OLTC is tested for Power Frequency Test of 70 kV / 1 min.

and found withstood in


1). Between all contacts to ground. 2) Between Phases
<br><br><b>6.PAINT SHADE AND THICKNESS :</B> 631 of IS 5 & 90microns.

OLTC is tested for Power Frequency Test of 70 kV / 1 min. and found withstood in
1). Between all contacts to ground. 2) Between Phases
<br><br><b>6.PAINT SHADE AND THICKNESS :</B> 632 of IS 5 & 90microns.

OLTC is tested for Power Frequency Test of 70 kV / 1 min. and found withstood in
1). Between all contacts to ground. 2) Between Phases
<br><br><b>6.PAINT SHADE AND THICKNESS :</B> 697 of IS 5 & 125microns.

Super Royal Ivory & 90microns

OLTC is tested for Power Frequency Test of 70 kV / 1 min. and found withstood in
1). Between all contacts to ground. 2) Between Phases
<br><br><b>6.PAINT SHADE AND THICKNESS :</B> 220 of IS 5 & 90microns.

OLTC is tested for Power Frequency Test of 70 kV / 1 min. and found withstood in
1). Between all contacts to ground. 2) Between Phases
<br><br><b>6.PAINT SHADE AND THICKNESS :</B>692 - BS 381C & 90microns

http://192.168.1.100:8080/OLG_LIVE/Jsp/Login/Login.jsp?X

OLTC TEST CERTIFICATE


OLGQA/F.08/E
OLTC SI.No : 41118
Customer : Esennar Transformers Unit-2
Customer Reference : 4509
OLG W.O.NO : T20223

A:ON-LOAD TAP CHANGER RATING:


Type : ABS III 200 12 17.17.0 Serial No 41118
Rated Voltage : 11.0 kv Phase III Phase
Current : 200 A Frequency 50HZ
Transition Step Voltage 550.0 v
Resistance 4.63 Ohms/Phase
Ohmic value :
Measured Value : "U" Phase: 4.6 "V" Phase: 4.6 "W" Phase: 4.6 Ohms Connection
Gen.Arrgt.Drg : 1001330/R27 3050380/R4
Diagram
Schematic Control Circuit
1074270/R1 110 v
Diagram : Voltage
Driver Motor : 415V Phase III Phase
Specification to which tested IS 8468/IEC 60214-1

B:TRANSFORMER DETAILS:
Rated Voltage : 11/0.433 kV Rated Current : 53.48 A Step Voltage : 137.5 V

C:TEST FOR ON-LOAD TAP-CHANGER & MOTOR DRIVE:


1.MECHANICAL TEST: The tap-changer fully assembled with motor drive TEN complete cycle of
operation were performed satisfactorily without any sign of failure

2.SEQUENCE TEST: During the routine mechanical test sequence of operation of selector switch
contact was recorded oscillographically and switching time recorded was 50.03 millisecond which is
within the acceptable range

3.PRESSURE TEST:
i) OLTCs: 1Kg/sq.cm 30 Mints.(Tested on fabricated tank by applying Air pressure)
ii) Terminal Board : Tested Seprarately for 0.7kg/sq.cm 3Hours (Hot Oil at 80 Degree C)

4.AUXILIARY CIRCUIT INSULATION TEST: A test voltage of 2kV,50HZ was applied for one
minute between live terminals of all auxiliary circuits and the earth terminal on the housing.The test
was performed satisfactorily with out any sign of failure

Date: 06-Jan-2018 OLGQA


AUTHORIZED SIGNATORY