Sie sind auf Seite 1von 4

VISTA-128FBP/V128FBP-24

COMMERCIAL FIRE AND PARTITIONED


BURGLARY ALARM PLATFORM

To meet UL approval for


ANSI/SIA CP-01-2000 order
part number VISTA-128SIA

Designed to integrate seamlessly with CCTV, access control RF receivers and relays are supported by this extremely
and Honeywell’s full range of fire and burglary components, powerful control platform. The VISTA-128FBP has been
the new VISTA-128FBP provides the ultimate protection of life designed to mount quickly and easily in an attack resistant
and property. The UL listed Commercial Fire and Burglary cabinet, and is available in 12V and 24V models. A
Control Platform controls up to eight partitions and supports revolutionary new feature called Panel Linking allows multiple
up to 128 zones/points using hardwired, wireless and V-Plex partitions, panels—even buildings—to be armed, disarmed
addressable technologies. A diverse line of Honeywell and have status checked all from one location.
initiating devices, notification circuits, digital dialers, keypads,

FEATURES

• Eight hardwired zones standard, • Supports CCTV applications with • Supports Remote Control via
expandable to 120 V-Plex the new VistaView-100 CCTV the Internet**
addressable points/zones or Switcher Module
• Supports Internet Alarm Reporting**
128 wireless points/zones
• Identifies the point or zone of a fire or
• Supports Graphical User
• Can control eight separate areas alarm using the new FSA-8/FSA-24 Fire
Interface Consoles
independently (8 partitions) System Annunciator
• Supports up to 250 access card
• Supports Panel-Linking allows • Programmable to meet SIA false alarm
holders using VistaKey
up to 8 systems or building to be prevention specifications and UL
controlled from one central location approval for ANSI/SIA CP-01-2000 • Supports AlphaNumeric Pager
(using VA8200) order part number VISTA-128SIA up to eight different numbers using
the VA8201
• Supports Commercial UL Wireless Fire • Two on-board notification (bell) circuits
and Burg delivering 2.3A @ 12V or 3.4A @ 24V * Connects to Honeywell Access’ PassPoint
Access Control Systems. Maximum 32 doors.
• Stores up to 512 events and can • Automatic smoke detector sensitivity
accommodate 150 user codes maintenance testing ** When used with AlarmNet-i.

• Supports V-Plex addressable VistaKey • Four-wire smoke reset using onboard


access control (1 to 8 doors) J2 output trigger
• Supports up to 16 doors of • Supports Dynamic Signaling for
access control using VISTA LRR backup
Gateway Module (VGM)*
VISTA-128FBP/ V128FBP-24
COMMERCIAL FIRE AND PARTITIONED BURGLARY ALARM PLATFORM

ADDITIONAL FEATURES
• Notification Appliance Circuits (two): – Increased current draw capacity • Access Control integration
– Programmable (128mA) – Full integration with PassPoint
– Temporal code compliant – Supervised by panel Access Control System
– Individually silenceable – Individually assignable to Complete Gateway interface of
partitions, notification circuit VISTA and access functions
• Programmable on-board auxiliary relay (bell) output or aux relay
– 4,000 ft. capability without the • Up to eight doors using VistaKey
• SIA false alarm reduction features: V-Plex Access Control
– Exit error logic use of shielded cable
– Exit delay reset – Extender/Isolation bus module • Event reporting
– Cross zoning – Two-wire smoke detector
– Call waiting defeat zone/group expansion module • Local printer of access or VISTA related event
– Recent close report adds two or four zones • Scheduled uploading of events to
– Eight zone – Class A and B central station
• Supports commercial hardwired, addressable extender module
V-Plex polling loop and wireless zones – Eight zone – Class B extender • Stored events for one call retrieval
• Hardwired zones module
• Communication
– Provides eight style B hardwired zones – One zone supervised contact
– Phone mapping by zone
– EOLR supervised for Fire and monitor module
response type
UL burglary installations • UL Listed wireless expansion – Supports VIP interactive phone
– Supports N.O. or N.C. sensors – Supports up to 128 wireless voice module
– Individually assignable to any zones/points using 5881ENHC – Panel operation during
eight partitions receiver download
– Up to 32 two-wire smoke – Supervised by control for – Uploading equipment list to
detectors each on zone one and check-in signals central station
two (64 total) – Tamper protection for – Communication to PassPoint via VISTA
– Up to 50 two-wire glassbreak detectors transmitters Gateway Module
on zone eight – Individually assignable up to
• CCTV integration
• Patented addressable V-Plex polling loop eight partitions
– Supports VistaView-100 ECP based
technology – Supports UL864/NFPA
CCTV switchers
– Supports 120 two-wire zones points approved wireless smoke detectors
– Global polling technology for
faster processing

4208U 4193SN 4208SNF


5192 Eight-Zone Serial Interface 5192
Series Smoke Eight-Zone
Series Smoke Expansion Module Expansion
Detectors Module V-Plex Detectors
Module
Loop 5881 With 2 Class A
Wireless Zones
Receiver

6160CR
Red Alpha
Console
VistaView-100
CCTV
Switcher
VistaKey V-Plex
Access Control
Module

4204
Notification Appliances
VISTA-128FBP Relay
Module
NAC (Bell) Circuit
4204CF

Eight Class B Hardware Zones

Parallel Printer 5140 LED


416
Keyswitch Communicator
Option Status Module

Serial Printer
4100SM
Printer
Interface
Module

RS232 6220S Printer Notification Appliances

Alpha Paging Phone Line to Central Station


Module

7720ULF Long 7835CF Cellular


Radio
Range Radio
SPECIFICATIONS
Applications • Aux. standby pwr: 12VDC, 1A max Environmental
The VISTA-128FBP control is well • Total power: 2.3A at 12VDC, 3.4A at • Storage temp: 14° F to 158° F
suited for a variety of applications as (-10° C to 70° C)
24VDC from all sources
an integrated fire and burglary control. A
• Operating temp: 32° F to 122° F
diverse line of Honeywell initiating devices • Standby time: 24 hours with 1A standby
(0° C to 50° C)
supports this extremely powerful control. load using 34.4AH battery
Some of the applications supported are: • Humidity: 85% RH
medical and professional buildings, • Fusing: Battery input, aux. and notification
churches or synagogues, office buildings, (bell) circuit outputs are protected using • EMI: Meets or exceeds the following
schools, strip malls, larger residences and PTC circuit protectors. All outputs are requirements:
factory or warehouse environments. power limited. – FCC Part 15, Class B Device
– FCC Part 68
Installation • Optional 24-volt power supply, PS 24 – IEC EMC Directive
supplies two 24 VFW, 1.7A full wave
The VISTA-128FBP alarm system has been rectified, unfiltered outputs Agency Listings Burglary
designed to mount both quickly
• UL609 Grade A Local Mercantile
and easily. It meets all applicable Main Dialer
Premises and Mercantile Safe and Vault
requirements for UL commercial fire • Line seize: Double Pole
and burglary installations. • UL611/1610 Grades A, AA,
• Ringer equiv.: 0.7B Central Station
Electrical
• Primary power: 18VAC @ 72VA • Formats: ADEMCO Low Speed, • UL365 Grades A, AA Police Connect
Honeywell No. 1451 ADEMCO 4+2 Express, ADEMCO High
Speed, ADEMCO Contact ID, Sescoa and Fire
• Control panel quiescent current draw: Radionics • UL864/NFPA72 Local, Central Station
300mA and Remote Station
• Dual phone line capability (using
• Backup battery: 5140DLM module) • Factory Mutual
– 12VDC, 12AH min to 34.4AH max
Cabinet dimensions • California State Fire Marshal
– Lead acid battery (gel type)
• 18" H x 14.5" W x 4.3" D • MEA
• Alarm power: 12VDC, 1.7A max for
each notification (bell) circuit output • UL985
Total 2.3A @ 12V

Manual Pull Stations


5140MPS - 1*
5140MPS - 2*

4193SN 4190SN
Serial Interface V-Plex Two-Zone 4293SN
Module V-Plex Adapter 4944SN
Expander
Addressable Tamper Switch*
Recessed Mount
Contact Flow Switch*
5881
Wireless Receiver Low Temp Switch*
ECP Bus (Max Two)

4297
Isolation/
5808W3 Extender Module
6139R Photoelectric
32 Character Smoke/Heat 5890
Red-Alpha Detectors Wireless PIR
Keypad
4209U
Group Zoning
Module
4204CF
Supervised 5816
NAC Door/Window 5808W3
Module Miniature Photoelectric 4190SN
Transmitter Smoke/Heat Supports Up To 16 V-Plex
Detectors Conventional 2-Wire Two-Zone
Symphony Notification Smoke Detectors Expander
Appliance

PassPoint

VGM (PTVGM)
VISTA
Gateway
Module
Supports Up To 64
Conventional 2-Wire
Smoke Detectors

VISTA-128FBP VISTA-128FBP

Panel Linking Panel Linking


Module Module
VISTA-128FBP/V128FBP-24
COMMERCIAL FIRE AND PARTITIONED BURGLARY ALARM PLATFORM

SPECIFICATIONS
Auxiliary Devices • 4293SN One-Zone Serial Interface Commercial Wireless Devices
• 6160CR – Red Alpha Keypad Module • 5808W3 – Photoelectric
• 6139R – Red Alpha • 4297 Isolation/Extender Module Smoke/Heat Detector
Keypad/Annunciator V-Plex (Addressable) Smoke • 5809 – Wireless Heat Detector
• FSA-8 & FSA-24 annunciator modules Detectors: • 5817CB – Wireless Commercial
• 4204 – Relay Module, four form C Transmitter
contacts • 5192SD • 4192SD • 4192CP • 5869 – Hold-Up Transmitter
• 4204CF – Two supervised output • 5192SDT • 4192SDT • 4192CPM • 5881ENHC – Commercial Fire/Burg
circuits • 4192SDTM Receiver
• 5881 Series – RF receiver supporting V-Plex Passive Infrared Detectors
5800 Series wireless detectors Access Control
• 998MX • VistaKey V-Plex (addressable)
• 6220S – System printer used with • 4275EX-SN
4100SM serial module Access Control
• 4278EX-SN • VistaKey-SK Starter Kit
Two-Wire Smoke Detectors V-Plex (Addressable) Contacts • VistaKey-EX Expansion Kit
Conventional • VGM Vista Gateway Module to
• 4939SN-WH
• 2100 Series Photoelectric • 4944SN-WH PassPoint Access Control
• 2400 Series Photoelectric • 4959SN • Pro-Watch
• 1100 Series Ionization • Win-Pak (PE or SE)
V-Plex Glassbreak Detectors
Four-Wire Smoke Detectors CCTV
Conventional • FG1625SN • VistaView-100 CCTV Switcher
• 2112/24 Series Photoelectric VISTA Interactive Phone Module or Module
• 1412 Series Ionization • 4286 Voice Module Alarm Communications
Horn/Strobes Optional 24V Power Supply • Graphical user interface with
• System Sensor Notification Appliances Internet capability
• PS24 – 24V power supply – 3.4A
• Internet Remote Control-Networking
Manual Pull Stations Long Range Radio Module
• 5140MPS-1 • 7720ULF-XX, 7835C, 7835CF, 7845C • Internet Alarm Communicator (7845i)
• 5140MPS-2 • 7845GSM – Digital Cellular
Upgraded software Communicator
V-Plex (Addressable) Devices • 7845i-GSM – Internet and Digital
• Upgraded Compass Downloader
• 4208U Loop Expansion Module Windows compatible Cellular Communicator
– eight zones • GSMCF/iGSMCF – Comercial Fire
• 4101SN Single Relay/Zone Module Wireless Devices Communication Kits
• 4208SNF Class A/B Expander Module • 5804BDV – Bidirectional with voice
• 4209U Group Zoning Module • 5804BD – Bidirectional Key Paging
– two/four zones • 5816 – Door/Window Transmitter • VA8201 AlphaNumeric Pager
• 4190SN Remote Point Module • 5804 – Wireless Key
– two zones • 5827BD – Bidirectional Keypad
• 4193SN Two-Zone Serial Interface • 5890 – PIR
Module • 5849 – Glassbreak Detector
• VSI Module • 5819 – Shock Sensor

ORDERING
VISTA-128FBP Commercial Fire and Partitioned Burglary Alarm Platform 12V Model
V128FBP-24 Commercial Fire and Partitioned Burglary Alarm Platform 24V Model

Automation and Control Solutions


Honeywell Security & Communications
2 Corporate Center Dr. Suite 100
P.O. Box 9040
L/V128FBP/D
Melville, NY 11747 October 2008