB (A) <50 dB (A) <45 dB (A) <50 dB (A) <50 dB (A)
Noise Level (Fail-Safe) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A)
2-Way
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi] [psi]
B224VS 43 400 $1,026 $1,095 $1,278
1” [25]
B225VS 68 200 $1,225 $1,293 $1,412
B232VS 48 1.25” [32] 600 psig 600 $1,296 $1,363 $1,493
13-7
B3…L Series Ball Valves with Non-Spring Return Actuators
3-way Valve, Nickel Plated Brass Body, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic modified linear
End Fitting NPT female ends
Body forged brass, nickel plated
Ball chrome plated brass
Stem nickel plated brass
Seat EPDM
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage watertight
13-8
B3…L Series Ball Valves with Spring Return Actuators
3-way Valve, Nickel Plated Brass Body, NPT Female Ends
Valve Specifications
chilled , hot water, up to 60%
Service
glycol
Flow Characteristic modified linear
End Fitting NPT female ends
Body forged brass, nickel plated Visit www.belimo.uss to see additional Spring Return options.
Ball chrome plated brass
Stem nickel plated brass
Seat EPDM
Media Temperature Range
0°F to 250°F [-18°C to +120°C]
(Water)
Max Differential Pressure
50 psi
(Water)
Leakage watertight
13-9
B2…VS Series Ball Valves with NEMA 4X Non-Spring Return Actuators
2-way Valve, Bronze Body, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic modified equal percentage
90° rotation, valve open CW, valve
Controllable Flow Range
closed CCW
End Fitting SAE NPT (female connections)
Body B584-C84400 bronze
Ball 316 stainless steel
Seat reinforced PTFE w/ Durafill
Stem 316 stainless steel
Bearing reinforced PTFE
Stem Packing reinforced PTFE
Body Seal PTFE
Retainer B16 brass
Gland B16 brass
Jam Nut stainless steel
Media Temperature Range
-22°F to +280°F [-30°C to +138°C]
(Water)
Maximum Velocity 15 FPS
Leakage ANSI Class VI
13-10
B2…VSS Series Ball Valves with Non-Spring Return Actuators
2-way Valve, Stainless Steel Body, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic modified equal percentage
90° rotation, valve open CW, valve
Controllable Flow Range
closed CCW
End Fitting SAE NPT (female connections)
Body A351-CF8M 316 stainless steel
Ball 316 stainless steel
Seat reinforced PTFE w/ Durafill
Stem 316 stainless steel
Bearing reinforced PTFE
Stem Packing reinforced PTFE
Body Seal PTFE
Retainer 316 stainless steel
Gland A276-316
Jam Nut stainless steel
Media Temperature Range
-22°F to +298°F [-30°C to +148°C]
(Water)
Maximum Velocity 15 FPS
Leakage ANSI Class VI
[mm]
Rating [psi] [psi]
B2050VSS-15 15 0.5” [15] 2000 psig WOG 1000 $805 $1,182
B219VSS 30 0.75” [20] 1500 psig 1000 $1,117 $1,491
B224VSS 43 1” [25] WOG 1000 $1,257 $1,580
B249VSS 108 2” [50] 1000 $2,442 $2,617
13-11
B2…VSS Series Ball Valves with Spring Return Actuators
2-way Valve, Stainless Steel Body, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic modified equal percentage
90° rotation, valve open CW, valve
Controllable Flow Range
closed CCW Visit www.belimo.uss for additional Spring Return options.
End Fitting SAE NPT (female connections)
Body A351-CF8M 316 stainless steel
Ball 316 stainless steel
Seat reinforced PTFE w/ Durafill
Stem 316 stainless steel
Bearing reinforced PTFE
Stem Packing reinforced PTFE
Body Seal PTFE
Retainer 316 stainless steel
Gland A276-316
Jam Nut stainless steel
Media Temperature Range
-22°F to +298°F [-30°C to +148°C]
(Water)
Maximum Velocity 15 FPS
Leakage ANSI Class VI
2*AFX24-
ACTUATOR PART # LF24 US LF24-MFT US NFB24-X1 NFX24-MFT-X1 AFB24-X1 AFX24-MFT-X1
MFT-X1
Control On/Off Proportional/MFT On/Off Proportional/MFT On/Off Proportional/MFT Proportional/MFT
Manual Override • • • • •
150 seconds 150 seconds 150 seconds 150 seconds
(default), variable (default), variable (default), variable (default), variable
Running Time (Motor) 75 seconds <75 seconds <75 seconds
(75 to 300 (40 to 220 (70 to 220 (70 to 220
seconds) seconds) seconds) seconds)
< 20 seconds @ 20 seconds @
20 sec @ -4°F to <20 sec @ -4°F to 20 sec @ -4°F to
-4°F to +122°F -4°F to +122°F
+122°F [-20°C to +122°F [-20°C to +122°F [-20°C to
Running Time (Fail-Safe) <25 seconds <25 seconds [-20°C to +50°C], [-20°C to +50°C],
+50°C], <60 sec +50°C], <60 sec +50°C], <60 sec @
< 60 sec @ -22°F < 60 sec @ -22°F
@ -22°F [-30°C] @ -22°F [-30°C] -22°F [-30°C]
[-30°C] [-30°C]
Noise Level (Motor) <50 dB (A) <50 dB (A) <50 dB (A) <50 dB (A) <50 dB (A) <45 dB (A) <50 dB (A)
Noise Level (Fail-Safe) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A)
2-Way
VS, VSS BALL VALVES
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi] [psi]
B2050VSS-15 15 0.5” [15] 2000 psig WOG 1000 $837 $1,310
B219VSS 30 0.75” [20] 1500 psig 1000 $1,271 $1,718
B224VSS 43 1” [25] WOG 1000 $1,367 $1,832
B249VSS 108 2” [50] 1000 $3,884
13-12
B2…VSS Series Ball Valves with NEMA 4X Non-Spring Return Actuators
2-way Valve, Stainless Steel Body, NPT Female Ends
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic modified equal percentage
90° rotation, valve open CW, valve
Controllable Flow Range
closed CCW
End Fitting SAE NPT (female connections)
Body A351-CF8M 316 stainless steel
Ball 316 stainless steel
Seat reinforced PTFE w/ Durafill
Stem 316 stainless steel
Bearing reinforced PTFE
Stem Packing reinforced PTFE
Body Seal PTFE
Retainer 316 stainless steel
Gland A276-316
Jam Nut stainless steel
Media Temperature Range
-22°F to +298°F [-30°C to +148°C]
(Water)
Maximum Velocity 15 FPS
Leakage ANSI Class VI
13-13
Selection
S l i off R
Replacement
l Solutions
S l i at Your
Y Finger
Fi Ti
Tips
Belimo’s Retrofit App allows you to quickly and easily find HVAC replacement solutions for valves and
actuators. Select based on:
• Application
• Product Model
• Control Type
• Product Type
Replacement results provide a complete selection of products that are compatible with most control systems.
14
V BALL CONTROL VALVES
High Performance for
Aggressive Applications
• High performance ANSI Class 150
and 300 carbon steel bodies ideal for
aggressive applications.
• Fluid temperature up to 380°F is
ideal for chilled, hot water or steam service.
• Fitted with rotary actuators for easy field
assembly and installation.
Ordering Example
Non-Spring Models
P-10001 (A01) Tagging:
NO = Normally Open Valves may be tagged per
P-100xx (Axx) Control voltage applications customer specification.
NC = Normally Closed
P-200xx (Wxx) Pulse width modulation ($10.00 per tag)
Spring Return Models applications
NO/FO = Normally Open/Fail Open P-300xx (Fxx) Floating Point applications Example:
NO/FC = Normally Open/Fail Closed AHU-1
P-400xx (Jxx) On/Off applications
FCU-2
X-XXXXX Create custom MFT
NC/FO = Normally Closed/Fail Open
configuration code Part number for tagging:
NC/FC = Normally Closed/Fail Closed
X-XXXXX Create custom MFT 99981-00101
Refers to valve ports A to AB. configuration in the field
with MFT-actuator PC-Tool software
NF Series
024 1 25 B2100VB-024
AM Series
055 1½ 40 B2150VB-055
SY Series
077 2 50 B2200VB-077
AF
Equal Percentage
GK Series
207 3 80 B6300VB-207
Characteristic
GM
350 4 100 B6400VB-350
Actuator Specifications
Control type on/off, floating point,
proportional, 2-10 VDC
multi-function technology (MFT)
Manual override GM, AM, SY, NF, AF, GK
Electrical connection 3 ft. [1 m] cable with
½” conduit fitting, terminal block
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Valve Specifications
Service chilled or hot water,
(60% glycol), steam
Flow characteristic equal percentage
Sizes 1”, 1½”, 2”, 3”, 4”, 5”, 6”
End fitting SAE NPT female (1” to 2”)
ANSI flanged (3” to 6”)
Materials
Body carbon steel
Characterizing ball hardened chrome plated
stainless steel
Stem stainless steel
Seats Teflon®
O-rings ALFAS
Packing spring loaded Teflon® V-ring
Bushings PEEK
Media temp. range 380°F max.
Body pressure rating NPT ANSI 300 (1” to 2”)
Flanged ANSI 150 (3” to 6”)
Maximum ΔP steam 100 psi
Maximum ΔP water 150 psi
Close-off pressure
Water 150 psi
Steam 200 psi
Maximum inlet pressure
Steam 200 psi
Leakage ANSI Class IV
14-1
B2...VB and B6...VB V Ball Control Valves
General Information / Typical Installation
FLOW PATTERN
A AB
PIPING DIAGRAMS
Water Application Steam Application
2-way Valve Piping Diagram 2-way Valve Piping Diagram
PIPING/MOUNTING ORIENTATION
Assembly can be mounted horizontally or vertically for water applications. For steam applications the valve can be mounted vertically but if mounted horizontally
the valve must be 90° off center of the pipe. Do not install with actuator below pipe.
14-2
Piping Reduction Chart
V Ball Valves
LINE SIZE
VALVE 1” 1¼” 1½” 2” 2½” 3” 4” 5” 6” 8” 10”
Cv TYPE MODEL #
SIZE Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv Fp Cv
1” 24 2-Way NPT B2100VB-024 24.0 22.6 21.1 19.3 - - - - - - -
1½” 55 2-Way NPT B2150VB-055 - - 55.0 50.4 46.3 43.9 - - - - -
2” 77 2-Way NPT B2200VB-077 - - - 77.0 74.1 70.5 66.2 - - - -
3” 207 2-Way Flanged B6300VB-027 - - - - - 207.0 191.3 177.2 168.9 - -
4” 350 2-Way Flanged B6400VB-350 - - - - - - 350.0 333.0 313.2 290.3 -
6” 507 2-Way Flanged B6600VB-507 - - - - - - - - 507.0 491.5 475.5
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
V BALL VALVES
14-3
V Ball Valves with Non-Spring Return Actuators
2-way Valve with Stainless Steel Ball and Stem
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic equal percentage
Controllable Flow Range 75°
NPT female ends (1” to 2”); ANSI
End Fitting
flange (3” to 6”)
Body WCC grade carbon steel
Ball stainless steel
Stem stainless steel
Seat Teflon®
Packing spring loaded Teflon® V-ring
Media Temperature Range
-22°F to +380°F [-30°C to +193°C]
(Water)
Media Temperature Range
-22°F to +380°F [-30°C to +193°C]
(Steam)
Max Differential Pressure
150 psi
(Water)
Max Differential Pressure
100 psi
(Steam)
Max Inlet Pressure
200 psi
(Steam)
Leakage ANSI Class IV
14-4
V Ball Valves with Spring Return and Electronic Fail-Safe Actuators
2-way Valve with Stainless Steel Ball and Stem
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic equal percentage
Controllable Flow Range 75° Visit www.belimo.uss for additional Spring Return
NPT female ends (1” to 2”); ANSI
End Fitting and Electronic Fail-Safe options.
flange (3” to 6”)
Body WCC grade carbon steel
Ball stainless steel
Stem stainless steel
Seat Teflon®
Packing spring loaded Teflon® V-ring
Media Temperature Range
-22°F to +380°F [-30°C to +193°C]
(Water)
Media Temperature Range
-22°F to +380°F [-30°C to +193°C]
(Steam)
Max Differential Pressure
150 psi
(Water)
Max Differential Pressure
100 psi
(Steam)
Max Inlet Pressure
200 psi
(Steam)
Leakage ANSI Class IV
Running Time (Fail-Safe) <20 seconds <20 seconds <20 seconds <20 seconds <20 seconds <20 seconds <20 seconds 35 seconds 35 seconds
Noise Level (Motor) <50 dB (A) <50 dB (A) <50 dB (A) <50 dB (A) <45 dB (A) <50 dB (A) <50 dB (A) <45 dB (A) <45 dB (A)
Noise Level (Fail-Safe) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <45 dB (A) <45 dB (A)
18 GA 18 GA 18 GA
18 GA
applicance applicance applicance
plenum rated
rated cable rated cable rated cable 3 ft, 18 GA
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
cable with
with ½” with ½” with ½” plenum rated
3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA ½” conduit
conduit conduit conduit cable with
appliance appliance appliance appliance connector
connector connector connector ½” conduit
Electrical Connection cable, ½” cable, ½” cable, ½” cable, ½” protected
protected protected protected connector
conduit conduit conduit conduit NEMA 2
NEMA 2 NEMA 2 NEMA 2 protected
connector connector connector connector (IP54) 3 ft
(IP54) 3 ft (IP54) 3 ft (IP54) 3 ft NEMA 2
[1 m] 10 ft
[1 m] 10 ft [1 m] 10 ft [1 m] 10 ft (IP54)
[3 m] and
[3 m] and [3 m] and [3 m] and
16 ft [5 m]
16 ft [5 m] 16 ft [5 m] 16 ft [5 m]
2-Way
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi] [psi]
B2100VB-024 24 1” [25] 200 $2,520 $2,736
ASME/ANSI
B2150VB-055 55 1.5” [40] 200 $2,953 $3,170
Class 300
B2200VB-077 77 2” [50] 200 $3,237 $3,301 $3,439
B6300VB-207 207 3” [80] ASME/ANSI 200 $5,610 $5,886 $6,379 $6,623
B6400VB-350 350 4” [100] Class 150 200 $7,327 $7,757
2* Denotes tandem actuators.
V BALL VALVES
14-5
Valve Accessories
Ball Valves
ELECTRONIC
NON-SPRING RETURN SPRING RETURN
FAIL-SAFE
WEATHER SHIELDS LM NM AM GM LF NF AF GK List Price
ZS-SPBV-10
NM/AM/GM/NF/AF/GK series on • • • • • • $291
VS/VSS/VB
ZS-SPBV-20
Dual GM/AF/GK series on VS/ • • • $542
VSS/VB
ZS-BVVS-0002
• $287
LM on VS/VSS
ZS-BVVS-0003
• $287
LF series on VS/VSS
AUXILIARY SWITCHES & POTENTIOMETERS
S1A
Auxiliary switch - 1x SPDT, • • • • $88
3A (0.5A Inductive) @ 250 VAC
S2A
Auxiliary switch - 1x SPDT, • • • • $131
3A (0.5A Inductive) @ 250 VAC
P140A
• • • • $144
Feedback potentiometer 140 Ω
P500A GR
• • • • $144
Feedback potentiometer 500 Ω
P1000A GR
• • • • $144
Feedback potentiometer 1000 Ω
P2800A GR
• • • • $144
Feedback potentiometer 2800 Ω
P5000A GR
• • • • $144
Feedback potentiometer 5000 Ω
P10000A GR
• • • • $144
Feedback potentiometer 10000 Ω
BATTERY BACKUP
NSV24 US
• • • • • • • • $817
Battery backup module
SPRING
NON-SPRING RETURN
RETURN
ELECTRIC DISCONNECT AM GM SY AF List Price
HOA-120V
• $478
Local electric disconnect SY2-SY12 110/230V - 2 position
HOA-120VMFT
• $478
Local electric disconnect SY2-SY12 110/230V - proportional
HOA-24V
• $478
Local electric disconnect SY2-SY12 24V - 2 position
HOA-24VMFT
• $478
Local electric disconnect SY2-SY12 24V - proportional
V BALL VALVES
14-6
Valve Accessories
Ball Valves
SPRING
NON-SPRING RETURN
RETURN
PROGRAMMING TOOLS AM GM SY AF List Price
MFT-P
Belimo MFT configuration software (V3.X)
• • • • $166
Includes: PC-Tool software (interface cables [ZTH US]
not included)
INTERFACES, CABLES
ZTH US
• • • • $701
Handheld interface module that allows field programming.
ZK1-GEN
Cable for use with ZTH US to connect to new generation
• • $107
non-spring return actuator via diagnostic/
programming socket
ZK2-GEN
Cable for use with ZTH US to connect with spring and
• • • • $49
non-spring return actuators not equipped with diagnostic/
programming socket
ZK6-GEN
Cable for use with ZTH US to connect to SY actuator via • $51
RJII port
BATTERY BACKUP
EXT-NSV-B01-120
• $5,228
Battery backup system, SY1 - SY3 120 VAC, on/off actuators
EXT-NSV-B02-120
• $6,448
Battery backup system, SY1 - SY3 120 VAC, MFT actuators
EXT-NSV-B03-120
• $5,962
Battery backup system, SY4 - SY6 120 VAC, on/off actuators
EXT-NSV-B04-120
• $6,840
Battery backup system, SY4 - SY6 120 VAC, MFT actuators
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
EXT-NSV-B05-120
• $6,902
Battery backup system, SY7 - SY12 120 VAC, on/off actuators
EXT-NSV-B06-120
• $7,037
Battery backup system, SY7 - SY12 120 VAC, MFT actuators
EXT-NSV-B11-24
• $5,879
Battery backup system, SY1 24 VAC, on/off actuators
EXT-NSV-B12-24
• $7,098
Battery backup system, SY1 24 VAC, MFT actuators
EXT-NSV-B13-24
• $7,563
Battery backup system, SY2 - SY5 24 VAC, on/off actuators
EXT-NSV-B14-24
• $7,233
Battery backup system, SY2 - SY5 24 VAC, MFT actuators
EXT-NSV-B21-230
• $5,879
Battery backup system, SY1 - SY3 230 VAC, on/off actuators
EXT-NSV-B22-230
• $8,524
V BALL VALVES
14-7
Belimo University provides online and classroom training in multiple
languages. Our programs are focused on the technical aspects of
HVAC products from sizing and selection to mounting and installation.
Ordering Example
Tagging:
Valves may be
tagged per customer
24 = 24 VAC
-S = Built-in specification. ($10.00
Auxiliary charge per tag)
Switch
Example:
FCU-1
Zone
Zone
3.5 ¾ 20 ZONE220N-35 ZONE220S-35
5 ¾ 20 ZONE220N-50 ZONE220S-50
8 1 25 ZONE225N-80 ZONE225S-80
Mode of Operation
Zone valves provide a convenient way to create individual
Valve Nominal Size Type Suitable Actuators zones or equipment isolation in a hydronic system.
Utilizing one pump along with multiple zone valves, flow
Cv Inches DN [mm] 3-way NPT 3-way Sweat Normally Closed can be started, stopped, or diverted through the system
to provide individual room or area comfort control and
1 ½ 15 ZONE315N-10 ZONE315S-10 energy savings.
Valve Specifications
Q11000- 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
15-1
Electronic Zone Valves
Installation
MOUNTING ORIENTATION
The valve can be installed vertically or horizontally, but not below horizontal.
– A 3-way valve cannot be transformed into a 2-way valve and visa versa.
– The NC versions have an override handle.
– 3-way zone valves can be fitted with NC actuator only (rotate the valve body 180° for NO application).
FLOW PATTERN
2-way Valve 3-way Valve
2-WAY 3-WAY
Port ”A” closed
N.C. without power Port ”A” closed Port ”B” open
Port ”AB” open
Port ”A” open
N.C. open with power Port ”A” open Port ”B” closed
Port ”AB” open
B A
A B Port ”A” open
N.C. manually open Port ”A” open Port ”B” open
(NO) (NC) Port ”AB” open
AB
Installed on the supply Installed on the supply in diverting Installed on the supply in diverting
configuration configuration
ZONE VALVES
15-2
Electronic Zone Valves with Spring Return Actuators
2-way and 3-way Valves with NPT or Sweat Connection
Valve Specifications
chilled or hot water, up to 50%
Service
glycol
on/off (2-way)
Flow Characteristic
on/off, diverting (3-way)
NPT female ends
End Fitting
sweat
Body forged brass
Stem stainless steel
Seat EPDM
Body Seal EPDM
Media Temperature Range
32°F to 212°F [0°C to 100°C]
(Water)
Leakage ANSI Class III 0.1%
15-3
Electronic Zone Valves with Spring Return Actuators
2-way and 3-way Valves with NPT or Sweat Connection
Valve Specifications
chilled or hot water, up to 50%
Service
glycol
on/off (2-way)
Flow characteristic
on/off, diverting (3-way)
NPT female ends
End Fitting
sweat
Body forged brass
Stem stainless steel
Seat EPDM
Body Seal EPDM
Media Temperature Range
32°F to 212°F [0°C to 100°C]
(Water)
Leakage ANSI Class III 0.1%
15-4
16
PIPE PACKAGES
Fast Delivery and Ease
of Installation
• Simple design using SelectPro Piping
Package configurator.
• Factory assembled and tested saving
time and money.
• 100% leak tested.
* Pipe Package Smart Code does not include the Belimo Control Valve and price.
Pipe Package Component Pricing
PIPE PACKAGES
ISOLATION ISOLATION MANUAL BALANCE
UNION UNION MANUAL BALANCE VALVE
PART NUMBER VALVE PART NUMBER VALVE PART NUMBER VALVE
BODY x TAIL LIST PRICE BODY x TAIL
BODY x TAIL LIST PRICE LIST PRICE
½" x ½" PPU111 $54 ½" x ½" PPV1110 $96 PPL1111 $162
¾" x ¾" PPU211 $62 ¾" x ¾" PPV2110 $110 ½" x ½"(Max 2.65 GPM) PPL1112 $162
1" x 1" PPU311 $81 1" x 1" PPV3110 $164 ½" x ½" (Max 7.00 GPM) PPL1113 $162
1" x ¾" PPU411 $81 1" x ¾" PPV4110 $164 ¾" x ¾" (Max 1.30 GPM) PPL2111 $166
¾" x ½" PPU511 $62 ¾" x ½" PPV5110 $110 ¾" x ¾" (Max 2.65 GPM) PPL2112 $166
1½" x 1½" PPUA11 $163 1½" x 1½" PPVA110 $481 ¾" x ¾" (Max 7.00 GPM) PPL2113 $166
1¼" x 1¼" PPUB11 $117 1¼" x 1¼" PPVB110 $374 1" x 1" (Max 7.00 GPM) PPL3114 $252
2" x 2" PPUC11 $238 2" x 2" PPVC110 $650 1" x 1" (Max 17.50 GPM) PPL3115 $252
1¼" x 1" PPUD11 $117 1¼" x 1" PPVD110 $374 1" x ¾" (Max 7.00 GPM) PPL4114 $252
1½" x 1¼" PPUE11 $163 1½" x 1¼" PPVE110 $481 1" x ¾" (Max 7.00 GPM) PPL4115 $252
2" x 1½" PPUF11 $238 2" x 1½" PPVF110 $650 1" x ¾" (Max 17.50 GPM) PPL5111 $166
1" x ½" PPUG11 $81 1" x ½" PPVG110 $164 1" x ¾" (Max 17.50 GPM) PPL5112 $166
1¼" to ¾" PPUH11 $117 1¼" to ¾" PPVH110 $374 ¾" x ½" (Max 1.30 GPM) PPL5113 $166
1½" x 1" PPUJ11 $163 1½" x 1" PPVJ110 $481 1½" x 1½" (Max 40.80 GPM) PPLA11B $446
2" x 1¼" PPUK11 $238 2" x 1¼" PPVK110 $650 1¼" x ¼" (Max 10.6 GPM) PPLB11A $252
2" x 2" (Max 56.90 GPM) PPLC11C $611
2" x 2" (Max 95.00 GPM) PPLC11D $611
1¼" x 1" (Max 35.80 GPM) PPLD11D $513
1¾" x 1½" (Max 12.8 GPM) PPLE11B $446
2" x 1½" (Max 95.00 GPM) PPLF11C $611
1" x ½" (Max 7.00 GPM) PPLG114 $252
1" x ½" (Max 17.50 GPM) PPLG115 $252
1¼" x ¾" (Max 35.80 GPM) PPLH11A $370
1½" x 1" (Max 40.80 GPM) PPLJ11B $446
2" x 1¼" (Max 56.90 GPM) PPLK11C $611
Add price for Isolation Bypass Valve for 3-way CCV Packages. Bypass Valve is not shown in the reorder number.
Example: A ½" 3-way CCV, will get a ½" Isolation Valve for the Bypass Port. The adder for the Isolation Valve in this example is $96 List Price.
16-1
Pipe Packages for 2-way PICCVs
PIPE PACKAGES
16-2
Pipe Packages for 2-way PICCVs
PIPE PACKAGES
ISOLATION
PIPE PACKAGE SMARTCODE (PICCV) UNION STRAINER
VALVE
LIST PRICE
Pipe Package Part # Valve Nominal Size Body End/ Body End/ Body End/
(2-way PICCV) without Hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
PP 111 1110 1111 0 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $280
PP 121 1210 1212 0 ½ 15 Sweat/M-NPT Sweat/M-NPT Sweat/Sweat $280
PP 131 1110 1113 0 ½ 15 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $280
PP 131 1210 1213 0 ½ 15 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $280
PP 211 2110 2111 0 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $330
PP 221 2210 2212 0 ¾ 20 Sweat/M-NPT Sweat/M-NPT Sweat/Sweat $330
PP 231 2110 2113 0 ¾ 20 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $330
PP 231 2210 2213 0 ¾ 20 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $330
PP 311 3110 3111 0 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $422
PP 321 3210 3212 0 1 25 Sweat/M-NPT Sweat/M-NPT Sweat/Sweat $422
SMARTCODE ORDER NOMENCLATURE
COMPONENT ORDER NOMENCLATURE PP 331 3110 3113 0 1 25 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $422
EXAMPLE: PP 331 3210 3213 0 1 25 M-NPT/M-NPT Sweat/M-NPT Sweat/Sweat $422
PP 211 2110 2111 3
PP-PICCV
Union Isolation Strainer Hose PIPE PACKAGE SMARTCODE (PICCV) UNION
ISOLATION
STRAINER
PPU211 PPV2110 PPS2111 PHOSE3 VALVE
LIST PRICE
Pipe Package Part # Valve Nominal Size Body End/ Body End/ Body End/
(2-way PICCV) with 12” Hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
PP 111 1110 1111 1 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $364
PP 111 1210 1211 1 ½ 15 Sweat/M-NPT Sweat/M-NPT Sweat/F-NPT $364
PP 211 2110 2111 3 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $462
PP 211 2210 2211 3 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $462
PP 311 3110 3111 5 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $674
PP 311 3210 3211 5 1 25 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $674
ISOLATION
PIPE PACKAGE SMARTCODE (PICCV) UNION STRAINER
VALVE
LIST PRICE
Pipe Package Part # Valve Nominal Size Body End/ Body End/ Body End/
(2-way PICCV) with 24” hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
PP 111 1110 1111 2 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $384
PP 111 1210 1211 2 ½ 15 Sweat/M-NPT Sweat/M-NPT Sweat/F-NPT $384
PP 211 2110 2111 4 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $500
PP 211 2210 2211 4 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $500
PP 311 3110 3111 6 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $714
Extension Packages Include:
PP 311 3210 3211 6 1 25 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $714
• Extended handle for Isolation Valve and Strainer
All combinations of reorder numbers are not reflected above. Please use the nomenclature or download the SelectPro
• Extended P/T port for Union, Isolation Valve and software at www.belimo.us to configure other possible combinations.
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Strainer
• Extended air vent for Isolation Valve
16-3
Pipe Packages for 2-way CCVs
PIPE PACKAGES
16-4
Pipe Packages for 2-way CCVs
PIPE PACKAGES
MANUAL
PIPE PACKAGE SMARTCODE (CCV) UNION STRAINER
BALANCE VALVE LIST
Pipe Package Model # Valve Nominal Size Body End/ Body End/ Body End/ PRICE
(2-way CCV) without hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
P2 111 1111 1111 0 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $346
P2 121 1112 1212 0 ½ 15 Sweat/M-NPT F-NPT/M-NPT Sweat/Sweat $346
P2 131 1113 1113 0 ½ 15 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $346
P2 131 1211 1213 0 ½ 15 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $346
P2 131 1212 1213 0 ½ 15 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $346
P2 131 1213 1213 0 ½ 15 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $346
P2 211 2111 2111 0 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $387
P2 221 2112 2212 0 ¾ 20 Sweat/M-NPT F-NPT/M-NPT Sweat/Sweat $387
P2 231 2113 2113 0 ¾ 20 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $387
P2 231 2211 2213 0 ¾ 20 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $387
P2 231 2212 2213 0 ¾ 20 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $387
P2 231 2213 2213 0 ¾ 20 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $387
SMARTCODE ORDER NOMENCLATURE P2 311 3114 3111 0 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $510
COMPONENT ORDER NOMENCLATURE
P2 321 3114 3212 0 1 25 Sweat/M-NPT F-NPT/M-NPT Sweat/Sweat $510
EXAMPLE:
111 1111 1111 1 P2 331 3115 3113 0 1 25 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $510
P2
P2 311 3115 3213 0 1 25 F-NPT/M-NPT F-NPT/M-NPT Sweat/M-NPT $510
Union MBV Strainer Hose
PPU111 PPL1111 PPS1111 PHOSE1 P2 321 3214 3213 0 1 25 Sweat/M-NPT Sweat/M-NPT Sweat/M-NPT $510
P2 331 3215 3213 0 1 25 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $510
MANUAL
PIPE PACKAGE SMARTCODE (CCV) UNION STRAINER
BALANCE VALVE LIST
Pipe Package Model # Valve Nominal Size Body End/ Body End/ Body End/ PRICE
(2-way CCV) with 12” hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
P2 111 1111 1111 1 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $430
P2 111 1112 1211 1 ½ 15 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $430
P2 111 1113 1111 1 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $430
P2 111 1211 1211 1 ½ 15 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $430
P2 111 1212 1111 1 ½ 15 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $430
P2 111 1213 1211 1 ½ 15 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $430
P2 211 2111 2111 3 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $519
P2 211 2112 2211 3 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $519
P2 211 2113 2111 3 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $519
P2 211 2211 2211 3 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $519
P2 211 2212 2111 3 ¾ 20 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $519
Extension Packages Include: P2 211 2213 2211 3 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $519
• Extended handle for Manual Balance Valve, P2 311 3114 3111 5 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $762
Isolation Valve and Strainer P2 311 3115 3211 5 1 25 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $762
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
• Extended P/T ports for Union, Manual P2 311 3214 3111 5 1 25 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $762
Balance Valve, Strainer or Isolation Valve P2 311 3215 3211 5 1 25 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $762
• Extended air vent for Manual Balance Valve
MANUAL
and Isolation Valve PIPE PACKAGE SMARTCODE (CCV) UNION
BALANCE VALVE
STRAINER
LIST
Pipe Package Model # Valve Nominal Size Body End/ Body End/ Body End/ PRICE
(2-way CCV) with 24” hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
P2 111 1111 1111 2 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $450
P2 111 1112 1211 2 ½ 15 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $450
P2 111 1113 1111 2 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $450
P2 111 1211 1211 2 ½ 15 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $450
P2 111 1212 1111 2 ½ 15 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $450
P2 111 1213 1211 2 ½ 15 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $450
P2 211 2111 2111 4 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $557
P2 211 2112 2211 4 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $557
P2 211 2113 2111 4 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $557
P2 211 2211 2211 4 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $557
P2 211 2212 2111 4 ¾ 20 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $557
P2 211 2213 2211 4 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $557
P2 311 3114 3111 6 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $802
P2 311 3115 3211 6 1 25 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $802
P2 311 3214 3111 6 1 25 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $802
P2 311 3215 3211 6 1 25 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $802
All combinations of reorder numbers are not reflected above. Please use the nomenclature or download the SelectPro
software at www.belimo.us to configure other possible combinations.
16-5
Pipe Packages for 3-way CCVs
PIPE PACKAGES
Strainer
Isolation Valve
Optional hoses are available
*Note: Extra piping for Isolation Valve to CCV and Strainer is
required (not supplied).
* Extra piping not supplied by B
Belimo
Supply side packages feature the Belimo control valve on
the supply side of the coil and the above components
arranged in a supply configuration. Refer to the SelectPro
software for supply side configurations.
Union Technical Specifications Manual Balance Valve Technical Specifications Strainer Technical Specifications
Service chilled or hot water, 60% chilled or hot water, 60% Service chilled or hot water, 60%
glycol glycol glycol
Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2” Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2” Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2”
Materials: Materials: Materials:
Body forged brass Body forged brass Body forged brass
Union nut forged brass Ball chrome plated/forged brass Union nut forged brass
Tailpiece forged brass Stem extruded brass Ball chrome plated/forged brass
Gasket EPDM Union forged brass Stem & gland nut forged brass
glass reinforced nylon Tailpiece forged brass Tailpiece forged brass
Insulator
(dielectric) Gland nut extruded brass Seals & packing PTFE
Readout port body & cap extruded brass Seats & packing virgin PTFE Stem o-rings Viton
Readout port seal Nordel O-rings Viton Strainer screen 304 stainless steel /
Pressure/temperature ratings: Venturi extruded brass 20 mesh standard
½” to 2” 400 psi Readout port body & cap extruded brass Readout port body & cap extruded brass
Component temperature 250°F maximum Readout port seal Nordel Readout port seal Nordel
0°F to 250°F Memory stop forged brass Pressure/temperature ratings:
16-6
Pipe Packages for 3-way CCVs
PIPE PACKAGES
MANUAL
PIPE PACKAGE SMARTCODE (CCV) UNION STRAINER
BALANCE VALVE LIST
Pipe Package Model # Valve Nominal Size Body End/ Body End/ Body End/ PRICE
(3-way CCV) without hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
P3 111 1111 1111 0 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $442
P3 121 1112 1212 0 ½ 15 Sweat/M-NPT F-NPT/M-NPT Sweat/Sweat $442
P3 131 1113 1113 0 ½ 15 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $442
P3 131 1211 1213 0 ½ 15 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $442
P3 131 1212 1213 0 ½ 15 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $442
P3 131 1213 1213 0 ½ 15 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $442
P3 211 2111 2111 0 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $496
P3 221 2112 2212 0 ¾ 20 Sweat/M-NPT F-NPT/M-NPT Sweat/Sweat $496
P3 231 2113 2113 0 ¾ 20 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $496
P3 231 2211 2213 0 ¾ 20 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $496
P3 231 2212 2213 0 ¾ 20 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $496
P3 231 2213 2213 0 ¾ 20 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $496
P3 311 3114 3111 0 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $674
P3 321 3114 3212 0 1 25 Sweat/M-NPT F-NPT/M-NPT Sweat/Sweat $674
P3 331 3115 3113 0 1 25 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $674
P3 311 3115 3213 0 1 25 F-NPT/M-NPT F-NPT/M-NPT Sweat/M-NPT $674
SMARTCODE ORDER NOMENCLATURE
COMPONENT ORDER NOMENCLATURE P3 321 3214 3213 0 1 25 Sweat/M-NPT Sweat/M-NPT Sweat/M-NPT $674
EXAMPLE: P3 331 3215 3213 0 1 25 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $674
311 3114 3111 5
P3 MANUAL
Union MBV Strainer Hose PIPE PACKAGE SMARTCODE (CCV) UNION STRAINER
BALANCE VALVE LIST
PPU311 PPL3114 PPS3111 PHOSE5 Pipe Package Model # Valve Nominal Size Body End/ Body End/ Body End/ PRICE
(3-way CCV) with 12” hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
P3 111 1111 1111 1 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $526
P3 111 1112 1211 1 ½ 15 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $526
P3 111 1113 1111 1 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $526
P3 111 1211 1211 1 ½ 15 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $526
P3 111 1212 1111 1 ½ 15 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $526
P3 111 1213 1211 1 ½ 15 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $526
P3 211 2111 2111 3 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $628
P3 211 2112 2211 3 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $628
P3 211 2113 2111 3 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $628
P3 211 2211 2211 3 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $628
P3 211 2212 2111 3 ¾ 20 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $628
P3 211 2213 2211 3 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $628
P3 311 3114 3111 5 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $926
P3 311 3115 3211 5 1 25 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $926
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
16-7
Pipe Packages for Zone Valves
PIPE PACKAGES
16-8
PIPE PACKAGES
Pipe Packages for Zone Valves
MANUAL
PIPE PACKAGE SMARTCODE (ZONE) UNION STRAINER
BALANCE VALVE LIST
Pipe Package Model # Valve Nominal Size Body End/ Body End/ Body End/ PRICE
(2-way Zone) without hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
PZ 111 1111 1111 0 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $346
PZ 121 1112 1212 0 ½ 15 Sweat/M-NPT F-NPT/M-NPT Sweat/Sweat $346
PZ 131 1113 1113 0 ½ 15 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $346
PZ 131 1211 1213 0 ½ 15 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $346
PZ 131 1212 1213 0 ½ 15 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $346
PZ 131 1213 1213 0 ½ 15 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $346
PZ 211 2111 2111 0 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $387
PZ 221 2112 2212 0 ¾ 20 Sweat/M-NPT F-NPT/M-NPT Sweat/Sweat $387
SMARTCODE ORDER NOMENCLATURE PZ 231 2113 2113 0 ¾ 20 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $387
COMPONENT ORDER NOMENCLATURE PZ 231 2211 2213 0 ¾ 20 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $387
EXAMPLE: PZ 231 2212 2213 0 ¾ 20 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $387
111 1111 1111 0
PP2 PZ 231 2213 2213 0 ¾ 20 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $387
Union MBV Strainer No Hose PZ 311 3114 3111 0 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $510
PPU111 PPL1111 PPS1111 PZ 321 3114 3212 0 1 25 Sweat/M-NPT F-NPT/M-NPT Sweat/Sweat $510
PZ 331 3115 3113 0 1 25 M-NPT/M-NPT F-NPT/M-NPT F-NPT/M-NPT $510
PZ 311 3115 3213 0 1 25 F-NPT/M-NPT F-NPT/M-NPT Sweat/M-NPT $510
PZ 321 3214 3213 0 1 25 Sweat/M-NPT Sweat/M-NPT Sweat/M-NPT $510
PZ 331 3215 3213 0 1 25 M-NPT/M-NPT Sweat/M-NPT Sweat/M-NPT $510
MANUAL
PIPE PACKAGE SMARTCODE (ZONE) UNION STRAINER
BALANCE VALVE LIST
Pipe Package Model # Valve Nominal Size Body End/ Body End/ Body End/ PRICE
(2-way Zone) with 12” hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
PZ 111 1111 1111 1 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $430
PZ 111 1112 1211 1 ½ 15 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $430
PZ 111 1113 1111 1 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $430
PZ 111 1211 1211 1 ½ 15 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $430
PZ 111 1212 1111 1 ½ 15 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $430
PZ 111 1213 1211 1 ½ 15 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $430
PZ 211 2111 2111 3 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $519
PZ 211 2112 2211 3 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $519
PZ 211 2113 2111 3 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $519
PZ 211 2211 2211 3 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $519
Extension Packages Include: PZ 211 2212 2111 3 ¾ 20 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $519
• Extended handle for Manual Balance Valve, PZ 211 2213 2211 3 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $519
Isolation Valve and Strainer PZ 311 3114 3111 5 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $762
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
• Extended P/T ports for Union, Manual PZ 311 3115 3211 5 1 25 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $762
Balance Valve, Strainer or Isolation Valve PZ 311 3214 3111 5 1 25 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $762
• Extended air vent for Manual Balance Valve PZ 311 3215 3211 5 1 25 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $762
and Isolation Valve
MANUAL
PIPE PACKAGE SMARTCODE (ZONE) UNION STRAINER
BALANCE VALVE LIST
Pipe Package Model # Valve Nominal Size Body End/ Body End/ Body End/ PRICE
(2-way Zone) with 24” hose Inches DN [mm] Tailpiece End Tailpiece End Tailpiece End
PZ 111 1111 1111 2 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $450
PZ 111 1112 1211 2 ½ 15 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $450
PZ 111 1113 1111 2 ½ 15 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $450
PZ 111 1211 1211 2 ½ 15 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $450
PZ 111 1212 1111 2 ½ 15 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $450
PZ 111 1213 1211 2 ½ 15 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $450
PZ 211 2111 2111 4 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $557
PZ 211 2112 2211 4 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $557
PZ 211 2113 2111 4 ¾ 20 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $557
PZ 211 2211 2211 4 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $557
PZ 211 2212 2111 4 ¾ 20 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $557
PZ 211 2213 2211 4 ¾ 20 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $557
PZ 311 3114 3111 6 1 25 F-NPT/M-NPT F-NPT/M-NPT F-NPT/F-NPT $802
PZ 311 3115 3211 6 1 25 F-NPT/M-NPT F-NPT/M-NPT Sweat/F-NPT $802
PZ 311 3214 3111 6 1 25 F-NPT/M-NPT Sweat/M-NPT F-NPT/F-NPT $802
PZ 311 3215 3211 6 1 25 F-NPT/M-NPT Sweat/M-NPT Sweat/F-NPT $802
All combinations of reorder numbers are not reflected above. Please use the nomenclature or download the SelectPro
software at www.belimo.us to configure other possible combinations.
16-9
PIPE PACKAGES
• Calculate control valve and pipe package costs for any size project
• Generate valve, actuator, and piping package data submittals for a project
G2 14 LVX 24 -MFT
Valve Type Valve Size Trim Material Actuator Type Power Supply Control
G2 = 2-way NPT 12-50 = ½” to 2” Blank = Bronze Trim Non-Spring Return 24 = 24 VAC/DC Blank = On/Off
G3 = 3-way NPT 65-150 = 2½” to 6” S = Stainless Trim LV 120 = 120 VAC -3 = On/Off, Floating Point
G6 = 2-way Flanged (Flanged) -250 = ANSI 250 SV UP = 24-240 VAC -SR = 2-10 VDC
G7 = 3-way Flanged Bronze Trim EV or 24-125 VDC -MFT or MFT-X1= Multi-Function
S-250 = ANSI 250 RV Technology
Stainless Spring Return -MFT95-X1= 0-135 Ω
Trim LF
C = Bronze NF
Trim Pressure
AF
Compensated
Electronic Fail-Safe
CS = Stainless
GK
Trim Pressure
Compensated LVK
SVK
GLOBE VALVES
Ordering Example
Non-Spring Models
G43 Tagging:
NO = Normally Open Valves may be tagged per
G43 2 to 10 VDC customer specification.
NC = Normally Closed
G53 0.5 to 10 VDC ($10.00 per tag)
Fail-Safe Models W3M 0.02 to 5.00 seconds PWM Example:
NO/FO = Normally Open/Fail Open G13 Floating Point AHU-1
NO/FC = Normally Open/Fail Closed FCU-2
G03 On/Off
NC/FO = Normally Closed/Fail Open Part number for tagging:
NC/FC = Normally Closed/Fail Closed 99981-00101
LVK Series
LF Series
LV Series
14 1 25 G225 –
Valve Specifications
10 1 25 G224S –
Service chilled or hot water, 60% glycol, steam
NF Series
Body bronze
20 1¼ 32 – G332D Stem stainless steel
Plug brass
28 1½ 40 G240 – stainless steel: G2..S
Seat bronze
28 1½ 40 G240S G340
stainless steel: G2..S
28 1½ 40 – G340D Packing spring loaded TFE
AFX Series
17-1
Control Valve Product Range
Globe Valve Product Range
Actuator Specifications
170 4 100 G6100C-250
Control type on/off, floating point, 2-10 VDC
170 4 100 G6100CS-250 multi-function technology (MFT)
Manual override all models
170 4 100 G6100LCS
Electrical connection 3 ft [1 m] cable with
263 5 125 G6125C ½” conduit fitting
263 5 125 G6125CS
263 5 125 G6125C-250 Valve Specifications
Service chilled or hot water,
263 5 125 G6125CS-250 60% glycol, steam
263 5 125 G6125LCS Flow characteristic
G6 A-port equal percentage
344 6 150 G6150C
17-2
Control Valve Product Range
Globe Valve Product Range
AVK Series
68 2½ 65 G765S-250
85 3 80 G780
EV / RV Series
AFX Series
85 3 80 G780S
85 3 80 G780-250
Mode of Operation
85 3 80 G780S-250 The control valve is operated by an electronic actuator
that responds to a standard voltage for on/off control, a
190 4 100 G7100 proportional VDC/4…20 mA, or 3-point control system. The
actuator will then move the plug of the valve to the position
190 4 100 G7100S
dictated by the control signal thus changing the flow.
190 4 100 G7100-250 Product Features
Linear characteristic
190 4 100 G7100S-250
Actuator Specifications
280 5 125 G7125
Control type on/off, floating point, 2-10 VDC
GK Series
280 5 125 G7125S multi-function technology (MFT)
Manual override all models
280 5 125 G7125-250 Electrical connection 3 ft [1 m] cable with
RV Series
½” conduit fitting
280 5 125 G7125S-250
340 6 150 G7150 Valve Specifications
340 6 150 G7150S Service chilled or hot water,
60% glycol
340 6 150 G7150-250 Flow characteristic linear
340 6 150 G7150S-250 Sizes 2½” - 6”
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Packing
85 3 80 G780DS-250 G7 bronze trimmed: NLP
G7...S stainless trimmed: NLP
154 4 100 G7100D
AFX Series
EV Series
17-3
Electronic Screwed Globe Valves
Flow Direction
LVK, SVK Series NC/FO: Normally closed A to AB with NO/FO: Normally open A to AB with NC/FC: Normally closed A to AB with NO/FC: Normally open A to AB with
power and min. signal applied. When power and min. signal applied. When power and min. signal applied. When power and min. signal applied. When
G2 2-way Valve loss of power will fail open A to AB. If loss of power will fail open A to AB. If loss of power will fail closed
sed A to AB. loss of power will fail closed A to AB.
desired both normal position and fail desired both normal position and fail If desired both normal position and If desired both normal position and
position can be reversed in field with position can be reversed in field with fail position can be reversed in field fail position can be reversed in field
ELECTRONIC FAIL-SAFE
AND SPRING RETURN
direction switch. direction switch. with direction switch. with direction switch.
LVK, SVK, LF, NF, NC/FC: Normally closed A to AB, valve NO/FO: Normally open A to AB, valve
AF Series (on/off) will drive open with power. Fail Action: will drive open with power. Fail Action:
Will fail closed A to AB upon power Will fail open A to AB upon power
loss. Can be reversed with direction loss. Can be reversed with direction
switch or actuator remounting. switch or actuator remounting.
Stem Up
LF, NF, AF Series NC/FO: Normally closed A to AB with NO/FO: Normally open A to AB with NC/FC: Normally closed A to AB with NO/FC: Normally open A to AB with
Open A to AB power and min. signal applied. When power and min. signal applied. When power and min. signal applied. When power and min. signal applied.
loss of power will fail open A to AB. loss of power will fail open A to AB. loss of power will fail closed A to AB. When loss of power will fail closed
If desired both normal position and If desired both normal position and If desired both normal position and A to AB. If desired both normal
fail position can be reversed in field fail position can be reversed in field fail position can be reversed in field position and fail position can be re-
with direction switch and actuator with direction switch and actuator with direction switch and actuator versed in field with direction switch
remounting. remounting. remounting. and actuator remounting.
will open upon increase in min. will close upon increase in min.
NON-
LVK, SVK Series NC/FO: Normally closed A to AB with NO/FO: Normally open A to AB with NC/FC: Normally closed A to AB with NO/FC: Normally open A to AB with
power and min. signal applied. When power and min. signal applied. When power and min. signal applied. When power and min. signal applied. When
loss of power will fail open A to AB. If loss of power will fail open A to AB. If loss of power will fail closed A to AB. loss of power will fail closed A to AB.
desired both normal position and fail desired both normal position and fail If desired both normal position and If desired both normal position and
G3 3-way position can be reversed in field with position can be reversed in field with fail position can be reversed in field fail position can be reversed in field
ELECTRONIC FAIL-SAFE
AND SPRING RETURN
Mixing Valve direction switch. direction switch. with direction switch. with direction switch.
LVK, SVK, LF, NF, NC/FC: Normally closed A to AB, valve NO/FO: Normally open A to AB, valve
AF Series (on/off) will drive open with power. Fail Action: will drive open with power. Fail Action:
Will fail closed A to AB upon power Will fail open A to AB upon power
loss. Can be reversed with direction loss. Can be reversed with direction
switch or actuator remounting. switch or actuator remounting.
will open upon increase in min. will close upon increase in min.
NON-
LVK, SVK Series NC/FO: Normally closed B to AB with NO/FO: Normally open B to AB with NC/FC: Normally closed B to AB with NO/FC: Normally open B to AB with
power and min. signal applied. When power and min. signal applied. When power and min. signal applied. When power and min. signal applied. When
loss of power will fail open B to AB. If loss of power will fail open B to AB. If loss of power will fail closed B to AB. loss of power will fail closed B to AB.
desired both normal position and fail desired both normal position and fail If desired both normal position and If desired both normal position and
G3 3-way position can be reversed in field with position can be reversed in field with fail position can be reversed in field fail position can be reversed in field
ELECTRONIC FAIL-SAFE
AND SPRING RETURN
direction switch. direction switch. with direction switch. with direction switch.
Diverting Valve
LVK, SVK, LF, NF, NC/FC: Normally closed B to AB, valve NO/FO: Normally open B to AB, valve
AF Series (on/off) will drive open with power. Fail Action: will drive open with power. Fail Action:
Will fail closed B to AB upon power Will fail open B to AB upon power
loss. Can be reversed with direction loss. Can be reversed with direction
switch or actuator remounting. switch or actuator remounting.
LF, NF, AF Series NC/FO: Normally closed B to AB with NO/FO: Normally open B to AB with NC/FC: Normally closed B to AB with NO/FC: Normally open B to AB with
power and min. signal applied. When power and min. signal applied. When power and min. signal applied. When power and min. signal applied.
loss of power will fail open B to AB. loss of power will fail open B to AB. loss of power will fail closed B to AB. When loss of power will fail closed
If desired both normal position and If desired both normal position and If desired both normal position and B to AB. If desired both normal
Stem Up fail position can be reversed in field fail position can be reversed in field fail position can be reversed in field position and fail position can be re-
Open B to AB with direction switch and actuator with direction switch and actuator with direction switch and actuator versed in field with direction switch
remounting. remounting. remounting. and actuator remounting.
17-4
Electronic Flanged Globe Valves
GLOBE VALVES
A AB A B
Flow arrow shown
on rear of valve B AB
2-WAY VALVE
NOTE FAIL POSITION STAYS IN LAST
NON-SPRING
POSITION
RETURN
NC: Normally closed A to AB, valve will open upon increase in signal/power. NO: Normally open A to AB, valve will close upon increase in signal/power.
EV, RV Series
Note: To change valve to A to AB open, reverse the directional switch in actuator. Note: To change valve to A to AB closed, reverse the directional switch in actuator.
AFB, AFX Series NO/FO: Normally open A to AB valve will drive closed. Spring Action: Will fail open A to NC/FC: Normally closed A to AB valve will drive open. Spring Action: Will fail closed
SPRING RETURN
NO/FC or NC/FC: Valve: Can be open or closed, will drive closed or open A to AB
ELECTRONIC
(can be chosen with CW/CCW switch). Fail Position: Will default fail A to AB open,
FAIL-SAFE
NC/FO: Normally closed A to AB, valve will open upon increase in signal. Note: To
AVK, GK Series change valve to A to AB open, reverse CW/CCW switch.Fail Position: Will default fail A to from the factory. Fail position can be set from 0%-100%, in 10% increments.
AB open, from the factory. Fail position can be set from 0%-100%, in 10% increments. NO/FO: Normally open A to AB. Fail Position: Will default fail A to AB open, from the
factory. Fail position can be set from 0%-100%, in 10% increments.
POSITION
RETURN
NC: Normally closed A to AB, will open upon increase in signal/power. NO: Normally open A to AB, will close upon increase in signal/power.
EV, RV Series
Note: To change valve to A to AB open, reverse the directional switch in actuator. Note: To change valve to A to AB closed, reverse the directional switch in actuator.
AFB, AFX Series NO/FO Normally open A to AB, valve will drive closed. Spring Action: Will fail open A to NC/FC Normally closed A to AB, valve will drive open. Spring Action: Will fail closed
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
NO/FC or NC/FC Valve: Can be open or closed, will drive closed or open A to AB
ELECTRONIC
(can be chosen with CW/CCW switch). Fail Position: Will default fail A to AB open,
FAIL-SAFE
NC/FO Normally closed A to AB, valve will open upon increase in signal. Note: To change
AVK, GK Series valve to A to AB open, reverse CW/CCW switch. Fail Position: Will default fail A to AB from the factory. Fail position can be set from 0%-100%, in 10% increments.
open, from the factory. Fail position can be set from 0%-100%, in 10% increments. NO/FO Normally open A to AB. Fail Position: Will default fail A to AB open, from the
factory. Fail position can be set from 0%-100%, in 10% increments.
POSITION
RETURN
NC: Normally closed AB to B, will open upon increase in signal/power. NO: Normally open AB to B, will close upon increase in signal/power.
EV, RV Series
Note: To change valve to AB to B open, reverse the directional switch in actuator. Note: To change valve to AB to B closed, reverse the directional switch in actuator.
AFB, AFX Series NO/FO Normally open AB to B, valve will drive closed. Spring Action: Will fail open AB to NC/FC Normally closed AB to B, valve will drive open. Spring Action: Will fail closed
On/Off B upon power loss. AB to B upon power loss.
SPRING RETURN
NO/FC or NC/FC Valve: Can be open or closed, will drive closed or open AB to B
ELECTRONIC
(can be chosen with CW/CCW switch). Fail Position: Will default fail AB to B open,
FAIL-SAFE
NC/FO Normally closed AB to B, valve will open upon increase in signal. Note: To change
AVK, GK Series valve to AB to B open, reverse CW/CCW switch. Fail Position: Will default fail AB to B from the factory. Fail position can be set from 0%-100%, in 10% increments.
open, from the factory. Fail position can be set from 0%-100%, in 10% increments. NO/FO Normally open AB to B. Fail Position: Will default fail AB to B open, from the
factory. Fail position can be set from 0%-100%, in 10% increments.
17-5
Customize Products
Default and MFT Programming Codes
CONTROL
CONFIGURATION
ACTUATOR TYPE P-CODE CONTROL INPUT FEEDBACK POSITION RUNNING TIME List Price
DESCRIPTION
-3 and -SR N/A 0 2-10 VDC (for -3) 2-10 VDC (for -3) 150 seconds No Charge
N/A 2 2-10 VDC (for -SR) 2-10 VDC (for -SR) 90 seconds No Charge
P-10001 A01 2-10 VDC 2-10 VDC 150 seconds No Charge*
GLOBE VALVES
G42 (G22 for -SR) 2-10 VDC 2-10 VDC 60 seconds No Charge
G43 (G23 for -SR) 2-10 VDC 2-10 VDC 90 seconds No Charge
G44 (G24 for -SR) 2-10 VDC 2-10 VDC 150 seconds No Charge
-MFT G51 0.5-10 VDC 0.5-10 VDC 35 seconds No Charge
G52 0.5-10 VDC 0.5-10 VDC 60 seconds No Charge
G53 0.5-10 VDC 0.5-10 VDC 90 seconds No Charge
G54 0.5-10 VDC 0.5-10 VDC 150 seconds No Charge
G2A 5.5-10 VDC 5.5-10 VDC 150 seconds No Charge
G2B 0.5-4.5 VDC 0.5-4.5 VDC 150 seconds No Charge
G2C 2-10 VDC 0.5-5 VDC 150 seconds No Charge
G2D 6-9 VDC 2-10 VDC 150 seconds No Charge
G2E 10.5-13.5 VDC 2-10 VDC 150 seconds No Charge
W3M (LV, SV only) 0.02-5.00 seconds PWM 2-10 VDC 90 seconds No Charge
W3P (LV, SV only) 0.2-5.00 seconds PWM 2-10 VDC 90 seconds No Charge
17-6
G2/G3 Series Globe Valves with Non-Spring Return Actuators
2-way and 3-way Valves with Bronze Trim, NPT Female Ends
Valve Specifications
(G2) chilled, hot water, 60%
Service G2,G3 glycol, steam;
(G3) chilled, hot water, 60% glycol
(G2) equal percentage;
Flow Characteristic G2, G3
(G2S, G3) linear
(G2) stem up - open A to AB;
GLOBE VALVES
Action
(G3) stem up - open B to AB
End Fitting NPT female ends
Body bronze
Seat bronze
Stem stainless steel
Packing spring loaded TFE
Plug brass
Media Temp. Water G2,G3 20°F to 280°F [-7°C to +138°C]
Media Temp. Steam G2 32°F to 280°F [0°C to 138°C]
Max DeltaP (Water) 35 psi (241 kPa)
(G2) 20 psi (103 kPa);
Max DeltaP (Steam) G2
(G2S) 35 psi (241 kPa)
(G2) 35 psi (241 kPa);
Max Inlet PSI (Steam) G2
(G2S) 100 psi (345 kPa)
(G2) ANSI Class IV;
Leakage G2,G3
(G3) ANSI Class III
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-7
G2/G3 Series Globe Valves with Electronic Fail-Safe Actuators
2-way and 3-way Valves with Bronze Trim, NPT Female Ends
Valve Specifications
(G2) chilled, hot water, 60%
Service G2,G3 glycol, steam;
(G3) chilled, hot water, 60% glycol
(G2) equal percentage;
Flow Characteristic G2, G3
(G2S, G3) linear
(G2) stem up - open A to AB;
GLOBE VALVES
Action
(G3) stem up - open B to AB
End Fitting NPT female ends
Body bronze
Seat bronze
Stem stainless steel
Packing spring loaded TFE
Plug brass
Media Temp. Water G2,G3 20°F to 280°F [-7°C to +138°C]
Media Temp. Steam G2 32°F to 280°F [0°C to 138°C]
Max DeltaP (Water) 35 psi (241 kPa)
(G2) 20 psi (103 kPa);
Max DeltaP (Steam) G2
(G2S) 35 psi (241 kPa)
(G2) 35 psi (241 kPa);
Max Inlet PSI (Steam) G2
(G2S) 100 psi (345 kPa)
(G2) ANSI Class IV;
Leakage G2,G3
(G3) ANSI Class III
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-8
G2…S Series Globe Valves with Non-Spring Return Actuators
2-way Valve with Stainless Steel Trim, NPT Female Ends
Valve Specifications
(G2) chilled, hot water, 60%
Service G2,G3 glycol, steam;
(G3) chilled, hot water, 60% glycol
(G2) stem up - open A to AB;
Action
(G3) stem up - open B to AB
GLOBE VALVES
End Fitting NPT female ends
Body bronze
Seat stainless steel
Stem stainless steel
Packing spring loaded TFE
Plug stainless steel
Media Temp. Water G2S 20°F to 280°F [-7°C to +138°C]
Media Temp. Steam G2S 32°F to 338°F [0°C to 170°C]
Max DeltaP (Water) 35 psi (241 kPa)
(G2) 20 psi (103 kPa);
Max DeltaP (Steam) G2
(G2S) 35 psi (241 kPa)
(G2) 35 psi (241 kPa);
Max Inlet PSI (Steam) G2
(G2S) 100 psi (345 kPa)
(G2) ANSI Class IV;
Leakage G2,G3
(G3) ANSI Class III
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-9
G2…S Series Globe Valves with Electronic Fail-Safe Actuators
2-way Valve with Stainless Steel Trim, NPT Female Ends
Valve Specifications
(G2) chilled, hot water, 60%
Service G2,G3 glycol, steam;
(G3) chilled, hot water, 60% glycol
(G2) stem up - open A to AB;
Action
(G3) stem up - open B to AB
End Fitting NPT female ends
GLOBE VALVES
Body bronze
Seat stainless steel
Stem stainless steel
Packing spring loaded TFE
Plug stainless steel
Media Temp. Water G2S 20°F to 280°F [-7°C to +138°C]
Media Temp. Steam G2S 32°F to 338°F [0°C to 170°C]
Max DeltaP (Water) 35 psi (241 kPa)
(G2) 20 psi (103 kPa);
Max DeltaP (Steam) G2
(G2S) 35 psi (241 kPa)
(G2) 35 psi (241 kPa);
Max Inlet PSI (Steam) G2
(G2S) 100 psi (345 kPa)
(G2) ANSI Class IV;
Leakage G2,G3
(G3) ANSI Class III
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-10
G2…(S) Series Globe Valves with Spring Return Actuators
2-way Valve with Bronze Trim / Stainless Steel Trim
Valve Specifications
(G2) chilled, hot water, 60%
Service G2,G3 glycol, steam;
(G3) chilled, hot water, 60% glycol
(G2) equal percentage; Visit www.belimo.uss for additional Spring Return options.
Flow Characteristic G2, G3
(G2S, G3) linear
GLOBE VALVES
(G2) stem up - open A to AB; Prices do not reflect additional programming codes surcharge. See page 17-6
Action for linear actuator MFT codes. Note: All ”B” versions available as customizable
(G3) stem up - open B to AB
End Fitting NPT female ends ”X” versions. Please see www.belimo.us for details.
Body bronze
bronze
Seat
stainless steel
Stem stainless steel
Packing spring loaded TFE
brass
Plug
stainless steel
Media Temp. Water G2,G3 20°F to 280°F [-7°C to +138°C]
Media Temp. Steam G2 32°F to 280°F [0°C to 138°C]
Media Temp. Steam G2S 32°F to 338°F [0°C to 170°C]
Max DeltaP (Water) 35 psi (241 kPa)
(G2) 20 psi (103 kPa);
Max DeltaP (Steam) G2
(G2S) 35 psi (241 kPa)
(G2) 35 psi (241 kPa);
Max Inlet PSI (Steam) G2
(G2S) 100 psi (345 kPa)
(G2) ANSI Class IV;
Leakage G2,G3
(G3) ANSI Class III
18 GA applicance
rated cable with
3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA ½” conduit
appliance cable, plenum cable plenum cable appliance cable, appliance cable, appliance cable, connector
Electrical Connection
½” conduit with ½” conduit with ½” conduit ½” conduit ½” conduit ½” conduit protected NEMA 2
connector connector connector connector connector connector (IP54) 3 ft [1 m]
10 ft [3 m] and
16 ft [5 m]
2-Way
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi]
0.4 250 $1,090 $1,165 $1,194 $1,260
G213 1.3 250 $1,092 $1,168 $1,197 $1,263
0.5” [15]
G214 2.2 250 $1,094 $1,173 $1,200 $1,265
G215 4.4 250 $1,097 $1,175 $1,202 $1,267
G219 5.5 ANSI 250 140 $1,125 $1,202 $1,228 $1,296
0.75” [20]
G220 7.5 140 $1,127 $1,205 $1,234 $1,302
G224 10 220 $1,188 $1,297 $1,458
1” [25]
G225 14 220 $1,190 $1,299 $1,460
G232 20 1.25” [32] 140 $1,279 $1,388 $1,551
2-Way
G212S 0.4 210 $1,389 $1,429 $1,497 $1,565
G213S 1.3 210 $1,391 $1,431 $1,499 $1,567
0.5” [15]
G214S 2.2 210 $1,393 $1,433 $1,501 $1,570
G215S 4.4 210 $1,395 $1,435 $1,503 $1,572
G219S 5.5 ANSI 250 140 $1,431 $1,462 $1,730 $1,798
0.75” [20]
G220S 7.5 140 $1,433 $1,464 $1,732 $1,800
G224S 10 220 $1,651 $1,771 $1,937
1” [25]
G225S 14 220 $1,653 $1,774 $1,940
G232S 20 1.25” [32] 140 $1,975 $2,101 $2,265
17-11
G2/G3 Series Globe Valves with Spring Return Actuators
2-way and 3-way Valves with Bronze Trim / Stainless Steel Trim
Valve Specifications
(G2) chilled, hot water, 60%
Service G2,G3 glycol, steam;
(G3) chilled, hot water, 60% glycol
(G2) equal percentage;
Flow Characteristic G2, G3
(G2S, G3) linear Visit www.belimo.uss for additional Spring Return options.
(G2) stem up - open A to AB;
GLOBE VALVES
Action
(G3) stem up - open B to AB
End Fitting NPT female ends
Body bronze
bronze
Seat
stainless steel
Stem stainless steel
Packing spring loaded TFE
brass
Plug
stainless steel
Media Temp. Water G2,G3 20°F to 280°F [-7°C to +138°C]
Media Temp. Steam G2 32°F to 280°F [0°C to 138°C]
Max DeltaP (Water) 35 psi (241 kPa)
(G2) 20 psi (103 kPa);
Max DeltaP (Steam) G2
(G2S) 35 psi (241 kPa)
(G2) 35 psi (241 kPa);
Max Inlet PSI (Steam) G2
(G2S) 100 psi (345 kPa)
(G2) ANSI Class IV;
Leakage G2,G3
(G3) ANSI Class III
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-12
G3...(D) Series Globe Valves with Spring Return Actuators
3-way Valve with Bronze Trim, Mixing and Diverting, NPT Female Ends
Valve Specifications
(G2) chilled, hot water, 60%
Service G2,G3 glycol, steam;
(G3) chilled, hot water, 60% glycol
(G2) equal percentage;
Flow Characteristic G2, G3 Visit www.belimo.uss for additional Spring Return options.
(G2S, G3) linear
GLOBE VALVES
(G2) stem up - open A to AB;
Action
(G3) stem up - open B to AB
End Fitting NPT female ends
Body bronze
Seat bronze
Stem stainless steel
Packing spring loaded TFE
Plug brass
Media Temp. Water G2,G3 20°F to 280°F [-7°C to +138°C]
Max DeltaP (Water) 35 psi (241 kPa)
(G2) ANSI Class IV;
Leakage G2,G3
(G3) ANSI Class III
10 ft [3 m] and
16 ft [5 m]
3-Way Mixing
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi]
G314 2.2 210 $1,097 $1,175 $1,200 $1,265
0.5” [15]
G315 4.4 210 $1,099 $1,177 $1,202 $1,267
G320 7.5 0.75” [20] ANSI 250 140 $1,102 $1,180 $1,205 $1,270
G325 14 1” [25] 220 $1,076 $1,303 $1,497
G332 20 1.25” [32] 140 $1,179 $1,404 $1,603
3-Way Diverting
G315D 4.4 0.5” [15] 250 $1,280 $1,358 $1,383 $1,450
G320D 7.5 0.75” [20] 250 $1,304 $1,380 $1,405 $1,473
ANSI 250
G325D 14 1” [25] 250 $1,340 $1,561 $1,754
G332D 20 1.25” [32] 250 $1,725 $1,948 $2,147
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-13
G6...C/G7(D) Series Flanged Globe Valves with Non-Spring Return Actuators
2-way and 3-way Valves with Bronze Trim – ANSI 125 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear
Action G6 stem up - open A to AB
GLOBE VALVES
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-14
G6...C/G7(D) Series Flanged Globe Valves with Spring Return Actuators
2-way and 3-way Valves with Bronze Trim– ANSI 125 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear Visit www.belimo.uss for additional Spring Return options.
GLOBE VALVES
Action G6 stem up - open A to AB
Action G7 stem up - open B to AB
Action G7D stem up - open AB to B
End Fitting 125 lb. flanged
Body cast iron - ASTM A126 Class B
Seat bronze
Stem stainless steel
Packing NLP (no lip packing)
Plug bronze
Media Temp. Water G6 32°F to 300°F [0°C to 149°C]
Media Temp. Steam G6 32°F to 280°F [0°C to 138°C]
Media Temp. Water G7 32°F to 350°F [0°C to 176°C]
Media Temp. Water G7D 32°F to 300°F [0°C to 149°C]
Max Differential Pressure
25 psi (172 kPa)
(Water)
Max Differential Pressure
15 psi (103 kPa)
(Steam)
Leakage ANSI Class III
Max Inlet PSI (Water)
150 psi (1034 kPa) @ 250°F
G6, G7
Max Inlet Pressure
35 psi (241 kPa)
(Steam)
3 ft, 18 GA appliance cable, ½” ½” conduit connector protected 3 ft, 18 GA appliance cable, ½” ½” conduit connector protected
Electrical Connection
conduit connector NEMA 2 (IP54) 3 ft [1 m] conduit connector NEMA 2 (IP54) 3 ft [1 m]
10 ft [3 m] and 16 ft [5 m] 10 ft [3 m] and 16 ft [5 m]
2-Way
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi]
65 2.5” [65] 140 $2,987 $3,136
G680C 90 3” [80] 140 $3,273 $3,423
G6100C 170 4” [100] ANSI 125 140 $4,124 $4,223
G6125C 263 5” [125] 140 $5,765 $5,919
G6150C 344 6” [150] 112 $6,363 $6,409
3-Way Mixing
G765 68 40 $2,526 $2,656
2.5” [65]
G765 68 100 $3,245 $3,490
G780 85 ANSI 125 26 $2,758 $2,894
3” [80]
G780 85 68 $3,479 $3,750
G7100 190 4” [100] 12 $4,282 $4,332
3-Way Diverting
G765D 68 2.5” [65] 140 $5,078 $5,227
G780D 85 3” [80] 140 $5,711 $5,845
G7100D 154 4” [100] ANSI 125 140 $6,573 $6,730
G7125D 195 5” [125] 175 $9,137 $9,436
G7150D 248 6” [150] 175 $11,766 $12,114
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-15
G6...C/G7(D) Series Flanged Globe Valves with Electronic Fail-Safe Actuators
2-way and 3-way Valves with Bronze Trim – ANSI 125 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear
Action G6 stem up - open A to AB
GLOBE VALVES
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-16
G6...CS/G7...(D)S Series Flanged Globe Valves with Non-Spring Return Actuators
2-way and 3-way Valves with Stainless Steel Trim– ANSI 125 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear
GLOBE VALVES
Action G6 stem up - open A to AB
Action G7 stem up - open B to AB
Action G7D stem up - open AB to B
End Fitting 125 lb. flanged
Body cast iron - ASTM A126 Class B
Seat stainless steel
Stem stainless steel
Packing NLP (no lip packing)
Plug stainless steel
Media Temp. Water G6 32°F to 350°F [0°C to 176°C]
Media Temp. Steam G6 32°F to 338°F [0°C to 170°C]
Media Temp. Water G7 32°F to 350°F [0°C to 176°C]
Media Temp. Water G7D 32°F to 300°F [0°C to 149°C]
Max Differential Pressure
50 psi (345 kPa)
(Water)
Max Differential Pressure
50 psi (345 kPa)
(Steam)
Leakage ANSI Class III
Max Inlet PSI (Water)
150 psi (1034 kPa) @ 250°F
G6, G7
Max Inlet Pressure
100 psi (680 kPa)
(Steam)
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi]
G665CS 65 2.5” [65] 125 $3,782 $3,869 $3,922
G680CS 90 3” [80] 125 $4,405 $4,492 $4,545
G6100CS 170 4” [100] ANSI 125 125 $5,899 $5,985 $6,039
G6125CS 263 5” [125] 125 $7,830 $7,917 $7,971
G6150CS 344 6” [150] 125 $8,352 $8,439 $8,493
3-Way Mixing
68 94 $3,407 $3,494 $3,547
2.5” [65]
G765S 68 125 $3,864 $4,475
G780S 85 63 $4,029 $4,116 $4,170
3” [80]
G780S 85 125 $4,484 $5,091
ANSI 125
G7100S 190 33 $5,034 $5,120 $5,174
4” [100]
G7100S 190 68 $5,269 $5,877
G7125S 280 5” [125] 42 $7,898 $8,525
G7150S 340 6” [150] 28 $9,727 $10,292
3-Way Diverting
G765DS 68 2.5” [65] 140 $7,435 $7,521 $7,575
G780DS 85 3” [80] 140 $8,447 $8,534 $8,587
G7100DS 154 4” [100] ANSI 125 140 $9,632 $9,718 $9,773
G7125DS 195 5” [125] 140 $13,913 $14,000 $14,054
G7150DS 248 6” [150] 175 $15,947 $16,034 $16,089
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-17
G6...CS/G7...(D)S Series Flanged Globe Valves with Spring Return Actuators
2-way and 3-way Valves with Stainless Steel Trim – ANSI 125 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear Visit www.belimo.uss for additional Spring Return options.
Action G6 stem up - open A to AB
GLOBE VALVES
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-18
G6...CS/G7...(D)S Series Flanged Globe Valves with Electronic Fail-Safe Actuators
2-way and 3-way Valves with Stainless Steel Trim – ANSI 125 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear
Action G6 stem up - open A to AB
GLOBE VALVES
Action G7 stem up - open B to AB
Action G7D stem up - open AB to B
End Fitting 125 lb. flanged
Body cast iron - ASTM A126 Class B
Seat stainless steel
Stem stainless steel
Packing NLP (no lip packing)
Plug stainless steel
Media Temp. Water G6 32°F to 350°F [0°C to 176°C]
Media Temp. Steam G6 32°F to 338°F [0°C to 170°C]
Media Temp. Water G7 32°F to 350°F [0°C to 176°C]
Media Temp. Water G7D 32°F to 300°F [0°C to 149°C]
Max Differential Pressure
50 psi (345 kPa)
(Water)
Max Differential Pressure
50 psi (345 kPa)
(Steam)
Leakage ANSI Class III
Max Inlet PSI (Water)
150 psi (1034 kPa) @ 250°F
G6, G7
Max Inlet Pressure
100 psi (680 kPa)
(Steam)
2-Way
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi]
G665CS 65 2.5” [65] 125 $3,929 $4,016
G680CS 90 3” [80] 125 $4,629 $4,715
G6100CS 170 4” [100] ANSI 125 125 $6,049 $6,136
G6125CS 263 5” [125] 125 $8,475 $8,561
G6150CS 344 6” [150] 125 $8,487 $8,574
3-Way Mixing
G765S 68 71 $3,388 $3,528
2.5” [65]
G765S 68 125 $6,492
G780S 85 47 $3,995 $4,135
3” [80]
G780S 85 ANSI 125 125 $7,003
G7100S 190 4” [100] 37 $7,829
G7125S 280 5” [125] 22 $10,476
G7150S 340 6” [150] 14 $12,242
3-Way Diverting
G765DS 68 2.5” [65] 140 $7,391 $7,531
G780DS 85 3” [80] ANSI 125 140 $8,405 $8,545
G7100DS 154 4” [100] 140 $9,472 $9,612
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-19
G6…LCS Series Flanged Globe Valves with Non-Spring Return Actuators
2-way Linear Valve with Stainless Steel Trim– ANSI 125 Flanged
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic linear
Action stem up - open A to AB
End Fitting 125 lb. flanged
Body cast iron - ASTM A126 Class B
GLOBE VALVES
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-20
G6...LCS Series Flanged Globe Valves with Spring Return Actuators
2-way Linear Valve with Stainless Steel Trim – ANSI 125 Flanged
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic linear
Action stem up - open A to AB
End Fitting 125 lb. flanged Visit www.belimo.uss for additional Spring Return options.
GLOBE VALVES
Body cast iron - ASTM A126 Class B
Seat stainless steel
Stem stainless steel
Packing NLP (no lip packing)
Plug stainless steel
Media Temperature Range
32°F to 350°F [0°C to 176°C]
(Water)
Media Temperature Range
32°F to 338°F [0°C to 170°C]
(Steam)
Max Differential Pressure
50 psi (345 kPa)
(Water)
Max Differential Pressure
50 psi (345 kPa)
(Steam)
Leakage ANSI Class III
Max Inlet Pressure (Water) 150 psi (1034 kPa) @ 250°F
Max Inlet Pressure
100 psi (680 kPa)
(Steam)
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi]
G665LCS 65 2.5” [65] 125 $4,110 $4,208
G680LCS 90 3” [80] 125 $4,729 $4,923
G6100LCS 170 4” [100] ANSI 125 125 $6,541 $6,319
G6125LCS 263 5” [125] 125 $8,651 $8,561
G6150LCS 344 6” [150] 110 $9,053 $8,831
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-21
G6...LCS Series Flanged Globe Valves with Electronic Fail-Safe Actuators
2-way Linear Valve with Stainless Steel Trim – ANSI 125 Flanged
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
Flow Characteristic linear
Action stem up - open A to AB
End Fitting 125 lb. flanged
Body cast iron - ASTM A126 Class B
GLOBE VALVES
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-22
G6…C-250/G7…-250 Series Flanged Globe Valves
with Non-Spring Return Actuators
2-way and 3-way Valves with Bronze Trim – ANSI 250 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
Service G6,G7 glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear
GLOBE VALVES
Action G6 stem up - open A to AB
Action G7 stem up - open B to AB
End Fitting 250 lb. flanged
Body cast iron - ASTM A126 Class B
Seat bronze
Stem stainless steel
Packing NLP (no lip packing)
Plug bronze
Media Temp. Water G6 32°F to 350°F [0°C to 176°C]
Media Temp. Steam G6 32°F to 280°F [0°C to 138°C]
Media Temp. Water G7 32°F to 350°F [0°C to 176°C]
Max Differential Pressure
25 psi (172 kPa)
(Water)
Max Differential Pressure
15 psi (103 kPa)
(Steam)
Leakage ANSI Class III
Max Inlet PSI (Water)
250 psi (1724 kPa) @ 350°F
G6, G7
Max Inlet Pressure
35 psi (241 kPa)
(Steam)
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-23
G6…C-250/G7…-250 Series Flanged Globe Valves with Spring Return Actuators
2-way and 3-way Valve with Bronze Trim – ANSI 250 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
Service G6,G7 glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear Visit www.belimo.uss for additional Spring Return options.
Action G6 stem up - open A to AB
GLOBE VALVES
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-24
G6…C-250/G7…-250 Series Flanged Globe Valves
with Electronic Fail-Safe Actuators
2-way and 3-way Valves with Bronze Trim – ANSI 250 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
Service G6,G7 glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear
GLOBE VALVES
Action G6 stem up - open A to AB
Action G7 stem up - open B to AB
End Fitting 250 lb. flanged
Body cast iron - ASTM A126 Class B
Seat bronze
Stem stainless steel
Packing NLP (no lip packing)
Plug bronze
Media Temp. Water G6 32°F to 350°F [0°C to 176°C]
Media Temp. Steam G6 32°F to 280°F [0°C to 138°C]
Media Temp. Water G7 32°F to 350°F [0°C to 176°C]
Max Differential Pressure
25 psi (172 kPa)
(Water)
Max Differential Pressure
15 psi (103 kPa)
(Steam)
Leakage ANSI Class III
Max Inlet PSI (Water)
250 psi (1724 kPa) @ 350°F
G6, G7
Max Inlet Pressure
35 psi (241 kPa)
(Steam)
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-25
G6…CS-250/G7…S(DS)-250 Series Flanged Globe Valves
with Non-Spring Return Actuators
2-way and 3-way Valves with Stainless Steel Trim – ANSI 250 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear
Action G6 stem up - open A to AB
GLOBE VALVES
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-26
G6…CS-250/G7…S(DS)-250 Series Flanged Globe Valves
with Spring Return Actuators
2-way and 3-way Valves with Stainless Steel Trim – ANSI 250 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear Visit www.belimo.uss for additional Spring Return options.
GLOBE VALVES
Action G6 stem up - open A to AB
Action G7 stem up - open B to AB
Action G7D stem up - open AB to B
End Fitting 250 lb. flanged
Body cast iron - ASTM A126 Class B
Seat stainless steel
Stem stainless steel
Packing NLP (no lip packing)
Plug stainless steel
Media Temp. Water G6 32°F to 350°F [0°C to 176°C]
Media Temp. Steam G6 32°F to 338°F [0°C to 170°C]
Media Temp. Water G7 32°F to 350°F [0°C to 176°C]
Media Temp. Water G7D 32°F to 300°F [0°C to 149°C]
Max Differential Pressure
50 psi (345 kPa)
(Water)
Max Differential Pressure
50 psi (345 kPa)
(Steam)
Leakage ANSI Class III
Max Inlet PSI (Water)
250 psi (1724 kPa) @ 350°F
G6, G7
Max Inlet Pressure
100 psi (680 kPa)
(Steam)
Electrical Connection
conduit connector NEMA 2 (IP54) 3 ft [1 m] conduit connector NEMA 2 (IP54) 3 ft [1 m]
10 ft [3 m] and 16 ft [5 m] 10 ft [3 m] and 16 ft [5 m]
2-Way
Body Close-Off
Size
Model # Cv Pressure Pressure
[mm]
Rating [psi]
G665CS-250 65 2.5” [65] 250 $3,419 $4,069
ANSI 250
G680CS-250 90 3” [80] 250 $5,381 $5,538
3-Way Mixing
G765S-250 68 40 $3,657 $3,836
2.5” [65]
G765S-250 68 100 $4,344 $4,696
G780S-250 85 ANSI 250 26 $4,208 $4,135
3” [80]
G780S-250 85 68 $4,895 $5,004
G7100S-250 190 4” [100] 12 $5,830
3-Way Diverting
G765DS-250 68 2.5” [65] 140 $8,658 $8,838
G780DS-250 85 3” [80] 140 $9,893 $10,056
G7100DS-250 154 4” [100] ANSI 250 140 $11,505 $11,695
G7125DS-250 195 5” [125] 140 $15,787 $16,144
G7150DS-250 248 6” [150] 175 $20,441 $20,798
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-27
G6…CS-250/G7…S(DS)-250 Series Flanged Globe Valves
with Electronic Fail-Safe Actuators
2-way and 3-way Valves with Stainless Steel Trim – ANSI 250 Flanged
Valve Specifications
(G6) chilled, hot water, 60%
glycol, steam;
(G7) chilled, hot water, 60% glycol
(G6) equal percentage;
Flow Characteristic G6, G7
(G6LCS, G7) linear
Action G6 stem up - open A to AB
GLOBE VALVES
Prices do not reflect additional programming codes surcharge. See page 17-6 for linear actuator MFT codes. Note: All ”B” versions available as customizable ”X” versions.
Please see www.belimo.us for details.
17-28
Valve Accessories
Globe Valves
GLOBE VALVES
LF series on G2/G3 globe valve
ZS-SPGV-10
Dual AF series on flanged • $405
globe valve
ZS-SPGV-20
Single NF/AF series on G2/
• • $405
G3 (NF/AF) and flanged globe
valve (AF)
ZS-SPGV-40
GK series on flanged • $405
globe valve
ZS-SPGV-50
Dual GK series on flanged • $405
globe valve
ZS-GV-001
Weather shield for LV/SV • • • • $491
(cover only)
ZS-GV-002
Weather shield for EV/RV/AVK • • • $520
(cover only)
AUXILIARY SWITCHES & POTENTIOMETERS
S1A
Auxiliary switch - 1x SPDT, • • $88
3A (0.5A inductive) @ 250 VAC
S2A
Auxiliary switch - 2x SPDT, • • $131
3A (0.5A inductive) @ 250 VAC
S2A-GV
Auxiliary switch - 2x SPDT, • • • • • • • $131
3A (0.5A inductive) @ 250 VAC
P140A GR
• • $144
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
NSV24 US
• • $817
Battery backup module
NSV-BAT
12VDC 1.2 AH battery • • $124
(2 required)
17-29
18
BUTTERFLY VALVES
BUTTERFLY VALVES
HDU, HD, VIC AND SHP SERIES
High Performance for a Wide
Range of Applications
• Resilient seat, grooved and high
performance butterfly valves meet a wide
range of applications.
• Advanced seat and disc design provides
a bubble tight shut-off capability at each
valve’s rated temperature/pressure while
maintaining a low seating torque.
• Stainless steel disc and shaft on HDU/HD
series are standard for superior durability
and long lasting operation.
2 Pos.
Field Logic Determines Normal Position Field Logic Determines Normal Position
Tagging:
Valves may be
Non-Spring Return
Non-Spring Return
Modulating
per tag)
NO (Normally Open) Master (Actuated) Valve
1 VDC/2 VDC/4mA = Open NO (Normally Open) Example:
1 VDC/2 VDC/4mA = Open Chiller 1
3rd Floor East
NO/FO (Normally Open/Fail Open) NO/FO (Normally Open/Fail Open) Part number for
Field Logic Determines Normal Position Field Logic Determines Normal Position tagging: 99981-00101
Spring Fails Valve OPEN Spring Fails Master Valve OPEN
Specify Flow Pattern [see pg. 18-4, 18-5]
NO/FO
1 VDC/2 VDC/4mA = Open 1 VDC/2 VDC/4mA = Master Valve Open 5
Spring Return
Spring Return
AF Series
AR
GR Series
AR
196 75 2½ 65 F665
GR Series
AF Series
GKR
302 116 3 80 F680
Mode of Operation
DKR
600 230 4 100 F6100 Butterfly valves offer higher flows with relatively low
SY Series
DR
DKR
DR
1579 605 6 150 F6150 pressure loss of a butterfly valve is too low to produce
SY Series
any significant effect on flow or the energy loss of a flow
3136 1202 8 200 F6200
system. Butterfly valves are controlled with a maintenance-
5340 2047 10 250 F6250 free electronic actuator or with a manually ergonomic
handle or gear operator.
8250 3162 12 300 F6300
Product Features
11917 4568 14 350 F6350 The unique disc and seat design ensures positive valve
seating while maintaining low seating torque.
16388 6282 16 400 F6400
21705 8320 18 450 F6450 Actuator Specifications
Control type on/off, floating point,
27908 10698 20 500 F6500
proportional, 2-10 VDC
43116 16528 24 600 F6600 multi-function technology (MFT)
Manual override all models
Electrical connection 3 ft. [1 m] cable
terminal block
3-way Suitable Actuators
Valve Specifications
Valve Non-Spring Spring Electronic
Type Service chilled, hot water,
Nominal Size Return Return Fail-Safe 60% glycol
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
115 44 2 50 F750
GM Series
AF Series
AF
Materials
302 116 3 80 F780
GK
18-1
Control Valve Product Range
Butterfly Valve Product Range
AF Series
AM
260 80 2½ 65 F665VIC
440 140 3 80 F680VIC GM Series
Mode of Operation
820 250 4 100 F6100VIC
GK
Grooved butterfly valves are designed for body pressures
DR Series
SY Series
ranging from full vacuum to 300 psi and for bi-directional,
1200 370 5 125 F6125VIC dead end services to full working pressure. The valve
1800 560 6 150 F6150VIC patented seat design ensures full 360° sealing. The
pressure-enhanced seat compresses to form a larger
3400 1050 8 200 F6200VIC seating area as the pressure increases. Valve construction
and performance meet and exceed MSS-SP-67
5800 1800 10 250 F6250VIC requirements.
9000 2790 12 300 F6300VIC Product Features
The unique single offset disc and seat design ensures
positive valve seating while maintaining low seating torque.
Actuator Specifications
Control type on/off, floating point,
proportional, 2-10 VDC
3-way Suitable Actuators multi-function technology (MFT)
Manual override all models
Valve Spring Electrical connection 3 ft. [1 m] cable
Type Non-Spring Return
Nominal Size Return terminal block
Cv Cv DN
IN 3-way Valve Specifications
90° 60° [mm]
Service chilled, hot water,
AM
115 36 2 50 F750VIC
AF
60% glycol
260 80 2½ 65 F765VIC Flow characteristic F6 modified equal percentage
Series
F7 modified linear
440 140 3 80 F780VIC Sizes 2” to 12”
820 250 4 100 F7100VIC End fitting grooved ANSI/AWWA (C606)
SY Series
Materials*
1200 370 5 125 F7125VIC Body ductile iron ASTM A536,
1800 560 6 150 F7150VIC grade 65-45-12
Body finish black alkyd enamel
3400 1050 8 200 F7200VIC Disc electrolysis nickel coated
ductile iron
5800 1800 10 250 F7250VIC Shaft 416 stainless steel
9000 2790 12 300 F7300VIC Seat EPDM
Bearings fiberglass with TFE lining
Media temp. range -20°F to +250°F
[-30°C to +120°C]
Body pressure rating 300 psi
Close-off pressure 200 psi
Rangeability 100:1 (for 30° to 70° range)
Maximum velocity 20 FPS
Leakage bubble tight shut-off
18-2
Control Valve Product Range
Butterfly Valve Product Range
GM Series
GM Series
GK Series
GK Series
AF Series
AF Series
146 80 2½ F665-150SHP F665-300SHP
228 125 3 F680-150SHP F680-300SHP Mode of Operation
High performance butterfly valves are designed for
451 248 4 F6100-150SHP F6100-300SHP modulating and isolation service and feature a machined
seat design and blow out proof solid shaft providing
714 392 5 F6125-150SHP F6125-300SHP
better torque consistency which offers longer actuator
1103 607 6 F6150-150SHP F6150-300SHP life and reduced risk of leakage. Available for a variety of
high temperature and pressure ratings ASME/ANSI Class
SY Series
SY Series
2064 1135 8 F6200-150SHP F6200-300SHP 300 or 150 @ 32 fps maximum velocity with 100:1 range
ability along with bubble tight leakage and valve sizes from
3517 1934 10 F6250-150SHP F6250-300SHP 2 to 24 inches.
4837 2660 12 F6300-150SHP F6300-300SHP Product Features
Unique body seat and double offset disc design ensures
6857 3592 14 F6350-150SHP F6350-300SHP
positive valve sealing to help assure leak free performance
9287 4865 16 F6400-150SHP F6400-300SHP in water applications while maintaining low seating torque.
Valve Specifications
3-way Valves Suitable Actuators
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
GM Series
GK Series
GK Series
SY Series
18-3
Butterfly Valve Selection
HDU/HD Series Valves, 3-way Configuration
D163_12
COMMON
COMMON
MASTER
MASTER
MASTER
SLAVE
COMMON
SLAVE SLAVE
Notes:
1. Slave Valve operates inversely of the Master Valve.
2. The Master Valve is always located on the run.
3. The Slave Valve may also have an actuator if required (Direct Coupled).
4. On/Off actuator normal position is a function of field logic.
5. Proportional actuator normal position is a function of the CCW/CW switch.
6. All 3-way assemblies are designed for 90 degree actuator rotation.
18-4
Butterfly Valve Selection
150 SHP/300 SHP Series Valves, 3-way Configuration
MASTER
MASTER
COMMON
MASTER
COMMON
SLAVE
FLOW FLOW FLOW
MIXING
COMMON
SLAVE SLAVE
BUTTERFLY VALVES
COMMON
COMMON
MASTER
MASTER
SLAVE
MASTER
DIVERTING
COMMON
SLAVE SLAVE
Notes:
1. Slave Valve operates inversely of the Master Valve.
2. The Master Valve is always located on the run.
3. The Slave Valve may also have an actuator if required (Direct Coupled).
4. On/Off actuator normal position is a function of field logic.
5. Proportional actuator normal position is a function of the CCW/CW switch.
6. All 3-way assemblies are designed for 90 degree actuator rotation.
18-5
Butterfly Valve Selection
Velocity Chart
HDU/HD Flow in Std Weight Pipe (Fluid Velocity in GPM). Use with HD/HDU Series Butterfly Valves.
SIZE 2 FPS 4 FPS 6 FPS 8 FPS 10 FPS 12 FPS
2” 19 39 59 78 98 117
2½” 30 61 92 122 153 184
3” 44 88 132 176 220 264
4” 78 157 235 313 392 470
5” 122 245 367 490 612 734
6” 176 352 529 705 881 1058
8” 313 627 940 1253 1567 1880
10” 490 979 1469 1958 2448 2738
12” 705 1410 2115 2820 3525 4230
14” 959 1919 2879 3838 4798 5758
16” 1253 2507 3760 5013 6267 7520
18” 1586 3173 4759 6345 7931 9518
BUTTERFLY VALVES
VIC Flow in Std Weight Pipe (Fluid Velocity in GPM). Use with Grooved Series Butterfly Valves.
SIZE 1 FPS 3 FPS 5 FPS 8 FPS 10 FPS 12 FPS 15 FPS 16 FPS 20 FPS
2” 10 31 52 84 105 126 157 167 209
2½” 15 45 75 119 149 179 224 239 298
3” 23 69 115 184 230 277 346 369 461
4” 40 119 198 317 397 476 595 635 794
5” 62 187 312 499 624 748 935 998 1247
6” 90 270 450 720 900 1081 1351 1441 1801
8” 156 468 780 1247 1559 1871 2339 2495 3119
10” 246 737 1229 1966 2458 2949 3687 3932 4916
12” 353 1058 1763 2820 3525 4230 5288 5640 7050
SHP Flow in Std Weight Pipe (Fluid Velocity in GPM). Use with SHP Series Butterfly Valves.
18-6
Butterfly Valve SY Actuators
CONTROL TYPE
SERIES MODEL Run Time(s) 90°@60Hz Power Supply Duty Cycle Proportional 3 Point On/Off Feedback List Price
SY1-110 11 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $1,241
SY1-24 20 seconds 24 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $1,241
SY1-220 10 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $1,241
SY1
SY1-110P 16 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $2,924
SY1-24P 15 seconds 24 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $2,924
SY1-220P 16 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $2,924
SY2-110 16 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,001
SY2-24 16 seconds 24 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,001
SY2-220 16 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,001
SY2
SY2-120MFT 17 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,080
SY2-24MFT 15 seconds 24 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,080
BUTTERFLY VALVES
SY2-230MFT 17 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,080
SY3-110 24 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,306
SY3-24 24 seconds 24 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,306
SY3-220 25 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,306
SY3
SY3-24MFT 22 seconds 24 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,418
SY3-120MFT 26 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,418
SY3-230MFT 26 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,418
SY4-110 18 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,870
SY4-24 25 seconds 24 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,870
SY4-220 18 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,870
SY4
SY4-24MFT 16 seconds 24 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,272
SY4-120MFT 18 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,272
SY4-230MFT 18 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,272
SY5-110 25 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $3,319
SY5-24 37 seconds 24 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $3,319
SY5-220 25 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $3,319
SY5
SY5-24MFT 22 seconds 24 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,741
SY5-120MFT 25 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,741
SY5-230MFT 25 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,741
SY6-110 29 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $4,022
SY6-220 28 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $4,022
SY6
SY6-120MFT 31 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $6,483
SY6-230MFT 31 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $6,483
SY7-110 54 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $4,829
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
SY7-220 54 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $4,829
SY7
SY7-120MFT 55 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $7,233
SY7-230MFT 55 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $7,233
SY8-110 58 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $6,684
SY8-220 55 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $6,684
SY8
SY8-120MFT 55 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $9,141
SY8-230MFT 55 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $9,141
SY9-110 62 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $8,271
SY9-220 63 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $8,271
SY9
SY9-120MFT 70 seconds 120 VAC ±10%, 50/60 Hz 50% • 2-10 VDC/4-20 mA $10,749
SY9-230MFT 70 seconds 230 VAC ±10%, 50/60 Hz 50% • 2-10 VDC/4-20 mA $10,749
SY10-110 63 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $8,681
SY10-220 64 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $8,681
SY10
SY10-120MFT 70 seconds 120 VAC ±10%, 50/60 Hz 50% • 2-10 VDC/4-20 mA $11,162
SY10-230MFT 70 seconds 230 VAC ±10%, 50/60 Hz 50% • 2-10 VDC/4-20 mA $11,162
SY11-110 65 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $11,554
SY11-220 64 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $11,554
SY11
SY11-120MFT 70 seconds 120 VAC ±10%, 50/60 Hz 50% • 2-10 VDC/4-20 mA $14,048
SY11-230MFT 70 seconds 230 VAC ±10%, 50/60 Hz 50% • 2-10 VDC/4-20 mA $14,048
SY12-110 65 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $12,368
SY12-220 63 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $12,368
SY12
SY12-120MFT 70 seconds 120 VAC ±10%, 50/60 Hz 50% • 2-10 VDC/4-20 mA $14,699
SY12-230MFT 70 seconds 230 VAC ±10%, 50/60 Hz 50% • 2-10 VDC/4-20 mA $14,699
Proportional actuators will accept 0-10 VDC, 2-10 VDC, or 4-20 mA control signals as standard.
All SY actuators are non-spring return, but can be used with NSV-SY back up systems for fail-safe applications.
These products carry a two year warranty when sold as part of an assembly or with a UFLK retrofit kit.
18-7
Butterfly Valve SY Actuators
18-8
Butterfly Valve SY Actuators
BUTTERFLY VALVES
Power Consumption Power Consumption VA VA
Model Torque Speed 60 Hz Speed 50 Hz Override Weight
(50 Hz) (60 Hz) (50 Hz) (60 Hz)
8mm Wrench
SY1-120P 310 in-lbs/ 35 Nm 12 seconds 13 seconds 0.5 A 0.5 A 60 60 Required 2.0 kg/4.9 lbs.
SY2-120MFT 800 in-lbs/ 90 Nm 15 seconds 17 seconds 1.4 A 1.1 A 168 132 Hand Wheel 11 kg/24.5 lbs.
SY3-120MFT 1330 in-lbs/ 150 Nm 22 seconds 26 seconds 1.6 A 1.2 A 192 144 Hand Wheel 11 kg/24.5 lbs.
SY4-120MFT 3540 in-lbs/ 400 Nm 16 seconds 18 seconds 2.3 A 2.0 A 276 240 Hand Wheel 22 kg/48.5 lbs.
SY5-120MFT 4430 in-lbs/ 500 Nm 22 seconds 25 seconds 2.2 A 1.9 A 264 228 Hand Wheel 22 kg/48.5 lbs.
SY6-120MFT 5750 in-lbs/ 650 Nm 28 seconds 31 seconds 2.2 A 1.9 A 264 228 Hand Wheel 22 kg/48.5 lbs.
SY7-120MFT 8850 in-lbs/ 1000 Nm 46 seconds 55 seconds 7.1 A 4.1 A 852 492 Hand Wheel 36 kg/79.5 lbs.
SY8-120MFT 13280 in-lbs/ 1500 Nm 46 seconds 55 seconds 6.9 A 4.0 A 828 480 Hand Wheel 36 kg/79.5 lbs.
SY9-120MFT 17700 in-lbs/ 2000 Nm 58 seconds 70 seconds 2.9 A 3.0 A 348 360 Hand Wheel 72 kg/176.4 lbs.
SY10-120MFT 22130 in-lbs/ 2500 Nm 58 seconds 70 seconds 3.1 A 3.4 A 372 406 Hand Wheel 72 kg/176.4 lbs.
SY11-120MFT 26550 in-lbs/ 3000 Nm 58 seconds 70 seconds 3.4 A 4.1 A 408 492 Hand Wheel 72 kg/176.4 lbs.
SY12-120MFT 30980 in-lbs/ 3500 Nm 58 seconds 70 seconds 4.3 A 4.7 A 516 564 Hand Wheel 72 kg/176.4 lbs.
18-9
F6/F7 HDU Series Butterfly Valves with Non-Spring Return Actuators
2-way and 3-way Valves, Tapered (Undercut) Disc for Lower Close-Off
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature
-22°F to +250°F [-30°C to +120°C]
Range (Water)
Rangeabilty 10:1 (for 30° to 70° range)
BUTTERFLY VALVES
18-10
F6/F7 HDU Series Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Tapered (Undercut) Disc with Reduced Torque
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 10:1 (for 30° to 70° range)
BUTTERFLY VALVES
Maximum Velocity 12 FPS
18-11
F6/F7 HDU Series Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Tapered (Undercut) Disc with Reduced Torque
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range -22°F to +250°F
(Water) [-30°C to +120°C]
BUTTERFLY VALVES
18-12
F6/F7 HDU Series Butterfly Valves with NEMA 4 Non-Spring Return Actuators
2-way and 3-way Valves, Tapered (Undercut) Disc with Reduced Torque
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 10:1 (for 30° to 70° range)
BUTTERFLY VALVES
Maximum Velocity 12 FPS
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
screw terminal screw terminal screw terminal screw terminal
Electrical Connection
(for 22 to 12 AWG wire) (for 22 to 12 AWG wire) (for 22 to 12 AWG wire) (for 22 to 12 AWG wire)
2-Way
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
6” ANSI 125,
F6150HDU 1579 605 50 $2,497 $2,694 $2,867 $3,064
[150] Standard Class B
18-13
F6/F7 HDU Series Butterfly Valves with Spring Return
and Electronic Fail-Safe Actuators
2-way and 3-way Valves, Tapered (Undercut) Disc with Reduced Torque
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 10:1 (for 30° to 70° range)
BUTTERFLY VALVES
Visit www.belimo.us for additional Spring Return and Electronic Fail-Safe options.
3-Way Mixing/Diverting
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F750HDU 115 44 2” [50] 50 $1,565 $1,847
F765HDU 196 75 2.5” [65] 50 $2,424
F780HDU 302 116 3” [80] ANSI 125, 50 $2,943
Standard
F7100HDU 600 230 4” [100] Class B 50 $4,525
F7125HDU 1022 392 5” [125] 50 $4,779
F7150HDU 1579 605 6” [150] 50 $4,945
18-14
F6 HDU Series Butterfly Valves with NEMA 4 Spring Return
and Electronic Fail-Safe Actuators
2-way Valves, Tapered (Undercut) Disc with Reduced Torque
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
Flow Characteristic modified equal percentage
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 10:1 (for 30° to 70° range)
Maximum Velocity 12 FPS
BUTTERFLY VALVES
ACTUATOR PART # AFRXUP N4 AFRXUP N4H AFRX24-MFT N4 AFRB24-MFT N4H
Control On/Off On/Off Proportional/MFT Proportional/MFT
Manual Override • • • •
150 seconds (default), variable 150 seconds (default), variable
Running Time (Motor) 75 seconds 75 seconds
(70 to 220 seconds) (70 to 220 seconds)
Running Time (Fail-Safe) < 20 seconds < 20 seconds < 20 seconds < 20 seconds
Noise Level (Motor) <50 dB (A) <45 dB (A) <45 dB (A) <40 dB (A)
Noise Level (Fail-Safe) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A)
3 ft, 18 GA appliance cable, ½” 3 ft, 18 GA appliance cables with 3 ft, 18 GA plenum cable with ½” 3 ft, 18 GA appliance cable, ½”
Electrical Connection
conduit connector ½” conduit connectors conduit connector conduit connector
2-Way
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F650HDU 115 44 2” [50] ANSI 125, 50 $1,404 $2,442 $1,540 $2,578
F665HDU 196 75 2.5” [65] Standard 50 $1,439 $2,476 $1,575 $2,612
F680HDU 302 116 3” [80] Class B 50 $1,453 $2,490 $1,590 $2,627
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
18-15
F6/F7 HD Series Butterfly Valves with Non-Spring Return Actuators
2-way and 3-way Valves, Standard (Full Rated) Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 10:1 (for 30° to 70° range)
BUTTERFLY VALVES
18-16
F6/F7 HD Series Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Standard (Full Rated) Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
EPDM
Seat
EPDM standard
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
BUTTERFLY VALVES
Rangeabilty 10:1 (for 30° to 70° range)
Maximum Velocity 12 FPS
18-17
F6/F7 HD Series Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Standard (Full Rated) Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 10:1 (for 30° to 70° range)
BUTTERFLY VALVES
SY5-24, SY5-24MFT,
SY6-110, SY6-120MFT, SY8-110, SY8-120MFT,
ACTUATOR PART # SY5-110, SY5-120MFT,
SY6-220 SY6-230MFT SY8-220 SY8-230MFT
SY5-220 SY5-230MFT
Control On/Off, Floating Point Proportional/MFT On/Off, Floating Point Proportional/MFT On/Off, Floating Point Proportional/MFT
Manual Override • • • • • •
Running Time (Motor) 37, 25, 25 seconds 22, 25, 25 seconds 29, 28 seconds 31 seconds 58, 55 seconds 55 seconds
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
Electrical Connection terminal block terminal block terminal block terminal block terminal block terminal block
2-Way
Body Close-Off
Cv Size
Model # Cv 60° Pressure Pressure
90° [mm] Rating [psi]
F6350HD 11917 4568 14” [350] ANSI 200 $8,238 $11,191
F6400HD 16388 6282 16” [400] 125, 200 $11,292 $12,562
F6450HD 21705 8320 18” [450] Standard 200 $13,883 $15,439
F6500HD 27908 10698 20” [500] Class B 200 $16,772 $18,675
SY5-24, SY5-24MFT,
SY6-110, SY6-120MFT, SY7-110, SY7-120MFT,
ACTUATOR PART # SY5-110, SY5-120MFT,
18-18
F6/F7 HD Series Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Standard (Full Rated) Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 10:1 (for 30° to 70° range)
BUTTERFLY VALVES
Maximum Velocity 12 FPS
SY11-110, SY11-120MFT,
ACTUATOR PART #
SY11-220 SY11-230MFT
SY8-110, SY8-120MFT,
ACTUATOR PART #
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
SY8-220 SY8-230MFT
18-19
F6/F7 HD Series Butterfly Valves with NEMA 4 Non-Spring Return Actuators
2-way and 3-way Valves, Standard (Full Rated) Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 10:1 (for 30° to 70° range)
BUTTERFLY VALVES
2*GMB24-
GMCX24-3- GMX24-MFT- 2*GMCX24- 2*GMX24- GMCB24-3- GMB24-MFT- 2*GMCB24-
ACTUATOR PART # MFT-T-X1
T-X1 N4 T-X1 N4 3-T-X1 N4 MFT-T-X1 N4 T-X1 N4H T-X1 N4H 3-T-X1 N4H
N4H
18-20
F6/F7 HD Series Butterfly Valves with Spring Return
and Electronic Fail-Safe Actuators
2-way and 3-way Valves, Standard (Full Rated) Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 10:1 (for 30° to 70° range)
BUTTERFLY VALVES
Maximum Velocity 12 FPS Visit www.belimo.us for additional Spring Return and Electronic Fail-Safe options.
2*AFX24-
ACTUATOR PART # AFRBUP-5 AFRX24-MFT GKRB24-3-5 GKRX24-MFT-5 DKRX24-3-T DKRX24-MFT-T
MFT-X1
On/Off, Floating On/Off, Floating
Control On/Off Proportional/MFT Proportional/MFT Proportional/MFT Proportional/MFT
Point Point
Manual Override • • • • • • •
150 seconds 150 seconds 90 seconds 150 seconds 150 seconds 150 seconds
Running Time (Motor) <75 seconds (default), variable (default), variable (default), variable (default), variable (default), variable (default), variable
(70 to 220 seconds) (70 to 220 seconds) 90 to 150 seconds (95 to 150 seconds) (90 to 150 seconds) (90 to 150 seconds)
20 seconds @
20 sec @ -4°F to 20 sec @ -4°F to
-4°F to +122°F
+122°F [-20°C to +122°F [-20°C to
Running Time (Fail-Safe) [-20°C to +50°C], 35 seconds 35 seconds 35 seconds 35 seconds
+50°C], <60 sec +50°C], <60 sec
< 60 sec @ -22°F
@ -22°F [-30°C @ -22°F [-30°C]
[-30°C]
Noise Level (Motor) <45 dB (A) <40 dB (A) <50 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
Noise Level (Fail-Safe) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <62 dB (A) <50 dB (A) <50 dB (A)
18 GA applicance 18 GA applicance
rated cable with rated cable with 3 ft, 18 GA
(2) 3 ft, 18 GA ½” conduit ½” conduit plenum rated
appliance cables connector connector cable with ½” cable with conduit
Electrical Connection terminal block terminal block
with ½” conduit protected NEMA 2 protected NEMA 2 conduit connector connector
connectors (IP54) 3 ft [1 m] (IP54) 3 ft [1 m] protected NEMA 2
10 ft [3 m] and 10 ft [3 m] and (IP54)
16 ft [5 m] 16 ft [5 m]
2-Way
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F650HD 115 44 2” [50] 200 $907 $1,113
F665HD 196 75 2.5” [65] ANSI 125, 200 $1,108 $1,357
Standard
F680HD 302 116 3” [80] Class B 200 $1,853 $1,655 $1,930
F6100HD 600 230 4” [100] 200 $1,973 $2,359
18-21
F6 HD Series Butterfly Valves with NEMA 4 Spring Return
and Electronic Fail-Safe Actuators
2-way Valves, Standard (Full Rated) Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
Flow Characteristic modified equal percentage
for use with ANSI Class 125/150
End Fitting
flanges
Body ductile iron ASTM A536
Body Finish epoxy powder coated
Disc 304 stainless steel
Shaft 416 stainless steel
Seat EPDM
O-ring EPDM
Bushings RPTEE
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 10:1 (for 30° to 70° range)
Maximum Velocity 12 FPS
BUTTERFLY VALVES
18-22
F6/F7 Victaulic Series Butterfly Valves with Non-Spring Return Actuators
2-way and 3-way Valves, Grooved End Body
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
End Fitting grooved ANSI\AWWA (C606)
ductile iron ASTM A536 grade
Body
65-45-12
Body Finish black alkyd enamel
electroless nickel coated ductile
Disc
iron
Shaft 416 stainless steel
Seat EPDM
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 20 FPS
BUTTERFLY VALVES
AMX24- GMX24- 2*GMB24- 2*GMX24- DRX24-
ACTUATOR PART # AMB24-3-X1 GMB24-3-X1 DRB24-3-T
MFT-X1 MFT-X1 3-X1 MFT-X1 MFT-T
On/Off, Floating Proportional/ On/Off, Floating Proportional/ On/Off, Floating Proportional/ On/Off, Floating Proportional/
Control
Point MFT Point MFT Point MFT Point MFT
Manual Override • • • • • • • •
90 seconds, 150 seconds 150 seconds 150 seconds 150 seconds 150 seconds 35 seconds 150 seconds
constant (default), constant, (default), constant, constant, constant, (default),
Running Time (Motor)
independent variable (90 to independent variable (90 to independent independent independent variable (90 to
of load 350 seconds) of load 150 seconds) of load of load of load 150 seconds)
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
18 GA plenum
3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA 3 ft, 18 GA
rated cable with
plenum rated plenum rated plenum rated plenum rated plenum rated
½” conduit
cable with cable with cable with cable with cable with screw terminal screw terminal
connector
Electrical Connection ½” conduit ½” conduit ½” conduit ½” conduit ½” conduit (for 22 to 12 (for 22 to 12
protected NEMA
connector connector (10 connector connector (10 connector AWG wire) AWG wire)
2 (IP54) 3 ft [1
protected ft [3 m] and 15 protected ft [3 m] and 15 protected
m] 10 ft [3 m]
NEMA 2 (IP54) ft [5 m] avail.) NEMA 2 (IP54) ft [5 m] avail.) NEMA 2 (IP54)
and 16 ft [5 m]
2-Way
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F650VIC 115 36 2” [50] 200 $1,477 $1,654
F665VIC 260 80 2.5” [65] 50 $1,789 $1,963
F665VIC 260 80 2.5” [65] 200 $1,941 $2,034
F680VIC 440 140 3” [80] 300 200 $2,033 $2,128
F6100VIC 820 250 4” [100] 200 $3,230 $3,325 $3,061 $3,207
F6125VIC 1200 370 5” [125] 200 $3,320 $3,466
F6150VIC 1800 560 6” [150] 200 $3,828 $3,974
3-Way Mixing/Diverting
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F750VIC 115 36 2” [50] 50 $3,386 $3,560
F750VIC 115 36 2” [50] 200 $3,546 $3,639
F765VIC 260 140 2.5” [65] 300 50 $4,193 $4,284 $4,929 $5,106
F765VIC 260 140 2.5” [65] 200 $5,106
F780VIC 440 140 3” [80] 50 $5,397
18-23
F6/F7 Victaulic Series Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Grooved End Body
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
End Fitting grooved ANSI\AWWA (C606)
ductile iron ASTM A536 grade
Body
65-45-12
Body Finish black alkyd enamel
electroless nickel coated ductile
Disc
iron
Shaft 416 stainless steel
Seat EPDM
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 20 FPS
BUTTERFLY VALVES
18-24
F6/F7 Victaulic Series Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Grooved End Body
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
End Fitting grooved ANSI\AWWA (C606)
ductile iron ASTM A536 grade
Body
65-45-12
Body Finish black alkyd enamel
electroless nickel coated ductile
Disc
iron
Shaft 416 stainless steel
Seat EPDM
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 20 FPS
BUTTERFLY VALVES
SY5-24, SY5-110, SY5-24MFT, SY5-120MFT, SY6-110, SY6-120MFT,
ACTUATOR PART #
SY5-220 SY5-230MFT SY6-220 SY6-230MFT
18-25
F6/F7 Victaulic Series Butterfly Valves with Spring Return Actuators
2-way and 3-way Valves, Grooved End Body
Valve Specifications
chilled or hot water, up to 60%
Service
glycol
F6- modified equal percentage
Flow Characteristic
F7- modified linear
End Fitting grooved ANSI\AWWA (C606)
ductile iron ASTM A536 grade
Body
65-45-12
Body Finish black alkyd enamel
electroless nickel coated ductile
Disc
iron
Shaft 416 stainless steel
Seat EPDM
Media Temperature Range
-22°F to +250°F [-30°C to +120°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 20 FPS
BUTTERFLY VALVES
3-Way Mixing/Diverting
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F750VIC 115 36 2” [50] 50 $3,551 $3,688
300
F750VIC 115 36 2” [50] 200 $5,012 $5,211
18-26
F6/F7 ANSI Class 150 Butterfly Valves with Non-Spring Return Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Steel Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
150 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
ACTUATOR PART # GMB24-3-X1 GMX24-MFT-X1 2*GMX24-MFT-X1
Control On/Off, Floating Point Proportional/MFT Proportional/MFT
Manual Override • • •
150 seconds (default), variable (90 to 150
Running Time (Motor) 150 seconds constant, independent of load 150 seconds constant, independent of load
seconds)
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A)
3 ft, 18 GA plenum rated cable with ½” con- 18 GA applicance rated cable with ½” conduit
3 ft, 18 GA plenum rated cable with ½” con-
Electrical Connection duit connector (10 ft [3 m] and 15 ft [5 m] connector protected NEMA 2 (IP54) 3 ft [1 m]
duit connector protected NEMA 2 (IP54)
avail.) 10 ft [3 m] and 16 ft [5 m]
2-Way
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F650-150SHP 102 56 2” [50] 285 $2,566 $2,665
F665-150SHP 146 80 2.5” [65] ASME/ 285 $2,580 $2,680
F680-150SHP 228 125 3” [80] ANSI Class 285 $2,595 $2,697
F6100-150SHP 451 248 4” [100] 150 150 $3,139 $3,239
F6100-150SHP 451 248 4” [100] 285 $3,630
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
3-Way Mixing/Diverting
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F750-150SHP 102 56 2” [50] 150 $5,186 $5,281
F750-150SHP 102 56 2” [50] 285 $5,663
F765-150SHP 146 80 2.5” [65] ASME/ 150 $5,321 $5,414
ANSI Class
F765-150SHP 146 80 2.5” [65] 150 285 $5,798
F780-150SHP 228 125 3” [80] 150 $5,329 $5,423
F780-150SHP 228 125 3” [80] 285 $5,832
18-27
F6/F7 ANSI Class 150 Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Steel Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
150 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
3-Way Mixing/Diverting
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F750-150SHP 102 56 2” [50] 285 $6,704 $8,231
F765-150SHP 146 80 2.5” [65] 285 $6,841 $8,368
F780-150SHP 228 125 3” [80] ASME/ 285 $6,851 $8,375
F7100-150SHP 451 248 4” [100] ANSI 285 $8,471 $9,993
F7125-150SHP 714 392 5” [125] Class 285 $10,845 $12,378
F7150-150SHP 1103 607 6” [150] 150 285 $10,852 $12,386
F7200-150SHP 2064 1135 8” [200] 285 $13,966 $15,734
F7250-150SHP 3517 1934 10” [250] 150 $20,232 $22,000
18-28
F6/F7 ANSI Class 150 Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
150 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
SY5-24, SY5-24MFT,
SY7-110, SY7-120MFT, SY8-110, SY8-120MFT,
ACTUATOR PART # SY5-110, SY5-120MFT,
SY7-220 SY7-230MFT SY8-220 SY8-230MFT
SY5-220 SY5-230MFT
Control On/Off, Floating Point Proportional/MFT On/Off, Floating Point Proportional/MFT On/Off, Floating Point Proportional/MFT
Manual Override • • • • • •
Running Time (Motor) 37, 25, 25 seconds 22, 25, 25 seconds 54 seconds 55 seconds 58, 55 seconds 55 seconds
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
Electrical Connection terminal block terminal block terminal block terminal block terminal block terminal block
2-Way
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F6300-150SHP 4837 2660 12” [300] 285 $12,648 $14,408
F6350-150SHP 6857 3592 14” [350] 150 $15,736 $17,507
F6350-150SHP 6857 3592 14” [350] ASME/ 285 $16,762 $18,481
ANSI
F6400-150SHP 9287 4865 16” [400] 285 $23,235 $24,956
Class
F6450-150SHP 11400 6270 18” [450] 150 150 $26,949 $28,671
F6450-150SHP 11400 6270 18” [450] 285 $28,102 $29,829
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
3-Way Mixing/Diverting
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F7250-150SHP 3517 1934 10” [250] 285 $20,537 $22,309
F7300-150SHP 4837 2660 12” [300] ASME/ 150 $26,158 $27,926
F7300-150SHP 4837 2660 12” [300] ANSI 285 $27,182 $28,904
F7350-150SHP 6857 3592 14” [350] Class 285 $36,244 $37,966
F7400-150SHP 9287 4865 16” [400] 150 150 $52,834 $54,617
F7450-150SHP 11400 6270 18” [450] 150 $61,339 $63,062
18-29
F6/F7 ANSI Class 150 Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
150 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
SY9-110, SY9-120MFT,
ACTUATOR PART #
18-30
F6/F7 ANSI Class 150 Butterfly Valves with NEMA 4 Non-Spring Return Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Steel Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
150 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
ACTUATOR PART # GMCX24-3-T-X1 N4 GMX24-MFT-T-X1 N4 GMCB24-3-T-X1 N4H GMB24-MFT-T-X1 N4H
Control On/Off, Floating Point Proportional/MFT On/Off, Floating Point Proportional/MFT
Manual Override • • • •
35 seconds constant, 150 seconds (default), variable 35 seconds constant, 150 seconds (default), variable
Running Time (Motor)
independent of load (95 to 150 seconds) independent of load (95 to 150 seconds)
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
Electrical Connection terminal block terminal block terminal block terminal block
2-Way
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F650-150SHP 102 56 2” [50] 285 $3,767 $3,874 $4,137 $4,244
F665-150SHP 146 80 2.5” [65] ASME/ 285 $3,830 $3,932 $4,200 $4,302
ANSI Class
F680-150SHP 228 125 3” [80] 150 285 $3,921 $4,024 $4,291 $4,394
F6100-150SHP 451 248 4” [100] 150 $4,064 $4,249 $4,434 $4,619
3-Way Mixing/Diverting
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
18-31
F6/F7 ANSI Class 150 Butterfly Valves with Spring Return
and Electronic Fail-Safe Actuators
2-way and 3-way Valves, Reinforced Teflon® Seat, 316 Stainless Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
150 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
18-32
F6 ANSI 300 Class Butterfly Valves with Non-Spring Return Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
300 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
ACTUATOR PART # GMB24-3-X1 GMX24-MFT-X1 2*GMX24-MFT-X1
Control On/Off, Floating Point Proportional/MFT Proportional/MFT
Manual Override • • •
150 seconds (default), variable (90 to 150
Running Time (Motor) 150 seconds constant, independent of load 150 seconds constant, independent of load
seconds)
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A)
3 ft, 18 GA plenum rated cable with ½” con- 18 GA applicance rated cable with ½” conduit
3 ft, 18 GA plenum rated cable with ½” con-
Electrical Connection duit connector (10 ft [3 m] and 15 ft [5 m] connector protected NEMA 2 (IP54) 3 ft [1 m]
duit connector protected NEMA 2 (IP54)
avail.) 10 ft [3 m] and 16 ft [5 m]
2-Way
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F650-300SHP 100 52 2” [50] 285 $2,856 $2,954
F650-300SHP 100 52 2” [50] 400 $3,337
F665-300SHP 143 75 2.5” [65] 285 $2,869 $2,970
F665-300SHP 143 75 2.5” [65] ASME/ 400 $3,354
ANSI
F680-300SHP 223 117 3” [80] Class 300 285 $2,890 $2,986
F680-300SHP 223 117 3” [80] 400 $3,366
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
18-33
F6/F7 ANSI 300 Class Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
300 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
18-34
F6/F7 ANSI 300 Class Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
300 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
SY5-24, SY5-24MFT,
SY7-110, SY7-120MFT, SY8-110, SY8-120MFT,
ACTUATOR PART # SY5-110, SY5-120MFT,
SY7-220 SY7-230MFT SY8-220 SY8-230MFT
SY5-220 SY5-230MFT
Control On/Off, Floating Point Proportional/MFT On/Off, Floating Point Proportional/MFT On/Off, Floating Point Proportional/MFT
Manual Override • • • • • •
Running Time (Motor) 37, 25, 25 seconds 22, 25, 25 seconds 54 seconds 55 seconds 58, 55 seconds 55 seconds
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
Electrical Connection terminal block terminal block terminal block terminal block terminal block terminal block
2-Way
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F6250-300SHP 3194 1673 10” [250] 400 $13,084 $14,854
F6250-300SHP 3194 1673 10” [250] 600 $14,104 $15,831
F6300-300SHP 4428 2319 12” [300] 285 $16,662 $18,433
F6300-300SHP 4428 2319 12” [300] 600 $17,685 $19,407
F6350-300SHP 5702 2986 14” [350] ASME/ 150 $27,001 $28,773
F6350-300SHP 5702 2986 14” [350] ANSI 400 $28,026 $28,773
F6350-300SHP 5702 2986 14” [350] Class 600 $29,179 $30,903
F6400-300SHP 8243 3988 16” [400] 300 150 $29,834 $31,555
F6400-300SHP 8243 3988 16” [400] 285 $30,987 $32,710
F6450-300SHP 9712 5088 18” [450] 150 $38,108 $39,830
F6450-300SHP 9712 5088 18” [450] 285 $39,263 $40,909
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
18-35
F6/F7 ANSI 300 Class Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
300 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
18-36
F6/F7 ANSI 300 Class Butterfly Valves with NEMA 4X Non-Spring Return Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
300 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
ACTUATOR PART # GMCB24-3-T-X1 N4 GMX24-MFT-T-X1 N4 GMCB24-3-T-X1 N4H GMB24-MFT-T-X1 N4H
Control On/Off, Floating Point Proportional/MFT On/Off, Floating Point Proportional/MFT
Manual Override • • • •
35 seconds constant, 150 seconds (default), variable 35 seconds constant, 150 seconds (default), variable
Running Time (Motor)
independent of load (95 to 150 seconds) independent of load (95 to 150 seconds)
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
Electrical Connection terminal block terminal block terminal block terminal block
2-Way
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F650-300SHP 100 52 2” [50] 285 $3,872 $4,063 $4,242 $4,433
F665-300SHP 143 75 2.5” [65] ASME/ 285 $4,078 $4,263 $4,448 $4,633
ANSI
F680-300SHP 223 117 3” [80] Class 300 285 $4,291 $4,479 $4,394 $4,849
F6100-300SHP 435 228 4” [100] 150 $4,573 $4,762 $4,943 $5,132
Manual Override • • • •
35 seconds constant, 150 seconds (default), variable 35 seconds constant, 150 seconds (default), variable
Running Time (Motor)
independent of load (95 to 150 seconds) independent of load (95 to 150 seconds)
Noise Level (Motor) <45 dB (A) <45 dB (A) <45 dB (A) <45 dB (A)
Electrical Connection terminal block terminal block terminal block terminal block
3-Way Mixing/Diverting
Body Close-Off
Cv Cv Size
Model # Pressure Pressure
90° 60° [mm] Rating [psi]
F750-300SHP 100 52 2” [50] 285 $8,200 $8,398 $8,505 $8,703
F765-300SHP 143 75 2.5” [65] ASME/ 285 $10,394 $10,908 $10,698 $10,908
ANSI
F780-300SHP 223 117 3” [80] Class 300 285 $10,748 $10,953 $11,052 $11,258
F7100-300SHP 435 228 4” [100] 150 $10,376 $10,564 $11,531 $11,718
18-37
F6/F7 ANSI 300 Class Butterfly Valves with Spring Return
and Electronic Fail-Safe Actuators
2-way and 3-way Valves, Reinforced Teflon Seat, 316 Stainless Disc
Valve Specifications
chilled or hot water, up to 60%
Service
glycol, steam
F6- modified equal percentage
Flow Characteristic
F7- modified linear
for use with ASME/ANSI Class
End Fitting
300 flanges
Body carbon steel full lug
Disc 316 stainless steel
Shaft 17-4 PH stainless steel
Seat RPTFE
Gland Seal TFE
Bushings glass backed PTFE
Media Temperature Range
-22°F to +400°F [-30°C to +204°C]
(Water)
Rangeabilty 100:1
Maximum Velocity 32 FPS
BUTTERFLY VALVES
18-38
Valve Accessories
Butterfly Valves
ELECTRONIC SPRING
NON-SPRING RETURN
FAIL-SAFE RETURN
PROGRAMMING TOOLS AM/AR GM/GR SY GK AF LIST PRICE
MFT-P
Belimo MFT configuration software (V3.X)
• • • • • $166
Includes: PC-Tool software (interface cables [ZTH US] not
included)
INTERFACES, CABLES
ZTH US
• • • • • $701
Handheld interface module that allows field programming
ZK1-GEN
Cable for use with ZTH US to connect to new generation non- • • • $107
spring return actuator via diagnostic/programming socket
BUTTERFLY VALVES
ZK2-GEN
Cable for use with ZTH US to connect with spring return and
• • • $49
non-spring return actuators not equipped with diagnostic/
programming socket
ZK6-GEN
Cable for use with ZTH US to connect to SY actuator via RJII • $51
port
SPRING
NON-SPRING RETURN
RETURN
BATTERY BACKUP AM/AR GM/GR/DR SY AF LIST PRICE
NSV24 US
• • $817
Battery backup module
NSV-BAT
• • $124
12VDC 1.2 AH battery (2 required)
EXT-NSV-B01-120
• $5,228
Battery backup system, SY1 - SY3 120 VAC, on/off actuators
EXT-NSV-B02-120
• $6,448
Battery backup system, SY1 - SY3 120 VAC, MFT actuators
EXT-NSV-B03-120
• $5,962
Battery backup system, SY4 - SY6 120 VAC, on/off actuators
EXT-NSV-B04-120
• $6,840
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
EXT-NSV-B05-120
• $6,902
Battery backup system, SY7 - SY12 120 VAC, on/off actuators
EXT-NSV-B06-120
• $7,037
Battery backup system, SY7 - SY12 120 VAC, MFT actuators
EXT-NSV-B11-24
• $5,879
Battery backup system, SY1 24 VAC, on/off actuators
EXT-NSV-B12-24
• $7,098
Battery backup system, SY1 24 VAC, MFT actuators
EXT-NSV-B13-24
• $7,563
Battery backup system, SY2 - SY5 24 VAC, on/off actuators
EXT-NSV-B14-24
• $7,233
Battery backup system, SY2 - SY5 24 VAC, MFT actuators
EXT-NSV-B21-230
• $5,879
Battery backup system, SY1 - SY3 230 VAC, on/off actuators
EXT-NSV-B22-230
• $8,524
Battery backup system, SY1 - SY3 230 VAC, MFT actuators
EXT-NSV-B23-230
• $6,623
Battery backup system, SY4 - SY6 230 VAC, on/off actuators
EXT-NSV-B24-230
• $7,491
Battery backup system, SY4 - SY6 230 VAC, MFT actuators
EXT-NSV-B25-230
• $7,563
Battery backup system, SY7 - SY12 230 VAC, on/off actuators
EXT-NSV-B26-230
• $7,687
Battery backup system, SY7 - SY12 230 VAC, MFT actuators
18-39
Valve Accessories
Butterfly Valves
SPRING
NON-SPRING RETURN ACTUATORS RETURN
ACTUATORS
WEATHER SHIELDS AM GM/GR SY AF LIST PRICE
ZS-BFV-10*
• $297
AM series for F6, F7 HD, HDU
ZS-BFV-20*
• $297
GM series for F6, F7 HD, HDU
ZS-BFV-30*
• $297
AF series for F6, F7 HD, HDU
ZS-BFV-60*
• $527
Dual GM series for F6 HD, HDU (4” - 6”)
ZS-BFV-70*
• $527
Dual AF series for F6 HD, HDU (2½” - 3”)
BUTTERFLY VALVES
ZS-BFV-80*
• $527
Dual AF series for F6 HD, HDU (4”, 5”)
ZS-BFV-90*
• • $527
Dual AF/GM series for F7 HD, HDU below 4” (specify valve size)
ZS-BFV-100*
• $527
Dual GM series for F7 HD, HDU (4” - 6”)
ELECTRIC DISCONNECT
HOA-120V
• $478
Local electric disconnect SY2-SY12; 2 position - 110/230V
HOA-120VMFT
• $478
Local electric disconnect SY2-SY12; proportional - 110/230V
HOA-24V
• $478
Local electric disconnect SY2-SY12; 2 position - 24V
HOA-24VMFT
• $478
Local electric disconnect SY2-SY12; proportional - 24V
AUXILIARY SWITCHES & POTENTIOMETERS
SY-1000-FB01
1000 Ω feedback potentiometer. • $257
2 Position, factory installed option only
SY-1000-FB02
1000 Ω feedback potentiometer.
• $257
P10000A GR
• • $144
Feedback potentiometer 10000 Ω
18-40
Valve Accessories
Butterfly Valves
SPRING
NON-SPRING RETURN ACTUATORS RETURN
ACTUATORS
HANDWHEELS AM GM SY AF LIST PRICE
ZG-SY23
• $47
SY2-SY3 handwheel (replacement only)
ZG-SY46
• $66
SY4-SY6 handwheel (replacement only)
ZG-SY78
• $212
SY7-SY8 handwheel (replacement only)
ZG-SY912
• $234
SY9-SY12 handwheel (replacement only)
VALVE
BUTTERFLY VALVES
MANUAL HANDLES HDU/HD LIST PRICE
F650HD+HND01
• $223
2” HD series valve with manual handle ductile iron, 200 psi close-off, Cv 115
F665HD+HND01
• $238
2½” HD series valve with manual handle ductile iron, 200 psi close-off, Cv 196
F680HD+HND01
• $262
3” HD series valve with manual handle ductile iron, 200 psi close-off, Cv 302
F6100HD+HND02
• $346
4” HD series valve with manual handle ductile iron, 200 psi close-off, Cv 600
F6125HD+HND02
• $500
5” HD series valve with manual handle ductile iron, 200 psi close-off, Cv 1022
F6150HD+HND02
• $584
6” HD series valve with manual handle ductile iron, 200 psi close-off, Cv 1579
GEAR OPERATORS
F650HD+GW01
• $358
2” HD series valve with manual gear operator ductile iron, 200 psi close-off, Cv 115
F665HD+GW01
• $470
2½” HD series valve with manual gear operator ductile iron, 200 psi close-off, Cv 196
F680HD+GW01
• $515
3” HD series valve with manual gear operator ductile iron, 200 psi close-off, Cv 302
F6100HD+GW02
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
• $595
4” HD series valve with manual gear operator ductile iron, 200 psi close-off, Cv 600
F6125HD+GW02
• $705
5” HD series valve with manual gear operator ductile iron, 200 psi close-off, Cv 1022
F6150HD+GW02
• $758
6” HD series valve with manual gear operator ductile iron, 200 psi close-off, Cv 1579
F6200HD+GW03
• $1,129
8” HD series valve with manual gear operator ductile iron, 200 psi close-off, Cv 3136
F6250HD+GW04
• $1,822
10” HD series valve with manual gear operator ductile iron, 200 psi close-off, Cv 5340
F6300HD+GW04
• $2,150
12” HD series valve with manual gear operator ductile iron, 200 psi close-off,Cv 8250
F6350HD+GW04
• $2,780
14” HD series valve with manual gear operator ductile iron, 150 psi close-off, Cv 11917
F6400HD+GW05
• $4,737
16” HD series valve with manual gear operator ductile iron, 150 psi close-off, Cv 16388
F6450HD+GW06
• $5,706
18” HD series valve with manual gear operator ductile iron, 150 psi close-off, Cv 21705
F6500HD+GW07
• $8,197
20” HD series valve with manual gear operator ductile iron, 150 psi close-off, Cv 27908
F6600HD+GW08
• $13,784
24” HD series valve with manual gear operator ductile iron, 150 psi close-off, Cv 43116
F6750HD+GW09
• $25,303
30” HD series valve with manual gear operator ductile iron, 150 psi close-off, Cv 73426
18-41
Valve Accessories
Butterfly Valves
VALVE
MANUAL HANDLES 150SHP LIST PRICE
F650-150SHP+HND05
• $2,425
2” SHP series valve with manual handle cast steel, ANSI 150 close-off limitations, Cv 102
F665-150SHP+HND05
• $2,390
2½” SHP series valve with manual handle cast steel, ANSI 150 close-off limitations, Cv 146
F680-150SHP+HND06
• $2,441
3” SHP series valve with manual handle cast steel, ANSI 150 close-off limitations, Cv 228
F6100-150SHP+HND06
• $2,601
4” SHP series valve with manual handle cast steel, ANSI 150 close-off limitations, Cv 451
F6125-150SHP+HND07
• $4,176
5” SHP series valve with manual handle cast steel, ANSI 150 close-off limitations, Cv 714
F6150-150SHP+HND07
• $3,815
6” SHP series valve with manual handle cast steel, ANSI 150 close-off limitations, Cv 1103
BUTTERFLY VALVES
F6200-150SHP+HND08
• $4,879
8” SHP series valve with manual handle cast steel, ANSI 150 close-off limitations, Cv 2064
GEAR OPERATORS
F650-150SHP+GW10
• $3,198
2” SHP series valve with manual gear operator cast steel, ANSI 150 close-off limitations, Cv 102
F665-150SHP+GW10
• $3,269
2½” SHP series valve with manual gear operator cast steel, ANSI 150 close-off limitations, Cv 146
F680-150SHP+GW11
• $3,319
3” SHP series valve with manual gear operator cast steel, ANSI 150 close-off limitations, Cv 228
F6100-150SHP+GW11
• $3,421
4” SHP series valve with manual gear operator cast steel, ANSI 150 close-off limitations, Cv 451
F6125-150SHP+GW12
• $4,709
5” SHP series valve with manual gear operator cast steel, ANSI 150 close-off limitations, Cv 714
F6150-150SHP+GW12
• $4,780
6” SHP series valve with manual gear operator cast steel, ANSI 150 close-off limitations, Cv 1103
F6200-150SHP+GW13
• $5,655
8” SHP series valve with manual gear operator cast steel, ANSI 150 close-off limitations, Cv 2064
F6250-150SHP+GW15
• $8,413
10” SHP series valve with manual gear operator cast steel, ANSI 150 close-off limitations, Cv 3517
F6300-150SHP+GW17
• $11,080
12” SHP series valve with manual gear operator cast steel, ANSI 150 close-off limitations, Cv 4837
18-42
Valve Accessories
Butterfly Valves
VALVE
MANUAL HANDLES 300SHP LIST PRICE
F650-300SHP+HND05
• $2,740
2” SHP series valve with manual handle cast steel, ANSI 300 close-off limitations, Cv 100
F665-300SHP+HND05
• $2,758
2½” SHP series valve with manual handle cast steel, ANSI 300 close-off limitations, Cv 143
F680-300SHP+HND06
• $2,536
3” SHP series valve with manual handle cast steel, ANSI 300 close-off limitations, Cv 223
F6100-300SHP+HND06
• $2,714
4” SHP series valve with manual handle cast steel, ANSI 300 close-off limitations, Cv 435
F6125-300SHP+HND07
• $4,739
5” SHP series valve with manual handle cast steel, ANSI 300 close-off limitations, Cv 688
F6150-300SHP+HND08
• $3,835
6” SHP series valve with manual handle cast steel, ANSI 300 close-off limitations, Cv 1041
BUTTERFLY VALVES
GEAR OPERATORS
F650-300SHP+GW10
• $3,374
2” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 100
F665-300SHP+GW10
• $3,392
2½” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 143
F680-300SHP+GW11
• $3,170
3” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 223
F6100-300SHP+GW11
• $3,343
4” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 435
F6125-300SHP+GW12
• $5,357
5” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 688
F6150-300SHP+GW13
• $4,453
6” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 1041
F6200-300SHP+GW14
• $5,930
8” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 1911
F6250-300SHP+GW16
• $9,834
10” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 3194
F6300-300SHP+GW18
• $12,987
12” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 4428
F6350-300SHP+GW20
• $22,949
14” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 5702
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
F6400-300SHP+GW22
• $27,121
16” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 8243
F6450-300SHP+GW24
• $35,420
18” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 9712
F6500-300SHP+GW26
• $44,094
20” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 10658
F6600-300SHP+GW28
• $64,723
24” SHP series valve with manual gear operator cast steel, ANSI 300 close-off limitations, Cv 16205
18-43
New Tools from Belimo to Make Your Life Easier
From sizing and selecting to estimating savings, Belimo offers the following tools
to help make your job easier:
• Retrofit App allows you to quickly and easily find HVAC replacement
solutions for valves and actuators.
• Energy Valve Savings Estimator is a Microsoft Excel based tool that profiles
constant speed chilled water plant performance.
Cutting Edge
Technology
• Application
• Product Model
• Control Type
RETROFIT SOLUTIONS
• Product Type
Replacement results provide a complete selection of products that are compatible with most control systems.
19
ZIP ECONOMIZER
Fast Route to Reliable Energy Savings
• Efficient Free Cooling.
• Fault Detection and Diagnostics.
• Plug and Play.
AND
ECON-ZIP-BASE ECON-ZIP-10K
(Supply Air Sensor)
ECONOMIZER SOLUTIONS
SINGLE DRY BULB DIFFERENTIAL DRY BULB SINGLE ENTHALPY DIFFERENTIAL ENTHALPY
OR
• Demand Control Ventilation (DCV)* - ECON-ZIP-EM + CO2 sensor • Remote Alarm Notification* - ECON-ZIP-COM
of your choice (0-2000PPM, 0-10VDC).
* May be required by local codes
• Preoccupancy Purge* - ECON-ZIP-EM
Requires thermostat with purge setting and contacts.
• Remote Damper Override - ECON-ZIP-EM + SGA24
• Exhaust Fan - ECON-ZIP-EM
See page 19-5 for a list of ZIP Pack Solutions & Retrofit Kits.
19-2
ECON-ZIP-BASE
ZIP Economizer
Specifications
Power supply 24 VAC ±20%, 50/60 Hz, class 2 power
4 VA base control (ECON-ZIP-BASE)
5.5 VA base control with Energy Module
(ECON-ZIP-BASE + ECON-ZIP-EM)
Power consumption* 5 VA base control with Communication Module
(ECON-ZIP-BASE + ECON-ZIP-COM)
6.5 VA base control with Energy Module and
Communication Module.
NTC 10K (type II thermistor)
Supported temperature sensor
sensor auto-detection
Supported humidity sensor 0-10 VDC; sensor auto-detection
Supported CO2 sensor 0-10 VDC; sensor auto-detection
Environmental RoHS, conformally coated
Ambient temperature -40°F to +158°F [-40°C to +70°C]
Storage temperature -40°F to +176°F [-40°C to +80°C]
Humidity 5 to 95% R.H. (non-condensing)
Wiring ¼” male spade connectors
Housing material UL94-5VA
Housing NEMA 1
Display 2x16 character LCD display; LED backlight
Display operating temperature** -22°F to +176°F [-30°C to +80°C]
EMC according to UL60730-1, cULus according
Agency listings
to UL873, CAN/CSA C22.2, No. 24-93
Energy code compliant ASHRAE 90.1, CA Title 24, NECB
ECONOMIZER SOLUTIONS
*The power consumption is for the control only and does not include connected loads
such as actuator, compressors, fans, and sensors. MODEL List Price
**At low temperatures the display has decreased response time. Below -22°F [-30°C] ECON-ZIP-BASE $440
it will not function.
TFB24-SR 2-10 VDC 2-10 VDC 24 VAC/DC 95 seconds <25 seconds 4 $401
*** Up to three actuators can be used. Visit www.ZIPeconomizer.com for details.
Belimo Spring Return actuators must be used to facilitate faster commissioning procedures (-SR acceptable).
ECON-ZIP-TH
The ECON-ZIP-TH Sensor may be used to measure temperature and humidity in the outdoor or return air stream. The temperature and humidity
output is via 2 discrete analog channels that can be independently measured with a multimeter. One sensor is used in the outdoor air intake for single
$150
enthalpy changeover strategy. An additional sensor can be added in the return air stream for differential enthalpy changeover strategy.
Note: When using the ECON-ZIP-TH it is not necessary to use a separate temperature sensor ECON-ZIP-10K for outdoor air (OAT), return air (RAT).
ECON-ZIP-10K
The ECON-ZIP-10K allows for reliable air temperature readings. The sensor may be used for outdoor air (OAT), return air (RAT), or supply air
(SAT) temperature measurements and control, with no configuration required. A minimum of one SAT and one OAT sensor is required for the ZIP $30
Economizer to function. An RAT sensor can be added for differential temperature change over strategy. For best control results, sensors should be
placed in the air stream. The T-Bracket mounting is universal and can be inserted through the ductwork, fan housing or surface mounted.
19-3
Optional Add-On Modules
ZIP Economizer
ECON-ZIP-EM
The ZIP Economizer Energy Module provides additional I/Os to offer higher control functionalities that will save even more energy. The Energy
Module is needed for demand control ventilation, indoor fan- 2 speed control, power exhaust fan, remote override for damper positioning, and
preoccupancy purge. The auto-detection and plug and play capability offers quick set up.
Technical Data
Type Name Description Electrical Specification
CO2 sensor 0-10 VDC
Input CO2 +/- input sensor auto-detection
100'000 cycles @ inrush current of
3A, normal current 1.5A
Indoor fan low impedance for auto detection
Output IF
speed enable @24V:
<600 Ω @ 60 Hz $100
<800 Ω @ 50 Hz
100'000 cycles @ inrush current of
3A, normal current 1.5A
Exhaust fan impedance for auto detection @
Output EF
enable 24V:
<600 Ω @ 60 Hz
<800 Ω @ 50 Hz
Auxiliary input
on/off, 24 VAC, 50/60 Hz
Input AUX1 ± purge contact
current load min. 10mA
ECONOMIZER SOLUTIONS
input
Auxiliary input
remote
Input AUX2 ± 2-10 VDC
potentiometer
input
ECON-ZIP-COM
The ZIP Economizer Communication Module provides remote alarm indication with future capabilities such as data trending and building
automation integration.
Technical Data
Type Name Description Electrical Specification
RS485 interface
optical isolation max. 1k VDC (for $156
Communication max. 1 min.)
I/O Comm
19-4
Retrofit Kits and ZIP Packs
ZIP Economizer
Components
Retrofit Kits for Honeywell Footmounted Actuators List Price
(# included in kit)
ECON-ZIP-ACT Shaft, M4x8 Screws (4),
Actuator Shaft Adapter allows easy retrofi t from Honeywell® black box motors (M7XXX) to Locking Nuts (4)
Belimo spring return actuator. $59
Components
ZIP Packs List Price
(# included in kit)
ECON-ZIP-SDTF ECON-ZIP-BASE, ECON-ZIP-EM,
ECONOMIZER SOLUTIONS
Single Dry Bulb with DCV Capability and TF Spring Return Actuator (22 in-lbs) ECON-ZIP-10K (2), TFB24-SR,
ECON-ZIP-TF1 $910
19-5
Retrofit Solutions, Economizer Actuators
Retrofit Replacement Solutions
LF24-SR-E US $491
ZG-LF112
$55
Crank arm adaptor kit - includes KH-LF crank arm and clip, ZG-112 bracket and mounting hardware.
20477-00001
$55
Logic module bracket for Honeywell
KH-LF
crank arm KG6
$17
Ball joint (if needed)
W7459
LF24-ECON-RO3 US $516
ZG-ECON1
$92
Includes ZG-112, KH-LF, 20477-00001 (logic module bracket), KG6 (ball joint), and 4 male spade connectors.
ZG-ECON2
$74
Includes ZG-112, KH-LF, KG6 (ball joint), and 4 female spade connectors.
Choose either ZG-ECON1 or ZG-ECON2.
LF24-SR US $446
ZG-ECON1
$92
Includes ZG-112, KH-LF, 20477-00001 (logic module bracket), KG6 (ball joint), and 4 male spade connectors.
KH-LF
crank arm
19-6
20
RETROFIT SOLUTIONS
Get Up and Running in Record Time
• Quickly and conveniently restores
applications without any interruption
in service.
• Custom solutions are available with our
in-house retrofit shop with lead times of
5 days or less.
• Simple way to implement Belimo actuators
in existing buildings whether electronic or
pneumatic.
Ordering Example
needed control type. AFB24-SR 2-10 VDC (4-20mA) 2-10 VDC 24 VAC/DC 95 seconds <20 secs 8.5 -
AFB24-SR-S
SR S 2 10 VDC (4
2-10 (4-20mA)
20mA) 2 10 VDC
2-10 24 VAC/DC
VAC/DC 95 seconds
seconds <20 secs
secs 85
8.5 Built-In
Built In
Decide between AFB24, AFB24-PC
PC
C 0 10 V Pha
0-10 Ph secutt 2 100 VDC
2-10 24 VAC/DC
VAC/DC 150 second
secondss <20 secs
secs 10 -
3 AFB24-MFT AFB24-MFT
AFB24-MFT 2-10 VDC (4-20m
(4 20mA)
A) 22-10
10 VDC 24 VAC/DC
VAC/DC 150 second
secondss <20
20 secs
secs 10
0 -
AFB24-MFT-S
MFT S 2-10 VDC (4-20m
(4-20mA)
A) 2-10 VDC 24 VAC/DC
VAC/DC 150 second
secondss <20 secs
secs 10 B ilt-In
Built I
In
AFB24-MFT95
MFT95 0 to 135 2-10 VDC 24 VAC/DC
VAC/DC 150 second
secondss <20 secs
secs 10 -
or SVKX24-3,
SVKX24-MFT.
Complete Ordering Example ACTUATOR PART # LVKX24-3 LVKB24-SR LVKX24-MFT SVKX24-3 SVKB24-SR SVKX24-MFT
Complete Ordering Example Actuator noise level <45 dB(A) <45 dB(A) <45 dB(A) <45 dB(A) <45 dB(A) <45 dB(A)
GVL LINKAGES
Option Two: Universal Adjustable for
4 Item 1: UGVL+
UGVL
1/2” to 2”
$ $ $ $ $ $
SGVL Schnieder
Schni eder VB7
VB7..., VB9
VB9... $ $ $ $ $ $
SVKX24-MFT
Retrofit and Replacement
How to Select an Actuator
Are you in need of a solution for a broken linkage, leaky hydraulic actuator, non-functioning electric or pneumatic
actuator? Do you have a need for replacing a non-functioning application within a day or so?
Belimo provides airside and waterside retrofit application solutions, with direct coupled or remote access linkages,
and efficient actuators.
Damaged linkages and/or actuators resulting in non-functioning HVAC system applications used to mean a loss
of properly functioning systems leading to a degradation of energy efficiency, consumer comfort, time, and labor.
Replacing a valve along with the actuator or trying to determine how to fix an airside linkage is not always a sensible
solution. Taking a system off-line to replace various components is not only laborious, it’s expensive. Facilities can
lose thousands of dollars a day during maintenance shut-down. With retrofit solutions this problem simply goes
away. Valves and damper applications can be quickly and conveniently restored without any interruption in service.
In fact, entire systems can often be updated in a day. A poorly functioning or even non-functioning system can be
transformed into a highly functioning, more efficient system.
Belimo provides many retrofit solutions that are compatible with all major control systems, so there is no need to
replace other system controls. MFT Technology is also available and can be reprogrammed to suit your controller
needs with just one MFT model actuator.
In addition, Belimo’s design team is ready and willing to customize a solution for non-standard retrofit solutions.
Call Belimo at 800-543-9038 for assistance in fulfilling your retrofit application requirements.
RETROFIT SOLUTIONS
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Retrofit using Belimo AF series damper actuators in BC Place, Vancouver, British Columbia, Canada
20-1
Retrofit and Replacement, Damper Actuators
Discontinued Belimo Products
20-2
Retrofit and Replacement, Valve Actuators
Discontinued Belimo Products
RETROFIT SOLUTIONS
MAR160-BP-24V 2,500 SY4-24MFT* 3,560
LV24-SR US CCV with LR... or TR….
MAR250-60-24V 5,000 SY5-24* 4,450
LV24-SR/200 US CCV with LR... or TR….
MAR250-60P-24V 5,000 SY5-24MFT* 4,450
LV24-SR/300 US CCV with LR... or TR….
*New linkage required.
LV24-SR-1 US CCV with LR... or TR….
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
LV24-SR-1/200 US CCV with LR... or TR…. NON-SPRING RETURN – 110 VAC NON-SPRING RETURN – 110 VAC
LV24-SR-1/300 US CCV with LR... or TR…. DISCONTINUED MODEL Torque REPLACEMENT MODEL Torque
LV24-SR-1-2.0 US CCV with LR... or TR…. MAR95-15B 1,000 SY3-110* 1,335
LV24-SR-1-2.0/200 US CCV with LR... or TR…. MAR95-15BP 1,000 SY3-120MFT* 1,335
LV24-SR-1-2.0/300 US CCV with LR... or TR…. MAR100B 1,500 SY4-110* 3,559
LR24 US LRB24-3 MAR160B 2,000 SY4-110* 3,560
LR24-MFT US LRX24-MFT + # LR100 RC1 ❑ ❑ ❑ MAR100BP 1,800 SY4-120MFT* 3,560
LR24/200 US LRX24-3 + # LR000 RC3 002 MAR160-BP 2,500 SY4-120MFT* 3,560
LR24/300 US LRX24-3 + # LR000 RC3 002 MAR250-30 5,000 SY5-110* 4,450
LR24-1 US LRB24-3 MAR250-30P 5,000 SY5-120MFT* 4,450
LR24-1/200 US LRX24-3 + # LR000 RC3 002 SY6-110* 6,450
LR24-1/300 US LRB24-3 + # LR000 RC3 002 SY6-120MFT* 6,450
LR24-3-1 US LRB24-3 MAR800-30 10,000 SY7-110* 9,790
LR24-3-1/200 US LRX24-3 + # LR000 RC3 002 MAR800-30P 10,000 SY7-120MFT* 9,790
LR24-3-1/300 US LRX24-3 + # LR000 RC3 002 SY8-110 * 13,350
LR24-SR/200 US LRX24-SR + # LR030 RC3 002 SY8-120MFT* 13,350
LR24-SR/300 US LRX24-SR + # LR030 RC3 002 MAR1600-70 21,000 SY10-110* 22,250
LR24-SR-1 US LRB24-SR MAR1600-70P 21,000 SY10-120MFT* 22,250
LR24-SR-1/200 US LRX24-SR + # LR030 RC3 002 MAR4000-70 48,000 SY12-110* 31,150
LR24-SR-1/300 US LRX24-SR + # LR030 RC3 002 MAR4000-70P 48,000 SY12-120MFT* 31,150
LR24-SR-1-2.0 US LRB24-SR *New linkage required.
LR24-SR-1-2.0/200 US LRX24-SR + # LR030 RC3 002
LR24-SR-1-2.0/300 US LRX24-SR + # LR030 RC3 002 SPRING RETURN – 110 VAC NON-SPRING RETURN – 110 VAC
LR24-SR-2.0 US LRB24-SR REPLACEMENT Torque &
DISCONTINUED MODEL Torque
LR24-SR-2.0/200 US LRX24-SR + # LR030 RC3 002 MODEL Battery System
LR24-SR-2.0/300 US LRX24-SR + # LR030 RC3 002 Sure49-30-CW 600 SY2-110* 800 + NSV-SY-01
LR24-MFT/200 US LRX24-MFT + # LR100 RC3 ❑ ❑ ❑ Sure100-30-CW 1,200 SY3-110* 1,335 + NSV-SY-01
LR24-MFT/300 US LRX24-MFT + # LR100 RC3 ❑ ❑ ❑ Sure49-30P-CW 600 SY2-120MFT* 800 + NSV-SY-02
❑ Placeholder for custom options. Sure100-30P-CW 1,200 SY3-120MFT* 1,335 + NSV-SY-02
*New linkage required.
20-3
Retrofit and Replacement
Discontinued Belimo Products
ZONE VALVES*
DISCONTINUED MODEL Size Cv Rating Close-off REPLACEMENT MODEL(S) Size Cv Rating Close-off
ZONE215N-10+ZONE24NO 1 75
Z214T+SEF24 NO ½” 2.3 43.5 ½”
ZONE215N-25+ZONE24NO 2.5 50
Z215T+SEF24 NO ½” 3.7 30 ZONE215N-35+ZONE24NO ½” 3.5 30
ZONE220N-35+ZONE24NO 3.5
Z220T+SEF24 NO ¾” 3.7 30 ¾” 30
ZONE220N-50+ZONE24NO 5
ZONE215N-10+ZONE120NO 1
Z214T+SEF120 NO ½” 2.3 43.5 ½” 75
ZONE215N-25+ZONE120NO 2.5
Z215T+SEF120 NO ½” 3.7 30 ZONE215N-35+ZONE120NO ½” 3.5 30
ZONE220N-35+ZONE120NO 3.5 30
Z220T+SEF120 NO ¾” 3.7 30 ¾”
ZONE220N-50+ZONE120NO 5 25
ZONE215N-10+ZONE24NC 1 75
Z214T+SEF24 NC ½” 2.3 43.5 ½”
ZONE215N-25+ZONE24NC 2.5 50
Z215T+SEF24 NC ½” 3.7 30 ZONE215N-35+ZONE24NC ½” 3.5 30
ZONE220N-35+ZONE24NC 3.5 30
Z220T+SEF24 NC ¾” 3.7 30 ¾”
ZONE220N-50+ZONE24NC 5 25
ZONE215N-10+ZONE120NC 1 75
Z214T+SEF120 NC ½” 2.3 43.5 ½”
ZONE215N-25+ZONE120NC 2.5 50
Z215T+SEF120 NC ½” 3.7 30 ZONE215N-35+ZONE120NC ½” 3.5 30
ZONE220N-35+ZONE120NC 3.5 30
Z220T+SEF120 NC ¾” 3.7 30 ¾”
ZONE220N-50+ZONE120NC 5 25
ZONE215N-10+ZONE24NC 1 75
Z214T+SEF24 NC ½” 2.3 43.5 ½”
ZONE215N-25+ZONE24NC 2.5 50
Z215T+SEF24 NC ½” 3.7 30 ZONE215N-35+ZONE24NC ½” 3.5 30
ZONE220N-35+ZONE24NC 3.5 30
Z220T+SEF24 NC ¾” 3.7 30 ¾”
ZONE220N-50+ZONE24NC 5 25
ZONE215N-10+ZONE120NC 1 75
Z214T+SEF120 NC ½” 2.3 43.5 ½”
ZONE215N-25+ZONE120NC 2.5 50
Z215T+SEF120 NC ½” 3.7 30 ZONE215N-35+ZONE120NC ½” 3.5 30
ZONE220N-35+ZONE120NC 3.5 30
Z220T+SEF120 NC ¾” 3.7 30 ¾”
ZONE220N-50+ZONE120NC 5 25
ZONE315N-10+ZONE24NC 1 75
Z315T+SEF24 NC ½” 5 30 ZONE315N-25+ZONE24NC ½” 2.5 50
ZONE315N-35+ZONE24NC 3.5 30
ZONE315N-10+ZONE120NC 1 75
RETROFIT SOLUTIONS
20-4
Retrofit and Replacement
Fire and Smoke Actuators
Model Numbers
RETROFIT SOLUTIONS
ML4115J FSLF120 US Yes Yes On/Off 120 120 30 30 18 15
Use FSNF for dampers >4 sq.ft.
ML4202 FSLF120 US Yes Yes On/Off 120 120 20 30 25 15
All HW 50 in-lbs passed UL555S same
ML4302 FSLF120 US Yes Yes On/Off 120 120 20 30 25 15
damper sizes as FSLF.
ML4702 FSLF230 US Yes Yes On/Off 230 230 20 30 25 15
ML4802 FSLF230 US Yes Yes On/Off 230 230 20 30 25 15
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
ECM Some replacements are possible. Call Belimo. Digital photographs of damper may be needed.
FSNF or FSAF. See www.belimo.us/media/downloads/Technical_Documents/Fire_and_Smoke_Actuators/Ruskin_P150_to_FSNF_or_FSAF.pdf
Phillips T150
or http://www.belimo.us/firesmoke, Installation Instructions for Retrofit Applications.
Prefco 5800 EMB 2X and other models. If damper shaft is present, replacement is possible. Call Belimo.
Proportional Various models of HW and other proportional can be replaced. FSAF24-SR, FSAFB24-SR, and FSAF24-BAL are available. All have a -S model available.
Pneumatic AHJ permission, permit, and inspection may be required. Call Belimo.
20-5
Retrofit and Replacement
Fire and Smoke Actuators
Model Numbers
Model Numbers
is necessary. Note that old linkage, spring, and MP2659 FSLF Series No Yes On/Off No Data 30 No Data 15
motor can be removed and mounting Belimo to
the shaft is the accepted procedure.
Air Balance. FSLF < 3 sq.ft.; FSNF 3 to 8 sq.ft.
20-6
Retrofit and Replacement
Fire and Smoke Actuators
Model Numbers
Model Numbers
RETROFIT SOLUTIONS
FSLF Series No Yes On/Off 24/120 24/120 <4 sq.ft use FSLF MA250 replaces
MA250
FSNF Series No Yes On/Off 24/120 24/120 >4.sq.ft. use FSNF MA220 and MA230
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
20-7
Select
Pro ™
Honeywell Ruskin
Invensys Siebe
Johnson Controls Multi Products
Siemens
RETROFIT SOLUTIONS
• Updated User Interface – Toggle screen, vertical scrolling, and the ability to clear
valve and actuator selection sections separately
• Manual Selection – Enter model numbers and skip the selection process
UGSL1200 Short-Stroke Valve Retrofit Kit
For CM and TF Series Actuators
Application
The UGSL1200 retrofit kit is designed to easily attach to the valve bonnet on
select Siemens 599 MT/MZ short-stroke valves utilizing Belimo CM and TF*
series actuators.
The unique coupler design allows the UGSL1200 to be mounted on any ½” to
1¼” two-way or three-way valves. In addition, the linkage is suitable for both
normally open and normally closed valves.
Default/Configuration
The default set up for this linkage is for usage with the CM actuator. Included in
the kit is an extension piece for TF actuators. Hardware is supplied to attach the
shaft extension and anti-rotation screws to both a CM or TF actuator.
Operation
The UGSL1200 linkage provides 6 mm of downward stroke with 95° CW rotation
on the actuator. This allows the valve to extend fully open or closed based on
signal. The slot located on the housing provides indication when the maximum
stroke has been reached. For troubleshooting when using a CM actuator, the
operator may use the manual override feature to rotate the linkage up or down.
When using the TF, refer to electronic override instructions according to actuator
List Price: $120 model.
Technical Data UGSL1200 Note: Linkage cannot be used on 1½” normally closed valves.
Housing aluminum
Materials: *TFL actuators required for on/off applications.
Coupling nut brass
Shafts stainless steel TF Dimensions (Inches [mm])
Base plate aluminum
D315
Upper plate stainless steel
Cams nylon 6/6 with MDS
Stroke 6 mm in CW direction
Max out force 67 lbf [300 N]
Mounting position 360° mountable as shown
Ambient temperature -22°F to +122°F [-30°C to +50°C]
RETROFIT SOLUTIONS
Storage temperature -40°F to +176°F [-40°C to +80°C]
Servicing chilled or hot water
max steam inlet 15 psi
Weight 1.25 lbs [0.57 kg]
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Mounting Configurations
D316
2.4” [60.3]
TF Actuator*
2.8” [72]
3.7” [95.2]
1.5” [37.9]
2.4” [60.3]
CM Actuator
20-9
Tips for Choosing a Globe Valve Retrofit Solution
B C D
H1
H2
H2
MAXIMUM DIMENSIONS – GVL Linkages with New Generation Linear Series Actuators
16.73”
[425] 16.73”
[425]
14” 14”
[356] [356]
5” [127] 5” [127]
20-10
Tips for Choosing a Globe Valve Retrofit Solution
MAXIMUM DIMENSIONS – GVL Linkages with New Generation Linear Series Actuators
UGVL with LV, SV Dimensions (Inches [mm]) UGVL with LVK, SVK Dimensions (Inches [mm])
4.4” [113] 4.4” [113]
12.1” [307]
11.4” [290]
8.5” [217]
7.9” [200]
8.4” [207]
7.5” [190]
SGVL with LV, SV Dimensions (Inches [mm]) SGVL with LVK, SVK Dimensions (Inches [mm])
RETROFIT SOLUTIONS
5.9” [150]
6.7” [169]
6.6” [167]
6” [152]
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
WGVL with EV, RV Dimensions (Inches [mm]) WGVL with AVK Dimensions (Inches [mm])
9.2” [233] 10.3” [262]
2.1” [53] 5.5” [140] 2.1” [53] 5.5” [140]
10.9” [276]
10.9” [276]
10.4” [264]
10.2” [259]
20-11
How to Select the Globe Valve Retrofit Solution
1 Based on the Valve Number, Configuration and Size, select the proper linkage or linkages for your valve.
Some valves will have more than one linkage offered, use the actuator or combination pages to determine the appropriate linkage
for a given application. In this example there is a UGLK1214, UGLK1350 and a UGVL series linkage available.
2 Use the selection guide and your close-off pressure requirement to select the correct actuator series for your application.
Looking at the UGLK1350 there are no fail-safe actuators that will achieve 200 psi close-off for 1¼" valve. Looking at the
UGLK1214 or UGVL, the AF or SVK Series actuator will provide over 200 psi close-off for the 1¼” valve.
needed control type. AFB24-SR 2-10 VDC (4-20mA) 2-10 VDC 24 VAC/DC 95 seconds <20 secs 8.5 -
AFB24-SR-S
SR S 2 10 VDC (4
2-10 (4-20mA)
20mA) 2 10 VDC
2-10 24 VAC/DC
VAC/DC 95 seconds
seconds <20 secs
secs 85
8.5 Built-In
Built In
Decide between AFB24, AFB24-PC
AFB24 PC 0 10 V Pha
0-10 Ph secutt 2 10 VDC
2-10 24 VAC/DC
VAC/DC 150 second
secondss <20 secs
secs 10 -
3 AFB24-MFT AFB24-MFT
MFT 2-10 VDC (4-20m
(4-20mA)
A) 22-10
10 VDC 24 VAC/DC
VAC/DC 150 second
secondss <200 secs
secs 10 -
AFB24-MFT-S
MFT S 2-10 VDC (4-20m
(4-20mA)
A) 2-10 VDC 24 VAC/DC
VAC/DC 150 second
secondss <20 secs
secs 10 B ilt-In
Built I
In
AFB24-MFT95
MFT95 0 to 135 2-10 VDC 24 VAC/DC
VAC/DC 150 second
secondss <20 secs
secs 10 -
or SVKX24-3,
SVKX24-MFT.
Complete Ordering Example ACTUATOR PART # LVKX24-3 LVKB24-SR LVKX24-MFT SVKX24-3 SVKB24-SR SVKX24-MFT
SGVL S h ieder
Schni d VBVB7..., VB9
VB7 VB9... $ $ $ $ $ $
SVKX24-MFT
20-12
Globe Valve Retrofit Actuators for UGLK Series
Actuator Suggestion Guide
Consult Specifications
(VDC, PWM, Floating Pt., On/Off)
LMB24-3-X1 Floating Point, On/Off - 24 VAC/DC $180
LM Series* Variable with MFT
LMX24-MFT-X1 variable VDC 24 VAC/DC $368
(VDC, PWM, Floating Point, On/Off)
NMB24-3-X1 Floating Point, On/Off - 24 VAC/DC $243
NM Series* Variable with MFT
NMX24-MFT-X1 variable VDC 24 VAC/DC $427
(VDC, PWM, Floating Point, On/Off)
AMB24-3-X1 Floating Point, On/Off - 24 VAC/DC $342
AM Series* Variable with MFT
AMX24-MFT-X1 variable VDC 24 VAC/DC $532
(VDC, PWM, Floating Point, On/Off)
GMB24-3-X1 • Floating Point, On/Off - 24 VAC/DC $526
GM Series* Variable with MFT
GMX24-MFT-X1 • variable VDC 24 VAC/DC $751
(VDC, PWM, Floating Point, On/Off)
GKB24-3-X1 • Floating Point, On/Off - 24 VAC $1,167
GK Series* Variable with MFT
GKX24-MFT-X1 • • variable VDC 24 VAC/DC $1,593
(VDC, PWM, Floating Point, On/Off)
*Please consult the Damper sections for a full list of product offerings. Standard run times should be considered in the selection. All air side products are applicable for retrofit kits.
Select “X1” actuators come with a handle.
MULTI-FUNCTION TECHNOLOGY
PROGRAMMING CODE Control Input Running Time Built-in Feedback List Price
P-10001 A01 2-10 VDC 150 seconds 2-10 VDC No Charge
P-10002 A02 0.5-10 VDC 150 seconds 0.5-10 VDC No Charge
ROTARY ACTUATOR
RETROFIT SOLUTIONS
P-10028 A28 0.5-10 VDC 150 seconds 0.5-10 VDC No Charge
P-10063 A63 0.5-4.5 VDC 150 seconds 0.5-4.5 VDC No Charge
P-10064 A64 5.5-10 VDC 150 seconds 5.5-10 VDC No Charge
P-20002 W02 0.02-5.00 seconds PWM 150 seconds 2-10 VDC No Charge
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
P-20003 W03 0.10-25.5 seconds PWM 150 seconds 2-10 VDC No Charge
P-30001 F01 Floating Point 150 seconds 2-10 VDC No Charge
P-40002 J02 On/Off 150 seconds 2-10 VDC No Charge
G01 On/Off 35 seconds 2-10 VDC MFT only No Charge
G02 On/Off 60 seconds 2-10 VDC MFT only No Charge
G03 On/Off 90 seconds 2-10 VDC MFT only No Charge
G04 On/Off 150 seconds 2-10 VDC MFT only No Charge
G11 Floating Point 35 seconds 2-10 VDC MFT only No Charge
G12 Floating Point 60 seconds 2-10 VDC MFT only No Charge
G13 Floating Point 90 seconds 2-10 VDC MFT only No Charge
G14 Floating Point 150 seconds 2-10 VDC MFT only No Charge
G41(G21 for -SR) 2-10 VDC 35 seconds 2-10 VDC No Charge
LINEAR ACTUATOR
G42 (G22 for -SR) 2-10 VDC 60 seconds 2-10 VDC No Charge
G43 (G23 for -SR) 2-10 VDC 90 seconds 2-10 VDC No Charge
G44 (G24 for -SR) 2-10 VDC 150 seconds 2-10 VDC No Charge
G51 0.5-10 VDC 35 seconds 0.5-10 VDC No Charge
G52 0.5-10 VDC 60 seconds 0.5-10 VDC No Charge
G53 0.5-10 VDC 90 seconds 0.5-10 VDC No Charge
G54 0.5-10 VDC 150 seconds 0.5-10 VDC No Charge
G2A 5.5-10 VDC 150 seconds 5.5-10 VDC No Charge
G2B 0.5-4.5 VDC 150 seconds 0.5-4.5 VDC No Charge
G2C 2-10 VDC 150 seconds 0.5-5 VDC No Charge
G2D 6-9 VDC 150 seconds 2-10 VDC No Charge
G2E 10.5-13.5 VDC 150 seconds 2-10 VDC No Charge
W3M 0.02-5.00 seconds PWM 90 seconds 2-10 VDC No Charge
W3P 0.2-5.00 seconds PWM 90 seconds 2-10 VDC No Charge
20-13
UGVL, SGVL, FGVL, WGVL Series Linkages with Non-Spring Return Actuators
Retrofit Linkages for NPT and Flanged Globe Valves
Actuator/Linkage Specifications
Force (valve size)
LV 112 lbf [500N] (½” to ¾”)
SV 337 lbf [1500N] (1” to 2”)
EV 562 lbf [2500N] (2½” to 4”)
RV 1011 lbf [4500N] (4” to 6”)
Linkage material aluminum and steel
Fits valve bonnet up to 1.7” [43.18 mm] UGVL
diameter up to 2.7” [68.5 mm] FGVL
Position indication adjustable inserts on linkage
Manual override external push button
LV, SV 4 mm hex (wrench supplied)
EV, RV 5 mm hex (wrench supplied)
Direction of rotation external switch
Dimensions
UGVL 7.5” to 11.4” x 7.8” x 4.5” All actuators
SGVL 6” x 7.8” x 3.8” have BDCM
ACTUATOR PART # LVB24-3 LVX120-3 LVB24-SR LVX24-MFT SVX24-3 SVX120-3 SVB24-SR SVX24-MFT
On/Off, On/Off, Proportional/ On/Off, On/Off, Proportional/
Control type Proportional Proportional
Floating Point Floating Point MFT Floating Point Floating Point MFT
Input signal / feedback - - 2-10 VDC* Variable - - 2-10 VDC* Variable
RETROFIT SOLUTIONS
Running time 90 seconds 90 seconds 90 seconds Variable 90 seconds 90 seconds 90 seconds Variable
Actuator travel 15 mm 15 mm 15 mm 15 mm 20 mm*** 20 mm 20 mm 20 mm
Actuator noise level 55 dB(A) 55 dB(A) 55 dB(A) 55 dB(A) 45 dB(A) 45 dB(A) 45 dB(A) 45 dB(A)
GVL LINKAGES
FGVL WGVL
20-14
UGVL, SGVL, FGVL, WGVL Series Linkages with Electronic Fail-Safe Actuators
Retrofit Linkages for NPT and Flanged Globe Valves
Actuator/Linkage Specifications
Force (valve size)
LVK 112 lbf [500N] (½” to ¾”)
SVK 337 lbf [1500N] (1” to 2”)
AVK 450 lbf [2000N] (2½” to 4”)
Linkage material aluminum and steel
Fits valve bonnet up to 1.7” [43.18 mm] UGVL
diameter up to 2.7” [68.5 mm] FGVL
Position indication adjustable inserts on linkage
Manual override external push button
LV, SV 4 mm hex (wrench supplied)
AVK 5 mm hex (wrench supplied)
Fail postion field selectable
Direction of rotation external switch
Dimensions
UGVL 8” to 12” x 9.5” x 4.5” All actuators
have BDCM
SGVL 6.5” x 9.5” x 4.5”
FGVL 14” x 9.2” x 5.5”
WGVL 10” x 9.2” x 5.5”
Electrical connection 3 ft., 18 GA plenum rated
cable, ½” conduit fitting
120V appliance cable
Overload protection electronic throughout stroke
Auxiliary switch(es) add on: 2 SPDT, 3A @ 250V
Housing NEMA 2/IP54, UL Enclosure
Type 2
Agency listings cULus according to UL
60730-1A/-2-14, CAN/CSA
E60730-1:02, CE according
to 2004/108/EC and
UGVL SGVL
2006/95/EC
ACTUATOR PART # LVKX24-3 LVKX120-3 LVKB24-SR LVKB24-MFT SVKX24-3 SVKX120-3 SVKB24-SR SVKB24-MFT
On/Off, On/Off, Proportional/ On/Off, On/Off, Proportional/
Control type Proportional Proportional
Floating Point Floating Point MFT Floating Point Floating Point MFT
Input signal / feedback - - 2-10 VDC* 2-10 VDC* - - 2-10 VDC* 2-10 VDC*
RETROFIT SOLUTIONS
Running time Motor 90 seconds 90 seconds 90 seconds 90 seconds 90 seconds 90 seconds 90 seconds 90 seconds
Fail-Safe 35 seconds 35 seconds 35 seconds 35 seconds 35 seconds 35 seconds 35 seconds 35 seconds
Actuator travel 15 mm 15 mm 15 mm 15 mm 20 mm*** 20 mm 20 mm 20 mm
Actuator noise level 55 dB(A) 55 dB(A) 55 dB(A) 55 dB(A) 45 dB(A) 45 dB(A) 45 dB(A) 45 dB(A)
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
GVL LINKAGES
UGVL Universal adjustable for ½” to 2” $893 $929 $945 $1,022** $1,003 $1,040 $1,056 $1,130**
Schneider VB7000 (½” to 2”),
SGVL $788 $824 $841 $942** $867 $902 $926 $995**
VB9000 (½” to 1¼”)
Variable with MFT.
* 4-20 mA with 500 Ω resistor ZG-R01
**Prices do not reflect additional programming codes surcharge. See page 20-13 for linear actuator MFT codes.
*** Longer stroke available. Verify valve travel requirements. Contact Belimo Technical Support for details.
FGVL WGVL
20-15
UGLK Retrofit Solution
Components
Back Plate
Drive Shaft
Rack
Box Frame
Set Screw Style 5
Style 3
Stem Adapter
Retaining Ring
Jam Nut
Base Bracket
Set Screw
Collar
20-16
Honeywell
V5011, V5013 Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
236
Yes SVK UGVL Pg # 20-15
Yes 26 LF UGLK1806 $600
Yes 153 AF UGLK1800 $600
1½”
No SV UGVL Pg # 20-14
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
160
Yes SVK UGVL Pg # 20-15
Yes 14 LF UGLK1806 $600
No SV UGVL Pg # 20-14
85
2” Yes SVK UGVL Pg # 20-15
Yes 86 AF UGLK1800 $600
Yes 173 GK UGLK1800 $600
Yes LVK UGVL Pg # 20-15
½” 236
No LV UGVL Pg # 20-14
Yes LVK UGVL Pg # 20-15
¾” 211
No LV UGVL Pg # 20-14
Yes LVK UGVL Pg # 20-15
93
No LV UGVL Pg # 20-14
1”
No SV UGVL Pg # 20-14
236
Yes SVK UGVL Pg # 20-15
No SV UGVL Pg # 20-14
V5013 Series 1¼” 236
Yes SVK UGVL Pg # 20-15
No SV UGVL Pg # 20-14
1½” 160
Yes SVK UGVL Pg # 20-15
No SV UGVL Pg # 20-14
2” 85
Yes SVK UGVL Pg # 20-15
No SV UGVL Pg # 20-14
2½” 52
Yes SVK UGVL Pg # 20-15
No SV UGVL Pg # 20-14
3” 40
Yes SVK UGVL Pg # 20-15
Yes LVK UGVL Pg # 20-15
½” Yes 236 LF UGLK1806 $600
V5013N Series No LV UGVL Pg # 20-14
Yes 110 LF UGLK1806 $600
¾”
Yes 211 LVK UGVL Pg # 20-15
All close-off pressures listed are approximate and based on valve condition and application.
20-17
Honeywell
V5011, V5013, V5045 Series Valves
Linkage/Actuator Selection Guide
½” 236
(1014, 1022, 1030, 1048, 1121, 1139) Yes NF UGLK1800 $600
Yes 110 LF UGLK1806 $600
V5011F (1055, 1147) ¾”
Yes 236 NF UGLK1800 $600
Yes 40 LF UGLK1806 $600
All close-off pressures listed are approximate and based on valve condition and application.
20-18
Honeywell
V5045, V3350, V3351, V3360 Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
40
No RV FGVL Pg # 20-14
No SV UGVL Pg # 20-14
55
Yes SVK UGVL Pg # 20-15
V3351 (A2008, C2005, D2002) 2½”
Yes 110 2*AF UGLK1870 $762
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
All close-off pressures listed are approximate and based on valve condition and application.
20-19
Honeywell
V3360, V3450, V3451, V3460 Series Valves
Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-20
Honeywell
V3460, V5011, V5013, VP52... Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
Yes 10 AF UGLK1802 $600
Yes 2*AF UGLK1872 $757
14
V5011 (A1882, B1047) 5” Yes GK UGLK1802 $600
Yes 2*GK UGLK1872 $757
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
22
No RV FGVL Pg # 20-14
Yes 2*AF UGLK1872 $757
10
Yes GK UGLK1802 $600
V5011 (A1916, B1078) 6”
Yes 2*GK UGLK1872 $757
22
No RV FGVL Pg # 20-14
Yes 52 AF UGLK1800 $600
V5013 (B1003, C1001) 2½”
Yes 211 2*GK UGLK1870 $762
Yes 77 GK UGLK1800 $600
V5013 (B1011, C1019) 3”
Yes 136 2*GK UGLK1870 $762
Yes AVK FGVL Pg # 20-15
No 22 EV FGVL Pg # 20-14
V5013 (B1029, C1027) 4” Yes GK UGLK1802 $600
Yes 2*GK UGLK1872 $757
40
No RV FGVL Pg # 20-14
Yes 10 AF UGLK1802 $600
Yes 2*AF UGLK1872 $757
No 14 EV FGVL Pg # 20-14
V5013 (B1037, C1035) 5”
Yes GK UGLK1802 $600
Yes 2*GK UGLK1872 $757
22
No RV FGVL Pg # 20-14
Yes 2*AF UGLK1872 $757
10
Yes GK UGLK1802 $600
V5013 (B1045, C1043) 6”
Yes 2*GK UGLK1872 $757
22
No RV FGVL Pg # 20-14
No CM UGLK1808 $434
½” 110
Yes TF UGLK1808 $434
VP525 Series
No CM UGLK1808 $434
¾” 55
Yes TF UGLK1808 $434
VP526 Series ½” No 50 CM UGLK1808 $434
All close-off pressures listed are approximate and based on valve condition and application.
20-21
Honeywell Johnson Controls
VP52..., VP531, VGF Series Valves V52... Series Valves
Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide
JOHNSON CONTROLS
Yes 2*AF UGLK1476 $764
Yes 52 AVK FGVL Pg # 20-15
No EV FGVL Pg # 20-14
All close-off pressures listed are approximate and based on valve condition and application.
20-22
Johnson Controls
V-52..., V-54... Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
Yes 2*GK UGLK1480 $769
22
No RV FGVL Pg # 20-14
Yes 2*AF UGLK1480 $769
No 10 EV FGVL Pg # 20-14
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
All close-off pressures listed are approximate and based on valve condition and application.
20-23
Johnson Controls
V-54...,V-58... Series Valves
Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-24
Johnson Controls
V-58...,VB-37..., VB-39..., VB-43... Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
Yes 2*GK UGLK1476 $764
93
No RV FGVL Pg # 20-14
Yes 14 AF UGLK1410 $553
Yes 2*GK UGLK1476 $764
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
52
No RV FGVL Pg # 20-14
VB-3970-17 4”
Yes 2*AF UGLK1476 $764
Yes 26 AVK FGVL Pg # 20-15
No EV FGVL Pg # 20-14
Yes 10 AF UGLK1414 $557
Yes 2*AF UGLK1480 $769
No 14 EV FGVL Pg # 20-14
VB-3970-20 5”
Yes GK UGLK1414 $557
Yes 2*GK UGLK1480 $769
22
No RV FGVL Pg # 20-14
Yes 2*AF UGLK1480 $769
No 10 EV FGVL Pg # 20-14
VB-3970-23 6” Yes GK UGLK1414 $557
Yes 2*GK UGLK1480 $769
22
No RV FGVL Pg # 20-14
Yes 2*AF UGLK1476 $764
Yes 52 AVK FGVL Pg # 20-15
No EV FGVL Pg # 20-14
VB-4322-11 3”
Yes 26 AF UGLK1410 $553
Yes 2*GK UGLK1476 $764
93
No RV FGVL Pg # 20-14
Yes 14 AF UGLK1410 $553
Yes 2*GK UGLK1476 $764
52
No RV FGVL Pg # 20-14
VB-4322-13 4”
Yes 2*AF UGLK1476 $764
Yes 26 AVK FGVL Pg # 20-15
No EV FGVL Pg # 20-14
All close-off pressures listed are approximate and based on valve condition and application.
20-25
Johnson Controls
VB-43..., VG22..., VG24..., VG28… Series Valves
Linkage/Actuator Selection Guide
No 93 RV FGVL Pg # 20-14
No 52 RV FGVL Pg # 20-14
VG2831 VM 4” Yes AVK FGVL Pg # 20-15
26
No EV FGVL Pg # 20-14
All close-off pressures listed are approximate and based on valve condition and application.
20-26
Johnson Controls
VG24, VG22, VG28, V52, V54 Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
26
Yes AVK FGVL Pg # 20-15
No 26 EV FGVL Pg # 20-14
Yes 14 AF UGLK1412 $553
Yes 2*GK UGLK1478 $764
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
52
No RV FGVL Pg # 20-14
V-5252-(15, 16, 37) 4”
Yes 2*AF UGLK1478 $764
Yes 26 AVK FGVL Pg # 20-15
No EV FGVL Pg # 20-14
Yes AF UGLK1404 $553
52
No EV FGVL Pg # 20-14
V-5252-(2, 4, 5, 6, 7, 8, 32, 33) 2½”
Yes AVK FGVL Pg # 20-15
110
No RV FGVL Pg # 20-14
Yes 110 2*AF UGLK1472 $769
V-5252-(4, 5, 6, 7, 8, 32, 33) 2½”
Yes 211 2*GK UGLK1472 $769
Yes AVK FGVL Pg # 20-15
52
No EV FGVL Pg # 20-14
Yes 77 2*AF UGLK1472 $769
V-5252-(9, 10, 11, 34) 3”
Yes 38 AF UGLK1404 $553
Yes 136 2*GK UGLK1472 $769
No 93 RV FGVL Pg # 20-14
Yes 38 AF UGLK1412 $553
Yes 2*GK UGLK1478 $764
136
No RV FGVL Pg # 20-14
V-5410-4595 2½”
Yes 2*AF UGLK1478 $764
Yes 75 AVK FGVL Pg # 20-15
No RV FGVL Pg # 20-14
Yes 2*AF UGLK1478 $764
Yes 52 AVK FGVL Pg # 20-15
No EV FGVL Pg # 20-14
V-5410-4596 3”
Yes 26 AF UGLK1412 $553
Yes 93 2*GK UGLK1478 $764
No RV FGVL Pg # 20-14
All close-off pressures listed are approximate and based on valve condition and application.
20-27
Johnson Controls
V-54, V-58 Series Valves
Linkage/Actuator Selection Guide
V-5462-36 3”
No EV FGVL Pg # 20-14
Yes 26 AF UGLK1412 $553
Yes 2*GK UGLK1478 $764
V-5462-36 3” 93
No RV FGVL Pg # 20-14
All close-off pressures listed are approximate and based on valve condition and application.
20-28
Johnson Controls
V-58, VB-39, VB-43, VG22, VG24, VG28 Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
VB-3970-11 2½”
Yes 110 AVK FGVL Pg # 20-15
No RV FGVL Pg # 20-14
Yes 211 2*GK UGLK1472 $769
Yes AF UGLK1404 $553
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
52
VB-4322-9 2½” No EV FGVL Pg # 20-14
Yes 110 2*AF UGLK1472 $769
Yes AVK FGVL Pg # 20-15
110
VB-4322-9 2½” No RV FGVL Pg # 20-14
Yes 211 2*GK UGLK1472 $769
Yes AVK FGVL Pg # 20-15
110
VG2231 TM 2½” No EV FGVL Pg # 20-14
No 211 RV FGVL Pg # 20-14
Yes AVK FGVL Pg # 20-15
52
VG2231 UN 3” No EV FGVL Pg # 20-14
No 93 RV FGVL Pg # 20-14
No 52 RV FGVL Pg # 20-14
VG2231 VN 4” Yes AVK FGVL Pg # 20-15
26
No EV FGVL Pg # 20-14
Yes AVK FGVL Pg # 20-15
110
VG2431 TM 2½” No EV FGVL Pg # 20-14
No 211 RV FGVL Pg # 20-14
Yes AVK FGVL Pg # 20-15
52
VG2431 UN 3” No EV FGVL Pg # 20-14
No 93 RV FGVL Pg # 20-14
No 52 RV FGVL Pg # 20-14
VG2431 VN 4” Yes AVK FGVL Pg # 20-15
26
No EV FGVL Pg # 20-14
Yes AVK FGVL Pg # 20-15
110
VG2831 TM 2½” No EV FGVL Pg # 20-14
No 211 RV FGVL Pg # 20-14
Yes AVK FGVL Pg # 20-15
52
VG2831 UN 3” No EV FGVL Pg # 20-14
No 93 RV FGVL Pg # 20-14
All close-off pressures listed are approximate and based on valve condition and application.
20-29
Johnson Controls
VG28, VG24, VG22, VB-37, VB-39, VB-43 Series Valves
Linkage/Actuator Selection Guide
93
No LV UGVL Pg # 20-14
1”
No SV UGVL Pg # 20-14
236
Yes SVK UGVL Pg # 20-15
V(B)-3754 Series, Bronze Trim
No SV UGVL Pg # 20-14
All close-off pressures listed are approximate and based on valve condition and application.
20-30
Johnson Controls
VB-58.., V-43, VG70, V-37, V-38, V-39 Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
1¼” 236
Yes SVK UGVL Pg # 20-15
No SV UGVL Pg # 20-14
1½” 160
Yes SVK UGVL Pg # 20-15
No SV UGVL Pg # 20-14
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
2” 85
Yes SVK UGVL Pg # 20-15
V-3754-(4, 1008, 1022, 1026) ¾” Yes 211 LF UGLK1550 $384
Yes 236 AF UGLK1402 $553
V-3754-(5, 1010, 1023, 1027) 1”
Yes 173 NF UGLK1402 $553
Yes 77 NF UGLK1402 $553
Yes 153 AF UGLK1402 $553
V-3754-(6, 1028, 1029, 1030) 1½”
Yes 211 2*AF UGLK1478 $764
Yes 236 GK UGLK1402 $553
Yes 40 NF UGLK1406 $553
Yes 2*GK UGLK1474 $764
236
No 2*GM UGLK1474 $764
V-3754-7 2” Yes 86 AF UGLK1406 $553
Yes 2*AF UGLK1474 $764
Yes 173 GK UGLK1406 $553
No GM UGLK1406 $553
Yes 110 NF UGLK1402 $553
V-3754-8 1¼”
Yes 221 AF UGLK1402 $553
Yes LF UGLK1552 $384
V-3766 ½” 236
No LM UGLK1552 $384
Yes LF UGLK1554 $384
V-3854-5 ½” 236
No LM UGLK1554 $384
Yes LF UGLK1552 $384
V-3966 ½” 236
No LM UGLK1552 $384
V-3974-(4, 1004, 1010) ¾” Yes 211 LF UGLK1550 $384
Yes 236 AF UGLK1402 $553
V-3974-(5, 1005, 1011) 1”
Yes 173 NF UGLK1402 $553
All close-off pressures listed are approximate and based on valve condition and application.
20-31
Johnson Controls
V-39, V-43, V-52, V-54, V-58 Series Valves
Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-32
Johnson Controls Robertshaw Siebe\Invensys\Barber Colman
V-58, VG-7..., VTM Series Valves V6700, V6800, V6600 Series Valves VB7000 Series Valves
Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
1½” 160
No SV UGVL Pg # 20-14
No SV UGVL Pg # 20-14
2” 85
Yes SVK UGVL Pg # 20-15
Yes LVK UGVL Pg # 20-15
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
All close-off pressures listed are approximate and based on valve condition and application.
20-33
Siebe\Invensys\Barber Colman
VB304X, VB7..., VB8... Series Valves
Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-34
Siebe\Invensys\Barber Colman
VB7..., VB9... VB30... Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
Yes AF UGLK1004 $548
221
No AM UGLK1004 $548
VB9XXX-0-4-(7, 8) 1” Yes 236 AF UGLK1000 $552
VB9XXX-0-4-1 ½” Yes 236 LF UGLK1150 $368
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
All close-off pressures listed are approximate and based on valve condition and application.
20-35
Siebe\Invensys\Barber Colman
VB9.., VB30, VB80... Series Valves
Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-36
Siebe\Invensys\Barber Colman
VB8.., VB9... Belimo USA G2, Belimo USA G3 Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
40
No EV FGVL Pg # 20-14
Yes 52 2*AF UGLK1070 $762
VB9XXX-0-5-13 3”
Yes 26 AF UGLK1010 $548
Yes 93 2*GK UGLK1070 $762
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
No 90 RV FGVL Pg # 20-14
Yes 10 AF UGLK1012 $548
Yes 22 2*AF UGLK1074 $757
No 30 RV FGVL Pg # 20-14
VB9XXX-0-5-14 4” Yes 2*GK UGLK1074 $757
40
No 2*GM UGLK1074 $757
No 15 EV FGVL Pg # 20-14
Yes 25 AVK FGVL Pg # 20-15
No 20 RV FGVL Pg # 20-14
5”
Yes 15 AVK FGVL Pg # 20-15
VB9XXX-0-5-15
No 20 RV FGVL Pg # 20-14
5”
Yes 15 AVK FGVL Pg # 20-15
VB9XXX-0-5-16 6” No 15 RV FGVL Pg # 20-14
1” Yes 250 AF UGLK1000 $552
1¼” Yes 250 AF UGLK1000 $552
Belimo USA G2 Series
1½” Yes 217 AF UGLK1000 $552
2” Yes 122 AF UGLK1000 $552
1” Yes 250 AF UGLK1000 $552
1¼” Yes 250 AF UGLK1000 $552
Belimo USA G3 Series
1½” Yes 217 AF UGLK1000 $552
2” Yes 122 AF UGLK1000 $552
½” Yes 250 LF UGLK1150 $368
¾” Yes 215 LF UGLK1150 $368
Belimo USA G2 Series
1” Yes 95 LF UGLK1150 $368
1¼” Yes 61 LF UGLK1150 $368
½” Yes 250 LF UGLK1150 $368
¾” Yes 215 LF UGLK1150 $368
Belimo USA G3 Series
1” Yes 95 LF UGLK1150 $368
1¼” Yes 61 LF UGLK1150 $368
All close-off pressures listed are approximate and based on valve condition and application.
20-37
Siebe\Invensys\Barber Colman Siemens\Landis\Powers
Belimo USA G2, G3 Series Valves 591 Series Valves
Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide
1½” 160
Yes SVK SGVL Pg # 20-15
Yes 85 SVK SGVL Pg # 20-15
2”
No 90 SV SGVL Pg # 20-14
SIEMENS \ LANDIS \ POWERS
All close-off pressures listed are approximate and based on valve condition and application.
20-38
Siemens\Landis\Powers
591, 599 Flowrite Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
No AM UGLK1200 $553
236
1¼” No SV UGVL Pg # 20-14
Yes SVK UGVL Pg # 20-15
Yes 160 NF UGLK1200 $553
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
All close-off pressures listed are approximate and based on valve condition and application.
20-39
Siemens\Landis\Powers
599 Flowrite, 656, 658, 599 Series Valves
Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-40
Siemens\Landis\Powers
599 Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
599-01129 MZ (Cv <6.3) ¾” Yes 26 TF UGSL1200 $120
599-01131 MZ (Cv <10) 1” Yes 26 TF UGSL1200 $120
599-01132 MZ (Cv <.4) ½” Yes 70 TF UGSL1200 $120
599-01133 MZ (Cv <.63) ½” Yes 70 TF UGSL1200 $120
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
All close-off pressures listed are approximate and based on valve condition and application.
20-41
Siemens\Landis\Powers Warren Controls
599 Series Valves 100, 1800 Series Valves
Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide
70
No 2*GM UGLK2272 $757
Yes AVK WGVL Pg # 20-15
22
No EV WGVL Pg # 20-14
4”
Yes 2*GK UGLK2272 $757
All close-off pressures listed are approximate and based on valve condition and application.
20-42
Warren Controls
1800, Type 20-22, Type 23, Type 30, Type 32 Series Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
3” 160
No EV WGVL Pg # 20-14
Type 23
Yes AVK WGVL Pg # 20-15
4”
No EV WGVL Pg # 20-14
236
Yes AVK WGVL Pg # 20-15
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
5”
No EV WGVL Pg # 20-14
Yes 71 AVK WGVL Pg # 20-15
2½” No 93 EV WGVL Pg # 20-14
No 185 RV WGVL Pg # 20-14
Yes 40 AVK WGVL Pg # 20-15
3” No 65 EV WGVL Pg # 20-14
Type 30
No 126 RV WGVL Pg # 20-14
4” No 65 RV WGVL Pg # 20-14
5” No 40 RV WGVL Pg # 20-14
Yes 10 2*AF UGLK2272 $757
6”
Yes 22 2*GK UGLK2272 $757
Yes 71 AVK WGVL Pg # 20-15
2½” No 93 EV WGVL Pg # 20-14
No 185 RV WGVL Pg # 20-14
Yes 40 AVK WGVL Pg # 20-15
3” No 65 EV WGVL Pg # 20-14
Type 32
No 126 RV WGVL Pg # 20-14
4” No 65 RV WGVL Pg # 20-14
5” No 40 RV WGVL Pg # 20-14
Yes 10 2*AF UGLK2272 $757
6”
Yes 22 2*GK UGLK2272 $757
All close-off pressures listed are approximate and based on valve condition and application.
20-43
Custom Globe Valve Solutions
UGSP Series Globe Valve Retrofit Solution
Globe valves which cannot be matched to one of the Belimo UGLK part numbers, for quotation and order entry purposes, please use p/n
UGSP0000 for valves requiring single actuation, and UGSP0002 for valves requiring dual actuation. These part numbers have no Bill of
Materials (BOM) associated with them, and therefore cannot be produced and shipped. When these two part numbers are quoted, sold
and orders processed, the “Globe Valve Retrofit” form must be completed and will accompany the order. Our engineering department will
then determine the correct UGSP linkage number for production. Please keep in mind that UGSP0000 and UGSP0002 will NOT show up
on final paperwork and will be replaced with the correct UGSP part number once such has been determined.
UGSP0000 The single actuated globe retrofit linkage (shown left) depicts
the MINIMUM and MAXIMUM dimensional data for use in
B C D determining the space required to mount the linkage. These
dimensions do NOT include VALVE dimensions which will affect
combined height requirements.
Dims H1 & H2 are used only when override handles are utilized
H1
on the linkage system, and are not required for proper operation
of the linkage system.
A
Dim A 7.5” [190] to 14” [356] Dim H1 9.5” [242]
H2
Dim B 3” [76] Dim H2 9.5” [242]
Dim C 9” [229]
Dim D 5” [127]
Custom kits are designed to your unique specification and are not returnable.
20-44
Custom Globe Valve Retrofit Solution Form
UGSP Series
Dimensions D1, D2 & D3 are used to determine the height of the linkage assembly required to clear the valves’ full stroke. A minimum of two
dimensions are required to manufacture the correct linkage system for your valve. These dimensions also provide the information necessary to
determine valve stroke. The maximum stroke from Belimo globe valve retrofit systems is 1.500”.
Dimension E refers to the valve bonnet diameter (regardless if threads are present or not). Over time, impurities will react to the bonnet threads and
corrode them to the point where they no longer meet the original thread specification. Because of this, we manufacture slip fit collars designed to
slide over the bonnet threads, and locking setscrews are provided which “bite” into the original threads. All retrofit systems are designed to work
with the raw valve body and do not account for previous actuation components which must be removed from the valve body before attaching the new
linkage system.
Dimension F refers to the thread specification on threaded bonnets, and refers to the minor diameter on slip on bonnets (Landis type). This
information helps us determine the length of the locking devices required to hold the collar onto the bonnet.
Dimensions G & H are used to determine working height of the bonnet region of your globe valve, while Dim I is used in calculating the minimum ID
of the collar that will fit over the packing nut. Additionally, information about the environment and process in which this linkage system will be utilized
should be provided.
All the requested information contained on this form is required to guarantee the complete, perfect fit of your retrofit system. Keep in mind that
retrofit kits are designed with close-tolerance components which afford the most efficient linkage systems. Measurements rounded to the nearest
1/8 or 1/16 inch will not perform as well as a kit designed around careful measurements using proper equipment. Our designs are typically +.005”
RETROFIT SOLUTIONS
tolerance.
DISCLAIMER:
We will do our best to provide a linkage system designed around your specifications and measurements. However, we cannot be held responsible for
linkages which do not fit as a result of incorrect data given to Belimo. We will re-work components which do not fit properly for a nominal fee.
To reduce the possibility of incorrect linkage solutions, we respectfully request that you fill out the retrofit form completely and forward that
information with your order. This will serve as a double check between your valve and the actuator/linkage package designed for your application.
Actuation, weather shields and linkages cannot be pre-assembled at the Belimo factory prior to your receipt. The linkages are designed to be attached
onto the valve body first, then optional weather shields, and finally actuation products.
Close-off pressures are calculated using actuator torque, valve stroke, and valve area. Other factors may affect the rated close-off pressures, including
flow rates, system maintenance schedules, chemicals used in the shot feeder process, vicinity to pumps, condition of valve stem seals, and assembly
of linkage material in the field.
Valves that are being considered for retrofit of actuation should be analyzed for their life expectancy before the retrofit has taken place. Valves that leak
through stem seals or casings will continue to leak with the new linkage system in place, maybe even more so. Rebuilding the packing on these valves
may be more costly than replacing the valves themselves. In some instances, older valve stem heights will require field modifications to the valve in order
to utilize the retrofit kit. Belimo takes no responsibility for the operation of these valves after they have been modified.
20-45
Custom Globe Valve Retrofit Solution Form
UGSP Series
D3 D1
E D2
D2
H F
G
E D3 D1 D3 D1
I
H G
G F E
F
(i.e. Barber Colman)
NOTE:
Internal Packing Nut
Nut "F" rotates on (i.e. Powers)
valve bonnet!!
D2 D2 VALVE STYLE:
DIM D1*:
G Stem up, length to base mount surface
D3 D1 D3 D1
I E DIM D2: max.
E G F Stem stroke, stem up vs. stem down (D1-D3) 1.500”
F DIM D3:
E H
Stem down, length to base mount surface
External Packing Nut (i.e. Honeywell)
DIM E:
Bonnet major diameter
DIM F:
Thread spec or bonnet minor diameter
STEM STYLE A AØ STEM STYLE B AØ
DIM G:
RETROFIT SOLUTIONS
STEM STYLE STEM DIAMETER THREAD LENGTH TO STEM GROOVE THREADS PER INCH STEM GROOVE HEIGHT
A or B: DIM A: DIM B: DIM B: DIM C: DIM C:
ACTUATOR
EXISTING ACTUATOR MODEL: _______________________ CONTROL TYPE: ON/OFF FLOATING POINT VDC PWM
FAIL SAFE: YES NO Range:_____ Range:_____
FAIL POSITION: NO NC INDOOR OUTDOOR
VOLTAGE _____
NOTE: THIS INFORMATION WILL BE UTILIZED IN THE FABRICATION OF A CUSTOM LINKAGE SYSTEM FOR YOUR VALVE REQUIREMENT; THEREFORE, IT IS ESSENTIAL THAT THE
ABOVE DIMENSIONS BE FURNISHED WITH READINGS TAKEN TO THE NEAREST .001". ANY ERRONEOUS DIMENSIONS FURNISHED WHICH RESULT IN IMPROPER FIT OF THIS LINKAGE
SYSTEM ARE NOT THE RESPONSIBILITY OF BELIMO AIRCONTROLS. ANY REWORK REQUIRED WILL RESULT IN AN EXTRA CHARGE.
CUSTOM KITS ARE DESIGNED TO YOUR UNIQUE SPECIFICATIONS AND ARE NOT RETURNABLE.
COMPANY CONTACT/DIMENSIONS PROVIDED BY: ____________________________________________________________________ DATE: ___________________
20-46
How to Select a Butterfly Valve Retrofit Solution
2 Determine the type of actuator you require: Belimo Spring Return, Non-Spring or SY Series Industrial. Belimo Spring and
Non-Spring actuators are typically only available on smaller sizes.
Look at the solution using the Non-Spring Return Belimo Actuator. Looking at the UFLK3500, the GM Series actuator will
provide a 200 psi close-off for the 2½” valve with Non-Spring Return actuation.
3 Use the actuator listings to make your final actuator selection. Decide between GMB24-3-X1 and GMB24-MFT-X1.
ACTUATOR NOT INCLUDED IN THE LIST PRICE OF THE LINKAGE.
C200 Rou
Round
nd Top
Top Serie
Seriess Butter
Butterfly
fly 2-way 2” No 200 AM UFLK3500
UFLK3500
Valves
SY1 UFLK3538
RETROFIT SOLUTIONS
Yes 200 AF UFLK3500
UFLK3500
Example: Centerline C200 Series, 2½” No 200 GM UFLK3500
2½” valve using a non-spring return SY1 UFLK3538
Belimo actuation. SY2 UFLK3540
UFLK3540
Yes 200 2*AF UFLK3502
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
20-47
Butterfly Valve Retrofit Actuators
Actuator Selection Guide
SY ACTUATORS
CONTROL TYPE
SERIES MODEL Run Time(s) 90°@60Hz Power Supply Duty Cycle Proportional 3 Point On/Off Feedback List Price
SY1-110 11 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $1,241
SY1-24 20 seconds 24 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $1,241
SY1-220 10 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $1,241
SY1
SY1-110P 16 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $2,924
SY1-24P 15 seconds 24 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $2,924
SY1-220P 16 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $2,924
SY2-110 16 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,001
SY2-24 16 seconds 24 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,001
SY2-220 16 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,001
SY2
SY2-120MFT 17 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,080
SY2-24MFT 15 seconds 24 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,080
SY2-230MFT 17 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,080
SY3-110 24 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,306
SY3-24 24 seconds 24 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,306
SY3-220 25 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,306
SY3
SY3-24MFT 22 seconds 24 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,418
SY3-120MFT 26 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,418
SY3-230MFT 26 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $4,418
SY4-110 18 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,870
SY4-24 25 seconds 24 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,870
SY4-220 18 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $2,870
SY4
SY4-24MFT 16 seconds 24 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,272
SY4-120MFT 18 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,272
SY4-230MFT 18 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,272
SY5-110 25 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $3,319
SY5-24 37 seconds 24 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $3,319
SY5-220 25 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $3,319
SY5
SY5-24MFT 22 seconds 24 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,741
SY5-120MFT 25 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,741
SY5-230MFT 25 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $5,741
SY6-110 29 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $4,022
SY6-220 28 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $4,022
SY6
SY6-120MFT 31 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $6,483
RETROFIT SOLUTIONS
SY6-230MFT 31 seconds 230 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $6,483
SY7-110 54 seconds 120 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $4,829
SY7-220 54 seconds 230 VAC ±10%, 50/60 Hz 30% • • none, opt 1k $4,829
SY7
SY7-120MFT 55 seconds 120 VAC ±10%, 50/60 Hz 75% • 2-10 VDC/4-20 mA $7,233
20-48
Butterfly Valve Retrofit Actuators
Actuator Selection Guide
ROTARY ACTUATORS
Tandem
Electronic Feedback Power
SERIES MODEL Spring Return Mounting Control Input List Price
Fail-Safe Position Supply
Available
AFBUP-X1 • • On/Off - 24-240 VAC $594
AF Series* Variable with MFT
AFX24-MFT-X1 • • variable VDC 24 VAC/DC $674
(VDC, PWM, Floating Point, On/Off)
AMB24-3-X1 Floating Point, On/Off - 24 VAC/DC $342
AM Series* Variable with MFT
AMX24-MFT-X1 variable VDC 24 VAC/DC $532
(VDC, PWM, Floating Point, On/Off)
GMB24-3-X1 Floating Point, On/Off - 24 VAC/DC $526
GM Series* Variable with MFT
GMX24-MFT-X1 • variable VDC 24 VAC/DC $751
(VDC, PWM, Floating Point, On/Off)
GKB24-3-X1 • Floating Point, On/Off - 24 VAC $1,167
GK Series* Variable with MFT
GKX24-MFT-X1 • • variable VDC 24 VAC/DC $1,593
(VDC, PWM, Floating Point, On/Off)
*Please consult the Damper sections for a full list of product offerings. Standard run times should be considered in the selection. All air side products are applicable for retrofit kits.
Select “X1” actuators come with a handle.
MULTI-FUNCTION TECHNOLOGY
P-CODE Control Input Running Time Built-in Feedback List Price
P-10001 A01 2-10 VDC 150 seconds 2-10 VDC No Charge
ROTARY ACTUATOR CODES
RETROFIT SOLUTIONS
SY MULTI-FUNCTION TECHNOLOGY
Description MFT-CODE Control Input Built-in Feedback Loss of Signal Running Time List Price
MFT ACE 2-10 VDC 2-10 VDC stop actuator(s) constant No Charge
MFT ACF 0.5-10 VDC 0.5-10 VDC stop actuator(s) constant No Charge
MFT ACG 4-20 mA 4-20 mA stop actuator(s) constant No Charge
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
20-49
Bray
30/31, 40/41 Series Butterfly Valves
Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-50
Bray Centerline
40/41 Series Butterfly Valves C200 Round Top Series Butterfly Valves
Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
14” No 150 UFLK3550 SY5 $742
16” No 150 UFLK3552 SY7 $848
18” No 150 UFLK3554 SY8 $848
20” No 150 UFLK3556 SY8 $848
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
All close-off pressures listed are approximate and based on valve condition and application.
20-51
Centerline
C200 Square Top, C225 Square Top Series Butterfly Valves
Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-52
Centerline Johnson Controls
C225 Square Top Series Butterfly Valves VF...(H) Series Butterfly Valves
Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
Yes 175 UFLK2102 2*AF $489
No 175 UFLK2136 SY1 $701
No 175 UFLK2138 SY2 $751
2½” Yes 175 UFLK2100 GK $383
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
No 175 GM $383
Yes 175 UFLK2102 2*AF $489
No 175 UFLK2136 SY1 $701
No 175 UFLK2138 SY2 $751
3” Yes 175 UFLK2100 GK $383
No 175 GM $383
Yes 175 UFLK2102 2*AF $489
No 175 UFLK2136 SY1 $701
No 175 UFLK2138 SY2 $751
4” Yes 175 UFLK2108 2*GK $489
No 175 2*GM $489
No 175 UFLK2140 SY2 $751
5” No 175 UFLK2142 SY3 $751
6” No 175 UFLK2144 SY4 $751
8” No 175 UFLK2158 SY4 $751
10” No 175 UFLK2146 SY5 $751
12” No 175 UFLK2148 SY7 $751
14” No 150 UFLK2156 SY7 $751
16” No 150 UFLK2150 SY9 $907
18” No 150 UFLK2152 SY10 $899
20” No 150 UFLK2154 SY10 $899
3-way 2” Yes 175 UFLK5100 GK $751
No 175 GM $751
Yes 175 UFLK5102 2*AF $808
No 175 UFLK5130 SY1 $808
No 175 UFLK5132 SY2 $1,019
2½” Yes 175 UFLK5102 2*GK $808
No 175 2*GM $808
No 175 UFLK5132 SY2 $1,019
All close-off pressures listed are approximate and based on valve condition and application.
20-53
Johnson Controls Keystone
VF...(H) Series Butterfly Valves 360/362, 370/372 Series Butterfly Valves
Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-54
Keystone
370/372, AR1/AR2, Figure 222 Series Butterfly Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
16” No 150 UFLK2350 SY9 $713
18” No 150 UFLK2352 SY10 $981
20” No 150 UFLK2352 SY11 $981
24” No 150 UFLK2354 SY12 $981
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
All close-off pressures listed are approximate and based on valve condition and application.
20-55
Keystone Milwaukee
Figure 222 Series Butterfly Valves CL Series Butterfly Valves
Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-56
Milwaukee
CL, ML Series Butterfly Valves
Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
5” Yes 150 UFLK2708 2*GK $477
No 150 2*GM $477
No 150 UFLK2736 SY2 $751
6” No 150 UFLK2738 SY3 $751
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
All close-off pressures listed are approximate and based on valve condition and application.
20-57
Milwaukee Nibco PDC
ML Series Butterfly Valves LD1/WD1, LD2/WD3, LD3 Series Butterfly Valves 27 Series Butterfly Valves
Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
*Remove old blue coupler.
20-58
PDC Victaulic
27 Series Butterfly Valves Masterseal, Vic300 Series Butterfly Valves
Linkage/Actuator Selection Guide Linkage/Actuator Selection Guide
RETROFIT SOLUTIONS
5” No 200 UFLK8184 SY3 $705
6” No 200 UFLK8184 SY3 $705
8” No 200 UFLK8188 SY4 $715
10” No 200 UFLK8190 SY5 $715
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
20-59
Victaulic
Vic300 Series Butterfly Valves
Linkage/Actuator Selection Guide
All close-off pressures listed are approximate and based on valve condition and application.
20-60
Specialty Solutions for Valve Manufacturers
Belimo offers specialty linkage solutions for the manufacturers in the chart below.
Please contact technical support for a quotation.
Valve Company Butterfly Valve Series Valve Configuration
2-way
Apollo 141/143 Series
3-way
2-way
Belimo HS, HSU, HD, HDU Series
3-way
2-way
Challenger CH100 Series
3-way
2-way
Chemtrol PVC Model C Series
3-way
2-way
Dezurik BRS Series
3-way
2-way
1 L/W Series
3-way
Flowseal
2-way
3 L/W Series
3-way
2-way
FNW Figure 1000/2000 Series
3-way
2-way
Figure 7700 (Double D Shaft 2003 and Newer) Series
3-way
Gruvlok
2-way
Figure 7700 (Sheared Pin Shaft Pre 2003) Series
3-way
2-way
Hammond 61/62 Series
3-way
2-way
815 L/W Series
3-way
Jamesbury
2-way
830 L/W Series
RETROFIT SOLUTIONS
3-way
2-way
Jenkins 22XXEXJ Series
3-way
2-way
Metraflex 200 WOG Series
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
3-way
2-way
Mueller 65/66 Series
3-way
2-way
PDC 27 Series (Double D Shaft)
3-way
2-way
Quartermaster 42/44 Series
3-way
2-way
Watts DBF Series (pre 2009)
3-way
Considerations:
• The kits above do not require a completed retrofit form. Only the make
and model of the competitor valve is needed.
• Each linkage order is custom made and will take additional time to ship
than a stock kit.
20-61
Custom Butterfly Valve Retrofit Solution Form
UFSP Series
DISCLAIMER
We will do our best to provide a linkage system designed around your specifications and measurements. However, we cannot be held responsible for
linkages which do not fit as a result of incorrect data given to Belimo. We will re-work components which do not fit properly for a nominal fee.
RETROFIT SOLUTIONS
To reduce the possibility of incorrect linkage solutions, we respectfully request that you fill out the retrofit form completely and forward that
information with your order. This will serve as a double check between your valve and the actuator/linkage package designed for your application.
Actuation, weather shields and linkages cannot be pre-assembled at the Belimo factory prior to your receipt. The linkages are designed to be attached
onto the valve body first, then optional weather shields, and finally actuation products.
20-62
Custom Butterfly Valve Retrofit Solution Form
UFSP Series
B DIM A:
DIM B:
A
A B DIM C:
MOUNTING VALVE
DIM. A & B MEASURED FROM CENTER OF HOLE
VALVE C HOLES C
BODY BODY
RETROFIT SOLUTIONS
SHAFT STYLE 5 .3125" SHAFT STYLE 9
F SHAFT STYLE 7
F
E .375" D F D
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
.4375"
G
D H .500" E E
WOODRUFF KEY CHECK ONE HEX SQUARE CHECK ONE
SHAFT STYLE
DIM D: DIM E: DIM F: DIM G: DIM H:
ACTUATOR
EXISTING ACTUATOR MODEL: _______________________ CONTROL TYPE: ON/OFF FLOATING POINT VDC PWM
FAIL SAFE: YES NO Range:_____ Range:_____
FAIL POSITION: NO NC INDOOR OUTDOOR
VOLTAGE_____
NOTE: THIS INFORMATION WILL BE UTILIZED IN THE FABRICATION OF A CUSTOM LINKAGE SYSTEM FOR YOUR VALVE REQUIREMENT; THEREFORE, IT IS ESSENTIAL THAT THE
ABOVE DIMENSIONS BE FURNISHED WITH READINGS TAKEN TO THE NEAREST .001". ANY ERRONEOUS DIMENSIONS FURNISHED WHICH RESULT IN IMPROPER FIT OF THIS LINKAGE
SYSTEM ARE NOT THE RESPONSIBILITY OF BELIMO AIRCONTROLS. ANY REWORK REQUIRED WILL RESULT IN AN EXTRA CHARGE.
CUSTOM KITS ARE DESIGNED TO YOUR UNIQUE SPECIFICATIONS AND ARE NOT RETURNABLE.
COMPANY CONTACT/DIMENSIONS PROVIDED BY: ____________________________________________________________________ DATE: ___________________
20-63
Custom Butterfly Valve Retrofit Solutions
Component Identification
VALVE COUPLING
DRIVE SHAFT DRIVE SHAFT
ACTUATOR PLATE
BRACKET
TI-ROTATION NUT
LOCK WASHER (4)
INDUSTRIAL
COUPLING
PIN VALVE COUPLING (WELDED)
PIN
BOLT (4)
ANTI-ROTATION NUT
SHAFT LOCK (2) SHAFT LOCK
BOLT (4)
BOLT (4)
VALVE STEM
BOLT (4)
ANTI-ROTATION PIN
TOP MOUNTING HOLES
NUT (4)
TOP MOUNTING HOLES
NUT (4) EXISTING VALVE BODY
VALVE STEM ANTI-ROTATION PIN
(2) ACTUATOR PLATE
EXISTING VALVE BODY
TOP MOUNTING HOLES VALVE STEM
NUT (8)
NUT (4)
EXISTING VALVE
EXISTING VALVE
20-64
Custom Ball Valve Retrofit Solution Form
UBSP Series
All dimensions should be taken with ALL original actuation and hardware components removed from the valve body.
An example using Mounting Style 3: Dimensions A & B (Dim A and Dim B) relate to the TOP mounting holes on the ball valve body. These holes
are usually arranged on the body in a “X” pattern (MOUNT STYLE 3). This information is entered on the UBSP Series Ball Valve Retrofit Form in the
MOUNT STYLE section. The length of the valve stem sticking out of the top of the valve body is recorded under Dim D and E. The TOP mounting
holes are usually drilled through the top flange, but sometimes are threaded. Enter this information on the form next to the mount style information
previously recorded.
MOUNT STYLE 3: Dimensions A & B (Dim A and Dim B) relate to the TOP mounting holes on the ball valve body. These holes are usually arranged on
the body in a “X” pattern (MOUNT STYLE 3). This information is entered on the UBSP Series Ball Valve Retrofit Form in the MOUNT STYLE section.
The length of the valve stem sticking out of the top of the valve body is recorded under Dim D and E. The TOP mounting holes are usually drilled
through the top flange, but sometimes are threaded. Enter this information on the form next to the mount style information previously recorded.
STEM STYLE: Examine the valve being retrofitted to establish which stem style matches the diagrams above. Use caution when recording these
dimensions. Dim H refers to the valve stem diameter and should be measured at several points up and down as well as around the stem itself.
Dim E refers to the length of the drive surface available, whether it is a key or flatted surface. Dim F refers to the width of the drive surface or the
distance across the flats. This is the most critical dimension for correct linkage operation. Please measure accordingly. Lastly please specify the
desired actuator orientation in reference to the valve body using the ports as reference, i.e. over the “A” port etc. We have also includes an ISO-5211
standard dimension chart for reference. If the valve is labeled please specify its “F” number so that we may confirm the dimensions per the ISO spec.
In addition, we require information about the environment and process in which this linkage system will be utilized. As well as the frequency of use
the current actuator runs. This will help to ensure the longevity of the new linkage and actuator. Having the prior actuator spec and model will help.
The form must be completed in its entirety to guarantee the complete, perfect fit of your retrofit system. Keep in mind that retrofit kits are designed
with close-tolerance components which afford the most efficient linkage systems. Measurements rounded to the nearest 1/8 or 1/16 inch will not
perform as well (sometimes not at all) as a kit designed around careful measurements using proper equipment. Our designs are typically +.005”
RETROFIT SOLUTIONS
tolerance.
DISCLAIMER
We will do our best to provide a linkage system designed around your specifications and measurements. However, we cannot be held responsible for
linkages which do not fit as a result of incorrect data given to Belimo. We will re-work components which do not fit properly for a nominal fee.
To reduce the possibility of incorrect linkage solutions, we respectfully request that you fill out the retrofit form completely and forward that
information with your order. This will serve as a double check between your valve and the actuator/linkage package designed for your application.
Actuation, weather shields and linkages cannot be pre-assembled at the Belimo factory prior to your receipt. The linkages are designed to be attached
onto the valve body first, then optional weather shields, and finally actuation products.
Close-off pressures are calculated using actuator torque, valve stroke, and valve area. Other factors may affect the rated close-off pressures, including
flow rates, system maintenance schedules, chemicals used in the shot feeder process, vicinity to pumps, condition of valve stem seals, and assembly
of linkage material in the field.
Valves that are being considered for retrofit of actuation should be analyzed for their life expectancy before the retrofit has taken place. Valves that leak
through stem seals or casings will continue to leak with the new linkage system in place, maybe even more so. Rebuilding the packing on these valves
may be more costly than replacing the valves themselves. In some instances, older valve stem heights will require field modifications to the valve in order
to utilize the retrofit kit. Belimo takes no responsibility for the operation of these valves after they have been modified.
20-65
Custom Ball Valve Retrofit Solution Form
E E A
A A
MOUNTING HOLE
C E MOUNTING HOLE
H
I LARGEST AREA
TO CLEAR OR NUT
H G
ACROSS
F H
FLATS
STEM STYLE
DIM F: DIM G: DIM H: DIM I: DIM J:
ACTUATOR ACTUATOR
EXISTING ACTUATOR MODEL: _______________________ CONTROL TYPE: ON/OFF FLOATING POINT VDC PWM ORIENTATION:
FAIL SAFE: YES NO Range:_____ Range:_____ A AB
FAIL POSITION: NO NC INDOOR OUTDOOR
FREQUENCY OF OPERATION (specify how often): DAILY_____ WEEKLY_____ MONTHLY_____ VOLTAGE: _____
B
NOTE: THIS INFORMATION WILL BE UTILIZED IN THE FABRICATION OF A CUSTOM LINKAGE SYSTEM FOR YOUR VALVE REQUIREMENT; THEREFORE, IT IS ESSENTIAL THAT THE
ABOVE DIMENSIONS BE FURNISHED WITH READINGS TAKEN TO THE NEAREST .001". ANY ERRONEOUS DIMENSIONS FURNISHED WHICH RESULT IN IMPROPER FIT OF THIS LINKAGE
SYSTEM ARE NOT THE RESPONSIBILITY OF BELIMO AIRCONTROLS. ANY REWORK REQUIRED WILL RESULT IN AN EXTRA CHARGE.
CUSTOM KITS ARE DESIGNED TO YOUR UNIQUE SPECIFICATIONS AND ARE NOT RETURNABLE.
COMPANY CONTACT/DIMENSIONS PROVIDED BY: ____________________________________________________________________ DATE: ___________________
20-66
Custom Ball Valve Retrofit Solutions
Component Identification
EXTENSION
BOLT
ANTI-ROTATION PIN
BUSHING
NUT
NYLON WASHER
ROLL PIN
ACTUATOR PLATE
DRIVE SHAFT
VALVE COUPLING
BOLT
BUSHING NUT
NUT
VALVE EXTENSION
COUPLING
BOLT
BOLT
ANTI-ROTATION
PIN
LOCK WASHER
BOLT
NUT ANTI-ROTATION
PIN MOUNTING
BRACKET
LOCK
WASHER
NUT
NUT
RETROFIT SOLUTIONS
MOUNTING
BRACKET
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
SPLIT LOCK
WASHER
BOLT
SY CPL/INTERFACE
VALVE COUPLING
BOLT
LOCK WASHER
20-67
New Tools from Belimo to Make Your Life Easier
From sizing and selecting to estimating savings, Belimo offers the following tools
to help make your job easier:
• Retrofit App allows you to quickly and easily find HVAC replacement
solutions for valves and actuators.
• Energy Valve Savings Estimator is a Microsoft Excel based tool that profiles
constant speed chilled water plant performance.
1977 2009
Release of the first direct coupled actuator. Launch of the 6-way Characterized Control Valve offering a cost
effective way to control heating and cooling using a single valve and
actuator for chilled beam and fan-coil applications.
1986
Assembly of the one millionth actuator.
2010
Launch of the Electronic Pressure Independent Valve (ePIV) with an
1989 integrated electronic flow sensor and control algorithm to maintain flow
set point regardless of differential pressure variations.
Belimo Aircontrols (USA), Inc. is established.
“Excellence Award” received for the best Swiss Company from Swiss
Investment Companies and professors from the Universities Zurich and
1995 Eichstatt-Ingoldstadt.
Belimo Aircontrols (CAN), Inc. is established.
2002 2012
Launch of the Belimo Energy Valve™, a pressure independent control
Belimo moves to a new production and administration facility in valve that measures energy, controls power and manages delta T in
Hinwil, uniting all locations in the Zurich Oberland region to one site in chilled and hot water applications.
Hinwil, Switzerland.
Awarded the “Business Leadership Award” from Ability Beyond.
2003
Invention of the Pressure Independent Characterized Control Valve 2013
(PICCV) that compensates for pressure variations and performs Launch of the ZIP Economizer; the fastest route to reliable energy
continual balancing to maintain system performance at varying loads. savings with patented ZIP code set up, alarms, superior troubleshooting
capability and a modular design.
2007
Launch of the thinnest damper actuator. The CM actuator, measuring 2014
0.63”, fits in the smallest of spaces with a torque of 18 in-lbs (2 Nm). Belimo Americas builds an energy efficient, LEED Certified™ Gold®
headquarters in Danbury, CT; continuing our commitment to the
community and our employees by expanding our capabilities to provide
outstanding quality, delivery, and customer service.
Retrofit and Replacement
How to Select a Damper Actuator
The “10 questions” method for sizing and selection shown below is ACTUATOR REQUIREMENTS APPLICATION DATA
recommended as the best method for your actuation requirements.
Use the “Application Data” column in this chart as a worksheet to help 6 Is fail-safe
actuation
in the selection process.
required?
❑ Yes
APPLICATION INFO APPLICATION DATA
❑ No
1 What is the
total area of
Consider the application. Is the
actuator and/or damper exposed to
the damper? outside air? If yes, use spring return.
sq.ft.
7 What is
the supply
Do you need
a step down
voltage to transformer? ❑ 24 VAC
2 Opposed blade
or Parallel
L” x W” = Total sq
inches/144 = total sq feet the actuator? If replacing an oil ❑ 120 VAC
• 24 VAC/DC immersed gear
blade control Opposed Blade train actuator, is the transformer in the
construction? w/o seals 3 in-lbs/sq feet* ❑ Opposed Blade
• 120 VAC
defective actuator? You may need to
❑ 230 VAC
• 230 VAC purchase one.
single phase
Opposed Blade
8
w/ seals 5 in-lbs/sq feet What is • 2 position ❑ On/Off
the control • Floating point
Parallel Blade ❑ Floating Point
w/o seals 4 in-lbs/sq feet signal to the • Modulating
actuator? ❑ 2-10 VDC
Parallel Blade • Sequencing
❑ 0-10 VDC
w/ seals 7 in-lbs/sq feet ❑ Parallel Blade • “Non-standard”
voltage signals ❑ 4-20 mA
*Less than 1,000 feet per
minute This will be a critical component to ❑ PWM____
the selection of an actuator. Consider range
the …MFT actuator product range and
❑ Other (MFT)
3 Are there blade
and edge seals
This will impact
the proper
the flexibility of its application.
on the damper?
selection as the
seals add resistance ❑ Yes 9 Can you direct
couple to a
Direct-
coupling has
requiring more torque. damper shaft? become the ❑ Yes
If unknown, use ❑ No industry
a worst case standard. ❑ No, see
scenario, parallel Some retrofit
blade with seals. applications
accessories
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
❑ Yes, see
accessories
5 What is the air For example, some applications require
APPENDIX
velocity, static _______W.G. the addition of an auxiliary switch for section or
pressure, or proof of position; a retrofit application actuator
_______CFM may require an additional mounting series for
design CFM? bracket and linkage kit. We advise that
_______FPM details
Systems above 1,000 FPM you identify these needs prior to leaving
require additional actuator torque the job site or ordering products.
21-3
Retrofit and Replacement
How to Select a Damper Actuator
Belimo actuators are compatible with many control inputs and all direct digital control (DDC) systems. There are many signals to select from
with today’s controllers.
On/Off or Open-Close: The actuator is able to drive either to its full Phasecut: An actuator drives depending on the power result of a
clockwise (CW) position, or to its full counter-clockwise (CCW) remaining wave. This signal type cuts the amplitude of the wave and
position. The same indication is used for spring return type the actuator recognizes this signal as a proportional movement.
actuators. Where the actuator will drive to its full CW position and
spring return to its CCW position. This can also be reversed.
21-4
Valve Sizing – Water Applications
[ [ [ [
2 2
Q* G Q* G Q* G Q* G
Cv = Δ P= Cv = Δ P=
ΔP Cv ΔP Cv
Cv = required Cv Cv = required Cv
Q = flow in Gallons per Minute Q = flow in Gallons per Minute
G = Specific gravity of fluid (estimated as 1 for water systems) G = Specific gravity of fluid (estimated as 1 for water systems)
ΔP = differential pressure over valve (deltaP) – stated in psi ΔP = differential pressure over valve (deltaP) – stated in psi
PROCEDURE PROCEDURE
1) Calculate Cv 1) Calculate Cv
2) Choose valve type (CCV, Zone, etc) 2) Choose valve type (CCV, Zone, etc)
3) Choose valve model number that has closest Cv rating 3) Choose valve model number that has closest Cv rating
(normally round down unless maximum ΔP for project is exceeded) (normally round down unless maximum ΔP for project is exceeded)
a. Refer to section 11 for CCV (Fp correction required) a. Refer to section 11 for CCV (Fp correction required)
b. Refer to section 12 for HTCCV
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
APPENDIX
4) Calculate actual ΔP based upon Cv of valve selected 4) Calculate actual ΔP based upon Cv of valve selected
5) If calculated ΔP is within project specified limits, proceed with actuator 5) If calculated ΔP is within project specified limits, proceed with actuator
selection selection
6) If #5 is no, need to select a valve with a higher/lower Cv 6) If #5 is no, need to select a valve with a higher/lower Cv
7) Select actuator based upon selection parameters above 7) Select actuator based upon selection parameters above
8) Based upon actuator/valve selection, verify close-off pressure (COP) meets 8) Based upon actuator/valve selection, verify close-off pressure (COP) meets
project requirements project requirements
21-5
Valve Sizing – Water Applications
PROCEDURE PROCEDURE
1) Obtain required GPM 1) Obtain required GPM
2) Choose valve model number that has closest GPM rating (round up) 2) Choose valve model number that has closest GPM rating (round up)
• Refer to section 7 for PICCV and ePIV • Refer to section 7 for PICCV and ePIV
• Refer to section 6 for Energy Valve • Refer to section 6 for Energy Valve
3) Verify that valve size is not larger than pipe size and in general, do not select 3) Verify that valve size is not larger than pipe size and in general, do not select
a valve less than ½ of the line size a valve less than ½ of the line size
4) Select actuator based upon selection parameters above 4) Select actuator based upon selection parameters above
5) Based upon actuator/valve selection, verify close-off pressure (COP) meets 5) Based upon actuator/valve selection, verify close-off pressure (COP) meets
project requirements project requirements
21-6
Valve Sizing – Steam Applications
Low Pressure Steam
Cv = 1000/(3*sqrt[1.5*28.2])
Q
Cv = 1000/(3*6.50)
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Cv = = 51.25
Cv = 1000/19.51 3 * h *P o
Required Cv = 51.25
APPENDIX
21-7
Valve Sizing – Steam Applications
Low Pressure Steam
Cv = 1000/(3*sqrt[12*17.7])
Q
Cv = 1000/(3*14.6) Cv = = 22.9
21-8
Valve Sizing – Steam Applications
Medium/High Pressure Steam
Cv = 1000/(3*sqrt[4*50.7])
Cv = 1000/(3*14.3) Q
Cv = = 23.41
Cv = 1000/42.7 3 * h *P o
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Required Cv = 23.42
APPENDIX
21-9
Valve Sizing – Steam Applications
Medium/High Pressure Steam
Cv = 1000/(3*sqrt[22.97*31.73])
Required Cv = 12.35
APPENDIX
21-10
Valve Sizing – Water Applications
Velocity Method
APPENDIX
21-11
Valve Sizing – Water Applications
Using Velocity Method
EXAMPLE
Application requires a 2-way, 400 GPM Butterfly valve, a valve of 4” minimum
would be selected. The 4” valve at 12 ft/second would be able to withstand a
capacity of 470 GPM, without damage to the liner.
21-12
General Sizing Information
MODELS OF VALVES/APPLICATIONS
FLOW MEDIUM PICCV CCV HTCCV BALL GLOBE BUTTERFLY ZONE VALVES
Chilled / Hot Water / Glycol PICCV-XX-XXX B2(B), B2...HT B2VS, B2VSS G2, G3(D), F6, F7… Z2
2-way only B3(B), B3...L G7(D), HD, HDU,
B6 G6C Series VIC, SHP
3-Way Mixing B3(B) G3, G7 F7, HD/HDU,
VIC, SHP
3-Way Diverting B3(B) B3...L G3D, G7D F7, HD/HDU, Z3
VIC, SHP
Low Pressure Steam B2...HT B2VS G2, G6C F6 ...SHP
(up to 15 inlet psi)
Medium Pressure Steam B2VS G2 up to F6 ...SHP
(15–50 inlet psi) (up to 35 psi only) (35 inlet psi only)
B2VSS G2S, G6C
(35 psi only),
G6CS
High Pressure Steam G2S, G6CS
(50-100 inlet psi)
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
APPENDIX
21-13
ANSI/FCI Standards
ANSI/FCI 70-2-2006 Specification
CONTROL VALVE SEAT LEAKAGE CLASSIFICATIONS (IN ACCORDANCE WITH ANSI/FCI 70-2)
Leakage Class Maximum Leakage Testing Procedures Required for
Test Medium Test Pressure
Designation Allowable Establishing Rating
No test required provided user and
I - - -
supplier so agree
Pressure applied to valve inlet with
outlet open to atmosphere or connected
Air or water at 50°F to 125°F 45-60 psig or max. operating
II 0.5% of rated capacity to a low head loss measuring device
(10°C to 52°C) differential whichever is lower.
full normal closing thrust provided by
actuator
III 0.1% of rated capacity As above As above As above
IV 0.01% of rated capacity As above As above As above
Pressure applied to valve inlet after
filling entire body cavity and connected
Max service pressure drop
0.0005 ml per minute of water piping with water and stroking valve
Water at 50°F to 125°F across valve plug, not to
V per inch of seat diameter per plug closed. Use net specified max
(10°C to 52°C) exceed ANSI body rating (100
psi differential. actuator thrust, but no more, even if
psi pressure drop minimum).
available during test. Allow time for
leakage flow to stabilize.
Actuator should be adjusted to
operating differential pressure
50 psig or max rated amounts
Not to exceed in following table Air or nitrogen at 50°F to 125°F conditions specified with full normal
VI across valve plug shown
based on seat diameter. (10°C to 52°C) closing thrust applied to valve plug seat.
whichever is lower.
Allow time for leakage flow to stabilize
and use suitable measuring device.
8 200 6.75 45
21-14
Water Guidelines
Molybdenum
Hot Systems ➡ 200 ppm <
(Mild Steel Corrosion Inhibitor)
< 250 ppm
Use water with low levels of chloride and sulfate, less than 25 ppm. Water hardness should be less than 50 ppm of hard water ions (Ca, Mg).
When water hardness is at unacceptable levels, a water softener expert should be consulted.
MAXIMUM TEMPERATURE AND PRESSURE RATINGS PRESSURE/TEMPERATURE CHART FOR ANSI CLASS 150/300
FOR FLANGED GLOBE VALVE BODIES BUTTERFLY VALVES
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
APPENDIX
21-15
APPENDIX
21-16
CONTACT NAME
Belimo Aircontrols (USA), Inc.
COMPANY 33 Turner Road 1049 Fortunato Loop
Danbury, CT 06810 Sparks, NV 89436
ADDRESS
Phone (203) 791-9915 Phone (775) 857-4243
Fax (203) 791-9919 Fax (775) 857-4255
TOLL FREE TOLL FREE
PHONE Phone (800) 543-9038 Phone (800) 987-9042
Fax (800) 228-8283 Fax (800) 987-8875
FAX (800) ACTUATE
Valve Quotation Form
800-543-9038 USA
PROJECT NAME
Cv
CCV
Size
(in.)
Pipe
(psi)
(psi)
Flow
Drop
Zone
Globe
(gpm)
PICCV
On-Off
Spring
Return
24 VAC
System
System
Desired
Desired
Quantity
Tri-State
120 VAC
Butterfly
Two-way
Pressure
Pressure
Switches
Close-Off
Three-way
Modulating
Floating Pt.
866-805-7089 CANADA
203-791-8396 LATIN AMERICA/CARIBBEAN
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
Custom MFT Configuration Order Form
FAX: (USA & Latin America and the Caribbean) 1-800-228-8283
#1 Select an Actuator (Canada) 1-866-805-7089
(use one sheet for each unique actuator/configuration)
Quantity Quantity
❑ EFX24-MFT ______ ❑ NMX24-MFT-X1 ______
Name _______________________________________________________________________________
❑ EFX24-MFT-S ______ ❑ NMX24-MFT95 ______
❑ AFX24-MFT ______ ❑ NMQX24-MFT ______
❑ AFX24-MFT-S ______ ❑ LMX24-MFT ______ Company ____________________________________________________________________________
❑ AFX24-MFT95 ______ ❑ LMX24-MFT-X1 ______
❑ NFX24-MFT ______ ❑ LMX24-MFT95 ______ Address _____________________________________________________________________________
❑ NFX24-MFT-S ______ ❑ LMQX24-MFT ______
❑ LF24-MFT US ______ ❑ AHKX24-MFT ______ City_______________________________________ State _____________Zip _____________________
❑ LF24-MFT-S US ______ ❑ AHX24-MFT ______
❑ TFX24-MFT ______ ❑ LHX24-MFT ______
Phone_____________________________________ Fax_______________________________________
❑ TFX24-MFT-S ______ ❑ LRX24-MFT ______
❑ GKX24-MFT ______ ❑ LUX24-MFT ______
❑ NKQX24-MFT ______ ❑ LVX24-MFT ______ Email _____________________________________
❑ GMX24-MFT ______ ❑ LVKX24-MFT ______
❑ GMX24-MFT-X1 ______ ❑ SVX24-MFT ______
❑ GMX24-MFT95 ______ ❑ SVKX24-MFT ______
❑ AMX24-MFT ______ ❑ EVX24-MFT ______
❑ AMX24-MFT-X1 ______ ❑ RVX24-MFT ______
❑ AMX24-MFT95 ______ ❑ AVKX24-MFT ______
❑ AMQX24-MFT ______ ❑ LUX24-MFT ______
❑ NMX24-MFT ______ (-S=Auxiliary Switch)
Stop . Start .
Stop .
APPENDIX
Position Feedback U Start DC . V (0.5...8 V) The finish must
be at least 2 V
Finish DC . V (2...10 V) above the start!
21-17
Custom Ball Valve Retrofit Solutions Form
UBSP Series Ball Valves
All dimensions should be taken with ALL original actuation and hardware components removed from the valve body.
An example using Mounting Style 3: Dimensions A & B (Dim A and Dim B) relate to the TOP mounting holes on the ball valve body. These holes
are usually arranged on the body in a “X” pattern (MOUNT STYLE 3). This information is entered on the UBSP Series Ball Valve Retrofit Form in the
MOUNT STYLE section. The length of the valve stem sticking out of the top of the valve body is recorded under Dim D and E. The TOP mounting
holes are usually drilled through the top flange, but sometimes are threaded. Enter this information on the form next to the mount style information
previously recorded.
MOUNT STYLE 3: Dimensions A & B (Dim A and Dim B) relate to the TOP mounting holes on the ball valve body. These holes are usually arranged on
the body in a “X” pattern (MOUNT STYLE 3). This information is entered on the UBSP Series Ball Valve Retrofit Form in the MOUNT STYLE section.
The length of the valve stem sticking out of the top of the valve body is recorded under Dim D and E. The TOP mounting holes are usually drilled
through the top flange, but sometimes are threaded. Enter this information on the form next to the mount style information previously recorded.
STEM STYLE: Examine the valve being retrofitted to establish which stem style matches the diagrams above. Use caution when recording these
dimensions. Dim H refers to the valve stem diameter and should be measured at several points up and down as well as around the stem itself.
Dim E refers to the length of the drive surface available, whether it is a key or flatted surface. Dim F refers to the width of the drive surface or the
distance across the flats. This is the most critical dimension for correct linkage operation. Please measure accordingly. Lastly please specify the
desired actuator orientation in reference to the valve body using the ports as reference, i.e. over the “A” port etc. We have also includes an ISO-5211
standard dimension chart for reference. If the valve is labeled please specify its “F” number so that we may confirm the dimensions per the ISO spec.
In addition, we require information about the environment and process in which this linkage system will be utilized. As well as the frequency of use
the current actuator runs. This will help to ensure the longevity of the new linkage and actuator. Having the prior actuator spec and model will help.
The form must be completed in its entirety to guarantee the complete, perfect fit of your retrofit system. Keep in mind that retrofit kits are designed
with close-tolerance components which afford the most efficient linkage systems. Measurements rounded to the nearest 1/8 or 1/16 inch will not
perform as well (sometimes not at all) as a kit designed around careful measurements using proper equipment. Our designs are typically +.005”
tolerance.
We will do our best to provide a linkage system designed around your specifications and measurements. However, we cannot be held responsible for
linkages which do not fit as a result of incorrect data given to Belimo. We will re-work components which do not fit properly for a nominal fee.
To reduce the possibility of incorrect linkage solutions, we respectfully request that you fill out the retrofit form completely and forward that
information with your order. This will serve as a double check between your valve and the actuator/linkage package designed for your application.
APPENDIX
Actuation, weather shields and linkages cannot be pre-assembled at the Belimo factory prior to your receipt. The linkages are designed to be attached
onto the valve body first, then optional weather shields, and finally actuation products.
Close-off pressures are calculated using actuator torque, valve stroke, and valve area. Other factors may affect the rated close-off pressures, including
flow rates, system maintenance schedules, chemicals used in the shot feeder process, vicinity to pumps, condition of valve stem seals, and assembly
of linkage material in the field.
Valves that are being considered for retrofit of actuation should be analyzed for their life expectancy before the retrofit has taken place. Valves that leak
through stem seals or casings will continue to leak with the new linkage system in place, maybe even more so. Rebuilding the packing on these valves
may be more costly than replacing the valves themselves. In some instances, older valve stem heights will require field modifications to the valve in order
to utilize the retrofit kit. Belimo takes no responsibility for the operation of these valves after they have been modified.
21-18
Custom Ball Valve Retrofit Solutions Form
UBSP Series Ball Valves Retrofit Form
E E A
A A
MOUNTING HOLE
C E MOUNTING HOLE
H
I LARGEST AREA
TO CLEAR OR NUT
H G F H
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
ACROSS
FLATS
G TOP OF G TOP OF
NUT TO NUT TO
TOP OF TOP OF
F STEM F STEM
STEM STYLE
DIM F: DIM G: DIM H: DIM I: DIM J:
APPENDIX
ACTUATOR ACTUATOR
EXISTING ACTUATOR MODEL: _______________________ CONTROL TYPE: ON/OFF FLOATING POINT VDC PWM ORIENTATION:
FAIL SAFE: YES NO Range:_____ Range:_____ A AB
FAIL POSITION: NO NC INDOOR OUTDOOR
FREQUENCY OF OPERATION (specify how often): DAILY_____ WEEKLY_____ MONTHLY_____ VOLTAGE: _____
B
NOTE: THIS INFORMATION WILL BE UTILIZED IN THE FABRICATION OF A CUSTOM LINKAGE SYSTEM FOR YOUR VALVE REQUIREMENT; THEREFORE, IT IS ESSENTIAL THAT THE
ABOVE DIMENSIONS BE FURNISHED WITH READINGS TAKEN TO THE NEAREST .001". ANY ERRONEOUS DIMENSIONS FURNISHED WHICH RESULT IN IMPROPER FIT OF THIS LINKAGE
SYSTEM ARE NOT THE RESPONSIBILITY OF BELIMO AIRCONTROLS. ANY REWORK REQUIRED WILL RESULT IN AN EXTRA CHARGE.
CUSTOM KITS ARE DESIGNED TO YOUR UNIQUE SPECIFICATIONS AND ARE NOT RETURNABLE.
COMPANY CONTACT/DIMENSIONS PROVIDED BY: ____________________________________________________________________ DATE: ___________________
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA/CARIBBEAN
21-19
Custom Globe Valve Retrofit Solutions Form
UGSP Series Globe Valves
Dimensions D1, D2 & D3 are used to determine the height of the linkage assembly required to clear the valves’ full stroke. A minimum of two
dimensions are required to manufacture the correct linkage system for your valve. These dimensions also provide the information necessary to
determine valve stroke. The maximum stroke from Belimo globe valve retrofit systems is 1.500”.
Dimension E refers to the valve bonnet diameter (regardless if threads are present or not). Over time, impurities will react to the bonnet threads and
corrode them to the point where they no longer meet the original thread specification. Because of this, we manufacture slip fit collars designed to
slide over the bonnet threads, and locking setscrews are provided which “bite” into the original threads. All retrofit systems are designed to work
with the raw valve body and do not account for previous actuation components which must be removed from the valve body before attaching the new
linkage system.
Dimension F refers to the thread specification on threaded bonnets, and refers to the minor diameter on slip on bonnets (Landis type). This
information helps us determine the length of the locking devices required to hold the collar onto the bonnet.
Dimensions G & H are used to determine working height of the bonnet region of your globe valve, while Dim I is used in calculating the minimum ID
of the collar that will fit over the packing nut. Additionally, information about the environment and process in which this linkage system will be utilized
should be provided.
All the requested information contained on this form is required to guarantee the complete, perfect fit of your retrofit system. Keep in mind that
retrofit kits are designed with close-tolerance components which afford the most efficient linkage systems. Measurements rounded to the nearest
1/8 or 1/16 inch will not perform as well as a kit designed around careful measurements using proper equipment. Our designs are typically +.005”
tolerance.
We will do our best to provide a linkage system designed around your specifications and measurements. However, we cannot be held responsible for
linkages which do not fit as a result of incorrect data given to Belimo. We will re-work components which do not fit properly for a nominal fee.
To reduce the possibility of incorrect linkage solutions, we respectfully request that you fill out the retrofit form completely and forward that
information with your order. This will serve as a double check between your valve and the actuator/linkage package designed for your application.
APPENDIX
Actuation, weather shields and linkages cannot be pre-assembled at the Belimo factory prior to your receipt. The linkages are designed to be attached
onto the valve body first, then optional weather shields, and finally actuation products.
Close-off pressures are calculated using actuator torque, valve stroke, and valve area. Other factors may affect the rated close-off pressures, including
flow rates, system maintenance schedules, chemicals used in the shot feeder process, vicinity to pumps, condition of valve stem seals, and assembly
of linkage material in the field.
Valves that are being considered for retrofit of actuation should be analyzed for their life expectancy before the retrofit has taken place. Valves that leak
through stem seals or casings will continue to leak with the new linkage system in place, maybe even more so. Rebuilding the packing on these valves
may be more costly than replacing the valves themselves. In some instances, older valve stem heights will require field modifications to the valve in order
to utilize the retrofit kit. Belimo takes no responsibility for the operation of these valves after they have been modified.
21-20
Custom Globe Valve Retrofit Solutions Form
UGSP Series Globe Valves Retrofit Form
D3 D1
E D2
D2
H F
G
E D3 D1 D3 D1
I
H G
G F E
F
(i.e. Barber Colman)
NOTE:
Internal Packing Nut
Nut "F" rotates on (i.e. Powers)
valve bonnet!!
D2 D2 VALVE STYLE:
DIM D1*:
G Stem up, length to base mount surface
D3 D1 D3 D1
I E DIM D2: max.
E G F Stem stroke, stem up vs. stem down (D1-D3) 1.500”
F DIM D3:
E H
Stem down, length to base mount surface
External Packing Nut (i.e. Honeywell)
DIM E:
Bonnet major diameter
DIM F:
Thread spec or bonnet minor diameter
STEM STYLE A AØ STEM STYLE B AØ
DIM G:
Bonnet mount height
C B DIM H:
B C
Bonnet minor diameter height
DIM I:
Q11000 - 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.
STEM STYLE STEM DIAMETER THREAD LENGTH TO STEM GROOVE THREADS PER INCH STEM GROOVE HEIGHT
A or B: DIM A: DIM B: DIM B: DIM C: DIM C:
APPENDIX
ACTUATOR
EXISTING ACTUATOR MODEL: _______________________ CONTROL TYPE: ON/OFF FLOATING POINT VDC PWM
FAIL SAFE: YES NO Range:_____ Range:_____
FAIL POSITION: NO NC INDOOR OUTDOOR
VOLTAGE _____
NOTE: THIS INFORMATION WILL BE UTILIZED IN THE FABRICATION OF A CUSTOM LINKAGE SYSTEM FOR YOUR VALVE REQUIREMENT; THEREFORE, IT IS ESSENTIAL THAT THE
ABOVE DIMENSIONS BE FURNISHED WITH READINGS TAKEN TO THE NEAREST .001". ANY ERRONEOUS DIMENSIONS FURNISHED WHICH RESULT IN IMPROPER FIT OF THIS LINKAGE
SYSTEM ARE NOT THE RESPONSIBILITY OF BELIMO AIRCONTROLS. ANY REWORK REQUIRED WILL RESULT IN AN EXTRA CHARGE.
CUSTOM KITS ARE DESIGNED TO YOUR UNIQUE SPECIFICATIONS AND ARE NOT RETURNABLE.
COMPANY CONTACT/DIMENSIONS PROVIDED BY: ____________________________________________________________________ DATE: ___________________
21-21
Custom Butterfly Valve Retrofit Solutions Form
UFSP Series Butterfly Valves
DISCLAIMER
We will do our best to provide a linkage system designed around your specifications and measurements. However, we cannot be held responsible for
linkages which do not fit as a result of incorrect data given to Belimo. We will re-work components which do not fit properly for a nominal fee.
To reduce the possibility of incorrect linkage solutions, we respectfully request that you fill out the retrofit form completely and forward that
information with your order. This will serve as a double check between your valve and the actuator/linkage package designed for your application.
Actuation, weather shields and linkages cannot be pre-assembled at the Belimo factory prior to your receipt. The linkages are designed to be attached
onto the valve body first, then optional weather shields, and finally actuation products.
to utilize the retrofit kit. Belimo takes no responsibility for the operation of these valves after they have been modified.
21-22
Custom Butterfly Valve Retrofit Solutions Form
UFSP Series Butterfly Valves Retrofit Form
B DIM A:
DIM B:
A
A B DIM C:
MOUNTING VALVE
DIM. A & B MEASURED FROM CENTER OF HOLE
VALVE C HOLES C
BODY BODY
.4375"
G
D H .500" E E
WOODRUFF KEY CHECK ONE HEX SQUARE CHECK ONE
SHAFT STYLE
DIM D: DIM E: DIM F: DIM G: DIM H:
APPENDIX
ACTUATOR
EXISTING ACTUATOR MODEL: _______________________ CONTROL TYPE: ON/OFF FLOATING POINT VDC PWM
FAIL SAFE: YES NO Range:_____ Range:_____
FAIL POSITION: NO NC INDOOR OUTDOOR
VOLTAGE_____
NOTE: THIS INFORMATION WILL BE UTILIZED IN THE FABRICATION OF A CUSTOM LINKAGE SYSTEM FOR YOUR VALVE REQUIREMENT; THEREFORE, IT IS ESSENTIAL THAT THE
ABOVE DIMENSIONS BE FURNISHED WITH READINGS TAKEN TO THE NEAREST .001". ANY ERRONEOUS DIMENSIONS FURNISHED WHICH RESULT IN IMPROPER FIT OF THIS LINKAGE
SYSTEM ARE NOT THE RESPONSIBILITY OF BELIMO AIRCONTROLS. ANY REWORK REQUIRED WILL RESULT IN AN EXTRA CHARGE.
CUSTOM KITS ARE DESIGNED TO YOUR UNIQUE SPECIFICATIONS AND ARE NOT RETURNABLE.
COMPANY CONTACT/DIMENSIONS PROVIDED BY: ____________________________________________________________________ DATE: ___________________
21-23
Terms and Conditions of Sale and Warranty
Terms and Conditions by the carrier’s agent and file with the carrier within 15 days after
receipt of product and notify Seller of the same. Seller is not
General liable for consequential damage to Client’s property or a third-
1.1. The following Terms and Conditions of Sale (“Terms”) apply party’s property resulting from the installation of damaged
to the sale of products described in this Product Guide Products.
(“Products”). As used herein, “Seller” or “Belimo” refers to
Belimo Aircontrols (USA) Inc. or Belimo Aircontrols (CAN) Inc., VI. Delivery
as applicable, and “Client” refers to the individual or business 6.1. Seller undertakes to make every attempt to adhere to its
entity that purchases the Products from Seller. These Terms stated delivery parameters and to make a timely delivery of the
shall apply unless the parties mutually agree to different terms Products but does not guarantee any delivery specifications.
and memorialize such agreement in writing signed by both Each contract entered into for the purchase of Products is not
Client and Seller. cancelable nor is Seller liable for any direct or indirect losses
that may arise, for any reason whatsoever, due to Seller’s failure
II. Price to meet any stated or assumed delivery schedules.
2.1. The Seller’s price for Products (the “Price”) is net, F.O.B.
Point of Origin, and is calculated in US currency for sales made VII. Return of Goods
by Belimo Aircontrols (USA), Inc. and calculated in Canadian 7.1. Products received by Client cannot be returned unless: (i)
currency for sales made by Belimo Aircontrols (CAN) Inc. Client alerts Seller that it intends to return such Products, (ii)
2.2. The Price, unless otherwise agreed upon, does not include Seller agrees to accept the return of such Products, (iii) Client
freight and packaging (wooden crates, pallets, etc), the costs of obtains a Return Material Authorization (“RMA”) number from
which will be charged to Client at cost for each shipment and Seller for the return of such Products, and (iv) Client follows all
shall be payable with payment of the Price. return instructions provided by the Seller. The RMA number
2.3. Orders for Products with a net value of less than US $300 must be clearly written on the outside of all packaging for any
(CAN $300) will be subject to a US $20 (CAN $20) handling fee returned Products. Only Products returned to the proper
(the “Handling Fee”). The Handling Fee will not be charged for location as instructed by Seller and identified with an RMA
orders of Products with a net value equal to or greater than number will be considered for credit.
US $300 (CAN $300) or for Products ordered through Seller’s 7.2. Only Products that are returned in original packaging may
eCommerce ordering system at: www.belimo.com. be accepted for return. All returned Products must be shipped
2.4. Seller reserves the right to make partial deliveries of orders to Seller at Client’s cost. Such returned Products must be
of Products, each of which deliveries may be invoiced received within 1 yr. from original sale date, in as-new condition,
separately by Seller. adequate for resale as new Products to qualify for credit. Client
2.5. The Price does not include charges for wiring diagrams, will be responsible for payment of a restocking charge for all
installation, and commissioning, which will be charged to Client returned Products in an amount no less than 20% of the invoice
separately and will be payable on demand. value of the Products (“Restocking Charges”). Product received
damaged or showing evidence of having been installed will be
III. Payment refused or assessed a higher restocking charge. Custom kits
3.1. Invoices are payable in US currency for sales made by designed to a Client’s unique specifications are not returnable.
Belimo Aircontrols (USA), Inc. and in Canadian currency for If Client requests product to be returned to them, the Client will
sales made by Belimo Aircontrols (CAN) Inc. and are due no be responsible for return shipping charges. See specific product
later than 30 days from the date of invoice, without any literature for exclusions or exceptions.
shipments of Products or may be required to pay for all future for the first two years from the date of production of the
deliveries of Products on a cash-on-delivery basis. Products. After the first two years from the date of Sale, the
warranty shall be conditional and the warranty coverage shall
IV. Title and Risk not apply to damage to Products caused by ordinary wear and
4.1. Title to all Products shall remain with Seller and shall not tear, negligence or improper use by Client, or other causes
pass to Client until Seller has received full payment for the beyond the control of the Seller. Product specific terms of
Products. warranty with regard to warranty period or conditions of
warranty may apply to certain specified Products as stated in
V. Damage or Loss in Transit the documentation for those Products.
5.1. Seller assumes no liability for damage or loss of shipment
of Products, which risk shall at all times remain with the carrier. VIII.B 2-year Conditional warranty
All shipments must be unpacked and examined by Client 8.2. Products that are listed in this Product Guide as carrying a
immediately upon receipt. Any external evidence of loss or 2-year warranty to a location in the United States or Canada
damage must be noted on the freight bill accompanying the shall carry a 2-year warranty. The 2-year warranty is conditional
shipment of Products or carrier’s receipt and signed by the and the warranty coverage shall not apply to damage to
carrier’s agent at the time of delivery. Failure to do so will result Products caused by ordinary wear and tear, negligence or
in the carrier’s refusal to honor any claim relating to damage of improper use by Client, or other causes beyond the control of
Products. Client must also notify Seller of such damage by the Seller. Product specific terms of warranty with regard to
providing Seller with a copy of the freight bill or damage report warranty period or conditions of warranty may apply to certain
so that Seller can file a claim for loss or damage in transit with specified Products as stated in the documentation for those
the carrier. If the damage does not become apparent until the Products.
shipment is unpacked, Client must make a request for inspection
21-24
Terms and Conditions of Sale and Warranty
(ii) six months, effective from the date the repaired, exchanged appears likely to make any claim regarding Products (including,
or replaced Products are shipped by Seller (the “Replacement without limitation, regarding Product defects or rights infringed
Warranty Period”). by Products), then Client shall immediately inform Seller and
8.10. Advanced replacement Products for Products covered afford to Seller all assistance that Seller may require to enforce
under warranty may be obtained from Seller after the Belimo its rights and defend such claim.
customer service troubleshooting process has been completed.
For industrial products (such as butterfly valves), a purchase XI. Proper Law and Jurisdiction
order is required. The purchase order will be credited upon the 11.1. All sales of Products under these Terms and the warran-
APPENDIX
receipt and verification by Seller of the returned defective ties described herein shall be governed by the laws of the State
Products. For non-industrial products, an invoice will be issued of Connecticut, and the parties agree to submit to the exclusive
and shall be due and payable if the returned Products are not jurisdiction of the Federal and state courts located in the State
received by Seller within 60 days from the date that the replace- of Connecticut with respect to any dispute arising from the sub-
ment Products are shipped. Additional charges may apply if the ject matter hereof. The parties hereby waive all rights to a jury
nature of the problem has been misrepresented by Client. trial in connection with any claims relating to the subject matter
8.11. Both the conditional and unconditional warranties cover hereof.
the Products only, and do NOT cover labor associated with the
troubleshooting, removal or replacement of such Products.
8.12. New Products ordered in an attempt to circumvent the
warranty process may NOT be reimbursed if, upon receipt of
returned Products, it is determined that the defect in the
returned Products is actually field related, or the Products have
been returned for cosmetic reasons only.
8.13. Advanced replacement Products for butterfly valve actua-
tors may not be new, but have been verified by the Seller for
electrical and mechanical operation. Such Products carry the
full warranty for the entire Replacement Warranty Period.
21-25
Actuator/Valve Specification
12. The manufacturer shall warrant all components for a period of 5 D. The manufacturer shall warrant all components for a period of 5
years from the date of production, with the first two years years from the date of production, with the first two years
unconditional. unconditional (except as noted).
B. Industrial Actuators (ONLY TO BE USED WITH 2.16.I Butterfly Valves E. Pressure Independent Control Valves
– Resilient Seat and 2.16.J Butterfly Valves – High Performance.)
1. Manufactured, brand labeled or distributed by BELIMO. 1. NPS 2 and Smaller: Forged brass body rated at no less than 400
2. The combination of valve and actuator shall meet the close-off PSI, chrome plated brass ball and stem, female NPT union ends,
requirements as specified in Section 2.16.H – Butterfly Valves. dual EPDM lubricated O-rings and a brass or TEFZEL
3. Coupling: ISO 5211 mounting standards. characterizing disc.
4. Overload Protection: A self resetting thermal switch embedded in 2. NPS 2-1/2 through 6: GG25 cast iron body according to ANSI
the motor. Class 125, standard class B, stainless steel ball and blowout proof
Override: Actuator shall be equipped with a hand wheel or
5. Manual Override: stem, flange to match ANSI 125 with a dual EPDM O-ring packing
shaft for manual override to permit operation of the actuator in the design, PTFE seats, and a stainless steel flow characterizing disc.
event of an electrical power failure 3. Accuracy: The control valves shall accurately control the flow from
6. Power Requirements: 24VAC [120VAC] [230VAC] 1 pH. 0 to 100% full rated flow with an operating pressure differential
range of 5 to 50 PSI differential across the valve with a valve body
7. Auxiliary Switches: 2 SPDT rated 3A at 250 VAC. accuracy of +/- 5% variance due to differential pressure fluctuation
8. Temperature Rating: -22 to +150ºF. -30 to +65ºC. or +/- 10% total assembly error incorporating differential pressure
9. Housing: Minimum requirement NEMA type 4X/ IP67 with an fluctuation, .manufacturing tolerances and valve hysteresis
industrial quality coating. Actuator shall have an internal heater to 4. Flow Characteristics: Equal percentage characteristics.
prevent condensation within the housing. A A visual indication Remember to modify 2.15.A.6 to incorporate electronic fail-safe option
beacon shall indicate position status of the device. for 2-1/2” through 6” Pressure Independent Valves, where fail safe
10. Agency Listing: ISO, CE, CSA applications are required.
11. The manufacturer shall warrant for 2 years from the date of
production.
Belimo Americas Platinum Distributors
USA
ACR Supply Company Inc. G & O Thermal Supply South Side Control Supply, Co.
4040 S. Alston Avenue 5435 N. Northwest Highway 488 N. Milwaukee Avenue
Durham, NC 27713 Chicago, IL 60630 Chicago, IL 60610-3923
Phone: 919-765-8081 Phone: 773-763-1300 Phone: 312-226-4900
With branches in NC With branches in IL With branches in IL, IN
Aireco Supply Industrial Controls Distributors, LLC Stromquist and Company
9120 Washington Boulevard (was Climatic Control) 4620 Atlanta Road
Savage, MD 20763-0414 5061 W. State Street Smyrna, GA 30080
Phone: 301-953-8800 Milwaukee, WI 53208 Phone: 404-794-3440
With branches in MD, VA Phone: 800-242-1656 With a branch in Orlando, FL
With branches in WI Temperature Control Systems
Amcon Controls, Inc.
11906 Warfield Street Industrial Controls Distributors, LLC 10315 Brockwood Road
San Antonio,TX 78216 17 Christopher Way Dallas, TX 75238
Phone: 210-349-6161 Eatontown, NJ 07724 Phone: 214-343-1444
Houston, TX branch 713-464-7002 Phone:800-543-8200 With branches in OK, TX
Mandeville, LA branch 985-624-3303 With branches in GA, KY, IN, MA, ME, T.F. Campbell Company
NC, NY, OH, PA, TN 1203 Edgebrook Avenue
Wilson Mohr (was Applied Automation)
3186 South Washington Street, #230 Interstate HVAC Controls Pittsburgh, PA 15226
Salt Lake City, UT 84115 30 Vineland Street Phone: 412-881-8006
Phone: 801-486-6454 Brighton, MA 02135 Tower Equipment Co., Inc.
With branches in CO, TX Phone: 617-782-9000 1320 West Broad Street
Boston Aircontrols, Inc. Jackson Controls Stratford, CT 06615
8 Blanchard Road 1708 E. 10th Street Phone: 800-346-4647
Burlington, MA 01803 Indianapolis, IN 46201 Twinco Supply Corporation
Phone: 781-272-5800 Phone: 317-231-2200 55 Craven Street
Charles D. Jones Co. M & M Controls Huntington Station, NY 11746-2143
445 Bryant Street, Unit #1 9E West Aylesbury Road Phone: 800-794-3188
Denver, CO 80204-4800 Timonium, MD 21093 With branches in NY
Phone: 800-777-0910 Phone: 410-252-1221 Wilson Mohr
With branches in CO, MO, KS With a branch in Alexandria, VA 12610 West Airport Blvd, Suite 100
Cochrane Supply and Engineering, Inc. MICONTROLS, Inc. Sugarland, TX 77478
30303 Stephenson Highway 6516 5th Place South Phone: 281-295-8850
Madison Heights, MI 48071-1633 Seattle, WA 98124
Phone: 800-482-4894 Phone: 800-877-8026
Q11000- 04/15 - Subject to change. © Belimo Aircontrols (USA), Inc.