Sie sind auf Seite 1von 8

ABSTRACT

Name of work: Providing and strengthening power distribution arrangements to the


new Library
building at Government College of engineering, Salem-11.

Estimate Amount: Rs. 5.80 lakhs

S Qty Description of work Rate Per Amount


lno

1 1 Supply and erection of 315A capacity dust


Set and vermin proof cubical panel board
made up of 16 SWG CRCA sheet steel
with supply and fixing of the following
interior mounding fuse switches with HRC
fuses arranged in two horizontal rows with
one switch over the other, with a central
bus bar chamber and 2nos of horizontal
cable chambers at the ends one on each
side next to the fuse switch chamber and
conforming to IE rules.

i) 1No: 315A TPN switch disconnector


fuse units interior only with HRC fuses
double break.

ii) 1No:200A TPN switch disconnector


fuse units interior only with HRC fuses
double break.

iii) 6Nos:63A TPN switch disconnector


fuse units interior only with HRC fuses
double break.

The bus bar chamber will consist of


4Nos of suitable size of copper flat for
phase and neutral buses on epoxy bus
insulators at proper and sufficient spacing
between the buses as per IE rules. This bus
bar chamber should be segregated from the
adjacent chambers by providing hylam sheet
of suitable thickness as partisans. Suitable
size of copper flats should be provided all
round the panel for earth bus.

The fuse switches should be connected


with the phase and neutral buses with
suitable size of rigid copper rod or flat and
each switch should be connected with the
earth bus with 2 runs of 25x3mm copper
flats. Switches should be connected to the
buses by suitable size of rigid copper rod /
flat phase and neutral copper buses should
be tinned properly.

The panel should be painted with one


coat red oxide as primer coat and two coats
of enable paint of approved colour, approved
by the site Engineer and also the danger
board. The capacity of the fuse switches
size of the incoming and out going cables 69907.75 Set 69908.00
the place to which the supply is fed shall be
marked on switch chamber. The panel board
should be mounded on 75mmx37mm MS
channel provided all round at bottom of the
2 1 panel. The whole arrangement should be
No erected on a masonry pedestal to be—

--constructed with suitable foundation bolts 17144.40 Each 17144.00


and nuts such that the lowest switch handle
is at a height of 0.5mtr from the ground
level. (Including less credit to the old scrap
materials).
3 910
Mtr (Data-1)
Supply and fixing of 315A TPN switch
disconnector fuse units in sheet steel 1183.80 Mtr 1077258.00
enclosure with HRC fuses double break on
existing panel board with suitable copper
bus bar to extended existing panel and with
connection.
4 60
Mtr (Data-2) 1367.95 Mtr 82077.00

Supply and laying of 3½x 240sqmm PVC


LTUG cable in a trench to be excavated at a

5 8 depth of 0.75mtr putting 0.15mtr. Layer of

Mtr sand and covering the cable completely with 1119.35 Mtr 8955.00
bricks and sand refilling the earth to make
good. (Including less credit to the old scrap
materials).

6 8
(SD-206)
Mtr 1127.40 Mtr 9019.00

Supply and laying of 3½x 240sqmm PVC


LTUG cable in a trench to be excavated of
7 2
PVC pipe for road crossing.
Nos 249.00 Each 498.00

(Data-3)

Supply and laying of 3½x 240sqmm PVC


8 2 LTUG cable in a existing trench.
Nos
(Data-4) 373.15 Each 746.00

Supply and clamping of 3½ x 240sqmm


9 2 PVC LTUG armored cable on wall with MS
Nos clamps.
1265605.00
(SD-224)
1265605.00

Supply and fixing of brass cable gland for


3½ x 240sqmm PVC LTUG armored cable 1145.20 Each 2290.00
with earth connection.

(SD-188)

Supply and providing cable end 1267895.00


termination of 31/2 x 240sqmm PVC LTUG
armored cable with necessary aluminum
cable sockets by crimping etc. With
electrical connection complete.

(SD-235)

Earthing as per ISI specification with an


earth electrode of 2.1mtr. Class‘B’ GI pipe of
dia not less than 40mm with copper earth
plate of size

125mmx50mmx6mm with necessary funneling


arrangements with necessary masonry work
and with 38mm RCC cover slab for the brick
masonry.

(SD-227)

Unforeseen items

( Rupees Eighty thousand only)


DATA SHEET

Data-1
1no: 315A TPN switch disconnector fuses units
Interior only with HRC fuses double break @ 11125.00/each
= 11125.00

1no: 200A TPN switch disconnector fuses units


Interior only with HRC fuses double break @
6666.00/each = 6666.00

6nos: 63A TPN switch disconnector fuses units


Interior only with HRC fuses double break @ 2370.00/each
= 14220.00

7m: 36x6mm copper flat for 3 phases bus and


14.7kg interconnection of 315A switch @ 350.00/kg =
5145.00

2.5m: 36x3mm copper flat for neutral bus,


2.6kg and interconnection of 315A switch @ 350.00/kg =
921.00

2m: 25x6mm copper flat for and interconnection


2.8kg of 200A switch @ 350.00/kg =
980.00

1.73 kg: No.8 SWG copper wire for


Earth connection of all switches @ 350.00/kg =
605.50

12sqmtr: 16SWG CRCA sheet steel @ 65.00/kg =


9750.00
150kg

4.5mtr: 75mmx37mm M.S. base channel @ 30.00/kg


= 843.90
22.4kg

1sqmt: 6mm Thick hylam sheet @ 525.00/sqm =


525.00

3set: Epoxy moulded bus support insulator @ 175.00/set =


525.00

1set: Ammeter, Voltmeter with selector switches with


LED indicator etc = 3000.00

Labour for fabrication work sheet cutting, bending


And welding etc = 2500.00

Labour charges for erection and giving connection


to switches and earth connection =
1500.00
Painting with one coat of primary and two
Coats of enamel paint with lettering
= 1500.00

For Tin coating of copper flats =


500.00
Masonry pedestal = 1000.00

Labour charges for testing and commissioning etc


= 1000.00
62306.40
2% Sundries, such as Bolt & nuts =
1246.12
63552.52
10% for mofussil 6355.25
69907.77
(Say)
69 907.7 5
Data-2
1 no: 315A TPN disconnector fuses units
with HRC fuses double break @ 13354.00/each =
13354.00

2m: 36x6mm copper flat for interconnection of


4.2kg 315A switch @ 350.00/kg =
5145.00

1no: cable entry box @ 110.00/each =


110.00
14934.00
1% Sundries
149.34 Labour charges
502.50
15585.84
10% for mofussil
1558.58
17144.42
(Say)
17144.40

Data-3
As per SD 206 = 1076.20
Add:
1mtr: 4” PVC pipe @ 167.40/mtr =
167.40
1243.60
10% for mofussil
124.36
1367.95

Das könnte Ihnen auch gefallen